ANALOG DEVICES ADM1029 Service Manual

查询ADM1029供应商查询ADM1029供应商
Dual PWM Fan Controller and Temperature
a
FEATURES Software Programmable and Automatic Fan Speed
Control
Automatic Fan Speed Control Allows Control
Independent of CPU Intervention after Initial Setup
Control Loop Minimizes Acoustic Noise and Power
Consumption Remote and Local Temperature Monitoring Dual Fan Speed Measurement Supports Backup and Redundant Fans
FUNCTIONAL BLOCK DIAGRAM
ADM1029
SLAVE ADDRESS
REGISTER
PRESENT1
FAULT1
FAN 1 STATUS
REGISTER
FAN 1 MIN
SPEED REGISTER
Monitor for High Availability Systems
ADM1029*
Supports Hot Swapping of Fans Cascadable Fault Output Allows Fault Signaling
between Multiple ADM1029s Address Pin Allows Up to Eight ADM1029s in A System Small 24-Lead QSOP Package
APPLICATIONS Network Servers and Personal Computers Microprocessor-Based Office Equipment High Availability Telecommunications Equipment
V
CC
SERIAL BUS
INTERFACE
ADDRESS POINTER
REGISTER
INTERRUPT MASK
REGISTERS
INTERRUPT STATUS
REGISTERS
INTERRUPT
MASKING
SCL
SDA
INT
CFAULT
DRIVE1
TACH1
TACH2
PRESENT2
FAULT2
DRIVE2
*Protected by U.S. Patent Numbers 6,255,973 and 6,188,189
PWM
CONTROLLER
PWM
CONTROLLER
FAN 1 ALARM
SPEED REGISTER
FAN 1 HOT-PLUG
SPEED REGISTER
FAN SPEED
COUNTER
FAN 2 STATUS
REGISTER
FAN 2 MIN
SPEED REGISTER
FAN 2 ALARM
SPEED REGISTER
FAN 2 HOT-PLUG
SPEED REGISTER
REFERENCE
GND
REV. 0
Information furnished by Analog Devices is believed to be accurate and reliable. However, no responsibility is assumed by Analog Devices for its use, nor for any infringements of patents or other rights of third parties that may result from its use. No license is granted by implication or otherwise under any patent or patent rights of Analog Devices.
LIMIT COMPARATOR
VALUE AND LIMIT
REGISTERS
G.P. I/O REGISTER
ADC
ANALOG
MUX
BANDGAP
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A. Tel: 781/329-4700 www.analog.com Fax: 781/326-8703 © Analog Devices, Inc., 2001
REMOTE SENSOR
SIGNAL
CONDITIONING
BANDGAP
TEMP SENSOR
RESET
GPIO2
AIN1/GPIO1
AIN0/GPIO0
D2+/GPIO6
D2–/GPIO5
D1+/GPIO4
D1–/GPIO3
TMIN/INSTALL
ADD
1, 2
ADM1029–SPECIFICATIONS
(TA = T
Parameter Min Typ Max Unit Test Conditions/Comments
POWER SUPPLY
Supply Voltage, V Supply Current, I
CC
CC
3.0 3.30 5.5 V
TEMPERATURE-TO-DIGITAL CONVERTER
Internal Sensor Accuracy ± 1 ± 3 °C Resolution 1 °C External Diode Sensor Accuracy ± 3 ± 5 °C0°C ≤ T Resolution 1 °C Remote Sensor Source Current 90 µA High Level
ANALOG-TO-DIGITAL CONVERTER
Total Unadjusted Error, TUE ± 1 % Note 3 Differential Nonlinearity, DNL ± 1 LSB Power Supply Sensitivity ± 1 %/ V Conversion Time
Analog Input or Internal Temperature 11.6 ms External Temperature 185.6 ms
FAN RPM-TO-DIGITAL CONVERTER
Accuracy ± 6%60°C ≤ TA 100°C: VCC = 3.3 V Full-Scale Count 255 FAN 1 and FAN 2 Nominal Input RPM
4
Internal Clock Frequency 56.4 60.0 63.6 kHz
OPEN-DRAIN DIGITAL OUTPUTS (INT, CFAULT)
Output Low Voltage, V High Level Output Current, I
OL
OH
OPEN-DRAIN SERIAL DATA BUS OUTPUT (SDA)
Output Low Voltage, V High Level Output Leakage Current, I
OL
OH
SERIAL BUS DIGITAL INPUTS (SCL, SDA)
Input High Voltage, V Input Low Voltage, V
IL
IH
2.1 V
Hysteresis 500 mV
DIGITAL INPUT LOGIC LEVELS RESET, GPIO1-6, FAULT1/2, TACH1/2, PRESENT1/2
Input High Voltage, V Input Low Voltage, V
IL
IH
2.1 V
DIGITAL INPUT CURRENT
Input High Current, I Input Low Current, I Input Capacitance, C
SERIAL BUS TIMING
Clock Frequency, f Glitch Immunity, t Bus Free Time, t Start Setup Time, t Start Hold Time, t
IH
IL
IN
5
SCLK
SW
BUF
SU:STA
HD:STA
Stop Condition Setup Time, t
SU:STO
–1 µAV
10 100 kHz See Figure 1
4.7 µs See Figure 1
4.7 µs See Figure 1 4 µs See Figure 1 4 µs See Figure 1
to T
MIN
, VCC = V
MAX
MIN
to V
, unless otherwise noted.)
MAX
1.7 3.0 mA Interface Inactive, ADC Active
1.5 mA ADC Inactive, DAC Active 10 60 µA Shutdown Mode
100°C
A
5.5 µA Low Level
8800 rpm Divisor = 1, Fan Count = 153 4400 rpm Divisor = 2, Fan Count = 153 2200 rpm Divisor = 4, Fan Count = 153 1100 rpm Divisor = 8, Fan Count = 153
0.4 V I
0.1 1 µAV
0.4 V I
0.1 1 µAV
= –6.0 mA, VCC = 3 V
OUT
= V
OUT
CC
= –6.0 mA, VCC = 3 V
OUT
= V
OUT
CC
0.8 V
0.8 V
= V
IN
+1 µAV
IN
CC
= 0
20 pF
50 ns See Figure 1
–2–
REV. 0
ADM1029
Parameter Min Typ Max Unit Test Conditions/Comments
5
SERIAL BUS TIMING
SCL Low Time, t SCL High Time, t SCL, SDA Rise Time, t SCL, SDA Fall Time, t Data Setup Time, t Data Hold Time, t
NOTES
1
All voltages are measured with respect to GND, unless otherwise specified.
2
Typicals are at TA = 25°C and represent most likely parametric norm. Shutdown current typ is measured with VCC = 3.3 V.
3
TUE (Total Unadjusted Error) includes Offset, Gain, and Linearity errors of the ADC, multiplexer.
4
The total fan count is based on two pulses per revolution of the fan tachometer output.
5
Timing specifications are tested at logic levels of VIL = 0.8 V for a falling edge and VIH = 2.1 V for a rising edge.
