Anderson Greenwood AMAL IR Series (Removable Element) Flame Arresters IOM (ES/0/0/132), Anderson Greenwood-EN Manuals & Guides

Page 1
ANDERSON GREENWOOD AMAL IR SERIES (REMOVABLE ELEMENT) FLAME ARRESTERS
INSTALLATION & MAINTENANCE INSTRUCTIONS
Includes: IRF, IRD, IRDB, IRQ & IRQS types and eccentric variants (E)
1. GENERAL
IR Series flame arresters are intended for use in piping systems handling flammable gases/ vapors.
1.
Maximum temperature limits -20° to +60°C covering the general range of flame arresters (see special conditions for safe use).
2. IR series detonation or deflagration type flame arresters are designed to protect piping systems and equipment from explosions, detonations or deflagrations that have occurred in associated piping/ equipment or external to the vent piping.
3. ONLY install for the application for which it has been designed and specified and within its tested/certified limitations ­refer to product data sheet for guidance. It is potentially dangerous to use in other applications.
4. Mounting of any electrical monitoring devices shall be in accordance with EN 50018:2000.
5. Flame arresters should not be positioned near hot equipment unless certified for the elevated temperature, as heat transfer to the flame arrester will reduce its performance and may cause it to fail.
6. Shut-off devices should be fully open during normal operation.
7. Continuous monitoring of pressure drop is advised if the process is known to contain particulates or substances which can block the element and over-pressurize the system.
8. Metal parts insulated by gaskets should be earthed where necessary.
9. Flame velocities and pressures of flammable mixtures can be enhanced by upstream turbulence, which can be caused by bends, valves or any change in section of the pipework. The flame arrester should only be used for the process application; if the process conditions or the pipework configuration change, the flame arrester specification should be re-checked with the manufacturer.
10. If the normal operating or atmospheric temperature can cause freezing within the flame arrester, it is advisable to provide trace heating to the flame arrester element and housings - if electrical this must be in accordance with EN500018:2000. It is important to ensure that the flame arrester unit is ATEX certified for use at the elevated temperature of the process fluid, created by the external heating source.
11.
Where a dedicated heating jacket (steam or hot fluids) is supplied as part of the flame arrester unit, the flame arrester will be denoted J type e.g. IRQJ. In these cases, the flame arrester should be fitted with the heating fluid connection in a vertical attitude. The inlet connection should be at the top of the housing and the outlet should be at the bottom of the housing to facilitate drainage. Extra care should be taken to ensure that when the heating fluid pipes are removed for maintenance purposes, heat resisting hand protection is worn to protect the operator from any potential burning. Monitor the temperature of the flame arrester unit to ensure that the process fluid does not rise above its auto ignition temperature.
3. INSTALLATION
1. Remove all packaging from the flame arrester prior to installation, paying particular attention to the inlet and outlet housing sections.
2. Mount the flame arrester in the pipeline in the orientation for which it has been designed. Amal IRDB, IRQ, IRQS (E) types are normally bi-directional and can be fitted either way round unless they are made one directional by accessories fitted to the inlet or outlet housing sections only - in this case a directional arrow is included showing the direction of normal flow. Types IR, IRF & IRD are one directional and a directional arrow is included.
2.1 Flanged connection - bolt to flanges
of the same specification as those fitted to the flame arrester itself, with intermediate gaskets of a type appropriate to the service conditions. Tighten the bolting uniformly to ensure a good seal.
2.2 Screwed connection (DN 80 or 3 NPS and smaller) - fit to the corresponding male/female threads. Sealing tape or sealant may be used to ensure a good seal.
3. Ensure that any accessory nozzles are fitted
with the necessary accessories or with plugs/blanking flanges as appropriate.
4. When appropriate, it is recommended that
a protective cage be installed to guard the flame arrester against accidental impact from vehicles or from heavy falling objects.
Emerson.com/FinalControl
© 2017 Emerson. All Rights Reserved.
VCIOM-02440-EN 15/12
Page 2
ANDERSON GREENWOOD AMAL IR SERIES (REMOVABLE ELEMENT) FLAME ARRESTERS
INSTALLATION & MAINTENANCE INSTRUCTIONS
4. MAINTENANCE
Maintenance should only be carried out by suitably qualified personnel.
1.
During service the element matrix may become blocked with particles and impurities from the atmosphere and/or process. If too severe, the blockage will impair the free flow of gases/vapors. In severe cases this can cause damage to equipment and the flame arrester itself. If excessive pressure drop is experienced, or after any flashback or incident, immediate inspection should be made. Where a process is known to be 'dirty', a pressure limiting device, installed within the associated pipeline is strongly recommended.
