Analytic Systems BCA610 Data Sheet

Page 1
Power sensitive electronics
of safe and
Marine & other rugged environments
Electric Utilities and Substations Base Station Power
AC Battery Chargers
Ultra-Quiet
without interference
Rugged & Reliable
Ensure years
trouble free operation
Fast & Accurate Charging
Automotive / RV
(Radio & Telecommunications)
OEM Applications
Field Work / Construction Sites
Solar Power Systems
Emergency Power Backup (UPS)
Security Systems
Charge any 12, 24, 32, 48 or 72 Volt
Battery System
The BCA610 battery charger provides up to 600 watts to charge a 12, 24, 32, 48 or 72 Volt battery system (1, 2 or Optional 3 banks) from a 110 or 220VAC source. The batteries must share a common ground.
This all-new single board design incorporates state of the art switchmode technology for unmatched efficiency and ultra-quite operation. Multiple stages of filtering reduce radiated or conducted noise to very low levels. Extra features include adjustable output voltage, audible and visual indicators for low input voltage, low output voltage, over temperature and an equalize charging cycle. Safety features include both charger and battery over-temperature shutdown, current limiting, short circuit protection with automatic recovery, input undervoltage shutdown, reverse battery hook-up protection, a dry contact alarm relay output and output overvoltage crowbar.
Opti onal features include a Digital Volt/Ammeter, 3-Bank Charging, a Remote Control Panel, and/or a second Battery Temperature Sensor. We are confident that you will get many years of reliable service from this AC Battery Charger.
Adjustable output voltage for charging standard or deep cycle lead-acid, VRLA or Gel cell type battery
Extremely rugged and well s uite d for marine and other demanding environments
High tolerance for shock and vibration
Ultra-quiet low EMI operation
Can be left permanently connected
Can function as a power supply
User selectable 2 or 3 stage
charging profile
Audible & visual in d icators for output overload, low input voltage, low output voltage & over-temperature
Over-temperature shutdown
Temperature compensated
charging
Short circuit protection
Output over-voltage
crowbar
Inrush Current Limiting with solid state bypass
Dry contact output fail relay
3 year parts and labour
warranty
Page 2
-25° to +40°C @ maximum output (Optional -40°C extra wide temp. operation avail.)
0 - 95°C Relative Humidity
Audible Noise
NONE Ødb @ 3 ft
Typical Service Life
> 10 yrs. (87,600 hrs)
Nominal (ip)
110 220
Actual (Vac)
90-130 180-260
Input Amps (max)
9.3 4.7
Input Fuse (MDA)
10A 5A
Input Frequency
45-65 Hz
Noise on Input
< 50 mV
Output Nominal (op)
12 24 32 48 72
Output Volts (DC)
Absorption Voltage (Vdc)
14.4 28.8 38.4 57.6 86.4
Charging Amps
40 22 16.5 11 7
Absorption to Float (15%)
Output Adjustment (Vdc)
± 1V
Output Fuses (ATC)
40 x 2 30 x 2 20 x 2 15 x 2 15 x 2
Battery Banks
1 or 2 (3 Bank Option Available)
Battery Size (Amp Hrs.)
160 – 240 88 – 132 66 – 99 44 – 66 22 – 33
Output Crowbar
16.0 ± 0.5V 32.0 ± 1.0V 42.7 ± 1.3V 63.9 ± 2.0V
Output Ripple & Noise
< 50 mV
Regulation (Line & Load)
< +/- 0.5%
Temperature Comp.
-30 mV/°C -60 mV/°C -80 mV/ °C -120 mV/°C -240 mV/°C
Duty Cycle
Continuous 100% for 24 hours per day
Efficiency
Stages
2 or 3 (user selectable)
Material
Marine Grade Aluminium
Black Anodize / Powder Epoxy Coat
Fastenings
All 18-8 Stainless Steel
Weight
7.2 lb / 3.3 kg
Four contact output terminal
Warranty
3 years
Built to meet UL458 & CSA 22.2.107.1
Available From:
Operating Temp. Range
Humidity
13.6 ± 0.05 27.2 ± 0.05 36.3 ± 0.05 54.4 ± 0.05 81.6 ±0.05
6.0 Amps 3.3 Amps 2.48 Amps 1.65 Amps 1.05 Amps
> 75% @ Maximum Output
Isolation
Derate Linearly 2.5% per °C from 40°C
(non-condensing) with optional conformal coating
Input-Case & Input-Output 1500VDC Output-Case 500VDC (1500V @ 48V Output)
Length Width Height Clearance
Finish
Connections
Safety
14.5 in / 36.8 cm
9.9 in / 25.1 cm
3.0 in / 7.6 cm 1 inch (2.5 cm) all around
Loading...