Analytic Systems LVS1000 Data Sheet

Page 1
Description
DC/AC Pure Sine Inverters
Model LVS1000
Benefits
Ultra-Quiet
Power sensitive electronics without interference
Rugged & Reliable
Ensure years of safe and trouble free operation
Low profile, compact size, light weight
Input is filtered to EN 55022 Class B (typical)
Sinusoidal wave shape
1000VA of output power
Full electronic protection
Field-proven design topology
The LVS1000 Series compact DC/AC Inverter utilizes established design techniques to ensure high reliability.
Suitable for a wide range of applications, the LVS1000 features full electronic protection, high efficiency and low output noise.
The built-in fan provides sufficient airflow for operation without de-rating up to 50oC ambient temperature. Extended operating temperature (-40 to +65oC) is available.
The inverter can be loaded with a fluorescent lamp load up to the full specified output power.
Applications
Marine / Automotive / RV
Electric Utilities and Substations
Telecom Power Plants
Manufacturing Locations
Steel Mills
Military Applications (COTS)
Industrial Controls
OEM Applications
Solar / Alternative Power Systems
Fuel Cells
Page 2
DC/AC Sinewave Telecom Inverters
LVS1000
Input Voltage
Input Protection ermal fuse / Inrush current limiting / Reverse polarity protection
Isolation Input to chassis: 1500VDC/ Input to output: 3000VDC/ Output to chassis : 2250VDC
Output Voltage
Wav e F orm Sinusoidal
Total Harmonic Distortion Less than 5% at full load
Eciency Min 78% at full load
Line Regulation Maximum 0.5%
Load Regulation Maximum ± 2% from 10% load to full load.
Output Protection
EMI EN 55022 Class B (typical)
Load Crest Factor Maximum 3.0 at 90% load
24V, 36V, 48V, 125V, 250VDC ± 20% are standard Other input voltages available
115VAC / 8.7A continuous or 230VAC / 4.34A continuous at 50, 60 or 400Hz with grounded neutral Isolated oating output optional / Other outputs available
Current limiting with short circuit protection, thermal shutdown with automatic recovery in case of continuous overload or insucient airow
Operating Temperature Range 0o C to +50o C
Humidity 5 - 95% non-condensing
Temperature Dri 0.05% per o C over operating temperature range
Dimensions 2.64” x 19” x 13.97” enclosed case (H x W x L)
Connections
Weight 17.6 lb (8.0 kg)
Safety Designed to meet C22.2 No. 107.1 - 01, UL 458 and EN60950
Options
Note: Specifications are subject to change without notice.
Designed to meet common approval requirements. Specifications Subject to Change Without Notice
Input: Compression-type terminal Output: Standard AC receptacle
Output Fail Alarm (Form C) Remote Inhibit: By closing external contacts on the inhibit terminals
Warranty: Twenty four months subject to application within good engineering practice
Enhancements to these general specifications can be accommodated upon request
Designed and Manufactured in Canada