2. A periodic maintenance schedule is recommended for the flame arrester, the frequency to be based on operational experience and actual operating conditions, but at least annually.
3. No special tools are required. Standard spanners and lifting equipment for larger sizes of flame arrester, are required.
4. IR series flame arresters are designed to allow inspection and maintenance in situ, however, this should only be done if it is safe to do so.
NOTE: Potentially toxic substances may
have been passing through the flame arrester. Always wear appropriate safety equipment, with eye protection, when working on or near flame arresters.
If the flame arrester has a heating jacket it
will be necessary to drain the flame arrester jacket, and in order to do this the heating fluid pipes will need to be disconnected. Always ensure that heat resisting gloves are worn before this is done since hot fluid may spill from the connecting joints.
5.
Loosen the bolting around the central flanges containing the element assembly/assemblies.
6. Separate the central flanges, using any jacking bolts that may be fitted to the flame arrester or other appropriate means, by an amount sufficient to allow removal of the gaskets and element assembly/assemblies. Note that where unsupported backing flanges have been used this may not be possible and the complete flame arrester may have to be taken from the pipeline.
7.
Remove sufficient bolting to allow the gaskets and element assembly to be removed or, where a swing out element assembly is fitted, for it to be swung out for inspection.
8. Remove the element(s), using lifting equipment where appropriate, and examine both surfaces. DO NOT insert any probes into the element.
9.
If the element matrix is visibly damaged or corroded it must be replaced before the flame arrester is returned into service. If cleaning is required see Section 5 before re-fitting.
10. Check that the sealing face of the housing is clean and free from particles that may affect the sealing of the element.
NOTE: Any gaps between the housing and
gaskets/element may provide a flame path around the flame arrester element and are therefore DANGEROUS.
11. Fit new gaskets of the same specification and re-fit the element(s) ensuring that it is located centrally - there may be locating collars fitted to some of the bolts to assist in this.
12. Where more than one element is fitted ensure that all lifting eyes are in complete alignment.
13. Replace the bolting and tighten to the appropriate torque.
14. After any external fire in the locality of the flame arrester, it is recommended that the equipment be examined for damage, with particular attention paid to the joint gaskets, replacing them if necessary. Also check the tightness of the flange bolting and retighten if necessary.
5. CLEANING THE ELEMENT ASSEMBLY
1. DO NOT attempt to remove the element matrix from its cage/casing.
2. DO NOT allow the element assembly to become blocked severely.
3. DO NOT clean by inserting probes into the cell structure.
4. DO NOT use excessively corrosive materials (e.g. hydrochloric acid) to clean the element.
5. High-pressure water jets ARE NOT recommended.
6. The following ARE recommended: detergents, solvents, compressed air, steam or ultrasonic. The actual cleaning method will depend on the nature of the substance causing the blockage.
7. If the element is damaged during cleaning a NEW element assembly should be fitted. If in doubt refer to your nearest representative for advice.
6. SPARE PARTS
Under normal conditions only the element assembly and gaskets should need replacing. It is recommended that for every three-flame arresters of a given type and size, at any one site, at least one spare element assembly is available at all times. One set of gaskets for each flame arrester assembly should also be available. When requesting spare elements the full type code, part number, and serial number MUST be quoted fitting the incorrect element is potentially DANGEROUS. See the flame arrester label and/or associated detailed spare parts list for details.
2
Page 3
ANDERSON GREENWOOD AMAL IR SERIES (REMOVABLE ELEMENT) FLAME ARRESTERS
INSTALLATION & MAINTENANCE INSTRUCTIONS
7. AFTER SALES SERVICE
After sales service is available through the relevant Emerson office in the United Kingdom or through our worldwide network of regional offices and agents.
8. MARKING ON THE FLAME ARRESTER (CE PLATE)
9. MARKING ON THE FLAME ARRESTER (NAMEPLATE)
Detonation or deflagration
Either IIA, IIB1, IIB3, IIB or IIC
3
Page 4
ANDERSON GREENWOOD AMAL IR SERIES (REMOVABLE ELEMENT) FLAME ARRESTERS
INSTALLATION & MAINTENANCE INSTRUCTIONS
10. SPECIAL CONDITIONS FOR SAFE USE – MANUFACTURING IS INTENDED AS FOLLOWS: Flame Arrester Matrix for ATEX approval covering Certificates INERIS03ATEX0075X with Additions /01, /02 and /03
Max. temp.
Type Connection Gas group Size range Short burn Det. Deflag.
