FEATURES
Up to Nine Measurement Channels
Inputs Programmable-to-Measure Analog Voltage, Fan
Speed or External Temperature
External Temperature Measurement with Remote
Diode (Two Channels)
On-Chip Temperature Sensor
Five Digital Inputs for VID Bits
LDCM Support
System Management Bus (SMBus)
Chassis Intrusion Detect
Interrupt and Over Temperature Outputs
Programmable RESET Input Pin
Shutdown Mode to Minimize Power Consumption
Limit Comparison of all Monitored Values
FUNCTIONAL BLOCK DIAGRAM
V
VID0/IRQ0
VID1/IRQ1
VID2/IRQ2
VID3/IRQ3
VID4/IRQ4
CC
100k⍀
PULLUPS
VID0–3 AND
FAN DIVISOR
REGISTER
VID4 AND
DEVICE ID
REGISTER
ADM1024
Remote Diode Thermal Sensing
ADM1024
APPLICATIONS
Network Servers and Personal Computers
Microprocessor-Based Office Equipment
Test Equipment and Measuring Instruments
PRODUCT DESCRIPTION
The ADM1024 is a complete system hardware monitor for
microprocessor-based systems, providing measurement and limit
comparison of various system parameters. Eight measurement
inputs are provided, of which three are dedicated to monitoring
5 V and 12 V power supplies and the processor core voltage.
The ADM1024 can monitor a fourth power-supply voltage by
measuring its own V
remote temperature-sensing diode. Two further pins can be
SERIAL BUS
INTERFACE
CHANNEL
MODE
REGISTER
. One input (two pins) is dedicated to a
CC
(continued on page 7)
NTEST OUT/ADD
SDA
SCL
FAN SPEED
COUNTER
ADDRESS
FAN1/AIN1
FAN2/AIN2
+V
CCP1
+2.5VIN/D2+
+5V
+12V
V
/D2–
CCP2
D1+
D1–
V
IN
IN
CC
POWER TO CHIP
BANDGAP
TEMPERATURE
SENSOR
INPUT
ATTENUATORS
AND
ANALOG
MULTIPLEXER
POINTER
REGISTER
TEMPERATURE
CONFIGURATION
REGISTER
10-BIT ADC
BANDGAP
REFERENCE
GND
REV. 0
Information furnished by Analog Devices is believed to be accurate and
reliable. However, no responsibility is assumed by Analog Devices for its
use, nor for any infringements of patents or other rights of third parties
which may result from its use. No license is granted by implication or
otherwise under any patent or patent rights of Analog Devices.
Input High Current, I
Input Low Current, I
Input Capacitance, C
SERIAL BUS TIMING
Clock Frequency, f
Glitch Immunity, t
Bus Free Time, t
Start Setup Time, t
Start Hold Time, t
SCL Low Time, t
SCL High Time, t
SCL, SDA Rise Time, t
SCL, SDA Fall Time, t
Data Setup Time, t
Data Hold Time, t
NOTES
1
All voltages are measured with respect to GND, unless otherwise specified.
2
Typicals are at TA = 25°C and represent most likely parametric norm. Shutdown current typ is measured with VCC = 3.3 V.
3
TUE (Total Unadjusted Error) includes Offset, Gain and Linearity errors of the ADC, multiplexer and on-chip input attenuators, including an external series input
protection resistor value between zero and 1 kΩ.
4
Total monitoring cycle time is nominally m × 755 µs + n × 33244 µs, where m is the number of channels configured as analog inputs, plus two for the internal V
measurement and internal temperature sensor, and n is the number of channels configured as external temperature channels (D1 and D2).
5
The total fan count is based on two pulses per revolution of the fan tachometer output.
6
Open-drain digital outputs may have an external pull-up resistor connected to a voltage lower or higher than VCC (up to 6.5 V absolute maximum).
7
All logic inputs except ADD are tolerant of 5 V logic levels, even if VCC is less than 5 V. ADD is a three-state input that may connected to VCC, GND, or left open-circuit.
8
Timing specifications are tested at logic levels of VIL = 0.8 V for a falling edge and VIH = 2.2 V for a rising edge.
*Stresses above those listed under Absolute Maximum Ratings may cause
permanent damage to the device. This is a stress rating only; functional operation
of the device at these or any other conditions above those indicated in the
operational section of this specification is not implied. Exposure to absolute
maximum rating conditions for extended periods may affect device reliability.
THERMAL CHARACTERISTICS
24-Lead Small Outline Package: θJA = 50°C/W, θJC = 10°C/W.
ORDERING GUIDE
TemperaturePackagePackage
ModelRangeDescriptionOption
ADM1024ARU0°C to 100°C24-Lead TSSOPRU-24
PIN CONFIGURATION
NTEST OUT/ADDVID0/IRQ0
FAN1/AIN1VID4/IRQ4
FAN2/AIN2+V
NTEST IN/AOUTD1+
1
2
THERM
SDAVID2/IRQ2
3
4
SCLVID3/IRQ3
5
ADM1024
6
TOP VIEW
(Not to Scale)
7
CI+2.5VIN/D2+
8
GNDV
9
V
CC
10
INT
11
12
RESET
24
23
VID1/IRQ1
22
21
20
19
18
17
16
+5V
15
+12V
14
13
D1–
CCP1
CCP2
/D2–
IN
IN
–4–
REV. 0
ADM1024
PIN FUNCTION DESCRIPTIONS
Pin
No.MnemonicDescription
1NTEST_OUT/ADDDigital I/O. Dual Function pin. This is a three-state input that controls the 2 LSBs of the Serial
Bus Address. This pin functions as an output when doing a NAND test.
2THERMDigital I/O. Dual Function pin. This pin functions as an interrupt output for temperature interrupts
only, or as an interrupt input for fan control. It has an on-chip 100 kΩ pull-up resistor.
3SDADigital I/O. Serial Bus bidirectional Data. Open-drain output.
4SCLDigital Input. Serial Bus Clock.
5FAN1/AIN1Programmable Analog/Digital Input. 0 V to 2.5 V analog input or digital (0 to V
tachometer input.
6FAN2/AIN2Programmable Analog/Digital Input. 0 V to 2.5 V analog input or digital (0 to V
tachometer input.
7CIDigital I/O. An active high input from an external latch which captures a Chassis Intrusion event.
This line can go high without any clamping action, regardless of the powered state of the ADM1024. The
ADM1024 provides an internal open drain on this line, controlled by Bit 6 of Register 40h or Bit 7 of
Register 46h, to provide a minimum 20 ms pulse on this line, to reset the external Chassis Intrusion La tch.
8GNDSystem Ground.
9V
CC
POWER (2.8 V to 5.5 V). Typically powered from 3.3 V power rail. Bypass with the parallel combination of
10 µF (electrolytic or tantalum) and 0.1 µF (ceramic) bypass capacitors.
10INTDigital Output. Interrupt Request (open-drain). The output is enabled when Bit 1 of Register 40h
is set to 1. The default state is disabled. It has an on-chip 100 kΩ pull-up resistor.
11NTEST_IN/AOUTDigital Input/Analog Output. An active-high input that enables NAND Test mode board-level connectivity
testing. Refer to section on NAND testing. Also functions as a programmable analog output when NAND
Test is not selected.
12RESETDigital I/O. Master Reset, 5 mA driver (open drain), active low output with a 45 ms minimum pulsewidth.
Set using Bit 4 in Register 40h. Also acts as reset input when pulled low (e.g., power-on reset). It has an
on-chip 100 kΩ pull-up resistor.
13D1–Analog Input. Connected to cathode of first external temperature sensing diode.
14D1+Analog Input. Connected to anode of first external temperature sensing diode.
15+12 V
16+5 V
17V
CCP2
IN
IN
/D2–Programmable Analog Input. Monitors second processor core voltage or cathode of second external
Programmable Analog Input. Monitors 12 V supply.
Analog Input. Monitors 5 V supply.
temperature sensing diode.
18+2.5 VIN/D2+Programmable Analog Input. Monitors 2.5 V supply or anode of second external temperature sensing diode.
19+V
CCP1
Analog Input. Monitors 1st processor core voltage (0 V to 3.6 V).
20VID4/IRQ4Digital Input. Core Voltage ID readouts from the processor. This value is read into the VID4 Status Regis-
ter. Can also be reconfigured as an interrupt input. It has an on-chip 100 kΩ pull-up resistor.
21VID3/IRQ3Digital Input. Core Voltage ID readouts from the processor. This value is read into the VID0–VID3 Status
Register. Can also be reconfigured as an interrupt input. It has an on-chip 100 kΩ pull-up resistor.
22VID2/IRQ2Digital Input. Core Voltage ID readouts from the processor. This value is read into the VID0-VID3 Status
Register. Can also be reconfigured as an interrupt input. It has an on-chip 100 kΩ pull-up resistor.
23VID1/IRQ1Digital Input. Core Voltage ID readouts from the processor. This value is read into the VID0–VID3 Status
Register. Can also be reconfigured as an interrupt input. It has an on-chip 100 kΩ pull-up resistor.
24VID0/IRQ0Digital Input. Core Voltage ID readouts from the processor. This value is read into the VID0–VID3 Status
Register. Can also be reconfigured as an interrupt input. It has an on-chip 100 kΩ pull-up resistor.
) amplitude fan
CC
) amplitude fan
CC
REV. 0
–5–
ADM1024–Typical Performance Characteristics
30
20
10
0
–10
–20
–30
TEMPERATURE ERROR – ⴗC
–40
–50
–60
11003.3
LEAKAGE RESISTANCE – M⍀
DXP TO GND
DXP TO VCC (5V)
1030
Figure 2. Temperature Error vs. PC Board Track Resistance
6
5
4
250mV p-p REMOTE
3
2
1
TEMPERATURE ERROR – ⴗC
0
100mV p-p REMOTE
120
100
90
80
70
60
50
READING
40
30
20
10
0
011010
203040 50
MEASURED TEMPERATURE
6070 8090 100
Figure 5. Pentium® III Temperature Measurement vs.
