Anderson-Negele HB Manual

Page 1
Instruction Manual
Anderson Instrument Co., Inc. 156 Auriesville Road Fultonville, NY 12072 Phone: 800-833-0081 www.anderson-negele.com
Instrument Model Number
Instrument Serial Number
HB Series Mini Level Sensor
Form Number AIC2006 © May 1998 Revised: 6/14 Supersedes: 5/14
Page 2
Section 1 - Ordering Matrix
HB
1
Span Range
1 0”-20” to 0”-60” Water Column 2 0”-60.1” to 0”-100” Water Column 3 0”-101” to 0”-160” Water Column
Fitting
005 2” Tri-Clamp
Diaphragm Material
1 Stainless Steel - 316L
Note: Calibration information must be provided
at time of order. Inches of Water
Column or Inches Height and Specic
Gravity.
Section 2 - Specifications
Environmental Specifications
Ambient Operating Temperature Range: 40°F to 120°F (4°C to 49°C) Storage Temperature Range: -40°F to 250°F (-40°C to 121°C) Humidity: 0 to 95% RH, condensing
Material / Construction
Housing: 304 Stainless Steel, Ra40 maximum nish Wetted Parts: 316L Stainless Steel, Ra25 maximum nish Process Connection: 2” Tri-Clamp
Approvals & Documentation
Ratings: NEMA 4X/IP-66,IP-67 3A Authorized Models equipped with optional conduit connector must be installed with conduit to maintain Standards: Designed and manufactured to sound engineering practices in accordance with Article 3.3 of the PED 97/23/EC CSA B51-03 CRN# CSA0F9754.5C
Calibration
### Height in inches w.c. (to nearest tenth up to 99.9 then whole numbers from 100” to 160”) 000 Field Calibrated
Cable Length
A0 QDR w/No Cable, no FWC C1 Sealed Cable w/Conduit Connection and 25' Cable C2 Sealed Cable w/Conduit Connection and 50' Cable C3 Sealed Cable w/Conduit Connection and 100' Cable
Examples: 100 100 inches 305 30.5 inches
Mounting
0 Horizontal 1 Verticle (Diaphragm facing up) 2 Other (Specify angle)
Operating Specifications
Range: HB1 0-20” to 0-60” Water Column HB2 0-60.1” to 0-100” Water Column HB3 0-101" to 0-160" Water Column Over-Range Capacity: 2.5 times Upper Range Limit Response Time: 200 uSec Accuracy: Factory calibrated to ±0.2% of Upper Range Limit (URL) Stabilized at 75°F (24°C) Process Temperature Limits: 32°F to 250°F (0°C to 121°C) Compensated 32°F to 200°F (0°C to 93°C) Temperature Stability: Within ±2.0”/100°F over the compensated process and ambient operational temperature range
Power / Signal / Electrical
Voltage: 12-40 VDC Load Impedance: 1400 ohms (max) @ 40 VDC Output: 4-20 mA DC, 2-wire Electrical Connection: Standard - 5 pin M12 Pins 1 & 2 Active
Figure 1 Dimensions
2.31" 2.31"
2.09" 2.09"
2.65" 2.65"
Quick Disconnect
Receptacle (QDR)
Recommended Cable: Shielded 5 pin M12 molded cordset Pins 1 & 2 Active, Shield must connect to cordset nut
Conduit Connector
Optional: Sealed Cable with 1/2" NPT Conduit Connection
Page 3
Section 3 Description
The HB Series Mini-Level Transmitter is an integral unit designed to measure static head pressure (level) in Pasteurization Loop Balance Tanks and small Open Atmosphere Sanitary Storage Vessels. The unit converts head pressure exerted by the product into a proportional 4-20 mA DC signal. This signal may feed instrumentation such as controllers or digital indicators. The all stainless sealed design meets the demands of damp or wet applications, and may be directly washed down during normal cleanup. Units are
typically shipped pre-calibrated from the Factory, with provisions provided for eld calibration via onboard
adjustment potentiometers (Pots).
Section 4 Wiring
A 12 to 40 VDC loop power source is required for operation of the HB transmitter. If below 24 VDC, it is recommended that a regulated supply be utilized.