Specifications subject to change without notice.
(continued)
LOW
HIGH
SU:DAT
HD:DAT
1.3 µs See Figure 1 450µs See Figure 1
R
F
1000 ns See Figure 1
300 ns See Figure 1 250 ns See Figure 1 300 ns See Figure 1
ABSOLUTE MAXIMUM RATINGS*
Positive Supply Voltage (VCC) . . . . . . . . . . . . . . . . . . . . . 6.5 V
Voltage on Pins 13–18 . . . . . . . . . . . . –0.3 V to (V
+ 0.3 V)
CC
Voltage on Any Other Input or Output Pin . . . . –0.3 V to +6.5 V
Input Current at Any Pin . . . . . . . . . . . . . . . . . . . . . . . ±5 mA
Package Input Current . . . . . . . . . . . . . . . . . . . . . . . ± 20 mA
Maximum Junction Temperature (T
max) . . . . . . . . . . 150°C
J
Storage Temperature Range . . . . . . . . . . . . –65°C to +150°C
Lead Temperature
Vapor Phase (60 sec) . . . . . . . . . . . . . . . . . . . . . . . . . 215°C
Infrared (15 sec) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200°C
ESD Rating All Pins . . . . . . . . . . . . . . . . . . . . . . . . . . . 2000 V
*Stresses above those listed under Absolute Maximum Ratings may cause perma-
nent damage to the device. This is a stress rating only; functional operation of the device at these or any other conditions above those indicated in the operational section of this specification is not implied. Exposure to absolute maximum rating conditions for extended periods may affect device reliability.
THERMAL CHARACTERISTICS
24-Lead QSOP Package:
= 105°C/W, θJC = 39°C/W
θ
JA
ORDERING GUIDE
Temperature Package Package
Model Range Description Option
ADM1029ARQ 0°C to 100°C Shrink Small Outline RQ-24
Package (QSOP)
PIN CONFIGURATION
1
DRIVE1
2
FAULT1
3
TACH1
SCL
SDA
GND
V
INT
GPIO2
RESET
CC
4
5
6
7
(Not To Scale)
8
9
10
11
12
ADM1029
TOP VIEW
PRESENT1
CFAULT
24
DRIVE2
23
FAULT2
22
TACH2
21
PRESENT2
20
AIN1/GPIO1
19
AIN0/GPIO0
18
TMIN/INSTALL
17
D2+/GPIO6
16
D2–/GPIO5
15
ADD
14
D1+/GPIO4
13
D2–/GPIO3
REV. 0
SCL
SDA
t
R
t
LOW
t
HD;STA
t
BUF
S
P
t
HD;DAT
t
HIGH
t
F
t
SU;DAT
t
HD;STA
t
t
SU;STA
S
SU;STO
P
Figure 1. Diagram for Serial Bus Timing
–3–
ADM1029
PIN FUNCTION DESCRIPTIONS
Pin No. Mnemonic Description
1 DRIVE1 Open Drain Digital Output. Pulsewidth Modulated (PWM) output to control the speed of
Fan 1. Requires 10 k typical pull-up resistor.
2 FAULT1 Open Drain Digital I/O. When used with a fan having a fault output, a Logic 0 input to this pin
signals a fault on Fan 1. Also used as a fault output.
3 TACH1 Open Drain Digital Input. Digital fan tachometer input for Fan 1. Will accept logic signals up
to 5 V even when V
4 PRESENT1
Open Drain Digital Input. A shorting link in the fan connector holds this pin low when
Fan 1 is connected. 5 SCL Open Drain Digital Input. Serial Bus Clock. Requires 2.2 k pull-up typical. 6 SDA Digital I/O. Serial Bus bidirectional data. Open-drain output requires 2.2 k pull-up. 7 GND System Ground 8V
CC
Power (3.0 V to 5.5 V). Typically powered from 3.3 V power rail. Bypass with the parallel
combination of 10 µF (electrolytic or tantalum) and 0.1 µF (ceramic) bypass capacitors. 9 CFAULT
Open Drain Digital I/O. Cascade fault input/output used for fault signaling between
multiple ADM1029s. 10 INT Digital Output. Interrupt Request (Open Drain). The output is enabled when Bit 1 of the
Configuration Register is set to 0. The default state is enabled. 11 GPIO2 Open Drain Digital I/O. General-purpose logic I/O pin. 12 RESET Open Drain Digital Input. Active low reset input. 13 D1–/GPIO3 Analog Input/Open Drain Digital I/O. Connected to cathode of external temperature-sensing
diode, or may be reconfigured as a general-purpose logic input/output. 14 D1+/GPIO4 Analog Input/Open Drain Digital I/O. Connected to anode of external temperature-sensing
diode, or may be reconfigured as a general-purpose logic input/output. 15 ADD Eight-Level Analog Input. Used to set the three LSBs of the serial bus address. 16 D2–/GPIO5 Analog Input/Open Drain Digital I/O. Connected to cathode of external temperature-sensing
diode, or may be reconfigured as a general-purpose logic input/output. 17 D2+/GPIO6 Analog Input/Open Drain Digital I/O. Connected to anode of external temperature-sensing
diode, or may be reconfigured as a general-purpose logic input/output. 18 TMIN/INSTALL Eight-Level Analog Input. The voltage on this pin defines whether automatic fan speed control
is enabled, the minimum temperature at which the fan(s) will turn on in automatic speed con-
trol mode, and the number of fans that should be installed. 19 AIN0/GPIO0 Analog Input/Open Drain Digital I/O. May be configured as a 0 V to 2.5 V analog input or as a
general-purpose digital I/O pin. 20 AIN1/GPIO1 Analog Input/Open Drain Digital I/O. May be configured as a 0 V to 2.5 V analog input or as a
general-purpose digital I/O pin. 21 PRESENT2 Open Drain Digital Input. A shorting link in the fan connector holds this pin low when Fan 2
is connected. 22 TACH2 Open Drain Digital Input. Digital fan tachometer input for Fan 2. Will accept logic signals up
to 5 V even when V 23 FAULT2 Open Drain Digital I/O. When used with a fan having a fault output, a Logic 0 input to this pin
signals a fault on Fan 2. Also used as a fault output. 24 DRIVE2 Open Drain Digital Output. Pulsewidth Modulated (PWM) output to control the speed of
Fan 2. Requires 10 k typical pull-up resistor.
is lower than 5 V.
CC
is lower than 5 V.
CC
–4–
REV. 0
Typical Performance Characteristics–ADM1029
110
100
90
80
70
60
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 100 110
READING
MEASURED TEMPERATURE
1 0
12345678
910111213141516
1.0 2.2 3.3 4.7 10.0 22.0 47.0
REMOTE TEMPERATURE ERROR – C
DXP – DXN CAPACITANCE – nF
15
10
5
0
5
10
15
REMOTE TEMPERATURE ERROR C
20
0 3.3 10 30 100
LEAKAGE RESISTANCE – M
DXP TO GND
DXP TO VCC(3.3V)
TPC 1. Remote Temperature Error vs. PC Board Track Resistance
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0
REMOTE TEMPERATURE ERROR – C
V
0.5
1.0
0 1 4 8 12 16 20 50 100 200 300
= 100mV p-p
IN
VIN = 250mV p-p
FREQUENCY – MHz
400
500
600
TPC 2. Remote Temperature Error vs. Power Supply Noise Frequency
TPC 4. Pentium® III Temperature Measurement vs. ADM1029 Reading
TPC 5. Remote Temperature Error vs. Capacitance Between D+ and D–
10
9
8
7
6
5
4
3
Pentium is a registered trademark of Intel Corporation.