ADM1024 Reading
25
20
15
10
5
TEMPERATURE ERROR – ⴗC
0
–1
5050M500
5k
50k
FREQUENCY – Hz
500k5M
Figure 3. Temperature Error vs. Power Supply Noise
Frequency
25
20
15
10
5
TEMPERATURE ERROR – ⴗC
0
–5
5050M500
5k50k500k5M
FREQUENCY – Hz
100mV p-p
50mV p-p
25mV p-p
Figure 4. Temperature Error vs. Common-Mode Noise
Frequency
–5
1102.2
3.24.77
DXP-DXN CAPACITANCE – nF
Figure 6. Temperature Error vs. Capacitance Between D+
and D–
10
9
8
TEMPERATURE ERROR – ⴗC
7
6
5
4
3
2
1
0
5050M500
5k50k500k5M
10mV SQ. WAVE
100k25M
FREQUENCY – Hz
Figure 7. Temperature Error vs. Differential-Mode Noise
Frequency
–6–
REV. 0
ADM1024
26.5
26.0
SHUTDOWN CURRENT – A
25.5
25.0
24.5
24.0
23.5
23.0
22.5
–40–20
VDD = 3.3V
020406080100120
TEMPERATURE – C
Figure 8. Standby Current vs. Temperature
(continued from page 1)
configured as inputs to monitor a 2.5 V supply and a second
processor core voltage, or as a second temperature sensing input.
The remaining two inputs can be programmed as general-purpose
analog inputs or as digital fan-speed measuring inputs.
Measured values can be read out via an SMBus serial System
Management Bus, and values for limit comparisons can be
programmed in over the same serial bus. The high-speed
successive-approximation ADC allows frequent sampling of
all analog channels to ensure a fast interrupt response to any
out-of-limit measurement.
The ADM1024’s 2.8 V to 5.5 V supply voltage range, low supply
current, and SMBus interface make it ideal for a wide range
of applications. These include hardware monitoring and protection applications in personal computers, electronic test equipment,
and office electronics.
GENERAL DESCRIPTION
The ADM1024 is a complete system hardware monitor for
microprocessor-based systems. The device communicates with
the system via a serial System Management Bus. The serial bus
controller has a hardwired address line for device selection (Pin
1), a serial data line for reading and writing addresses and data
(Pin 3), and an input line for the serial clock (Pin 4). All control
and programming functions of the ADM1024 are performed over
the serial bus.
MEASUREMENT INPUTS
Programmability of the measurement inputs makes the ADM1024
extremely flexible and versatile. The device has a 10-bit A-to-D
converter, and nine measurement input pins that can be configured
in different ways.
Pins 5 and 6 can be programmed as general-purpose analog
inputs with a range of 0 V to 2.5 V, or as digital inputs to
monitor the speed of fans with digital tachometer outputs. The
fan inputs can be programmed to accommodate fans with different speeds and different numbers of pulses per revolution from
their tach outputs.
Pins 13 and 14 are dedicated temperature inputs and may be
connected to the cathode and anode of an external temperaturesensing diode.
Pins 15, 16, and 19 are dedicated analog inputs with on-chip
attenuators, configured to monitor 12 V, 5 V and the processor
core voltage, respectively.
Pins 17 and 18 may be configured as analog inputs with on-chip
attenuators to monitor a second processor core voltage and a
2.5 V supply, or they may be configured as a temperature input
and connected to a second temperature-sensing diode.
The ADC also accepts input from an on-chip bandgap temperature sensor that monitors system-ambient temperature.
Finally, the ADM1024 monitors the supply from which it is
powered, so there is no need for a separate 3.3 V analog input,
if the chip V
can be configured for either a 3.3 V or 5 V V
is 3.3 V. The range of this VCC measurement
CC
by Bit 3 of the
CC
Channel Mode Register.
SEQUENTIAL MEASUREMENT
When the ADM1024 monitoring sequence is started, it cycles
sequentially through the measurement of analog inputs and the
temperature sensor, while at the same time the fan speed inputs
are independently monitored. Measured values from these inputs
are stored in Value Registers. These can be read out over the
serial bus, or can be compared with programmed limits stored in
the Limit Registers. The results of out-of-limit comparisons are
stored in the Interrupt Status Registers, and will generate an
interrupt on the INT line (Pin 10).
Any or all of the Interrupt Status Bits can be masked by appropriate programming of the Interrupt Mask Register.
PROCESSOR VOLTAGE ID
Five digital inputs (VID4 to VID0—Pins 20 to 24) read the
processor voltage ID code. These inputs can also be reconfigured
as interrupt inputs.
The VID pins have internal 100 k⍀ pull-up resistors.
CHASSIS INTRUSION
A chassis intrusion input (Pin 7) is provided to detect unauthorized
tampering with the equipment.
RESET
A RESET input/output (Pin 12) is provided. Pulling this pin low
will reset all ADM1024 internal registers to default values. The
ADM1024 can also be programmed to give a low-going 45 ms
reset pulse at this pin.
The RESET pin has an internal, 100 kΩ pull-up resistor.
ANALOG OUTPUT
The ADM1024 contains an on-chip, 8-bit digital-to-analog
converter with an output range of zero to 2.5 V (Pin 11). This is
typically used to implement a temperature-controlled fan by
controlling the speed of a fan dependent upon the temperature
measured by the on-chip temperature sensor.
Testing of board level connectivity is simplified by providing a
NAND tree test function. The AOUT (Pin 11) also doubles as
a NAND test input, while Pin 1 doubles as a NAND tree output.
INTERNAL REGISTERS OF THE ADM1024
A brief description of the ADM1024’s principal internal registers is given below. More detailed information on the function
of each register is given in Tables VI to XIX.
REV. 0
–7–
ADM1024
Configuration Registers: Provide control and configuration.
Channel Mode Register: Stores the data for the operating
modes of the input channels.
Address Pointer Register: This register contains the address that
selects one of the other internal registers. When writing to the
ADM1024, the first byte of data is always a register address, which
is written to the Address Pointer Register.
Interrupt (INT) Status Registers: Two registers to provide
status of each Interrupt event. These registers are also mirrored
at addresses 4Ch and 4Dh.
Interrupt (INT) Mask Registers: Allow masking of individual
interrupt sources.
Temperature Configuration Register: The configuration of
the temperature interrupt is controlled by the lower three bits of
this register.
VID/Fan Divisor Register: The status of the VID0 to VID4
pins of the processor can be written to and read from these registers. Divisor values for fan-speed measurement are also stored
in this register.
Value and Limit Registers: The results of analog voltage
inputs, temperature and fan speed measurements are stored in
these registers, along with their limit values.
Analog Output Register: The code controlling the analog
output DAC is stored in this register.
Chassis Intrusion Clear Register: A signal latched on the
chassis intrusion pin can be cleared by writing to this register.
SERIAL BUS INTERFACE
Control of the ADM1024 is carried out via the serial bus. The
ADM1024 is connected to this bus as a slave device, under the
control of a master device, e.g., ICH.
The ADM1024 has a 7-bit serial bus address. When the device
is powered up, it will do so with a default serial bus address. The
five MSBs of the address are set to 01011, the two LSBs are
determined by the logical states of Pin 1 (NTESTOUT/ADD).
This is a three-state input that can be grounded, connected to
V
or left open-circuit to give three different addresses.
CC
Table I. ADD Pin Truth Table
ADD PinA1A0
GND10
No Connect00
V
CC
If ADD is left open-circuit the default address will be 0101100. ADD
is sampled only at power-up, so any changes made while power is
on will have no immediate effect.
The facility to make hardwired changes to A1 and A0 allows the
user to avoid conflicts with other devices sharing the same serial
bus, for example if more than one ADM1024 is used in a system.
The serial bus protocol operates as follows:
1. The master initiates data transfer by establishing a START
condition, defined as a high-to-low transition on the serial
data line SDA while the serial clock line, SCL, remains high.
This indicates that an address/data stream will follow. All slave
peripherals connected to the serial bus respond to the START
01
condition, and shift in the next eight bits, consisting of a
7-bit address (MSB first) plus an R/W bit, which determines
the direction of the data transfer, i.e., whether data will be
written to or read from the slave device.
The peripheral whose address corresponds to the transmitted
address responds by pulling the data line low during the low
period before the ninth clock pulse, known as the Acknowledge
Bit. All other devices on the bus now remain idle while the
selected device waits for data to be read from or written to it.
If the R/W bit is a 0, the master will write to the slave device.
If the R/W bit is a 1, the master will read from the slave device.
2. Data is sent over the serial bus in sequences of nine clock
pulses, eight bits of data followed by an Acknowledge Bit
from the slave device. Transitions on the data line must occur
during the low period of the clock signal and remain stable
during the high period, as a low-to-high transition when the
clock is high may be interpreted as a STOP signal. The number
of data bytes that can be transmitted over the serial bus in
a single READ or WRITE operation is limited only by what the
master and slave devices can handle.
3. When all data bytes have been read or written, stop conditions
are established. In WRITE mode, the master will pull the
data line high during the 10th clock pulse to assert a STOP
condition. In READ mode, the master device will override
the acknowledge bit by pulling the data line high during the
low period before the ninth clock pulse. This is known as No
Acknowledge. The master will then take the data line low
during the low period before the tenth clock pulse, then high
during the tenth clock pulse to assert a STOP condition.
Any number of bytes of data may be transferred over the serial
bus in one operation, but it is not possible to mix read and write
in one operation because the type of operation is determined at
the beginning and cannot subsequently be changed without
starting a new operation.
In the case of the ADM1024, write operations contain either
one or two bytes, and read operations contain one byte and
perform the following functions.
To write data to one of the device data registers or read data
from it, the Address Pointer Register must be set so that the
correct data register is addressed, then data can be written into
that register or read from it. The first byte of a write operation
always contains an address that is stored in the Address Pointer
Register. If data is to be written to the device, the write operation
contains a second data byte that is written to the register
selected by the address pointer register. This is illustrated in
Figure 9a. The device address is sent over the bus followed by
R/W set to 0. This is followed by two data bytes. The first data
byte is the address of the internal data register to be written
to, which is stored in the Address Pointer Register. The second
data byte is the data to be written to the internal data register.
When reading data from a register there are two possibilities:
1. If the ADM1024’s Address Pointer Register value is unknown
or not the desired value, it is first necessary to set it to the
correct value before data can be read from the desired data
register. This is done by performing a write to the ADM1024
as before, but only the data byte containing the register address
is sent, as data is not to be written to the register. This is shown
in Figure 9b.
