Marine & other rugged environments
Electric Utilities and Substations
Base Station Power
AC Battery Chargers
BCA1000 Series Battery Charger
(Shown with Optio nal Di git al Met er)
• Ultra-Quiet
• Power sensitive electro
without interference
• Rugged & Reliable
•
trouble free operation
• Fast & Accurate Charging
•
• Automotive / RV
•
•
(Radio & Telecommunications)
• OEM Applications
• Field Work / Construction Sites
• Solar Power Systems
• Emergency Power Backup (UPS)
• Security Systems
• Charge any 12, 24, 32, 48 or 72 Volt
The BCA1000 battery charger provides up to 1000 watts to charge a 12, 24, 32,
48 or 72 Volt battery system (1, 2 or Optional 3 banks) from a 110 or 220VAC
source. The batteries must share a common ground.
This all-new single board design incorporates state of the art switch mode
technology for unmatched efficiency and ultra-quite operation. Multiple stages of
filtering reduce radiated or conducted noise to very low levels. Extra features
include adjustable output voltage, audible and visual indicators for low input
voltage, low output voltage, over temperature and an equalize charging cycle.
Safety features include charger and battery over-temperature shutdown, current
limiting, short circuit protection with automatic recovery, input under voltage
shutdown, reverse battery hook-up protection, a dry contact alarm relay output
and output overvoltage crowbar.
Optional features include a Digital Volt/Ammeter, 3-Bank Charging, a Remote
Control Panel, and/or a second Battery Temperature Sensor. We are confident
that you will get many years of reliable service from this AC Battery Charger.
• Ideal as Global Marine Distress Safety System (GMDSS) power supply
when equipped with optional
voltmeter and ammeter.
• Adjustable output voltage for charging
standard or deep cycle lead-acid,
VRLA or Gel cell type battery
• Temperature compensated charging
• High tolerance for shock and vibration
• Ultra-quiet low EMI operation
• Can be left permanently connected
• Can function as a power supply
• Dry contact output fail relay
• User selectable 2 or 3 stage
charging profile
• 3 Bank Option Available
• Audible & visual indicators for
output overload, low input
voltage, low output voltage &
over-temperature
• Over-temperature shutdown
• Short circuit protection
• Output over-voltage crowbar
• Inrush Current Limiting with
solid state bypass
• Thermostatically controll ed fan
• 3 year parts and labour

0 - 95°C Relative Humidity
(non-condensing) with optional conformal coating
Output-Case 500VDC (1500V @ 48V Output)
20A(12V) 10 (12V)
25A all others 15A all others
1 inch (2.5 cm) all around
Black Anodize / Powder
Epoxy Coat
Built to meet UL458 &
CSA22.2.107.1
13.6 ± 0.05 27.2 ± 0.05 36.3 ± 0.05 54.4 ± 0.05 81.6± 0.05
Absorption to Float (15%)
9 Amps 6 Amps 4.5 Amps 3.0 Amps 2.0 Amps
40 x 2 40 x 2 40 x 2 30 x 2 15 x 2
1 or 2 (3 Bank Option Available)
16.0 ± 0.5V 32.0 ± 1.0V 42.7 ± 1.3V 63.9 ± 2.0V 95.9± 4.0V
240 – 360 160 – 240 120 – 180 80 – 120 10-60
-30 mV/°C -60 mV/°C -80 mV/°C -120 mV/°C -240 mV/°C
Continuous 100% for 24 hours per day
90 – 130 180 - 260
Input Fuse (MDA)
< 50 mV
> 75% @ Maximum Output
2 or 3 (user selectable)
Operating Temp. Range
Humidity
Audible Noise
Typical Service Life
Isolation
-25° to +40°C @ maximum output
Derate Linearly 2.5% per °C from 40°C
(Optional -40°C extra wide temp. operation avail.)
NONE Ødb @ 3 ft (34.5 dB when fan operating)
> 10 yrs. (87,600 hrs)
Input-Case & Input-Output 1500VDC
Marine Grade Aluminium
Finish
Connections
Safety
Four contact output
3 years