HB mini level transmitters are provided with either the standard M12 5 pin quick disconnect receptacle or with a ½” NPT conduit connector option that includes a sealed four conductor, foil shielded sealed cable connection.
Anderson recommends Molded cord-set P/N 42117H0025, 0050, 0100 for lengths 25ft, 50ft or 100ft. This is a premium molded cord-set designed to meet both the electrical and environmental requirements of the HB. Commercially available cord-sets may be used as long as shielding is connected to the attachment nut.
For HB ordered with the conduit connection option conduit must be installed to meet environmental protection rating. Conductor assignments as follows:.
RED = Loop (+) connection BLACK = Loop (-) connection GREEN = Not Used WHITE = Not Used GROUND = Attached at sensor
NOTE: If it becomes necessary to splice cable connections, be sure all joints are properly soldered
and sealed from moisture. As copper easily becomes contaminated from typical cleaning solutions, poor quality connections will eventually affect 4-20 mA signal output of the transmitter.
Figure 2 Wiring Diagram
Connection varies
based on configuration
+
RED (+)
12-40 VDC
POWER SUPPLY
-
BLACK (-)
RECEIVER
-
SIGNAL
Shield Ground
(One Point Only)
+
Page 4
Section 5 Transmitter Electronic Zero Calibration
Upon installation, and at typical six month intervals, a Zero calibration adjustment must be performed. The required procedure is as follows:
Tools required: Digital Multimeter (Known accurate) Fine - straight bladed screwdriver
NOTE: Must be performed with the sensor installed in the vessel, with appropriate loop power applied.
Be sure vessel is drained to a level at or below the sensor. The transmitter should be wired to the receiver at this point. To prevent possibly shorting receiver inputs, it is recommended that loop power be shut off while making test equipment connections. At the receiver, remove the (-) BLACK transmitter lead. Connect the (+) RED meter lead to the transmitter lead just removed. Connect the (-) BLACK meter lead to the resulting empty terminal in the receiver. The digital multimeter should be set in the mA DC mode. At this point, apply loop power again taking note of the resulting meter reading. You should see 4.00 mA registering on the meter display. If not, remove the screw at the end of the sensor labeled “ZERO”.
Using the ne screwdriver, adjust the internal potentiometer until a reading of 4.00 mA is achieved. Once
complete, replace the protective screw over the Zero potentiometer. Remove test equipment and install transmitter (-) BLACK lead back to receiver. Again, it is recommended that loop power be shut off while disconnecting equipment to prevent shorting of the receiver inputs.
Figure 3 Zero Adjustments
E
C
X
D
C
V
I
T
0
4
-
2
2
-
1
4
A
P
N
S
R
E
D
G
(
R
L
O
E
O
E
P
N
&
A
T
A
O
m
U
0
+
)
W
H
I
T
O
P
N
U
T
R
E
O
Z
)
-
P
O
)
O
D
L
E
(
S
K
U
C
A
L
B
T
O
N
(
I
T
E
Connection varies based on configuration
BLACK WIRE
RED WIRE
Remove Protective Cap Screw To Gain Access To Zero Potentiometer
Use screwdriver to adjust until multimeter reads 4.00 mA DC
4.00
Meter Red (+)
Power
Supply
MA DC
Meter Black (-)
Signal
Receiver
Page 5
Section 6 Calibration Ranges and Adjustments
The HB series transmitter is typically supplied pre-calibrated from the factory. Calibration data is located on the information stamping on the side housing:
CAL. RANGE: XXXXXXXXX (Factory Calibrated Range In Inches Of Water Column)
Calibration checks may be performed in the eld using known accurate pressure test equipment. Typical
devices read out directly in Inches of Water Column where 27.7” Water Column equals 1 psig. As the required calibration pressures are very low, it is recommended that a test gauge having a direct Inches Water Column scale be used. This will give the greatest resolution. In some instances, it may be required to alter calibration,
or perform calibration of the transmitter in the eld. Keep in mind that two ranges exist. A transmitter
supplied in the lower range cannot be re-spanned to operate in the higher range, and vice versa. Calibration adjustments within the same base range are allowed. The procedure for adjustment is as follows:
Calibration Using Pressure Simulator
· Be sure sensor is properly wired to loop power - remove Zero and Span protective cap screws
· Attach multimeter as in Figure 3 (Readout in mA DC)
· Attach pressure calibration equipment
· Orient sensor as close as possible to position as if it were installed in vessel