–8–
REV. 0
ADM1024
SCL
SDA
START BY
MASTER
191
0
1011
SERIAL BUS ADDRESS BYTE
FRAME 1
SCL (CONTINUED)
SDA (CONTINUED)
A0
A1
R/W
ACK. BY
ADM1024
1
D7D 6D5
D6
D7
ADDRESS POINTER REGISTER BYTE
D4D3D2D1
D5
FRAME 2
D4D3D2D1
FRAME 3
DATA BYTE
D0
ACK. BY
ADM1024
D0
9
9
ACK. BY
ADM1024
STOP BY
MASTER
Figure 9a. Writing a Register Address to the Address Pointer Register, then Writing Data to the Selected Register
D0
9
ACK. BY
ADM1024
STOP BY
MASTER
SCL
SDA
START BY
MASTER
191
0
1011A1A0D7
FRAME 1
SERIAL BUS ADDRESS BYTE
R/W
ACK. BY
ADM1024
D6
D5D4D3D2D1
ADDRESS POINTER REGISTER BYTE
FRAME 2
Figure 9b. Writing to the Address Pointer Register Only
191
SCL
SDA
START BY
MASTER
0
0
1
SERIAL BUS ADDRESS BYTE
1
FRAME 1
1
A0
A1
R/W
ACK. BY
ADM1024
Figure 9c. Reading Data from a Previously Selected Register
A read operation is then performed consisting of the serial bus
address, R/W bit set to 1, followed by the data byte read from
the data register. This is shown in Figure 9c.
2. If the Address Pointer Register is known to be already at the
desired address, data can be read from the corresponding
data register without first writing to the Address Pointer
Register, so Figure 9b can be omitted.
NOTES
1. Although it is possible to read a data byte from a data register
without first writing to the Address Pointer Register, if the
Address Pointer Register is already at the correct value, it is
not possible to write data to a register without writing to the
Address Pointer Register because the first data byte of a write is
always written to the Address Pointer Register.
2. In Figures 9a to 9c, the serial bus address is shown as the
default value 01011(A1)(A0), where A1 and A0 are set by
the three-state ADD pin.
MEASUREMENT INPUTS
The ADM1024 has nine external measurement pins that can be
configured to perform various functions by programming the
Channel Mode Register.
9
D6
D7
D4D3D2D1
D5
FRAME 2
DATA BYTE FROM ADM1024
D0
NO ACK.
BY MASTER
STOP BY
MASTER
Pins 13 and 14 are dedicated to temperature measurement, while
Pins 15, 16, and 19 are dedicated analog input channels. Their
function is unaffected by the Channel Mode Register.
Pins 5 and 6 can be individually programmed as analog inputs,
or as digital fan speed measurement inputs, by programming
Bits 0 and 1 of the Channel Mode Register.
Pins 17 and 18 can be configured as analog inputs or as inputs
for external temperature-sensing diodes by programming Bit 2
of the Channel Mode Register.
Bit 3 of the Channel Mode Register configures the internal V
CC
measurement range for either 3.3 V or 5 V.
Bits 4 to 6 of the Channel Mode Register enable or disable Pins
22 to 24, when they are configured as interrupt inputs by setting
Bit 7 of the Channel Mode Register. This function is controlled
for Pins 20 and 21 by Bits 6 and 7 of Configuration Register 2.
Bit 7 of the Channel Mode Register allows the processor core
voltage ID bits (VID0 to VID4, Pins 24 to 20) to be reconfigured
as interrupt inputs.
A truth table for the Channel Mode Register is given in Table II.
REV. 0
–9–
ADM1024
Table II. Channel Mode Register
Channel Mode Register BitControls Pin(s)Function
050 = FAN1, 1 = AIN1
160 = FAN2, 1 = AIN2
217, 180 = 2.5 V, V
3Int. V
These inputs are multiplexed into the on-chip, successive
approximation, analog-to-digital converter. This has a resolution
of eight bits. The basic input range is zero to 2.5 V, which is
the input range of AIN1 and AIN2, but five of the inputs have
built-in attenuators to allow measurement of 2.5 V, 5 V, 12 V
and the processor core voltages V
CCP1
and V
, without any
CCP2
external components. To allow for the tolerance of these supply
voltages, the A-to-D converter produces an output of 3/4 full-scale
(decimal 192) for the nominal input voltage, and so has adequate
headroom to cope with overvoltages. Table III shows the input
ranges of the analog inputs and output codes of the A-to-D
converter.
When the ADC is running, it samples and converts an input
every 748 µs, except for the external temperature (D1 and D2)
inputs. These have special input signal conditioning and are
averaged over 16 conversions to reduce noise, and a measurement on one of these inputs takes nominally 9.6 ms.
INPUT CIRCUITS
The internal structure for the analog inputs are shown in Figure
10. Each input circuit consists of an input protection diode,
an attenuator, plus a capacitor to form a first-order low-pass
filter which gives the input immunity to high frequency noise.
AIN1–AIN2
+12V
+5V
+2.5V
(SEE TEXT)
+V
CCP1
V
CCP2
80k⍀
10pF
122.2k⍀
22.7k⍀
91.6k⍀
55.2k⍀
36.7k⍀
IN
111.2k⍀
/
42.7k⍀
97.3k⍀
35pF
25pF
25pF
50pF
MUX
RRV
1
=
2
25
(–.)
FS
25
.
Negative and bipolar input ranges can be accommodated by
using a positive reference voltage to offset the input voltage range
so it is always positive.
To measure a negative input voltage, an attenuator can be used
as shown in Figure 12.
+V
OS
R2
R1
V
IN
AIN (1–2)
Figure 12. Scaling and Offsetting AIN(1–2) for Negative
Inputs
R
V
1
||
FS
–
=
R
V
2
OS
This is a simple and cheap solution, but the following point
should be noted. Since the input signal is offset but not inverted,
the input range is transposed. An increase in the magnitude of
the –12 V supply (going more negative), will cause the input
voltage to fall and give a lower output code from the ADC.
Conversely, a decrease in the magnitude of the –12 V supply will
cause the ADC code to increase. The maximum negative voltage
corresponds to zero output from the ADC. This means that the
upper and lower limits will be transposed.
Bipolar input ranges can easily be accommodated. By making R1
equal to R2 and VOS = 2.5 V, the input range is ±2.5 V. Other input
ranges can be accommodated by adding a third resistor to set the
positive full-scale input voltage.
+V
OS
R2
R1
V
IN
AIN (1–2)
R3
Figure 10. Structure of Analog Inputs
2.5 V INPUT PRECAUTIONS
When using the 2.5 V input, the following precautions should
be noted. There is a parasitic diode between Pin 18 and V
CC
due to the presence of a PMOS current source (which is used
when Pin 18 is configured as a temperature input). This will
become forward-biased if Pin 18 is more than 0.3 V above V
Therefore, V
should never be powered off with a 2.5 V input
CC
CC
.
connected.
SETTING OTHER INPUT RANGES
AIN1 and AIN2 can easily be scaled to voltages other than 2.5 V.
If the input voltage range is zero to some positive voltage, all
that is required is an input attenuator, as shown in Figure 11.
AIN (1–2)
R1
V
IN
R2
Figure 11. Scaling AIN(1–2)
REV. 0
–11–
Figure 13. Scaling and Offsetting AIN(1–2) for Bipolar Inputs
R
V
1
||
FS
–
=
R
R
22
(R3 has no effect as the input voltage at the device Pin is zero
when V
= minus full-scale.)
IN
RRV
1
3
(–.)
=
25
FS
+
25
.
(R2 has no effect as the input voltage at the device pin is 2.5 V
when V
= plus full-scale).
IN
Offset voltages other than 2.5 V can be used, but the calculation
becomes more complicated.
TEMPERATURE MEASUREMENT SYSTEM
Internal Temperature Measurement
The ADM1024 contains an on-chip bandgap temperature sensor,
whose output is digitized by the on-chip ADC. The temperature
data is stored in the Temperature Value Register (address 27h)
and the LSB from Bits 6 and 7 of the Temperature Configuration
ADM1024
Register (address 4Bh). As both positive and negative temperatures can be measured, the temperature data is stored in twos
complement format, as shown in Table IV. Theoretically, the
temperature sensor and ADC can measure temperatures from
–128°C to +127°C with a resolution of 1°C, although temperatures below –40°C and above +125°C are outside the operating
temperature range of the device.
External Temperature Measurement
The ADM1024 can measure the temperature of two external
diode sensors or diode-connected transistors, connected to Pins
13 and 14 or 17 and 18.
Pins 13 and 14 are a dedicated temperature input channel. Pins
17 and 18 can be configured to measure a diode sensor by setting Bit 2 of the Channel Mode Register to 1.
The forward voltage of a diode or diode-connected transistor,
operated at a constant current, exhibits a negative temperature
coefficient of about –2 mV/°C. Unfortunately, the absolute value of
V
, varies from device to device, and individual calibration is
BE
required to null this out, so the technique is unsuitable for massproduction.
The technique used in the ADM1024 is to measure the change
in V
when the device is operated at two different currents.
BE
This is given by:
∆V
= KT/q × ln(N)
BE
where:
K is Boltzmann’s constant
q is charge on the carrier
T is absolute temperature in Kelvins
N is ratio of the two currents.
Figure 14 shows the input signal conditioning used to measure
the output of an external temperature sensor. This figure shows the
external sensor as a substrate transistor, provided for temperature
monitoring on some microprocessors, but it could equally well
be a discrete transistor.
To prevent ground noise from interfering with the measurement,
the more negative terminal of the sensor is not referenced to
ground, but is biased above ground by an internal diode at the
D– input. As the sensor is operating in a noisy environment, C1 is
provided as a noise filter. See the section on layout considerations
for more information on C1.
To measure ∆V
, the sensor is switched between operating
BE
currents of I and N × I. The resulting waveform is passed through
a 65 kHz low-pass filter to remove noise, thence to a chopperstabilized amplifier that performs the functions of amplification
and rectification of the waveform to produce a dc voltage proportional to ∆V
. This voltage is measured by the ADC to give
BE
a temperature output in 8-bit twos complement format. To
further reduce the effects of noise. Digital filtering is performed
by averaging the results of 16 measurement cycles. An external
temperature measurement takes nominally 9.6 ms.
The results of external temperature measurements are stored in
8-bit, twos-complement format, as illustrated in Table IV.
Figure 14. Signal Conditioning for External Diode
Temperature Sensors
If a discrete transistor is used, the collector will not be grounded,
and should be linked to the base. If a PNP transistor is used, the
base is connected to the D– input and the emitter to the D+ input.
If an NPN transistor is used, the emitter is connected to the D–
input and the base to the D+ input.
–12–
LAYOUT CONSIDERATIONS
Digital boards can be electrically noisy environments, and care
must be taken to protect the analog inputs from noise, particularly
when measuring the very small voltages from a remote diode
sensor. The following precautions should be taken:
1. Place the ADM1024 as close as possible to the remote sensing
diode. Provided that the worst noise sources such as clock
generators, data/address buses and CRTs are avoided, this
distance can be 4 to 8 inches.
