Analytic Systems BCD315 Data Sheet

Page 1
Power sensitive electronics
afe and
Charger.
Marine & other Rugged Environments
ons (COTS)
Charge any DC/DC System
DC Battery Charger s
BCD315 Isolated Battery Charger
without interference
Rugged & Reliable
Ensure years of s
trouble free operation
Fast & Accurate Charging
Telecommunications Equipment
Electric Utilities and Substations
Manufacturing Plants
Steel Mills
Military Applic a t i
Industrial Controls
The BCD315 battery charger provides up to 300 watts to charge a 12 or 24 or 48 Volt battery system (1, 2 or 3 Banks) from a 24V, 48V or 72VDC source. The batteries must share a common ground but the source can be on a different positive or negative ground.
The all-new Current Mode switching design offers increased power and reliability in a compact package. The low ripple charging profile and standard equalize cycle greatly increases the lifetime of expensive battery systems. Extra input and output filtering reduce EMI to extremely low levels. Reliability features include an input fuse, thermal shutdown, current limiting, reverse battery hookup protection and output short circuit shutdown with automatic recovery.
Optional features include a Digital Volt/Ammeter, a Remote Control Panel, and/or a second Battery Temperature Sensor. We are confident that you will get many years of reliable service from this DC Battery
Fully Isolated Design
Adjustable output voltage for
charging standard or deep cycle lead-acid, VRLA or Gel cell type battery
Transient Voltage Suppressor
Extremely rugged and well suited
for marine and other demanding environments
User selectable 2 or 3 stage charging profile
Audible & visual in d ic at or s for output overload, low input voltage, low output voltage & over-temperature
Over-temperature shutdown
Short circuit protection
OEM Applications
Solar / Alternative Power Systems
Fuel Cells
High tolerance for shock and
vibration
Ultra-quiet low EMI operation
Can be left permanently
connected
Spark free connection
Output over-voltage
crowbar
Inrush Current Limiting with solid state bypass
Dry contact output fail relay
3 year parts and labour
warranty
Page 2
-25° to +40°C @ maximum output 0 - 95°C Relative Humidity
Audible Noise
NONE Ødb @ 3 ft
Typical Service Life
> 10 yrs. (87,600 hrs)
Nominal (ip)
24 48 72
Actual (Vdc)
20-35 40-60 65-90
Input Amps (max)
Input Fuse
MDA25 MDA15 MDA-10
Output Nominal (op)
12 24 48
Output Volts (DC)
Absorption Voltage (Vdc)
14.4 28.8 57.6
Charging Amps
20 10 5
Absorption to Float
3.0 Amps 1.5 Amps 0.75 Amps
Output Adjustment (Vdc)
± 1.0 V
Output Fuses (AGC)
25A 15A 10A
Battery Banks
1, 2 or 3
Battery Size (Amp Hrs.)
Output Crowbar
16.0 ± 0.5V 32.0 ± 1.0V 63.9 ± 2.0V
Output Ripple & Noise
< 25 mV
Regulation (Line & Load)
< +/- 0.5%
Temperature Comp.
-30 mV/°C -60 mV/°C -120 mV/°C
Duty Cycle
Continuous 100% for 24 hours per day
Efficiency
> 75% @ Maximum Output
Stages
Length
Width
8.2 in / 20.8 cm
Height
3.5 in / 6.4 cm
Clearance
1 inch (2.5 cm) all around
Material
Marine Grade Aluminium
Finish
Black Anodize / Powder Epoxy Coat
Fastenings
All 18-8 Stainless Steel
Weight
7.5 lb / 3.4 kg
Connections
Four contact output terminals
Warranty
3 years
Safety
Available From:
Shown without Digital Meter
Shown with Digital Meter
Noise on Input
18.7 9.4 5.7
< 25 mV
13.6 ± 0.05 27.2 ± 0.05 54.4 ± 0.05
80 -120 40 - 60 20 - 30
2 or 3 (user selectable)
Operating Temp. Range
Humidity
Isolation
Derate Linearly 2.5% per °C from 40°C (Optional -40°C extra wide temp. operation avail.)
(non-condensing) with optional conformal coating
Input-Case & Input-Output 1500VDC (500VDC@24V I/P) Output-Case 500VDC
9.6 in / 24.4 cm
Built to meet UL458 & CSA 22.2.107.1