IR (E) Flanged IIA DN12/450 Yes N/A Yes -20 / +60ºC N/A 1 x 0.8mm IR (E) Flanged IIB1/IIB3 DN12/450 Yes N/A Yes -20 / +60ºC N/A 1 x 0.8/0.6mm IRF, (E) Flanged IIA DN12/450 Yes N/A Yes -20 / +60ºC N/A 1 x 0.8mm IRF, (E) Flanged IIB1/IIB3 DN12/450 Yes N/A Yes -20 / +60ºC N/A 1 x 0.8/0.6mm IRE Flanged IIA DN40/200 Yes N/A Yes -20 / +60ºC N/A 1 x 0.6mm IR, IRF, (E) Flanged IIA DN12/450 No N/A Yes -20 / +165ºC N/A 1 x 0.6mm IR, IRF, (E) Flanged IIB1/IIB3 DN12/450 No N/A Yes -20 / +165ºC N/A 1 x 0.38mm IR, IRF, (E) Flanged IIB DN12/400 Yes N/A Yes -20 / +60º N/A 1 x 0.45mm IR, IRF (E) Flanged IIC DN12/150 Yes N/A Yes -20 / +60ºC N/A 1 x 0.15mm IR, IRF, (E) Flanged IIB DN12/100 No N/A Yes -20 / +165ºC N/A 1 x 0.3mm IR, IRF (E) Flanged IIC DN12/150 No N/A Yes -20 / +165ºC N/A 1 x 0.15mm IR, IRQ Flanged IIB3 DN200 No N/A Yes -20 / +260º N/A 1 x 0.38mm IRQ, IRQS, (E) Flanged IIA DN12/450 Yes N/A Yes -20 / +60ºC N/A 1 x 0.8mm IRQ, IRQS, (E) Flanged IIB1/IIB3 DN12/450 Yes N/A Yes -20 / +60ºC N/A 1 x 0.8/0.6mm IRQ, IRQS, (E) Flanged IIA DN12/450 No N/A Yes -20 / +165ºC N/A 1 x 0.6mm IRQ, IRQS, (E) Flanged IIB1/IIB3 DN12/450 No N/A Yes -20 / +165ºC N/A 1 x 0.38mm IRQ, IRQS, (E) Flanged IIB DN12/400 Yes N/A Yes -20 / +60ºC N/A 1 x 0.45mm IRQ, IRQS, (E) Flanged IIC DN12/150 Yes N/A Yes -20 / +60ºC N/A 1 x 0.15mm IRQ, IRQS, (E) Flanged IIB DN12/100 No N/A Yes -20 / +165ºC N/A 1 x 0.3mm IRQ, IRQS, (E) Flanged IIC DN12/100 No N/A Yes -20 / +165ºC N/A 1 x 0.15mm
deflagration
Max. temp. unstable detonation Element
Max. temp.
Type Connections Gas group Size range Short burn Det. Deflag.
IRD, IRDB, (E) Flanged IIA DN12/200 Yes Yes N/A N/A -20 / +60ºC 1 x 0.6/0.45mm IRD, IRDB, (E) Flanged IIA DN250/450 Yes Yes N/A N/A -20 / +60ºC 2 x 0.45mm IRD, IRDB, (E) Flanged IIA DN12/200 No Yes N/A N/A -20 / +165ºC 1 x 0.45mm IRD, IRDB, (E) Flanged IIA DN250/450 No Yes N/A N/A -20 / +165ºC 2 x 0.45mm IRD, IRDB, (E) Flanged IIB1/IIB3 DN12/150 Yes Yes N/A N/A -20 / +60ºC 1 x 0.45/0.38mm IRD, IRDB, (E) Flanged IIB1/IIB3 DN200/400 Yes Yes N/A N/A -20 / +60ºC 2x0.45/3 x0.38mm IRD, IRDB, (E) Flanged IIB1/IIB3 DN12/150 No Yes N/A N/A -20 / +165ºC 1 x 0.38mm IRD, IRDB, (E) Flanged IIB1/IIB3 DN200/400 No Yes N/A N/A -20 / +165ºC 3 x 0.38mm IRD, IRDB, (E) Flanged IIB DN12/150 Yes Yes N/A N/A -20 / +60ºC 1 x 0.3mm IRD, IRDB, (E) Flanged IIB DN12/100 No Yes N/A N/A -20 / +165ºC 1 x 0.3mm IRD, IRDB, (E) Flanged IIC DN12/150 Yes Yes N/A N/A -20 / +60ºC 1 x 0.15/2x0.15mm IRD, IRDB, (E) Flanged IIC DN100 No Yes N/A N/A -20 / +165ºC 2 x 0.15mm IRD, IRDB, (E) Flanged IIC DN12/80 No Yes N/A N/A -20 / +165ºC 1 x 0.15mm
deflagration
Max. temp. unstable detonation Element
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Anderson Greenwood is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson.com/FinalControl
4
Loading...