2. Route the D+ and D– tracks close together, in parallel, with
grounded guard tracks on each side. Provide a ground plane
under the tracks if possible.
3. Use wide tracks to minimize inductance and reduce noise
pickup. Ten mil track minimum width and spacing is
recommended.
REV. 0
ADM1024
GND
D+
D–
GND
10MIL
10MIL
10MIL
10MIL
10MIL
10MIL
10MIL
Figure 15. Arrangement of Signal Tracks
4. Try to minimize the number of copper/solder joints, which
can cause thermocouple effects. Where copper/solder joints
are used, make sure that they are in both the D+ and D–
path and at the same temperature.
Thermocouple effects should not be a major problem as 1°C
corresponds to about 240 µV, and thermocouple voltages are
about 3 µV/
o
C of temperature difference. Unless there are
two thermocouples with a big temperature differential between
them, thermocouple voltages should be much less than 200 mV.
5. Place 0.1 µF bypass and 2200 pF input filter capacitors close
to the ADM1024.
6. If the distance to the remote sensor is more than 8 inches, the
use of twisted pair cable is recommended. This will work up
to about 6 feet to 12 feet.
7. For really long distances (up to 100 feet) use shielded twisted
pair such as Belden #8451 microphone cable. Connect the
twisted pair to D+ and D– and the shield to GND close to the
ADM1024. Leave the remote end of the shield unconnected
to avoid ground loops.
Because the measurement technique uses switched current
sources, excessive cable and/or filter capacitance can affect the
measurement. When using long cables, the filter capacitor may
be reduced or removed.
Cable resistance can also introduce errors. One Ω series resistance introduces about 0.5°C error.
LIMIT VALUES
Limit values for analog measurements are stored in the appropriate limit registers. In the case of voltage measurements, high
and low limits can be stored so that an interrupt request will be
generated if the measured value goes above or below acceptable
values. In the case of temperature, a Hot Temperature or High
Limit can be programmed, and a Hot Temperature Hysteresis or Low Limit, which will usually be some degrees lower.
This can be useful as it allows the system to be shut down when
the hot limit is exceeded, and restarted automatically when it has
cooled down to a safe temperature.
MONITORING CYCLE TIME
The monitoring cycle begins when a one is written to the
Start Bit (Bit 0), and a zero to the INT_Clear Bit (Bit 3) of
the Configuration Register. INT_Enable (Bit 1) should be set
to one to enable the INT output. The ADC measures each analog
input in turn, as each measurement is completed the result is
automatically stored in the appropriate value register. This “roundrobin” monitoring cycle continues until it is disabled by writing
a 0 to Bit 0 of the Configuration Register.
As the ADC will normally be left to free-run in this manner, the
time taken to monitor all the analog inputs will normally not be
of interest, as the most recently measured value of any input can
be read out at any time.
For applications where the monitoring cycle time is important,
it can be calculated as follows:
m×t
×n×t
1
2
where:
m is the number of inputs configured as analog inputs, plus the
internal V
t
is the time taken for an analog input conversion, nominally
1
measurement and internal temperature sensor.
CC
755 µs.
n is the number of inputs configured as external temperature
inputs.
t
is the time taken for a temperature conversion, nominally
2
33.24 ms.
This rapid sampling of the analog inputs ensures a quick response
in the event of any input going out of limits, unlike other monitoring chips that employ slower ADCs.
FAN MONITORING CYCLE TIME
When a monitoring cycle is started, monitoring of the fan speed
inputs begins at the same time as monitoring of the analog inputs.
However, the two monitoring cycles are not synchronized in any
way. The monitoring cycle time for the fan inputs is dependent
on fan speed and is much slower than for the analog inputs. For
more details see Fan Speed Measurement section.
INPUT SAFETY
Scaling of the analog inputs is performed on chip, so external
attenuators are normally not required. However, since the power
supply voltages will appear directly at the pins, its is advisable to
add small external resistors in series with the supply traces to the
chip to prevent damaging the traces or power supplies should a
accidental short such as a probe connect two power supplies
together.
As the resistors will form part of the input attenuators, they will
affect the accuracy of the analog measurement if their value is
too high. The analog input channels are calibrated assuming an
external series resistor of 500 Ω, and the accuracy will remain
within specification for any value from zero to 1 kΩ, so a standard 510 Ω resistor is suitable.
The worst such accident would be connecting –12 V to +12 V—
a total of 24 V difference, with the series resistors this would draw
a maximum current of approximately 24 mA.
ANALOG OUTPUT
The ADM1024 has a single analog output from a unsigned 8-bit
DAC which produces 0 V–2.5 V. The analog output register
defaults to FF during power-on reset, which produces maximum
fan speed. The analog output may be amplified and buffered
with external circuitry such as an op amp and transistor to provide
fan speed control.
REV. 0
–13–
ADM1024
Suitable fan drive circuits are given in Figures 16a to 16f. When
using any of these circuits, the following points should be noted:
1. All of these circuits will provide an output range from zero
to almost 12 V, apart from Figure 17a which loses the baseemitter voltage drop of Q1 due to the emitter-follower
configuration.
2. To amplify the 2.5 V range of the analog output up to 12 V,
the gain of these circuits needs to be around 4.8.
3. Care must be taken when choosing the op amp to ensure
that its input common-mode range and output voltage swing
are suitable.
12V
AOUT
+
1/4
LM324
R1
10k⍀
R2
36k⍀
Q1
2N2219A
4. The op amp may be powered from the 12 V rail alone or from
±12 V. If it is powered from 12 V then the input commonmode range should include ground to accommodate the
minimum output voltage of the DAC, and the output voltage
should swing below 0.6 V to ensure that the transistor can
be turned fully off.
5. If the op amp is powered from –12 V, precautions such as a
clamp diode to ground may be needed to prevent the baseemitter junction of the output transistor being reverse-biased
in the unlikely event that the output of the op amp should
swing negative for any reason.
12V
AOUT
R1
100k⍀
MBT3904
Q1/Q2
DUAL
R2
100k⍀
3.9k⍀
R3
R4
1k⍀
Q3
IRF9620
Figure 16a. Fan Drive Circuit with Op Amp and Emitter—
Follower
12V
R3
1k⍀
R2
39k⍀
R4
1k⍀
Q1
BD136
2SA968
AOUT
+
1/4
LM324
R1
10k⍀
Figure 16b. Fan Drive Circuit with Op Amp and PNP Transistor
12V
AOUT
+
1/4
LM324
R1
10k⍀
100k⍀
R2
39k⍀
R3
Q1
IRF9620
Figure 16d. Discrete Fan Drive Circuit with P-Channel
MOSFET, Single Supply
12V
R2
AOUT
MBT3904
R1
4.7k⍀
Q1/Q2
DUAL
–12V
100k⍀
39k⍀
10k⍀
R3
R4
Q3
IRF9620
Figure 16e. Discrete Fan Drive Circuit with P-Channel
MOSFET, Dual Supply
12V
AOUT
100k⍀
MBT3904
R1
Q1/Q2
DUAL
R2
100k⍀
R5
100⍀
Q3
BC556
2N3906
R3
3.9k⍀
R4
1k⍀
Q4
BD132
TIP32A
Figure 16c. Fan Driver Circuit with Op Amp and P-Channel
MOSFET
Figure 16f. Discrete Fan Drive Circuit with Bipolar Output Dual Supply
–14–
REV. 0
ADM1024
12V
PULL-UP
4.7k⍀
TYP
TACHO
OUTPUT
FAN1 OR
FAN2
V
CC
FAN SPEED
COUNTER
160k⍀
6. In all these circuits, the output transistor must have an I
CMAX
greater than the maximum fan current, and be capable of
dissipating power due to the voltage dropped across it when
the fan is not operating at full speed.
7. If the fan motor produces a large back e.m.f when switched
off, it may be necessary to add clamp diodes to protect the
output transistors in the event that the output goes very
quickly from full scale to zero.
FAULT-TOLERANT FAN CONTROL
The ADM1024 incorporates a fault-tolerant fan control capability
that can override the setting of the analog output and force it to
maximum to give full fan speed in the event of a critical overtemperature problem even if, for some reason, this has not been
handled by the system software.
There are four temperature set points that will force the analog
output to FFh if any one of them is exceeded for three or more
consecutive measurements. Two of these limits are programmable
by the user and two are hardware limits intended as must not exceed
limits that cannot be changed.
The analog output will be forced to FFh if:
The temperature measured by the on-chip sensor exceeds the limit
programmed into register address 13h.
or
The temperature measured by either of the remote sensors exceeds
the limit programmed into address 14h.
or
The temperature measured by the on-chip sensor exceeds 70°C,
which is hardware programmed into a read-only register at
address 17h.
or
The temperature measured by either of the remote sensors exceeds
85°C, which is hardware programmed into a read-only register
at address 18h.
Once the hardware override of the analog output is triggered,
it will only return to normal operation after three consecutive
measurements that are 5 degrees lower than each of the above
limits.
The analog output can also be forced to FFh by pulling the
THERM pin (Pin 2) low.
The limits in registers 13h and 14h can be programmed by the
user. Obviously these limits should not exceed the hardware values
in registers 17h and 18h, as they would have no effect. The poweron default values of these registers are the same as the two
hardware registers, 70°C and 85°C respectively, so there is no
need to program them if these limits are acceptable.
Once these registers have been programmed, or if the defaults
are acceptable, the values in these registers can be locked by
writing a 1 to Bits 1 and 2 of Configuration Register 2 (address
4Ah). This prevents any unauthorized tampering with the limits.
These lock bits can only be written to 1 and can only be cleared
by power-on reset or by taking the RESET pin low, so registers
13h and 14h cannot be written to again unless the device is
powered off, then on.
LAYOUT AND GROUNDING
Analog inputs will provide best accuracy when referred to a clean
ground. A separate, low-impedance ground plane for analog
ground, which provides a ground point for the voltage dividers
and analog components, will provide best performance but is
not mandatory.
The power supply bypass, the parallel combination of 10 µF
(electrolytic or tantalum) and 0.1 µF (ceramic) bypass capacitors
connected between Pin 9 and ground, should also be located as
close as possible to the ADM1024.
FAN INPUTS
Pins 5 and 6 may be configured as analog inputs or fan speed
inputs by programming Bits 0 and 1 of the Channel Mode
Register. The power-on default for these bits is all zeroes, which
makes Pins 5 and 6 fan inputs.