REV. 0
2
1
REMOTE TEMPERATURE ERROR – C
0
–1
0 0.4 0.8 10 600150 40050 250 500100 200 350 450 550300
FREQUENCY – MHz
TPC 3. Remote Temperature Error vs. Common-Mode Noise Frequency
V
= 100mV p-p
IN
V
= 60mV p-p
IN
VIN = 40mV p-p
–5–
80
70
60
50
40
30
SUPPLY CURRENT – A
20
10
0
0 1 5 10 25 50 75 100 250 500 750 1000
SCLK FREQUENCY – kHz
VCC = 5V
VCC = 3.3V
TPC 6. Standby Current vs. Clock Frequency
ADM1029
13
12
11
10
9
8
7
6
5
4
3
2
1
REMOTE TEMPERATURE ERROR – C
0
–1
0
12 40020 300100 5001 4 8 16 50 200
VIN = 40mV p-p
VIN = 30mV p-p V
IN
FREQUENCY – MHz
= 20mV p-p
600
TPC 7. Remote Temperature Error vs. Differential-Mode Noise Frequency
32
30
28
26
24
22
20
18
16
14
12
10
SUPPLY CURRENT – A
8
6
4
2
0
1.0 1.4 1.8 2.2 2.6 3.0 3.4 3.8 4.2 4.6 SUPPLY VOLTAGE – V
TPC 8. Standby Supply Current vs. Supply Voltage
10
9
8
7
6
5
4
3
2
1
LOCAL TEMPERATURE ERROR – C
0
–1
0 1 4 8 12 16 20 50 100 200 300 400 500 600
FREQUENCY – MHz
VIN = 250mV p-p
VIN = 100mV p-p
TPC 10. Local Sensor Temperature Error vs. Power Supply Noise Frequency
120
110
100
90
80
70
60
50
40
TEMPERATURE – C
30
20
10
0
0 1 2 3 4 5 6 7 8 9 10
TIME – Seconds
TPC 11. ADM1029 Response to Thermal Shock
1.80
1.75
1.70
1.65
1.60
1.55
1.50
1.45
1.40
1.35
1.30
1.25
SUPPLY CURRENT – mA
1.20
1.15
1.10
1.05
1.00
2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6 4.8 5.0
SUPPLY VOLTAGE – V
TPC 9. Supply Current vs. Supply Voltage
–6–
0.10
0.00
0.10
0.20
0.30
0.40
0.50
0.60
ERROR C
0.70
0.80
0.90
1.00
1.10
1.20
0 20 40 60 80 85 100 105 120
TEMPERATURE – C
TPC 12. Remote Temperature Error
REV. 0
ADM1029
0.05
0.00
0.05
0.10
0.15
0.20
0.25
0.30
ERROR C
0.35
0.40
0.45
0.50
0.55
0.60
0 20 40 60 80 85 100 105 120
TEMPERATURE – C
TPC 13. Local Temperature Error
PRODUCT DESCRIPTION
The ADM1029 is a versatile fan controller and monitor for use in personal computers, servers, telecommunications equipment, or any high-availability system where reliable control and moni­toring of multiple cooling fans is required. Each ADM1029 can control the speed of one or two fans and can measure the speed of fans that have a tachometer output. The ADM1029 can also measure the temperature of one or two external sensing diodes or an internal temperature sensor, allowing fan speed to be adjusted to keep system temperature within acceptable limits. The ADM1029 has FAULT inputs for use with fans that can signal failure conditions, and inputs to detect whether or not fans are connected.
The ADM1029 communicates with the host processor over an System Management (SMBus) serial bus. It supports eight different serial bus addresses, so that up to eight devices can be connected to a common bus, controlling up to sixteen fans. This makes software support and hardware design scalable.
The ADM1029 has an interrupt output (INT) that allows it to signal fault conditions to the host processor. It also has a separate, cascadable fault output (CFAULT) that allows the ADM1029 to signal a fault condition to other ADM1029s.
The ADM1029 has a number of useful features including an automatic fan speed control option implemented in hardware with no software requirement, automatic use of backup fans in the event of fan failure, and supports hot-swapping of failed fans.
Table I. Resistor Ratios for Setting Serial Bus Address
FUNCTIONAL DESCRIPTION
SERIAL BUS INTERFACE
Control of the ADM1029 is carried out via the serial bus. The ADM1029 is connected to this bus as a slave device, under the control of a master device.
The ADM1029 has a 7-bit serial bus address. The four MSBs of the address are set to 0101. The three LSBs can be set by the user to give a total of eight different addresses, allowing up to eight ADM1029s to be connected to a single serial bus segment. To minimize device pin count and size, the three LSBs are set using a single pin (ADD, Pin 15). This is an 8-level input whose input voltage is set by a potential divider. The voltage on ADD is sampled immediately after power-up and digitized by the on-chip ADC to determine the value of the 3 LSBs. Since ADD is sampled only at power-up, any changes made while power is on will have no effect.
V
CC
R1
ADD
R2
GND
ADM1029
Figure 2. Setting the Serial Address
Table I shows resistor values for setting the 3 LSBs of the serial bus address. The same principle is used to set the voltage on Pin 18 (TMIN/INSTALL), which controls the automatic fan speed control function, and also tells the ADM1029 how many fans should be installed, as described later.
If several ADM1029s are used in a system, their ADD inputs can tap off a single potential divider, as shown in Figure 3.
V
CC
ADDRESS XXXX111
1.5k
ADDRESS XXXX110
1k
ADDRESS XXXX101
1k
ADDRESS XXXX100
1k
ADDRESS XXXX011
1k
ADDRESS XXXX010
1k
ADDRESS XXXX001
1.5k
ADDRESS XXXX000
GND
ADD
ADD
ADD
ADD
ADD
ADD
ADD
ADD
ADM1029 #1
ADM1029 #2
ADM1029 #3
ADM1029 #4
ADM1029 #5
ADM1029 #6
ADM1029 #7
ADM1029 #8
Figure 3. Setting Address of up to Eight ADM1029s
3 MSBs Ideal Ratio R1 R2 Actual Error of ADC R2/(R1 + R2) (k⍀)(k⍀) R2/(R1 + R2) % Address
111 N/A 0 1 0 0101111 110 0.8125 18 82 0.82 +0.75 0101110 101 0.6875 22 47 0.6812 –0.63 0101101 100 0.5625 12 15 0.5556 –0.69 0101100 011 0.4375 15 12 0.4444 +0.69 0101011 010 0.3125 47 22 0.3188 +0.63 0101010 001 0.1875 82 18 0.18 –0.75 0101001 000 N/A 0 0 0 0101000
REV. 0
–7–
ADM1029
The serial bus protocol operates as follows:
1. The master initiates data transfer by establishing a START condition, defined as a high-to-low transition on the serial data line SDA, while the serial clock line SCL remains high. This indicates that an address/data stream will follow. All slave peripherals connected to the serial bus respond to the START condition, and shift in the next eight bits, consisting of a 7-bit address (MSB first) plus an R/W bit, which deter­mines the direction of the data transfer, i.e., whether data will be written to or read from the slave device.
