Analytic Systems BCA310 Data Sheet

Page 1
BCA310 Battery Charger
Ultra-Quiet Power sensitive electronics
without interference
Rugged & Reliable  Ensure years of safe and
trouble free operation
Fast & Accurate Charging
Marine & other rugged environments  Automotive / RV  Electric Utilities and Substations  Base Station Power
(Radio & Telecommunications)
 OEM Applications  Field Work / Construction Sites  Solar Power Systems  Emergency Power Backup (UPS)  Security Systems  Charge any 12, 24, 32, or 48 Volt
Battery System
The BCA310 Battery Charger provides up to 300 watts to charge a 12, 24, 32, 48 or 72-volt battery system (1, 2 or 3 banks) from a 110 or 220VAC source. The batteries must share a common ground.
This all-new single board design incorporates state of the art switchmode technology for unmatched efficiency and ultra-quiet operation. Multiple stages of filtering reduce radiated or conducted noise to very low levels. Extra features include adjustabl e output voltage, audible and visual indicators for low input voltage, low output voltage, over temperature and an equalize charging cycle. Safety features include both charger and battery over-temperature shutdown, current limiting, short circuit protection with automatic recovery, input undervoltage shutdown, reverse battery hook-up protection, a dry contact alarm relay output and output overvoltag e crowbar.
Optional features include a Digital Volt/Ammeter, a Remote Control Panel, and/or a second Battery Temperature Sensor. We are confident that you will get many years of reliable service from this AC Battery Charger.
Adjustable output voltage for charging
standard or deep cycle lead-acid, VRLA or Gel cell type battery
Extremely rugged and well suited for
marine and other demanding environments
High tolerance for shock and vibration Ultra-quiet low EMI operation Can be left permanently connected Can function as a power supply User selectable 2 or 3 stage charging
profile
Audible & visual indicators for
output overload, low input voltage, low output voltage & over-temperature
Over-temperature shutdown Temperature compensated
charging
Short circuit protection Output over-voltage crowbar Inrush Current Limiting with solid
state bypass
Dry contact output fail relay 3 year parts and labour warranty
Page 2
Shown without Digital Meter
Shown with Digital Meter
Nominal (ip) 110 220 Actual (Vac) 105-125 210-250 Input Amps (max) 3.7 1.8 Input Fuse (MDA) 5A 3A Input Frequency 45-65 Hz Noise on Input < 25 mV
Operating Temp. Range
Humidity Audible Noise NONE Ødb @ 3 ft
Typical Service Life > 10 yrs. (87,600 hrs) Isolation
Output Nominal (op) 12 24 32 48 72 Output Volts (DC) 13.6 ± 0.05 27.2 ± 0.05 36.3 ± 0.05 54.4 ± 0.05 81.6 ± 0.05 Absorption Voltage (Vdc) 14.4 28.8 38.4 57.6 86.4 Charging Amps 20 10 7.5 5 2.5 Absorption to Float (15%) 3.0 Amps 1.5 Amps 1.1 Amps 0.75 Amps 0.38Amps Output Adjustment (Vdc) ± 1.0V Output Fuses (AGC) 25 Amp x 1 15 Amp x 1 10 Amp x 1 7 Amp x 1 6 Amp x 1 Battery Banks 1, 2 or 3 Bank Battery Size (Amp Hrs.) 80-120 40-60 30-45 20-30 10-15 Output Crowbar 16.0 ± 0.5V 32.0 ± 1.0V 42.7 ± 1.3V 63.9 ± 2.0V 95.4± 4.0V Output Ripple & Noise < 25 mV Regulation (Line & Load) < +/- 0.5% Temperature Comp. -30 mV/°C -60 mV/°C -80 mV/°C -120 mV/°C -240 mV/°C Duty Cycle Continuous 100% for 24 hours per day Efficiency > 75% @ Maximum Output Stages 2 or 3 (user selectable)
-25° to +40°C @ maximum output Derate Linearly 2.5% per °C from 40°C (Optional -40°C extra wide temp. operation avail.) 0 - 95°C Relative Humidity (non-condensing) with optional conformal coating
Input-Case & Input-Output 1500VDC Output-Case 500VDC (1500VDC @ 48V O/P)
Length 9.6 in / 24.4 cm Width 8.2 in / 20.8 cm Height 3.5 in / 6.4 cm Clearance 1 inch (2.5 cm) all around Material Marine Grade Aluminium
Finish Fastenings All 18-8 Stainless Steel
Weight 7.5 lb / 3.4 kg Connections Warranty 3 years
Safety
Black Anodize / Powder Epoxy Coat
Four contact output terminals
Built to meet UL458 & CSA22.2.107.1 ABS 11-HS794404A-PDA