Signal conditioning in the ADM1024 accommodates the slow
rise and fall times typical of fan tachometer outputs. The
maximum input signal range is 0 to V
. In the event that these
CC
inputs are supplied from fan outputs that exceed 0 V to 6.5 V,
either resistive attenuation of the fan signal or diode clamping
must be included to keep inputs within an acceptable range.
Figures 17a to 17d show circuits for most common fan tach
outputs.
If the fan tach output has a resistive pull-up to V
it can be directly
CC
connected to the fan input, as shown in Figure 17a.
Figure 17a. Fan with Tach. Pull-Up to +V
CC
If the fan output has a resistive pull-up to 12 V (or other voltage
greater than 6.5 V), the fan output can be clamped with a Zener
diode, as shown in Figure 17b. The Zener voltage should be
chosen so it is greater than V
but less than 6.5 V, allowing
IH
for the voltage tolerance of the Zener. A value of between 3 V
and 5 V is suitable.
12V
PULL-UP
4.7k⍀
TYP
TACHO
OUTPUT
*CHOOSE ZD1 VOLTAGE APPROX. 0.8 ⴛ V
FAN1 OR
ZD1*
ZENER
FAN2
160k⍀
CC
V
CC
FAN SPEED
COUNTER
Figure 17b. Fan with Tach. Pull-Up to Voltage >6.5 V
(e.g., 12 V ) Clamped with Zener Diode
REV. 0
–15–
ADM1024
If the fan has a strong pull-up (less than 1 kΩ) to 12 V, or a
totem-pole output, then a series resistor can be added to limit the
Zener current, as shown in Figure 17c. Alternatively, a resistive
attenuator may be used, as shown in Figure 17d.
R1 and R2 should be chosen such that:
2 V < V
PULL-UP
×R2/(R
+ R1 + R2) < 5 V
PULL-UP
The fan inputs have an input resistance of nominally 160 kΩ to
ground, so this should be taken into account when calculating
resistor values.
With a pull-up voltage of 12 V and pull-up resistor less than 1 kΩ,
suitable values for R1 and R2 would be 100 kΩ and 47 kΩ. This
will give a high-input voltage of 3.83 V.
V
160k⍀
CC
FAN SPEED
COUNTER
12V
PULL-UP
TYP. <1k⍀
OR TOTEM-POLE
TACHO
OUTPUT
*CHOOSE ZD1 VOLTAGE APPROX. 0.8 ⴛ V
R1
10k⍀
FAN1 OR
ZD1*
ZENER
FAN2
CC
Figure 17c. Fan with Strong Tach. Pull-Up to >VCC or
Totem-Pole Output, Clamped with Zener and Resistor
12V
<1k⍀
TACHO
OUTPUT
FAN1 OR
R1*
R2*
*SEE TEXT
FAN2
160k⍀
V
CC
FAN SPEED
COUNTER
Figure 17d. Fan with Strong Tach. Pull-Up to >VCC or
Totem-Pole Output, Attenuated with R1/R2
FAN SPEED MEASUREMENT
The fan counter does not count the fan tach output pulses directly,
because the fan speed may be less than 1000 rpm and it would
take several seconds to accumulate a reasonably large and accurate count. Instead, the period of the fan revolution is measured
by gating an on-chip 22.5 kHz oscillator into the input of an 8-bit
counter for two periods of the fan tach output, as shown in Figure 18; the accumulated count is actually proportional to the fan
tach period and inversely proportional to the fan speed.
22.5kHz
CLOCK
CONFIG.
REG. 1 BIT 0
FAN1
INPUT
FAN2
INPUT
START OF
MONITORING
CYCLE
FAN1
MEASUREMENT
PERIOD
FAN2
MEASUREMENT
PERIOD
Figure 18. Fan Speed Measurement
The monitoring cycle begins when a one is written to the Start
Bit (Bit 0), and a zero to the INT_Clear Bit (Bit 3) of the
Configuration Register. INT_Enable (Bit 1) should be set to
one to enable the INT output. The measurement begins on the
rising edge of a fan tach pulse, and ends on the next-but-one
rising edge. The fans are monitored sequentially, so if only one
fan is monitored the monitoring time is the time taken after the
Start Bit for it to produce two complete tach cycles or for the
counter to reach full scale, whichever occurs sooner. If more
than one fan is monitored, the monitoring time depends on the
speed of the fans and the timing relationship of their tach pulses.
This is illustrated in Figure 19. Once the fan speeds have been
measured, they will be stored in the Fan Speed Value Registers
and the most recent value can be read at any time. The measurements will be updated as long as the monitoring cycle continues.
To accommodate fans of different speed and/or different numbers of output pulses per revolution, a prescaler (divisor) of
1, 2, 4, or 8 may be added before the counter. The default value
is 2, which gives a count of 153 for a fan running at 4400 rpm
producing two output pulses per revolution.
The count is calculated by the equation:
Count = (22.5 × 10
3
× 60) /(rpm×Divisor)
For constant speed fans, fan failure is normally considered to have
occurred when the speed drops below 70% of nominal, which
would correspond to a count of 219. Full scale (255) would be
reached if the fan speed fell to 60% of its nominal value. For
temperature-controlled variable speed fans the situation will be
different.
Table V shows the relationship between fan speed and time
per revolution at 60%, 70%, and 100% of nominal rpm for fan
speeds of 1100, 2200, 4400, and 8800 rpm, and the divisor that
would be used for each of these fans, based on two tach pulses
per revolution.
FAN1 and FAN2 Divisors are programmed into Bits 4 to 7 of
the VID 0–3/Fan Divisor Register.
LIMIT VALUES
Fans in general will not overspeed if run from the correct voltage,
so the failure condition of interest is underspeed due to electrical
or mechanical failure. For this reason only, low-speed limits are
programmed into the limit registers for the fans. It should be noted
that, since fan period rather than speed is being measured, a fan
failure interrupt will occur when the measurement exceeds the
limit value.
MONITORING CYCLE TIME
The monitoring cycle time depends on the fan speed and number
of tach output pulses per revolution. Two complete periods of the
fan tach output (three rising edges) are required for each fan
–16–
REV. 0
ADM1024
74HC132
100k⍀
10k⍀
CI
MRD901
470k⍀
1N914
CMOS
BACKUP
BATTERY
5V
1N914
N1
N2
N3
N4
measurement. Therefore, if the start of a fan measurement just
misses a rising edge, the measurement can take almost three tach
periods. In order to read a valid result from the fan value registers,
the total monitoring time allowed after starting the monitoring cycle should, therefore, be three tach periods of FAN1 plus
three tach periods of FAN2 at the lowest normal fan speed.
Although the fan monitoring cycle and the analog input monitoring
cycle are started together, they are not synchronized in any
other way.
FAN MANUFACTURERS
Manufacturers of cooling fans with tachometer outputs are
listed below:
2408NL 2.36 in sq. × 0.79 in (60 mm sq. × 20 mm)9–16
2410ML 2.36 in sq. × 0.98 in (60 mm sq. × 25 mm) 14–25
3108NL 3.15 in sq. × 0.79 in (80 mm sq. × 20 mm) 25–42
3110KL3.15 in sq. × 0.98 in (80 mm sq. × 25 mm) 25–40
Mechatronics Inc.
P.O. Box 613
Preston, WA 98050
800-453-4569
Models—Various sizes available with tach output option.
Sanyo Denki, America, Inc.
468 Amapola Avenue
Torrance, CA 90501
310-783-5400
Models—109P Series
CHASSIS INTRUSION INPUT
The Chassis Intrusion input is an active high input/open-drain
output intended for detection and signalling of unauthorized
tampering with the system. An external circuit powered from
the system’s CMOS backup battery is used to detect and latch a
chassis intrusion event, whether or not the system is powered
up. Once a chassis intrusion has been detected and latched, the
CI input will generate an interrupt when the system is powered up.
The actual detection of chassis intrusion is performed by an
external circuit that will, for example, detect when the cover
has been removed. A wide variety of techniques may be used for
the detection, for example:
• Microswitch that opens or closes when the cover is removed.
• Reed switch operated by magnet fixed to the cover.
• Hall-effect switch operated by magnet fixed to the cover.
• Phototransistor that detects light when cover is removed.
The chassis intrusion interrupt will remain asserted until the
external detection circuit is reset. This can be achieved by setting
Bit 7 of the Chassis Intrusion Clear Register to one, which will
cause the CI pin to be pulled low for at least 20 ms. This register bit is self-clearing.
REV. 0
The chassis intrusion circuit should be designed so that it can be
reset by pulling its output low. A suitable chassis intrusion circuit
using a phototransistor is shown in Figure 19. Light falling on
the phototransistor when the PC cover is removed will cause it
to turn on and pull up the input of N1, thus setting the latch
N3/N4. After the cover is replaced, a low reset on the CI output
will pull down the input of N4, resetting the latch.
Figure 19. Chassis Intrusion Detector and Latch
The Chassis Intrusion input can also be used for other types of
alarm input. Figure 20 shows a temperature alarm circuit using
an AD22105 temperature switch sensor. This produces a lowgoing output when the preset temperature is exceeded, so the
output is inverted by Q1 to make it compatible with the CI input.
Q1 can by almost any small-signal NPN transistor, or a TTL
or CMOS inverter gate may be used if one is available. See the
AD22105 data sheet for information on selecting R
V
R1
AD22105
R
SET
TEMPERATURE
SENSOR
10k⍀
Q1
.
SET
CC
CI
Figure 20. Using the CI Input with a Temperature Sensor
Note: The chassis intrusion input does not have a protective
clamp diode to V
, as this could pull down the chassis intru-
CC
sion latch and reset it when the ADM1024 was powered down.
THE ADM1024 INTERRUPT STRUCTURE
The Interrupt Structure of the ADM1024 is shown in Figure 21.
As each measurement value is obtained and stored in the
appropriate value register, the value and the limits from the
corresponding limit registers are fed to the high and low limit
comparators. The result of each comparison (1 = out of limit,
0 = in limit) is routed to the corresponding bit input of the
Interrupt Status Registers via a data demultiplexer, and used to
set that bit high or low as appropriate.
The Interrupt Mask Registers have bits corresponding to each of
the Interrupt Status Register Bits. Setting an Interrupt Mask Bit
high forces the corresponding Status Bit output low, while setting
an Interrupt Mask Bit low allows the corresponding Status Bit
–17–
ADM1024
to be asserted. After masking, the status bits are all OR’d
together to produce the INT output, which will pull low if any
unmasked status bit goes high, i.e., when any measured value
goes out of limit. The ADM1024 also has a dedicated output for
temperature interrupts only, the THERM input/output Pin 2.