The peripheral whose address corresponds to the transmitted address responds by pulling the data line low during the low period before the ninth clock pulse, known as the Acknowl­edge Bit. All other devices on the bus now remain idle while the selected device waits for data to be read from or written to it. If the R/W bit is a 0, the master will write to the slave device. If the R/W bit is a 1 the master will read from the slave device.
2. Data is sent over the serial bus in sequences of nine clock pulses, eight bits of data followed by an acknowledge bit from the slave device. Transitions on the data line must
191
SCL
occur during the low period of the clock signal and remain stable during the high period, as a low-to-high transition when the clock is high may be interpreted as a STOP signal. The number of data bytes that can be transmitted over the serial bus in a single READ or WRITE operation is limited only by what the master and slave devices can handle.
3. When all data bytes have been read or written, stop condi­tions are established. In WRITE mode, the master will pull the data line high during the tenth clock pulse to assert a STOP condition. In READ mode, the master device will override the acknowledge bit by pulling the data line high during the low period before the ninth clock pulse. This is known as No Acknowledge. The master will then take the data line low during the low period before the tenth clock pulse, high during the tenth clock pulse to assert a STOP condition.
Any number of bytes of data may be transferred over the serial bus in one operation, but it is not possible to mix read and write in one operation, because the type of operation is determined at the beginning and cannot subsequently be changed without starting a new operation.
9
SDA
START BY
MASTER
0
101A2
SERIAL BUS ADDRESS BYTE
FRAME 1
SCL (CONTINUED)
SDA (CONTINUED)
A0
A1
R/W
ACK. BY
ADM1029
1
D7 D6 D5
D6
D7
ADDRESS POINTER REGISTER BYTE
D4 D3 D2 D1
D5
FRAME 2
D4 D3 D2 D1
FRAME 3
DATA BYTE
D0
ACK. BY
ADM1029
D0
ACK. BY
ADM1029
9
STOP BY
MASTER
Figure 4a. Writing a Register Address to the Address Pointer Register, then Writing Data to the Selected Register
SCL
SDA
START BY
MASTER
191
0
101A2
SERIAL BUS ADDRESS BYTE
FRAME 1
A0 D7
A1
R/W
ACK. BY
ADM1029
D6
ADDRESS POINTER REGISTER BYTE
D4 D3 D2 D1
D5
FRAME 2
D0
ACK. BY
ADM1029
9
STOP BY MASTER
Figure 4b. Writing to the Address Pointer Register Only
191
SCL
9
SDA
START BY
MASTER
0
101A2
SERIAL BUS ADDRESS BYTE
D6 D5
D4 D3 D2 D1
DATA BYTE FROM ADM1029
FRAME 2
FRAME 1
A0 D7
A1
R/W
ACK. BY
ADM1029
Figure 4c. Reading Data from a Previously Selected Register
–8–
D0
NO ACK.
BY MASTER
STOP BY MASTER
REV. 0
ADM1029
In the case of the ADM1029, write operations contain either one or two bytes, and read operations contain one byte, and perform the following functions:
To write data to one of the device data registers or read data from it, the Address Pointer Register must be set so that the correct data register is addressed, data can be written into that register or read from it. The first byte of a write operation always contains an address that is stored in the Address Pointer Regis­ter. If data is to be written to the device, the write operation contains a second data byte that is written to the register selected by the address pointer register.
This is illustrated in Figure 4a. The device address is sent over the bus followed by R/W set to 0. This is followed by two data bytes. The first data byte is the address of the internal data register to be written to, which is stored in the Address Pointer Register. The second data byte is the data to be written to the internal data register.
When reading data from a register there are two possibilities:
1. If the ADM1029’s Address Pointer Register value is unknown or not the desired value, it is first necessary to set it to the correct value before data can be read from the desired data register. This is done by performing a write to the ADM1029 as before, but only the data byte containing the register address is sent, as data is not to be written to the register. This is shown in Figure 4b.
A read operation is then performed consisting of the serial bus address, R/W bit set to 1, followed by the data byte read from the data register. This is shown in Figure 4c.
2. If the Address Pointer Register is known to be already at the desired address, data can be read from the corresponding data register without first writing to the Address Pointer Register, so Figure 4b can be omitted.
Note: although it is possible to read a data byte from a data register without first writing to the Address Pointer Register, if the Address Pointer Register is already at the correct value, it is not possible to write data to a register without writing to the Address Pointer Register, because the first data byte of a write is always written to the Address Pointer Register.
ALERT RESPONSE ADDRESS
The ADM1029 has an interrupt (INT) output that is asserted low when a fault condition occurs. Several INT outputs can be wire OR’d to a common interrupt line. When the host processor receives an interrupt request, it would normally need to read the interrupt status register of each device to identify which device had made the interrupt request. However, the ADM1029 sup­ports the optional Alert Response Address function of the SMBus protocol. When the host processor receives an interrupt request it can send a general call address (0001100) over the bus. The device asserting INT will then send its own slave address back to the host processor, so the device asserting INT can be identi­fied immediately.
If more than one device is asserting INT, all devices will try to respond with their slave address, but an arbitration process ensures that only the lowest address will be received by the host.
After sending its slave address, the first device will then clear its INT output. The host can then check if the INT is still low and send the general call again if necessary until all devices asserting INT have responded.
The ARA function can be disabled by setting Bit 2 of the Con­figuration Register (address 01h).
TEMPERATURE MEASUREMENT SYSTEM
LOCAL TEMPERATURE MEASUREMENT
The ADM1029 contains an on-chip bandgap temperature sensor, whose output is digitized by the on-chip ADC. The temperature data is stored in the Local Temp Value Register (address A0h). As both positive and negative temperatures can be measured, the temperature data is stored in two’s complement format, as shown in Table II. Theoretically, the temperature sensor and ADC can measure temperatures from –128°C to +127°C with a resolution of 1°C, but temperatures outside the operating temperature range of the device cannot be measured by the internal sensor.
REMOTE TEMPERATURE MEASUREMENT
The ADM1029 can measure the temperature of one or two remote diode-connected transistors, connected to Pins 13 and 14 and/or 16 and 17. The data from the temperature measure­ments is stored in the Remote 1 and Remote 2 Temp Value Registers (addresses A1h and A2h).
If two remote temperature measurements are not required, Pins 16 and 17 can be reconfigured as general-purpose logic I/O pins, as explained later.
