Power sensitive electronics
Marine & other Rugged Environments
Military Applications (COTS)
DC Battery Chargers
BCD615 Isolated Battery Charger
• Ultra-Quiet
•
without interference
• Rugged & Reliable
• Ensure
trouble free operation
• Fast & Accurate Charging
• Telecom Power Plants
• Electric Utilities and Substations
•
• Manufacturing Plants
• Steel Mills
•
• Industrial Controls
• OEM Applications
• Solar / Alternative Power Systems
• Fuel Cells
•
The model BCD615 Battery Charger charges either 12V, 24V or 48V
batteries from a 24V, 48V or 72VDC power source. Other battery voltages
up to 56 volts are also available by special order.
The all-new Current Mode switching design offers increased power and
reliability in a compact package. The low ripple charging profile and
standard equalize cycle greatly increases the lifetime of expensive battery
systems. Extra input and output filtering reduce EMI to extremely low
levels. Reliability features include an input fuse, thermal shutdown, current
limiting, reverse battery hookup protection and output short circuit
shutdown with automatic recovery.
The output voltage is easily adjusted 1.0 volts above or below the
standard output voltage to accommodate special charging require-ments.
Optional features include a Digital Volt/Ammeter, Remote Control Panel,
and/or 19” Rackmounting. We are confident that you will get many years
of reliable service from this DC Battery Charger.
• Fully Isolated Design
• Adjustable output voltage for
charging standard or deep cycle
lead-acid, VRLA or Gel cell type
battery
• Transient Voltage Suppressor
• Extremely rugged and we ll s uited
for marine and other demanding
environments
• High tolerance for shock and
vibration
• Ultra-quiet low EMI operation
• Can be left permanently
connected
• Spark free connection
• User selectable 2 or 3 stage
charging profile
• Audible & visual in d ic at ors
for output overload, low
input voltage, low output
voltage & over-temperature
• Over-temperature shutdown
• Short circuit protection
• Output over-voltage crowbar
• Dry contact output fail relay
• 3 year parts and labour
warranty

-25° to +40°C @ maximum output
(Optional -40°C extra wide-temp. operation avail.)
0 - 95°C Relative Humidity
(non-condensing) with optional conformal coating
NONE Ødb @ 3 ft (34.5 dB when fan operating)
13.6 ± 0.05 27.2 ± 0.05 54.4 ± 0.05
1 or 2 (3 Bank Option Available)
160 – 240 80 – 120 40 – 60
16.0 ± 0.5V 32.0 ± 1.0V 63.9 ± 2.0V
-30 mV/°C -60 mV/°C -120 mV/°C
1 inch (2.5 cm) all around
Black Anodize / Powder Epoxy Coat
Four contact output terminals
Built to meet UL458 & CSA 22.2.107.1
Noise on Input
20-35 40-60 65-90
< 50 mV
12 24 48
40 20 10
< 50 mV
Continuous 100% for 24 hours per day
Operating Temp.
Range
Humidity
Isolation
Derate Linearly 2.5% per °C from 40°C
> 10 yrs. (87,600 hrs)
Input-Case & Input-Output 1500VDC(500V @ 24V I/P)
Output-Case 500VDC (1500VDC @ 48V O/P)
4.3 in / 11.0 cm
3 years