The function of this is described later.
The INT output is enabled when Bit 1 of Configuration Register 1
(INT_Enable) is high, and Bit 3 (INT_Clear) is low.
The INT pin has an internal, 100 kΩ pull-up resistor.
VID/IRQ INPUTS
The processor voltage ID inputs VID0 to VID4 can be reconfigured as interrupt inputs by setting Bit 7 of the Channel Mode
Register (address 16h). In this mode they operate as level-triggered
interrupt inputs, with VID0/IRQ0 to VID2/IRQ2 being active
low and VID2/IRQ2 and VID4/IRQ4 being active high. The
individual interrupt inputs can be enabled or masked by setting
VID0/IRQ0
VID1/IRQ1
VID2/IRQ2
VID3/IRQ3
VID4/IRQ4
VID0–VID4
REGISTERS
or clearing Bits 4 to 6 of the Channel Mode Register and Bits
6 and 7 of Configuration Register 2 (address 4Ah). These interrupt
inputs are not latched in the ADM1024, so they do not require
clearing as do bits in the Status Registers. However, the external
interrupt source should be cleared once the interrupt has been
serviced, or the interrupt request will be reasserted.
INTERRUPT CLEARING
Reading an Interrupt Status Register will output the contents of
the Register, then clear it. It will remain cleared until the monitoring cycle updates it, so the next read operation should not be
performed on the register until this has happened, or the result
will be invalid. The time taken for a complete monitoring cycle
is mainly dependent on the time taken to measure the fan speeds,
as described earlier.
The INT output is cleared with the INT_Clear bit, which is Bit
3 of the Configuration Register, without affecting the contents
of the Interrupt (INT) Status Registers.
FROM
VALUE
AND LIMIT
REGISTERS
CHANNEL
MODE
REGISTER
CONFIGURATION
REGISTER 2
HIGH
LIMIT
HIGH
AND
VALUE
LOW
LIMIT
LOW
LIMIT
COMPARA-
TORS
4
5
6
7
6
7
1 = OUT
OF
LIMIT
DATA
DEMULTI-
PLEXER
MASKING
DATA
FROM BUS
2.5V/EXT.
TEMP 2
V
CCP1
V
CC
+5V
INT. TEMP
EXT. TEMP1
FAN1/AIN1
FAN2/AIN2
+12V
V
CCP2
RESERVED
RESERVED
CI
THERM
D1 FAULT
D2 FAULT
16 MASK BITS
INTERRUPT MASK
REGISTERS 1 AND 2
(SAME BIT ORDER AS
STATUS REGISTERS)
0
1
2
INTERRUPT
3
STATUS
4
REGISTER 1
5
6
7
0
1
2
INTERRUPT
3
STATUS
4
REGISTER 2
5
6
7
MASK GATING ⴛ 11
STATUS
BIT
MASK
BIT
THERM
INT
ENABLEINT CLEAR
CONFIGURATION
REGISTER 1
THERM
CLEAR
INT
THERM
Figure 21. Interrupt Register Structure
–18–
REV. 0
ADM1024
ANALOG
OUTPUT
FF
H
CLEARED BY
TEMP FALLING
BELOW LOW
LIMIT
TEMP
HIGH LIMIT
THERM
TEMP
PROGRAMMED
VALUE
EXT
THERM
INPUT
CLEARED BY
READ OR
THERM CLEAR
TEMP
LOW LIMIT
INTERRUPT STATUS MIRROR REGISTERS
Whenever a bit in one of the Interrupt Status Registers is updated,
the same bit is written to duplicate registers at addresses 4Ch
and 42h. These registers allow a second management system to
access the status data without worrying about clearing the data.
The data in these registers is for reading only and has no effect
on the interrupt output.
TEMPERATURE INTERRUPT MODES
The ADM1024 has two distinct methods of producing interrupts
for out-of-limit temperature measurements from the internal or
external sensors. Temperature errors can generate an interrupt
on the INT pin along with other interrupts, but there is also
a separate THERM pin that generates an interrupt only for
temperature errors.
Operation of the INT output for temperature interrupts is
illustrated in Figure 22. Assuming that the temperature starts off
within the programmed limits and that temperature interrupt
sources are not masked, INT will go low if the temperature
measured by any of the internal or external sensors exceeds the
programmed high temperature limit for that sensor, or the hardware limits in register 13h, 14h, 17h, or 18h.
100ⴗC
90ⴗC
80ⴗC
70ⴗC
60ⴗC
50ⴗC
40ⴗC
TEMP
*
*
*
HIGH LIMIT
*
*
LOW LIMIT
*
a. the temperature rises above the high limit
or
b. the low limit is/are reprogrammed, and the temperature then
falls below the new low limit
or
c. the THERM pin is pulled low externally, which sets Bit 5 of
Interrupt Status Register 2
or
d. an interrupt is generated by another source.
THERM INPUT/OUTPUT
The Thermal Management Input/Output (THERM) is a logic
input/output with an internal, 100 kΩ pull-up resistor, that
provides a separate output for temperature interrupts only. It is
enabled by setting Bit 2 of Configuration Register 1. The THERM
output has two operating modes that can be programmed by Bit
3 of Configuration Register 2 (address 4Ah). With this bit set to
the default value of 0, the THERM output operates in “Default”
interrupt mode. With this bit set to 1, the THERM output operates in “ACPI” mode.
Thermal interrupts can still be generated at the INT output
while THERM is enabled, but if these are not required they can
be masked by writing a 1 to bit 0 of Configuration Register 2
(address 4Ah). The THERM pin can also function as a logic
input for an external sensor, for example a temperature sensor such
as the ADM22105 used in Figure 23b. If THERM is taken low
by an external source, the analog output will be forced to FFh to
switch a controlled fan to maximum speed. This also generates
an INT output as previously described.
INT
ACPI CONTROL
METHODS
CLEAR EVENT
*ACPI AND DEFAULT CONTROL METHODS
ADJUST TEMPERATURE LIMIT VALUES
Figure 22. Operation of
INT
for Temperature Interrupts
Once the interrupt has been cleared, it will not be reasserted
even if the temperature remains above the high limit(s). However,
INT will be reasserted if:
a. the temperature falls below the low limit for the sensor
or
b. the high limit is/are reprogrammed to a new value, and the
temperature then rises above the new high limit on the next
monitoring cycle
or
c. the THERM pin is pulled low externally, which sets Bit 5 of
Interrupt Status Register 2
or
d. An interrupt is generated by another source.
Similarly, should the temperature measured by a sensor start off
within limits then fall below the low limit, INT will be asserted.
Once cleared, it will not be reasserted unless:
REV. 0
DEFAULT MODE
In Default mode, the THERM output operates like a thermostat
with hysteresis. THERM will go low and Bit 5 of Interrupt Status
Register 2 will be set, if the temperature measured by any of the
sensors exceeds the high limit programmed for that sensor.
It will remain asserted until reset by reading Interrupt Status
Register 2, by setting Bit 6 of Configuration Register 1, or when
the temperature falls below the low limit programmed for that
sensor.
Figure 23a.
INT
or
THERM
Output in Default Mode
–19–
ADM1024
If THERM is cleared by reading the status register, it will be
reasserted after the next temperature reading and comparison if
it remains above the high limit.
If THERM is cleared by setting Bit 6 of Configuration Register
1, it cannot be reasserted until this bit is cleared.
THERM will also be asserted if one of the hardware temperature
limits at addresses 13h, 14h, 17h, or 18h is exceeded for three
consecutive measurements. When this happens, the analog output
will be forced to FFh to boost a controlled cooling fan to full speed.
Reading Status Register 1 will not clear THERM in this case,
because errors caused by exceeding the hardware temperature
limits are stored in a separate register that is not cleared by
reading the status register. In this case, THERM can only be
cleared by setting Bit 0 of Configuration Register 2.
THERM will be cleared automatically if the temperature falls at
least 5 degrees below the limit for three consecutive measurements.
ACPI MODE
In ACPI mode, THERM responds only to the hardware temperature limits at addresses 13h, 14h, 17h and 18h, not to the
software programmed limits.
HARDWARE
TRIP POINT
5ⴗ
TEMP
THERM
EXT
THERM
INPUT
ANALOG
OUTPUT
Figure 23b.
PROGRAMMED
VALUE
THERM
FFhFFh
Output in ACPI Mode
THERM will go low if either the internal or external hardware
temperature limit is exceeded for three consecutive measurements.
It will remain low until the temperature falls at least 5 degrees
below the limit for three consecutive measurements. While
THERM is low, the analog output will go to FFh to boost a
controlled fan to full speed.
RESET INPUT/OUTPUT
RESET (Pin 12) is an I/O pin that can function as an opendrain output, providing a low-going 20 ms output pulse when
Bit 4 of the Configuration Register is set to 1, provided the reset
function has first been enabled by setting Bit 7 of Interrupt
Mask Registers #2 to 1. The bit is automatically cleared when
the reset pulse is output. Pin 11 can also function as a RESET
input by pulling this pin low to reset the internal registers of the
ADM1024 to default values. Only those registers that have power
on default values as listed in Table VI are affected by this function.
The DAC register, Value and Limit Registers are not affected.
NAND TESTS
A NAND gate is provided in the ADM1024 for Automated Test
Equipment (ATE) board level connectivity testing. The device
is placed into NAND Test Mode by powering up with Pin 11 held
high. This pin is automatically sampled after power-up and if it
is connected high, then the NAND test mode is invoked.
In NAND test mode, all digital inputs may be tested as illustrated
below. NTEST_OUT/ADD will become the NAND test output
pin. To perform a NAND tree test all pins included in the NAND
tree should first be driven high. Each pin can then be toggled
and a resulting toggle can be observed on NTEST_OUT/ADD.
Allow for a typical propagation delay of 500 ns. The structure of
the NAND tree is shown in Figure 24.
POWER-ON
RESET
C
NTEST
IN/AOUT
SDA
SCL
FAN1
FAN2
VID0
VID1
VID2
VID3
VID4
LATCH
QD
ENABLE
NTEST OUT/ADD
Figure 24. NAND Tree
Note that NTEST_OUT/ADD is a dual function line and if
both functions are required, then this line should not be hardwired directly to V
/GND. Instead it should be connected via a
CC
5 kΩ resistor.