The forward voltage of a diode or diode-connected transistor, operated at a constant current, exhibits a negative temperature coefficient of about –2 mV/°C. The absolute value of V
varies
BE
from device to device and individual calibration is required to null this out so, unfortunately, the technique is unsuitable for mass production.
The technique used in the ADM1029 is to measure the change in V
when the device is operated at two different currents.
BE
This is given by:
V
= KT/q × ln(N)
BE
where:
K is Boltzmann’s constant q is charge on the carrier T is absolute temperature in Kelvins N is ratio of the two currents
Figure 5 shows the input signal conditioning used to measure the output of a remote temperature sensor. This figure shows the external sensor as a substrate transistor, provided for tem­perature monitoring on some microprocessors, but it could equally well be a discrete transistor.
If a discrete transistor is used, the collector will not be grounded, and should be linked to the base. If a PNP transistor is used, the base is connected to the D– input and the emitter to the D+ input. If an NPN transistor is used, the emitter is connected to the D– input and the base to the D+ input.
REV. 0
–9–
ADM1029
V
DD
I
N I
REMOTE
SENSING
TRANSISTOR
I
D+
D–
BIAS
DIODE
BIAS
LOW-PASS FILTER
f
C
= 65kHz
Figure 5. Signal Conditioning for Remote Diode Temperature Sensors
V
OUT
TO ADC
V
OUT
+
To prevent ground noise interfering with the measurement, the more negative terminal of the sensor is not referenced to ground, but biased above ground by an internal diode at the D– input. If the sensor is used in a noisy environment, a capacitor of value up to 1000 pF may be placed between the D+/D– pins.
To measure ∆V
, the sensor is switched between operating currents
BE
of I and N × I. The resulting waveform is passed through a 65 kHz low-pass filter to remove noise, and to a chopper-stabilized amplifier that performs the functions of amplification and rectification of the waveform to produce a dc voltage proportional to ∆VBE. This voltage is measured by the ADC to give a temperature output in 8-bit two’s complement format. To further reduce the effects of noise, digital filtering is performed by averaging the results of 16 measurement cycles. An external temperature measurement takes nominally 9.6 ms.
The results of external temperature measurements are stored in 8-bit, two’s complement format, as illustrated in Table II.
OFFSET REGISTERS
Digital noise and other error sources can cause offset errors in the temperature measurement, particularly on the remote sen­sors. The ADM1029 offers a way to minimize these effects. The offsets on the three temperature channels can be measured during system characterization and stored as two’s complement values in three offset registers at addresses 30h to 32h. The offset values are automatically added to, or subtracted from, the tem­perature values, depending on whether the two’s complement number corresponds to a positive or negative offset. Offset val­ues from –15°C to +15°C are allowed.
The default value in the offset registers is zero, so if no offsets are programmed, the temperature measurements are unaltered.
TEMPERATURE LIMITS
The contents of the Local and Remote Temperature Value Regis­ters (addresses A0h to A2h) are compared to the contents of the High and Low Limit Registers at addresses 90h to 92h and 98h to 9Ah. How the ADM1029 responds to overtemperature/ undertemperature conditions depends on the status of the Tem­perature Fault Action Registers (addresses 40h to 42h). The response of CFAULT, INT, and fan-speed-to-temperature events depends on the setting of these registers, as explained later.
Table II. Temperature Data Format
Temperature Digital Output
–128°C 1000 0000 –125°C 1000 0011 –100°C 1001 1100 –75°C 1011 0101 –50°C 1100 1110 –25°C 1110 0111 0°C 0000 0000 +10°C 0000 1010 +25°C 0001 1001 +50°C 0011 0010 +75°C 0100 1011 +100°C 0110 0100 +125°C 0111 1101 +127°C 0111 1111
–10–
REV. 0
ADM1029
LAYOUT CONSIDERATIONS
Digital boards can be electrically noisy environments, and care must be taken to protect the analog inputs from noise, particu­larly when measuring the very small voltages from a remote diode sensor. The following precautions should be taken:
1. Place the ADM1029 as close as possible to the remote sens-
ing diode. Provided that the worst noise sources such as clock generators, data/address buses, and CRTs are avoided, this distance can be 4 to 8 inches.
2. Route the D+ and D– tracks close together, in parallel, with
grounded guard tracks on each side. Provide a ground plane under the tracks if possible.
3. Use wide tracks to minimize inductance and reduce noise
pickup. Ten mil track minimum width and spacing is recommended.
GND
D+
D–
GND
10MIL
10MIL
10MIL
10MIL
10MIL
10MIL
10MIL
Figure 6. Arrangement of Signal Tracks
4. Try to minimize the number of copper/solder joints, which
can cause thermocouple effects. Where copper/solder joints are used, make sure that they are in both the D+ and D– path and at the same temperature.
Thermocouple effects should not be a major problem as 1°C corresponds to about 240 µV, and thermocouple voltages are about 3 µV/
o
C of temperature difference. Unless there are two thermocouples with a big temperature differential between them, thermocouple voltages should be much less than 200 µV.
5. Place 0.1 µF bypass and 1000 pF input filter capacitors close to the ADM1029.
6. If the distance to the remote sensor is more than 8 inches, the use of twisted pair cable is recommended. This will work up to about 6 to 12 feet.
7. For really long distances (up to 100 feet), use shielded twisted pair such as Belden #8451 microphone cable. Con­nect the twisted pair to D+ and D– and the shield to GND close to the ADM1029. Leave the remote end of the shield unconnected to avoid ground loops.
Because the measurement technique uses switched current sources, excessive cable and/or filter capacitance can affect the measurement. When using long cables, the filter capacitor may be reduced or removed.
Cable resistance can also introduce errors. 1 series resistance introduces about 0.5°C error.
TEMPERATURE-RELATED REGISTERS
Table III is a list of registers on the ADM1029 that are specific to temperature measurement and control.
Table III. Temperature-Specific Registers
Address Description
0x06 Temp Devices Installed 0x30 Local Temp Offset 0x31 Remote 1 Temp Offset 0x32 Remote 2 Temp Offset 0x40 Local Temp Fault Action 0x41 Remote 1 Temp Fault Action 0x42 Remote 2 Temp Fault Action 0x48 Local Temp Cooling Action 0x49 Remote 1 Temp Cooling Action 0x4A Remote 2 Temp Cooling Action 0x80 Local Temp TMIN 0x81 Remote 1 Temp TMIN 0x82 Remote 2 Temp TMIN 0x88 Local Temp TRANGE/THYST 0x89 Remote 1 Temp TRANGE/THYST 0x8A Remote 2 Temp TRANGE/THYST 0x90 Local Temp High Limit 0x91 Remote 1 Temp High Limit 0x92 Remote 2 Temp High Limit 0x98 Local Temp Low Limit 0x99 Remote 1 Temp Low Limit 0x9A Remote 2 Temp Low Limit 0xA0 Local Temp Value 0xA1 Remote 1 Temp Value 0xA2 Remote 2 Temp Value
The flowchart in Figure 7 shows how to configure the ADM1029 to measure temperature. It also shows how to configure the ADM1029’s behavior for out-of-limit temperature measurements.
