Description
The IVS4000R Series is a compact 4000VA DC/AC pure sinewave inverter that uses established design techniques to ensure high reliability.
Suitable for a wide range of applications, the IVS4000R features full electronic protection, high efficiency and low output noise.
The built-in fan provides sufficient airflow for operation without de-rating up to 50oC ambient temperature.
Extended operating temperature (-40 to +65oC) is available.
DC/AC Pure Sine Inverters
Model IVS4000R
Benefits
Ultra-Quiet
Power sensitive electronics without interference
Rugged & Reliable
Ensure years of safe and trouble free operation
Input is filtered to EN 55022 Class A
Very low 60Hz input ripple current
Modular design
Sinusoidal wave shape
Multiple input and output voltages available
4000VA of output power
Full electronic protection
Field-proven design topology
Applications
Marine / Automotive / RV
Electric Utilities and Substations
Telecom Power Plants
Manufacturing Locations
Steel Mills
Military Applications (COTS)
Industrial Controls
OEM Applications
Solar / Alternative Power Systems
Fuel Cells
Page 2
DC/AC Pure Sinewave Inverters
IVS4000R Series Pure Sinewave Inverters
24V (21-29 VDC) / 48V (42-56VDC) / 125VDC (Operating range 100…150VDC) /
Input Voltage
Input Protection ermal fuse, Inrush current limiting, Reverse polarity protection
Isolation
250VDC nominal (Operating range 220…275VDC)
Other inputs available-please consult factory
For 125VDC input version: 2250VDC input to output; 1700VDC input to chassis;
2250VDC output to chassis
For 250VDC input version: 2250VDC input to output; 2400VDC input to chassis
2250VDC output to chassis
Output Voltage
Wav e F orm Sinusoidal
Total Harmonic Distortion Less than 5% at full load
Eciency Min 82% at full load
Line Regulation Maximum 0.5%
Load Regulation Maximum ± 6% from 10% load to full load ( ± 1% option available)
Output Noise High frequency ripple is better than 500mV rms (20MHz BW)
Output Protection
EMI / RFI Suppression Meets requirements of EN55022, Class A conducted emissions as a minimum
Output Over-voltage Protection By internal supply voltage limiting at 140VAC on output
Output Over-load Protection: Hiccup at 6,000W
Load Crest Factor Maximum 2.5 at 90% load
Operating Temperature Range 0o C to +50o C
Humidity 5 - 95% non-condensing
Temperature Dri 0.05% per o C over operating temperature range
115Vrms / 34A rms or 220VAC/ 18A (50 or 60Hz standard) with grounded neutral. Isolated oating output optional (Consult factory for other voltages and frequencies)
Current limiting with short circuit protection, thermal shutdown with automatic recovery in case of continuous overload or insucient airow
Dimensions & Weight 6U x 19” rack-mount enclosure / Depth is 16” maximum / 53 lb (24.1 kg)
Connections
Safety Compliance to C22.2 No. 107.1 - 01 and UL 458
Input Voltage
Note: Specifications are subject to change without notice.