Note: If any of the inputs shown in Figure 24 are unused, they
should not be connected directly to ground, but via a resistor such
as 10 kΩ. This will allow the ATE (Automatic Test Equipment)
to drive every input high so that the NAND tree test can be carried
out properly.
USING THE ADM1024
POWER-ON RESET
When power is first applied, the ADM1024 performs a “poweron reset” on several of its registers. Registers whose power-on
values are not shown have power-on conditions that are indeterminate (this includes the Value and Limit Registers). The ADC
is inactive. In most applications, usually the first action after
power-on would be to write limits into the Limit Registers.
Power-on reset clears or initializes the following registers (the initialized values are shown in Table VIII):
• Configuration Registers #1 and #2
• Channel Mode Register
• Interrupt (INT) Status Registers #1 and #2
• Interrupt (INT) Status Mirror Registers #1 and #2
• Interrupt (INT) Mask Registers #1 and #2
• VID/Fan Divisor Register
• VID4 Register
• Chassis Intrusion Clear Register
• Test Register
• Analog Output Register
• Hardware Trip Registers
INITIALIZATION
Configuration Register INITIALIZATION performs a similar,
but not identical, function to power-on reset. The Test Register
and Analog Output Register are not initialized.
Configuration Register INITIALIZATION is accomplished by
setting Bit 7 of the Configuration Register high. This bit automatically clears after being set.
–20–
REV. 0
ADM1024
USING THE CONFIGURATION REGISTERS
Control of the ADM1024 is provided through two configuration
registers. The ADC is stopped upon power-up, and the INT_Clear
signal is asserted, clearing the INT output. The Configuration
Registers are used to start and stop the ADM1024; enable or disable interrupt outputs and modes, and provide the initialization
function described above.
Bit 0 of Configuration Register 1 controls the monitoring loop
of the ADM1024. Setting Bit 0 low stops the monitoring loop
and puts the ADM1024 into a low power mode thereby reducing
power consumption. Serial bus communication is still possible
with any register in the ADM1024 while in low-power mode.
Setting Bit 0 high starts the monitoring loop.
Bit 1 of Configuration Register 1 enables or disables the INT
Interrupt output. Setting Bit 1 high enables the INT output,
setting Bit 1 low disables the output.
Bit 2 of Configuration Register 1 enables or disables the THERM
output. Setting Bit 1 high enables the INT output, setting Bit 1
low disables the output.
Bit 3 of Configuration Register 1 is used to clear the INT interrupt output when set high. The ADM1024 monitoring function
will stop until Bit 3 is set low. Interrupt Status register contents
will not be affected.
Bit 4 of Configuration Register 1 causes a low-going 45 ms (typ)
pulse at the RESET pin (Pin 12).
Bit 6 of Configuration Register 1 is used to clear an interrupt at
the THERM output when it is set to 1.
Bit 7 of Configuration Register 1 is used to start a Configuration
Register Initialization when it is set to 1.
Bit 0 of Configuration Register 2 is used to mask temperature
interrupts at the INT output when it is set to 1. The THERM
output is unaffected by this bit.
Bits 1 and 2 of Configuration Register 2 lock the values stored
in the Local and Remote Fan Control Registers at addresses 13h
and 14h. The values in these registers cannot be changed until a
power-on reset is performed.
Bit 3 of Configuration Register 2 selects the THERM interrupt
mode. The default value of 0 selects one-time mode. Setting this
bit to 1 selects ACPI mode.
STARTING CONVERSION
The monitoring function (analog inputs, temperature, and fan
speeds) in the ADM1024 is started by writing to Configuration
Register 1 and setting Start (Bit 0), high. The INT_Enable (Bit
1) should be set to 1, and INT Clear (Bit 3) set to 0 to enable
interrupts. The THERM enable bit (Bit 2) should be set to 1
and the THERM Clear bit (Bit 6) should be set to 0 to enable
temperature interrupts at the THERM pin. Apart from initially
starting together, the analog measurements and fan speed measurements proceed independently, and are not synchronized in
any way.
The time taken to complete the analog measurements depends
on how they are configured, as described elsewhere. The time
taken to complete the fan speed measurements depends on the
fan speed and the number of tach output pulses per revolution.
Once the measurements have been completed, the results can be
read from the Value Registers at any time.
REDUCED POWER AND SHUTDOWN MODE
The ADM1024 can be placed in a low-power mode by setting
Bit 0 of the Configuration Register to 0. This disables the internal ADC. Full shutdown mode may then be achieved by setting
Bit 0 of the Test Register to 1. This turns off the analog output
and stops the monitoring cycle, if running, but it does not affect
the condition of any of the registers. The device will return to its
previous state when this bit is reset to zero.
APPLICATION CIRCUIT
Figure 25 shows a generic application circuit using the ADM1024.
The analog monitoring inputs are connected to the power
supplies including two processor core voltage inputs. The VID
inputs are connected to the processor voltage ID pins. There are
two tach inputs from fans, and the analog output is used to control
the speed of a third fan. An opto-sensor for chassis intrusion
detection is connected to the CI input. Of course, in an actual
application, every input and output may not be used, in which
case unused analog and digital inputs should be tied to analog
or digital ground as appropriate.
REV. 0
–21–
ADM1024
CMOS
BACKUP
BATTERY
1N914
MRD901
470k⍀
12V
74HC132
N1
N3
N2
N4
5V
5V
100k⍀
1N914
10k⍀
2N2219A
12V
THERM I/O TO
OTHER CIRCUITS
510⍀
510⍀
510⍀
510⍀
510⍀
D1+
D1–
VID0/IRQ0
VID1/IRQ1
VID2/IRQ2
VID3/IRQ3
VID4/IRQ4
FROM
VID PINS
OF
PROCESSOR
+V
CCP1
+2.5VIN/D2+
+V
/D2–
CCP2
+5V
IN
+12V
IN
TEMP.
SENSING
TRANSISTOR
NTEST OUT/ ADD
THERM
SDA
SERIAL BUS
5V
5V
INT TO PROCESSOR
+
OP295
39k⍀
SCL
FAN1/AIN1
FAN2/AIN2
0.1F10F
+
NTEST IN/AOUT
10k⍀
RESET
GND D
V
CC
INT
V
ADM1024
CI
CC
10k⍀
Figure 25. Application Circuit
–22–
REV. 0
ADM1024
ADM REGISTERS
Table VI. Address Pointer Register
BitNameR/WDescription
7–0Address PointerWriteAddress of ADM1024 Registers. See the tables below for detail.
Table VII. List of Registers
HexPower-On Value
AddressDescription(Binary Bit 7–0)Notes
13hInternal Temperature= 70°CCan be written only if the write once bit in Configuration
Hardware Trip PointRegister 2 has not been set. Values higher than 70°C will
have no affect as the fixed trip point in register 16h will be
reached first.
14hExternal Temp= 85°CCan be written only if the write once bit in Configuration
Hardware Trip PointRegister 2 has not been set. Values higher than 85°C will
have no affect as the fixed trip point in register 17h will be
reached first.
15hTest Register0000 00X0Setting Bit 0 of this register to 1 selects shutdown mode.
Caution: Do not write to any other bits in this register.
16hChannel Mode Register0000 0000This register configures the input channels and configures
VID0 to VID as processor voltage ID or interrupt inputs.
17hInternal Temperature= 70°CRead Only. Cannot be changed.
Fixed Hardware Trip Point
18hExternal Temperature= 85°CRead Only. Cannot be changed.
Fixed Hardware Trip Point
19hProgrammed Value of Analog Output1111 1111
1AhAIN1 Low LimitIndeterminate
1BhAIN2 Low LimitIndeterminate
20h2.5 V Measured Value/EXT Temp2IndeterminateRead Only.
21hV
22hV
23h5 V ValueIndeterminateRead Only.
24h12 V Measured ValueIndeterminateRead Only.
25hV
26hExt. Temp1 ValueIndeterminateRead Only. Stores the measurement from a diode sensor
27hInternal Temperature ValueIndeterminateRead Only. This register is used to store eight bits of the
28hFAN1/AIN1 ValueIndeterminateRead Only. Stores FAN1 or AIN1 reading depending on
29hFAN2/AIN1 ValueIndeterminateRead Only. Stores FAN2 or AIN2 reading depending on
2AhReservedIndeterminate
2Bh2.5 V/Ext. Temp2 High LimitIndeterminateStores high limit for 2.5 V input or, in temperature mode,
2Ch2.5 V/Ext. Temp2 Low LimitIndeterminateStores low limit for 2.5 V input or, in temperature mode,
2DhV
2EhV
2FhV
30hV
31h5 V High LimitIndeterminate
32h5 V Low LimitIndeterminate
33h12 V High LimitIndeterminate
34h12 V Low LimitIndeterminate
Measured ValueIndeterminateRead Only.
CCP1
Measured ValueIndeterminateRead Only.
CC
Measured ValueIndeterminateRead Only
CCP2
connected to Pins 13 and 14.
internal temperature reading.
the configuration of Pin 5.
the configuration of Pin 6.
this register stores the high limit for a diode sensor connected to Pins 17 and 18.
this register stores the low limit for a diode sensor connected to Pins 17 and 18.
High LimitIndeterminate
CCP1
Low LimitIndeterminate
CCP1
High LimitIndeterminate
CC
Low LimitIndeterminate
CC
REV. 0
–23–
ADM1024
Table VII (continued)
HexPower-On Value
AddressDescription(Binary Bit 7–0)Notes
35hV
36hV
37hExt Temp1. High LimitIndeterminateStores high limit for a diode sensor connected to Pins 13
38hExt Temp1. Low LimitIndeterminateStores low limit for a diode sensor connected to Pins 13
39hInternal Temp. High LimitIndeterminateStores the high limit for the internal temperature reading.
3AhInternal Temp. Low LimitIndeterminateStores the low limit for the internal temperature reading.
3BhAIN1/FAN1 High LimitIndeterminateStores high limit for AIN1 or FAN1, depending on the
3ChAIN2/FAN2 High LimitIndeterminateStores high limit for AIN2 or FAN2, depending on the
3DhReservedIndeterminate
3EhCompany ID Number0100 0001This location will contain the company identification number
3FhRevision Number0001 nnnnLast four bits of this location will contain the revision number
40hConfiguration Register 10000 1000See Table IX.
41hInterrupt INT Status Register 10000 0000See Table X.
42hInterrupt INT Status Register 20000 0000See Table XI.
43hINT Mask Register 10000 0000See Table XII.
44hINT Mask Register 20000 0000See Table XIII.
