Analytic Systems BCD615 Data Sheet

Page 1
Power sensitive electronics
years of safe and
Marine & other Rugged Environments
Military Applications (COTS)
Charge any DC/DC System
DC Battery Chargers
BCD615 Isolated Battery Charger
Ultra-Quiet
without interference
Rugged & Reliable
Ensure
trouble free operation
Fast & Accurate Charging
Telecom Power Plants
Electric Utilities and Substations
Manufacturing Plants
Steel Mills
Industrial Controls
OEM Applications
Solar / Alternative Power Systems
Fuel Cells
The model BCD615 Battery Charger charges either 12V, 24V or 48V batteries from a 24V, 48V or 72VDC power source. Other battery voltages up to 56 volts are also available by special order.
The all-new Current Mode switching design offers increased power and reliability in a compact package. The low ripple charging profile and standard equalize cycle greatly increases the lifetime of expensive battery systems. Extra input and output filtering reduce EMI to extremely low levels. Reliability features include an input fuse, thermal shutdown, current limiting, reverse battery hookup protection and output short circuit shutdown with automatic recovery.
The output voltage is easily adjusted 1.0 volts above or below the standard output voltage to accommodate special charging require-ments. Optional features include a Digital Volt/Ammeter, Remote Control Panel, and/or 19” Rackmounting. We are confident that you will get many years of reliable service from this DC Battery Charger.
Fully Isolated Design
Adjustable output voltage for
charging standard or deep cycle lead-acid, VRLA or Gel cell type battery
Transient Voltage Suppressor
Extremely rugged and we ll s uited
for marine and other demanding environments
High tolerance for shock and vibration
Ultra-quiet low EMI operation
Can be left permanently
connected
Spark free connection
User selectable 2 or 3 stage
charging profile
Audible & visual in d ic at ors for output overload, low input voltage, low output voltage & over-temperature
Over-temperature shutdown
Short circuit protection
Output over-voltage crowbar
Dry contact output fail relay
3 year parts and labour
warranty
Page 2
-25° to +40°C @ maximum output (Optional -40°C extra wide-temp. operation avail.)
0 - 95°C Relative Humidity (non-condensing) with optional conformal coating
Audible Noise
NONE Ødb @ 3 ft (34.5 dB when fan operating)
Typical Service Life
Nominal (ip)
24 48 72
Actual (Vdc)
Input Amps (max)
37.9 19.4 12.1
Input Fuse (ATC)
15 x 3 25 x 1 20 x 1
Output Nominal (op)
Output Volts (DC)
13.6 ± 0.05 27.2 ± 0.05 54.4 ± 0.05
Absorption Voltage (Vdc)
14.4 28.8 57.6
Charging Amps
Absorption to Float
6 Amps 3 Amps 1.5 Amps
Output Adjustment (Vdc)
± 1.0 V
Output Fuses (ATC)
40 x 2 30 x 2 15 x 2
Battery Banks
1 or 2 (3 Bank Option Available)
Battery Size (Amp Hrs.)
160 – 240 80 – 120 40 – 60
Output Crowbar
16.0 ± 0.5V 32.0 ± 1.0V 63.9 ± 2.0V
Output Ripple & Noise
Regulation (Line & Load)
< +/- 0.5%
Temperature Comp.
-30 mV/°C -60 mV/°C -120 mV/°C
Duty Cycle
Efficiency
> 75% @ Maximum Output
Stages
2 or 3 (user selectable)
Length
14.5 in / 36.8 cm
Width
9.9 in / 25.1 cm
Height
Clearance
1 inch (2.5 cm) all around
Material
Marine Grade Aluminium
Finish
Black Anodize / Powder Epoxy Coat
Fastenings
All 18-8 Stainless Steel
Weight
7.6 lb / 3.3 kg
Connections
Four contact output terminals
Warranty
Safety
Built to meet UL458 & CSA 22.2.107.1
Available From:
Noise on Input
20-35 40-60 65-90
< 50 mV
12 24 48
40 20 10
< 50 mV
Continuous 100% for 24 hours per day
Operating Temp. Range
Humidity
Isolation
Derate Linearly 2.5% per °C from 40°C
> 10 yrs. (87,600 hrs) Input-Case & Input-Output 1500VDC(500V @ 24V I/P)
Output-Case 500VDC (1500VDC @ 48V O/P)
4.3 in / 11.0 cm
3 years
Loading...