FAN INTERFACING
The ADM1029 can be interfaced to many types of fan. It can be used to control the speed of a simple two-wire fan. It can mea­sure the speed of a fan with a tach output, and it can accept a logic input from fans with a FAULT output. By means of a shorting link in the fan connector it can also determine if a fan is present or not and if fans have been hot-swapped.
The ADM1029 can control or monitor one or two fans. Bits 0 and 1 of the Fans Supported In System Register (03h) tell the ADM1029 how many fans it should be controlling/monitoring.
In the following descriptions “installed” means that the corre­sponding bit of register 03h is set and the ADM1029 expects to see a fan interfaced to it. It does not necessarily mean that the fan is actually, physically, connected.
If a fan is installed, events such as a fault output and hot-swapping of the fan can cause INT and CFAULT to be asserted, unless they are masked for that particular event. If a fan is not installed, but is still physically connected to the ADM1029, these events will be ignored with respect to asserting INT or CFAULT, but will still be reflected in the corresponding Fan Status Register.
Setting Bit 0 indicates that Fan 1 is installed and is set to 1 at power-up by default. Setting Bit 1 indicates that Fan 2 is installed and depends on the state of Pin 18 (TMIN/INSTALL) at power-up.
REV. 0
–11–
ADM1029
DEFAULTS
LOCAL = 60ⴗC REMOTE 1 = 70ⴗC REMOTE 2 = 70ⴗC
DEFAULTS
LOCAL = 80ⴗC
REMOTE 1 = 100ⴗC REMOTE 2 = 100ⴗC
DEFAULTS
LOCAL = 0ⴗC REMOTE 1 = 0ⴗC REMOTE 2 = 0ⴗC
CONFIGURE
TEMPERATURE LOW
LIMITS
LOCAL (REG 0x98) REMOTE 1 (REG 0x99) REMOTE 2 (REG 0x9A)
CONFIGURE
TEMPERATURE HIGH
LIMITS
LOCAL (REG 0x90) REMOTE 1 (REG 0x91) REMOTE 2 (REG 0x92)
CONFIGURE
TEMPERATURE FAULT
ACTION
LOCAL (REG 0x40) REMOTE 1 (REG 0x41) REMOTE 2 (REG 0x42)
CONFIGURE
TEMPERATURE COOLING
ACTION
LOCAL (REG 0x48) REMOTE 1 (REG 0x49) REMOTE 2 (REG 0x4A)
CONFIGURE
TEMPERATURE OFFSETS
LOCAL (REG 0x30) REMOTE 1 (REG 0x31) REMOTE 2 (REG 0x32)
BIT 0 = 1 ASSERT CFAULT ON OVER-TEMPERATURE BIT 1 = 1 RUN FAN(S) ALARM SPEED ON OVER-TEMPERATURE BIT 2 = 1 ASSERT INT ON OVER-TEMPERATURE BIT 3 = 0 ALARM BELOW LOW TEMP LIMIT BIT 3 = 1 ALARM ABOVE LOW TEMP LIMIT BIT 4 = 1 ASSERT CFAULT WHEN LOW TEMP LIMIT CROSSED BIT 5 = 1 RUN FAN ALARM SPEED ON UNDER-TEMPERATURE BIT 6 = 1 ASSERT INT ON UNDER-TEMPERATURE BIT 7 LATCHES A TEMPERATURE OUT-OF-LIMIT EVENT
7 6 5 4 3 2 1 0
IS
TEMPERATURE
>
HIGH LIMIT?
YES
IS
TEMPERATURE
>
HIGH LIMIT?
YES
ALARM ABOVE OR
BELOW LOW TEMP
LIMIT?
0 = ALARM BELOW TEMP LIMIT
IS
TEMPERATURE
>
HIGH LIMIT?
YES
CFAULT
FANS RUN
ALARM SPEED
INT
MEASURE
TEMPERATURE
LOCAL (REG 0xA0) REMOTE 1 (REG 0xA1) REMOTE 2 (REG 0xA2)
LOW TEMP LIMIT
LOW TEMP LIMIT
CROSSED?
YES
AUTOMATIC FAN SPEED CONTROL (SEE TABLE X LATER)
BIT 0 = 1 FAN 1 RUNS AT ALARM SPEED FOR OUT-OF-LIMIT TEMPERATURE EVENTS;
BIT 1 = 1 FAN 2 RUNS AT ALARM SPEED FOR OUT-OF-LIMIT TEMPERATURE EVENTS;
XXXXXX10
OTHERWISE, FAN 1 RUNS AT SPEED DETERMINED BY AUTOMATIC FAN CONTROL.
OTHERWISE, FAN 2 RUNS AT SPEED DETERMINED BY AUTOMATIC FAN CONTROL.
LOW TEMP LIMIT
CROSSED?
YES
CROSSED?
1 = ALARM ABOVE TEMP LIMIT
CFAULT
YES
FANS RUN ALARM SPEED
INT
Figure 7. Temperature Sensing Flowchart
–12–
REV. 0
ADM1029
If two fans are installed, Bit 0 would be 1 by default and Pin 18 would be tied high* to set Bit 1. If only one fan is installed, it would normally be Fan 1 and Pin 18 would be tied low* to clear Bit 1. However, both of these bits can be modified by writing to the register, so it is possible to have Fan 2 installed and not Fan 1, or even have no fans installed.
*Note that Pin 18 also sets TMIN for automatic fan speed control. If this function
is used, Pin 18 would be set to some other level according to Table VIII.
FAULT INPUTS/OUTPUTS
The ADM1029 can be used with fans that have a fault output which indicates if the fan has stalled or failed. If one or both of the FAULT inputs (Pin 2 or Pin 23) goes low, both INT and CFAULT will be asserted.
Events on the fault inputs are also reflected in Bits 2 and 3 of the corresponding Fan Status Registers at addresses 10h and 11h. Bit 2 reflects the inverse state of the FAULT pin (0 if FAULT is high, 1 if FAULT is low), while Bit 3 is latched high if a FAULT input goes low. It must be cleared by writing a zero to it.
If the fan(s) being used do not have a FAULT output, the FAULT input(s) on the ADM1029 should be pulled high to V
CC
.
The FAULT pins can also be configured as open-drain outputs by setting Bit 5 of the corresponding Fan Fault Action Register (18h or 19h). If a FAULT pin is configured as an output, it will still function as an input. This means that when a fault input occurs it will be latched low by the fault output, even if the fault input is removed. The fault output can be used to drive a fan failure indicator such as an LED.
If the FAULT pin is used as an output, any input to the FAULT pin should also be open-drain. This will avoid the fault input trying to source a high current into the FAULT pin if the fault input goes high while the fault output is low.