46hChassis Intrusion Clear Register0000 0000See Table XIV.
47hVID 0–3/Fan Divisor Register0101 (VID3–VID0) See Table XV.
49hVID4 Register1000 000 (VID4)See Table XVI.
4AhConfiguration Register 20000 0000See Table XVII.
4ChInterrupt Status Register0000 0000See Table XVIII.
4DhInterrupt Status Register0000 0000See Table XIX.
0STARTR/WLogic 1 enables start-up of ADM1024, logic 0 places it in standby mode. Caution: The outputs of
the interrupt pins will not be cleared if the user writes a zero to this location after an interrupt has
occurred (see “INT Clear” bit). At start-up, limit checking functions and scanning begins. Note, all
high and low limits should be set into the ADM1024 prior to turning on this bit. (Power-Up Default = 0)
3INT_ClearR/WDuring Interrupt Service Routine (ISR) this bit is asserted Logic 1 to clear INT output without
affecting the contents of the Interrupt Status Register. The device will stop monitoring. It will resume
upon clearing of this bit. (Power-Up Default = 0)
4RESETR/WSetting this bit generates a low-going 45 ms reset pulse at Pin 12. This bit is self-clearing and power-
up default is 0.
5ReservedR/WDefault = 0.
6THERM CLR R/WA one clears the THERM output without changing the Status Register contents.
7InitializationR/WLogic 1 restores Power-Up default values to the Configuration register, Interrupt status registers,
Interrupt Mask Registers, Fan Divisor Register, and the Temperature Configuration Register. This bit
automatically clears itself since the power-on default is zero.
02.5 V/External Temp2 ErrorRead OnlyA one indicates that a High or Low limit has been exceeded.
1V
2V
ErrorRead OnlyA one indicates that a High or Low limit has been exceeded.
CCP1
ErrorRead OnlyA one indicates that a High or Low limit has been exceeded.
CC
35 V ErrorRead OnlyA one indicates that a High or Low limit has been exceeded.
4Internal Temp ErrorRead OnlyA one indicates that a temperature interrupt has been set, or that a High or
Low limit has been exceeded.
5External Temp1 ErrorRead OnlyA one indicates that a temperature interrupt has been set, or that a High or
Low limit has been exceeded.
6FAN1/AIN1 ErrorRead OnlyA one indicates that a High or Low limit has been exceeded.
7FAN2/AIN2 ErrorRead OnlyA one indicates that a High or Low limit has been exceeded.
Table XI. Register 42h, Interrupt Status Register 2 (Power-On Default = 00h)
BitNameR/WDescription
012 V ErrorRead OnlyA one indicates a High or Low limit has been exceeded.
1V
ErrorRead OnlyA one indicates a High or Low limit has been exceeded.
CCP2
2ReservedRead OnlyUndefined.
3ReservedRead OnlyUndefined.
4Chassis ErrorRead OnlyA one indicates Chassis Intrusion has gone high.
5THERM InterruptRead OnlyIndicates that THERM pin has been pulled low by an external source.
6D1 FaultRead OnlyShort or open-circuit sensor diode D1.
7D2 FaultRead OnlyShort or open-circuit sensor diode D2.
NOTES
1. Any time the STATUS Register is read out, the conditions (i.e., Register) that are read are automatically reset. In the case of the channel priority indication, if two
or more channels were out of limits, then another indication would automatically be generated if it was not handled during the ISR.
2. In the Mask Register, the errant voltage interrupt may be disabled, until the operator has time to clear the errant condition or set the limit higher/lower.
REV. 0
–25–
ADM1024
Table XII. Register 43h, INT Interrupt Mask Register 1 (Power-On Default = 00h)
BitNameR/WDescription
02.5 V/Ext. Temp2Read/WriteA one disables the corresponding interrupt status bit for INT interrupt.
1V
CCP1
2V
CC
35 VRead/WriteA one disables the corresponding interrupt status bit for INT interrupt.
4Int. TempRead/WriteA one disables the corresponding interrupt status bit for INT interrupt.
5Ext. Temp1Read/WriteA one disables the corresponding interrupt status bit for INT interrupt.
6FAN1/AIN1Read/WriteA one disables the corresponding interrupt status bit for INT interrupt.
7FAN2/AIN2Read/WriteA one disables the corresponding interrupt status bit for INT interrupt.
BitNameR/WDescription
012 VRead/WriteA one disables the corresponding interrupt status bit for INT interrupt.
1V
CCP2
2ReservedRead/WritePower-up default set to Low.
3ReservedRead/WritePower-up default set to Low.
4CIRead/WriteA one disables the corresponding interrupt status bit for INT interrupt.
5THERM (Input)Read/WriteA one disables the corresponding interrupt status bit for INT interrupt.
6D1 FaultRead/WriteA one disables the corresponding interrupt status bit for INT interrupt.
7D2 FaultRead/WriteA one disables the corresponding interrupt status bit for INT interrupt.
Read/WriteA one disables the corresponding interrupt status bit for INT interrupt.
Read/WriteA one disables the corresponding interrupt status bit for INT interrupt.
Table XIII. Register 44h, INT Mask Register 2 (Power-On Default = 00h)
Read/WriteA one disables the corresponding interrupt status bit for INT interrupt.
0–6 ReservedRead OnlyUndefined, always reads as 00h.
7Chassis Int. ClearRead/WriteA one outputs a minimum 20 ms active low pulse on the Chassis Intrusion
pin. The register bit clears itself after the pulse has been output.
Table XV. Register 47h, VID0–3/FAN Divisor Register (Power-On Default 0101(VID3–0))
Bit NameR/WDescription
0–3 VIDReadThe VID[3:0] inputs from processor core power supplies to indicate the
operating voltage (e.g., 1.3 V to 3.5 V)
4–5 FAN1 DivisorRead/WriteSets counter prescaler for FAN1 speed measurement
<5:4> = 00 – divide by 1
<5:4> = 01 – divide by 2
<5:4> = 10 – divide by 4
<5:4> = 11 – divide by 8.
6–7 FAN2 DivisorRead/WriteSets counter prescaler for FAN2 speed measurement
<7:6> = 00 – divide by 1
<7:6> = 01 – divide by 2
<7:6> = 10 – divide by 4
<7:6> = 11 – divide by 8.
Table XVI. Register 49h, VID4/Device ID Register (Power-On Default 1000000(VID4))
BitNameR/WDescription
0VID4Read OnlyVID4 Input from Pentium.
1–7 ReservedRead OnlyUndefined, always reads as 1000 000(VID4).
0Thermal INTRead/WriteSetting this bit masks the thermal interrupts for the INT output ONLY. The
MaskTHERM output will still be generated, regardless of the setting of this bit.
1Ambient TempRead/WriteWriting a one to this bit will lock in the values set into the ambient tempera-
Fan ControlOnceture automatic fan control register 13h. This register will not be able to be
Register Writewritten again until a reset is performed (either POR, Hard or Soft Reset).
Once Bit
2Remote TempRead/WriteWriting a one to this bit will lock in the values set into the remote tempera-
Fan ControlOnceture automatic fan control register 14h. This register will not be able to
Register Writebe written again until a reset is performed (either POR, Hard or Soft Reset).
Once Bit
3THERMRead/WriteIf this bit is 0 the THERM output operates in default mode.
Interrupt ModeIf this bit is 1, the THERM output operates in ACPI mode.
4, 5ReservedRead OnlyReserved.
6IRQ3 ENRead/WriteSetting this bit to 1 enables Pin 21 as an active high interrupt input, provided
Pins 20 to 24 have been configured as interrupts by setting Bit 7 of the
Channel Mode Register. Power-on default = 0.
7IRQ4 ENRead/WriteSetting this bit to 1 enables Pin 20 as an active high interrupt input, provided
Pins 20 to 24 have been configured as interrupts by setting Bit 7 of the
Channel Mode Register. Power-on default = 0.
Table XVIII. Register 4Ch, Interrupt Status Register 1 Mirror (Power-On Default <7:0> = 00h)
BitNameR/WDescription
02.5 V/Ext. Temp2 ErrorRead OnlyA one indicates that a High or Low limit has been exceeded.
1V
2V
ErrorRead OnlyA one indicates that a High or Low limit has been exceeded.
CCP1
ErrorRead OnlyA one indicates that a High or Low limit has been exceeded.
CC
35 V ErrorRead OnlyA one indicates that a High or Low limit has been exceeded.
4Internal Temp ErrorRead OnlyA one indicates that a temperature interrupt has been set, or that a High or
Low limit has been exceeded.
5External Temp1 ErrorRead OnlyA one indicates that a temperature interrupt has been set, or that a High or
Low limit has been exceeded.
6FAN1/AIN1 ErrorRead OnlyA one indicates that a High or Low limit has been exceeded.
7FAN2/AIN2 ErrorRead OnlyA one indicates that a High or Low limit has been exceeded.
Table XIX. Register 4DH, Interrupt Status Register 2 Mirror (Power-On Default <7:0> = 00h)
BitNameR/WDescription
012 V ErrorRead OnlyA one indicates a High or Low limit has been exceeded.
1V
ErrorRead OnlyA one indicates a High or Low limit has been exceeded.
CCP2
2ReservedRead OnlyUndefined.
3ReservedRead OnlyUndefined.
4Chassis ErrorRead OnlyA one indicates Chassis Intrusion has gone high.
5THERM InterruptRead OnlyIndicates that THERM pin has been pulled low by an external source.
6D1 FaultRead OnlyShort or open-circuit sensor diode D1.
7D2 FaultRead OnlyShort or open-circuit sensor diode D2.
NOTE
An error that causes continuous interrupts to be generated may be masked in its respective mask register, until the error can be alleviated.
REV. 0
–27–
ADM1024
OUTLINE DIMENSIONS
Dimensions shown in inches and (mm).
24-Lead TSSOP Package
(RU-24)
0.311 (7.90)
0.303 (7.70)
24
PIN 1
0.006 (0.15)
0.002 (0.05)
SEATING
PLANE
0.0256 (0.65)
BSC
13
121
0.0433 (1.10)
MAX
0.0118 (0.30)
0.0075 (0.19)
0.177 (4.50)
0.169 (4.30)
0.256 (6.50)
0.246 (6.25)
0.0079 (0.20)
0.0035 (0.090)
C00059–2.5–7/00 (rev. 0)
8ⴗ
0ⴗ
0.028 (0.70)
0.020 (0.50)
–28–
PRINTED IN U.S.A.
REV. 0
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.