· Perform ZERO potentiometer adjustment with NO pressure on transmitter (Meter to read 4.00 mA)
· Apply test pressure to transmitter
· Perform SPAN potentiometer adjustment on transmitter (Meter to read 20.00 mA)
· Replace sensor into vessel
· Perform ZERO potentiometer adjustment with NO pressure on transmitter (Meter to read 4.00 mA)
· Zero and Span are non-interactive - calibration is complete - replace protective cap screws
Calibration Using Product in Vessel
· Be sure sensor is properly wired to loop power - remove Zero and Span protective cap screws
· Attach multimeter as in Figure 3 (Readout in mA DC)
· Perform ZERO potentiometer adjustment with NO product on transmitter (Meter to read 4.00 mA)
· Fill tank to capacity with PRODUCT
· Perform SPAN potentiometer adjustment on transmitter (Meter to read 20.00 mA)
· Zero and Span are non-interactive - calibration is complete - replace protective cap screws
Calibration Using Water in Vessel
Specic Gravity = (Pounds Per Gallon for Product / 8.345)
· Calibration with water in a vessel that will hold another product requires Specic Gravity correction
· Determine Specic Gravity, or calculate if Pounds Per Gallon provided
· Correct for Specic Gravity: [ (16.00 mA / Specic Gravity) + 4.00 mA ] = Expected mA Signal
· Be sure sensor is properly wired to loop power - remove Zero and Span protective cap screws
· Attach multimeter as in Figure 3 (Readout in mA DC)
· Perform ZERO potentiometer adjustment with NO product on transmitter (Meter to read 4.00 mA)
· Fill tank to capacity with WATER
· Perform SPAN potentiometer adjustment on transmitter (Meter to read result of calculation per­formed above)
· Zero and Span are non-interactive - calibration is complete - replace protective cap screws
Contact Anderson Instrument Technical Services for further assistance
Please have Model and Serial number available
Page 6
Warranty and Return Statement
These products are sold by The Anderson Instrument Company (Anderson) under the warranties set forth in the following paragraphs. Such warranties are extended only with respect to a purchase of these products, as new merchandise, directly from Anderson or from an Anderson distributor, representative or reseller, and are extend-
ed only to the rst buyer thereof who purchases them other than for the purpose of resale.
Warranty
These products are warranted to be free from functional defects in materials and workmanship at the time the
products leave the Anderson factory and to conform at that time to the specications set forth in the relevent
Anderson instruction manual or manuals, sheet or sheets, for such products for a period of one year.
THERE ARE NO EXPRESSED OR IMPLIED WARRANTIES WHICH EXTEND BEYOND THE WARRANTIES HEREIN AND ABOVE SET FORTH. ANDERSON MAKES NO WARRANTY OF MERCHANTABILITY OR FIT­NESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE PRODUCTS.
Limitations
Anderson shall not be liable for any incidental damages, consequential damages, special damages, or any other damages, costs or expenses excepting only the cost or expense of repairs or replacement as described above.
Products must be installed and maintained in accordance with Anderson instructions. Users are responsible for the suitability of the products to their application. There is no warranty against damage resulting from corrosion,
misapplication, improper specications or other operating condition beyond our control. Claims against carriers for damage in transit must be led by the buyer.
This warranty is void if the purchaser uses non-factory approved replacement parts and supplies or if the pur­chaser attempts to repair the product themselves or through a third party without Anderson authorization.
Returns
Anderson’s sole and exclusive obligation and buyer’s sole and exclusive remedy under the above warranty is limited to repairing or replacing (at Anderson’s option), free of charge, the products which are reported in writing
to Anderson at its main ofce indicated below.
Anderson is to be advised of return requests during normal business hours and such returns are to include a statement of the observed deciency. The buyer shall pre-pay shipping charges for products returned and An­derson or its representative shall pay for the return of the products to the buyer.
An RMA (Return Merchandise Authorization) must be obtained from Anderson Customer Service before returning merchandise.
Approved returns should be sent to: Anderson Instrument Co., Inc. 156 Auriesville Rd. Fultonville, NY 12072
ATTN: Repairs Write RMA number on outside of package
Loading...