FAN PRESENT INPUTS
The fan PRESENT signal is implemented by a shorting link to ground in the fan connector. When the fan is plugged in, the corresponding PRESENT input (Pin 4 or Pin 21) on the ADM1029 is pulled low. If the fan is unplugged, the PRESENT input will be pulled high. INT and CFAULT will be asserted (unless masked) and the event will be reflected in Bits 0 and Bit 1 of the corresponding Fan Status Register.
Appearance or disappearance of a PRESENT input signal dur­ing normal operation signals to the ADM1029 that a fan has been hot-plugged or unplugged. INT and CFAULT will be asserted (unless masked). When a fan is hot-plugged, Bit 7 of the corresponding Fan Status Register will be set and a Fan Free Wheel Test commences automatically.
FAN SPEED MEASUREMENT
The fan counter does not count the fan tach output pulses directly, because at low fan speeds it would take several seconds to accumulate a reasonably large and accurate count. Instead, the period of the fan revolution is measured by gating an on­chip oscillator into the input of an 8-bit counter.
The fan speed measuring circuit is initialized on the first rising edge of a fan tach pulse after monitoring is enabled by setting Bit 4 of the Configuration Register. It then starts counting on the rising edge of the second tach pulse and counts for four fan tach periods, until the rising edge of the sixth tach pulse, or until the counter overranges if the fan tach period is too long.
After the speed of the first fan has been measured, the speed of the second fan (if installed) will be measured in the same way. The measurement cycle will repeat until monitoring is disabled. The fan speed measurements are stored in the Fan Tach Value registers at addresses 70h and 71h.
If both fans are installed, Fan 1 will be measured first. If only one fan is installed, the ADM1029 will still try to measure both fans, starting with Fan 1, but the measurement on the noninstalled fan will time out when the Fan Tach Value count overranges.
The fan speed count is given by:
Count = f 4 60/R/N
where:
f is oscillator frequency in Hz factor 4 is because 4 tach periods are counted factor 60 is to convert minutes to seconds R = fan speed in RPM N is number of tach pulses per revolution
The frequency of the oscillator can be adjusted to suit the expected frequency range of the fan tach pulses, which depends on the fan speed and the number of tach pulses produced for each revolution of the fan, which is either 1, 2, or 4. The oscillator frequency is set by Bits 7 and 6 of the Fan Configuration Regis­ters (68h for Fan 1 and 69h for Fan 2).
Table III. Oscillator Frequencies
Bit 7 Bit 6 Oscillator Frequency (Hz)
0 0 Measurement Disabled 0 1 470 1 0 940 1 1 1880
CLOCK
CONFIG
REG. BIT 4
FAN 1
TACH
FAN 2
TACH
START OF
MONITORING
CYCLE
FAN 1
MEASUREMENT
PERIOD
FAN 2
MEASUREMENT
PERIOD
Figure 8. Fan Speed Measurement
FAN SPEED LIMITS
Fans generally do not overspeed if run from the correct voltage, so the failure condition of interest is under-speed due to electri­cal or mechanical failure. For this reason only low-speed limits are programmed into the Tach Limit Registers for the fans. These registers are at address 78h for Fan 1 and 79h for Fan
2. It should be noted that, since fan period rather than speed is being measured, the fan speed count will be larger the slower the fan speed. Therefore a fan failure fault will occur when the measurement exceeds the limit value.
REV. 0
–13–
ADM1029
For the most accurate fan failure indication, the oscillator frequency should be chosen to give as large a limit value as possible without the counter overranging. A count close to 3/4 full-scale or 191 is the optimum value.
For example, if a fan produces two tach pulses per revolution and the fan failure speed is to be 600 rpm, the oscillator fre­quency should be set to 940 Hz. This will give a count at the fail speed of:
940 4 60/600/2 = 188
If the oscillator frequency were only 470 Hz, the count would be 94, while an oscillator frequency of 1880 Hz cannot be used because the count would be 376 and the counter would overrange.
FAN MONITORING CYCLE TIME
Five complete tach periods are required to carry out a fan speed measurement Therefore, if the start of a fan measurement just misses a rising edge, the measurement can take almost six tach periods for each fan.
The worst-case monitoring cycle time is when both fans are under speed and the fan speed counter counts up to its maxi­mum value. The actual count takes 256 oscillator pulses over four tach periods, plus a further two tach periods or 128 oscilla­tor pulses before the count starts. The total monitoring cycle time is therefore:
t
MEAS
= 384/f
OSC(FAN 1)
+ 384/f
OSC(FAN 2)
In order to read a valid result from the Fan Tach Value Registers, the total monitoring time allowed after starting the monitoring cycle should be greater than this.
TACH SIGNAL CONDITIONING
Signal conditioning in the ADM1029 accommodates the slow rise and fall times typical of fan tachometer outputs. The maxi­mum input signal range is 0 V to 5 V, even if V
is less than
CC
5 V. In the event that these inputs are supplied from fan outputs that exceed 0 V to 5 V, either resistive attenuation of the fan signal or diode clamping must be included to keep inputs within an acceptable range.
Figures 9a to 9d show circuits for most common fan tach outputs.
If the fan tach output has a resistive pull-up to V
, it can be
CC
connected directly to the fan input, as shown in Figure 9a.
12V
PULL-UP
4.7k TYP
TACH OUTPUT
TACH1
OR TACH2
Figure 9a. Fan with Tach Pull-Up to +V
V
CC
FAN SPEED
COUNTER
CC
If the fan output has a resistive pull-up to 12 V (or other voltage greater than 6.5 V), the fan output can be clamped with a Zener diode, as shown in Figure 9b. The Zener voltage should be chosen so that it is greater than V
but less than 6.5 V, allowing
IH
for the voltage tolerance of the Zener. A value of between 3 V and 5 V is suitable.
12V
PULL-UP
4.7k
*CHOOSE ZD1 VOLTAGE APPROX. 0.8 ⴛ V
TYP
TACH OUTPUT
OR TACH2
TACH1
ZD1* ZENER
V
CC
FAN SPEED
COUNTER
CC
Figure 9b. Fan with Tach. Pull-Up to Voltage >6.5 V (e.g., 12 V) Clamped with Zener Diode
If the fan has a strong pull-up (less than 1 kΩ) to 12 V, or a totem-pole output, a series resistor can be added to limit the Zener current, as shown in Figure 9c. Alternatively, a resistive attenuator may be used, as shown in Figure 9d.
R1 and R2 should be chosen such that:
2 V < V
PULLUP
× R2/(R
+ R1 + R2) < 5 V
PULLUP
The fan inputs have an input resistance of nominally 160 k to ground, so this should be taken into account when calculating resistor values.
With a pull-up voltage of 12 V and pull-up resistor less than 1 k, suitable values for R1 and R2 would be 100 k and 47 kΩ. This will give a high input voltage of 3.83 V.
12V
TACH O/P
PULL-UP
TYP <1k
OR TOTEM-POLE
*CHOOSE ZD1 VOLTAGE APPROX. 0.8 ⴛ V
R1
10k
TACH1
OR TACH2
ZD1 ZENER*
V
CC
FAN SPEED
COUNTER
CC
Figure 9c. Fan with Strong Tach. Pull-Up to >VCC or Totem-Pole Output, Clamped with Zener and Resistor
12V
<1k
R1*
TACH OUTPUT
OR TACH2
R2*
*SEE TEXT
TACH1
V
CC
FAN SPEED
COUNTER
Figure 9d. Fan with Strong Tach. Pull-Up to >VCC or Totem-Pole Output, Attenuated with R1/R2
FAN SPEED CONTROL
Fan speed is controlled using pulsewidth modulation (PWM). The PWM outputs (Pins 1 and 24) give a pulse output with a programmable frequency (default 250 Hz) and a duty-cycle defined by the contents of the relevant fan speed register, or by the automatic fan speed control when this mode is enabled. The speed at which a fan runs is determined by fault conditions and the settings of various control and mask registers.
A fan can only be driven if it is defined as being supported by the controller in register 02h. The ADM1029 supports up to two fans, so Bits 0 and 1 of this register are permanently set. This register is read-only.
–14–
REV. 0
ADM1029
A fan will only be driven if it is defined as being supported by the system in register 03h. If Bit 0 of this register is set, it indi­cates that Fan 1 is installed. This is the power-on default. If Bit 1 is set, it indicates that Fan 2 is installed. This bit is set by the state of Pin 18 at power-up. This register is read/write and the default/power-on setting can be overwritten. If a fan is not supported in register 03h it will not be driven, even if it is physi­cally installed.
The PWM outputs are open-drain outputs. They require pull-up resistors and must be amplified and buffered to drive the fans.
Minimum Speed
The normal operating fan speed is set by the four LSBs of the Fan 1 and Fan 2 Minimum/Alarm Speed Registers (addresses 60h, 61h). These bits also set the minimum speed at which a fan will run in automatic control mode. These bits should be set to 05h. This corresponds to 33% PWM duty-cycle, which is the lowest speed at which most fans will run reliably.
Fan(s) will run at minimum speed if there is no fault condition, automatic fan speed is disabled, and there are no other over­riding conditions.
Alarm Speed
Alarm speed is set by the four MSBs of the Fan 1 and Fan 2 Minimum/Alarm Speed Registers (addresses 60h, 61h). Fan(s) will run at alarm speed if any of the following conditions occurs, assuming the condition has not been masked out using the Fan Event Mask Registers:
Setting Bit 0 of register 07h forces Fan 1 to run at alarm speed
(Set Fan x Alarm Speed Register).
Setting Bit 1 of register 07h forces Fan 2 to run at alarm speed (Set Fan x Alarm Speed Register).
If monitoring is disabled by clearing Bit 4 of the Con­figuration Register, all fans controlled by the ADM1029 will run at alarm speed.
When a GPIO pin is configured as an input by setting Bit 0 of the corresponding GPIO Behavior Register, and Bit 4 of the GPIO Behavior Register is also set, all fans controlled by the ADM1029 will go to alarm speed when the logic input is asserted (high or low, depending on the polarity bit, Bit 1 of the corresponding GPIO Behavior Register).
If Bit 7 of a Fan Fault Action Register is set (18h—Fan 1, 19h —Fan 2) the corresponding fan will go to alarm speed when CFAULT is pulled low by an external source.
If a tach measurement exceeds the set limit, all fans controlled by the ADM1029 will run at alarm speed.
If a fan fault input pin is asserted (low), all fans controlled by the ADM1029 will run at alarm speed.
If Bit 1 of a Temp. Fault Action Register is set (40h—Local Sensor, 41h—Remote 1, 42h—Remote 2), all fans controlled by the ADM1029 will go to alarm speed if the corresponding temperature high limit is exceeded.
If Bit 5 of a Temp. Fault Action Register is set, all fans con­trolled by the ADM1029 will go to alarm speed if a temperature input crosses the corresponding temperature low limit, the direction depending on the setting of Bit 3 of the Temp. Con­trol register. (0 = alarm when input goes below low limit, 1 = alarm when input goes above low limit).
If Bit 1 of an AIN Behavior Register is set (50h—AIN0, 51h—AIN1), all fans controlled by the ADM1029 will go to alarm speed if the corresponding AIN high limit is exceeded.
If Bit 5 of an AIN Behavior Register is set, all fans controlled by the ADM1029 will go to alarm speed if an analog input crosses the corresponding AIN low limit, the direction depend­ing on the setting of Bit 3 of the AIN control register. (0 = alarm when input goes below low limit, 1 = alarm when input goes above low limit).
If a thermal override occurs while the ADM1029 is in sleep mode, all fans controlled by the ADM1029 will run at alarm speed.
Hot-Plug Speed
Hot-plug speed is set by the four LSBs of the Fan 1 and Fan 2 Configuration Registers (addresses 68h and 69h). The PWM frequency is set by Bits 4 and 5 of these registers, while Bits 6 and 7 set the number of pulses per revolution for fan speed measurement.
Fan(s) will run at hot-plug speed if any of the following condi­tions occur, assuming the condition has not been masked using the Fan Event Mask Registers:
If a fan is unplugged, the other fan (if any) controlled by the ADM1029 will run at hot-plug speed.
Setting Bit 0 of register 08h forces Fan 1 to run at hot-plug speed (Set Fan x Hot-Plug Speed).
Setting Bit 1 of register 08h forces Fan 2 to run at hot-plug speed (Set Fan x Hot-Plug Speed).
When a GPIO pin is configured as an input by setting Bit 0 of the corresponding GPIO Behavior Register, and Bit 5 of the GPIO Behavior Register is also set, all fans controlled by the ADM1029 will go to hot-plug speed when the logic input is asserted (high or low, depending on the polarity bit, Bit 1 of the corresponding GPIO Behavior Register).
If Bit 6 of a Fan Fault Action Register is set (18h for Fan 1, 19h for Fan 2) the corresponding fan will go to hot-plug speed when CFAULT is pulled low by an external source.
Note: If operating conditions and register settings are such that both alarm speed and hot-plug speed would be triggered, which one takes priority is determined by Bit 5 of the Fan 1 and Fan 2 Status Registers (addresses 10h and 11h). If this bit is set, hot-plug speed takes priority. If it is cleared, alarm speed takes priority.
Full Speed
Fans will run at full speed if the corresponding bits in the Set Fan x Full Speed Register (address 09h) are set: Bit 0 for Fan 1 and Bit 1 for Fan 2.
Fan Mask Registers
The effect of various conditions on fan speed can be enabled or disabled by mask registers. In all these registers, setting Bit 0 of the register enables Fan 1 to go to alarm speed or hot-plug speed if the corresponding event occurs, while setting Bit 1 enables Fan
2. Clearing these bits masks the effect of the corresponding event on fan speed.
Registers 20h and 21h are Fan Event Mask Registers. Bits 0 and 1 of register 20h enable (bit set) or mask (bit clear) the effect of a Fan 1 fault (underspeed or fault input) on Fan 1 and Fan 2 speed. Similarly, Bits 0 and 1 of register 21h enable (bit set)
REV. 0
–15–
Loading...
+ 33 hidden pages