Datasheet ADE7761A Datasheet (ANALOG DEVICES)

现货库存、技术资料、百科信息、热点资讯,精彩尽在鼎好!
V
Energy Metering IC with On-Chip Fault and
FEATURES
High accuracy, active energy measurement IC supports
IEC 62053-21 Less than 0.1% error over a dynamic range of 500 to 1 Supplies active power on the frequency outputs, F1 and F2 High frequency output CF is intended for calibration and
supplies instantaneous active power Continuous monitoring of the phase and neutral current
allows fault detection in 2-wire distribution systems Current channels input level best suited for shunt and
current transformer sensors Uses the larger of the two currents (phase or neutral) to
bill—even during a fault condition Continuous monitoring of the voltage and current inputs
allows missing neutral detection Uses one current input (phase or neutral) to bill when
missing neutral is detected Two logic outputs (FAULT and REVP) can be used to indicate
a potential miswiring, fault, or missing neutral condition Direct drive for electromechanical counters and 2-phase
stepper motors (F1 and F2) Proprietary ADCs and DSP provide high accuracy over large
variations in environmental conditions and time Reference 2.5 V ± 8% (drift 30 ppm/°C typical) with external
overdrive capability Single 5 V supply, low power
Missing Neutral Detection
ADE7761A
GENERAL DESCRIPTION
The ADE7761A is a high accuracy, fault-tolerant, electrical energy measurement IC intended for use with 2-wire distribution systems. The part specifications surpass the accuracy requirements as quoted in the IEC 62053-21 standard. The only analog circuitry used on the ADE7761A is in the ADCs and reference circuit. All other signal processing (such as multiplication and filtering) is carried out in the digital domain. This approach provides superior stability and accuracy over extremes in environmental conditions and over time. The ADE7761A incorporates a fault detection scheme similar to the ADE7751 by continuously monitoring both phase and neutral currents. A fault is indicated when the currents differ by more than 6.25%.
The ADE7761A incorporates a missing neutral detection scheme by continuously monitoring the input voltage. When a missing neutral condition is detected—no voltage input—the ADE7761A continues billing based on the active current signal (see the condition is indicated when the FAULT pin goes high. The ADE7761A supplies average active power information on the low frequency outputs, F1 and F2. The CF logic output gives instantaneous active power information.
The ADE7761A includes a power-supply monitoring circuit on the V that the voltage and current channels are matched. An internal no-load threshold ensures that the ADE7761A does not exhibit any creep when there is no load.
Missing Neutral Mode section). The missing neutral
supply pin. Internal phase matching circuitry ensures
DD
FUNCTIONAL BLOCK DIAGRAM
AGND FAULT
PGA
13
V
2
1A
4
V
1N
3
V
1B
7
MISCAL
6
V
2P
5
V
2N
2.5V
REFERENCE
Rev. 0
ADC
ADC
ADC
ADC
3kΩ
OSCILLATOR
9 14 17 10 11 12
IN/OUT
A>B
B>A A<>B
MISSING NEUT RAL
INTERNAL
HPF
GAIN ADJUST
15 18
ZERO CROSSING
DETECTI ON
MISSING NEUTRAL
DETECTI ON
DIGITAL-TO-FREQUENCY CONV ERTER
DD
POWER
SUPPLY MONITOR
ADE7761A
SIGNAL PROCESSING
BLOCK
LPF
16 18 19 20
F1F2CFREVPS0S1SCFDGNDRCLKINRE F
05040-0-001
Figure 1.
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A. Tel: 781.329.4700 www.analog.com Fax: 781.461.3113 ©2006 Analog Devices, Inc. All rights reserved.
ADE7761A
TABLE OF CONTENTS
Features .............................................................................................. 1
Analog Inputs ............................................................................. 11
General Description......................................................................... 1
Functional Block Diagram .............................................................. 1
Revision History ............................................................................... 2
Specifications..................................................................................... 3
Timing Characteristics ................................................................ 4
Absolute Maximum Ratings............................................................ 5
Performance Issues That May Affect Billing Accuracy........... 5
ESD Caution.................................................................................. 5
Pin Configuration and Function Descriptions............................. 6
Te r mi n ol o g y ...................................................................................... 8
Typical Performance Characteristics............................................. 9
Test Circ uit ...................................................................................... 10
Operation.........................................................................................11
Power Supply Monitor ............................................................... 11
Internal Oscillator ...................................................................... 12
Analog-to-Digital Conversion.................................................. 13
Active Power Calculation .......................................................... 14
Digital-to-Frequency Conversion............................................ 16
Transfer Fu nction .......................................................................16
Fault Detection ........................................................................... 17
Missing Neutral Mode............................................................... 18
Applications..................................................................................... 21
Interfacing to a Microcontroller for Energy Measurement.. 21
Selecting a Frequency for an Energy Meter Application ......21
Negative Power Information..................................................... 22
Outline Dimensions .......................................................................23
Ordering Guide .......................................................................... 23
REVISION HISTORY
7/06—Revision 0: Initial Version
Rev. 0 | Page 2 of 24
ADE7761A
SPECIFICATIONS
VDD = 5 V ± 5%, AGND = DGND = 0 V, on-chip reference, on-chip oscillator, T
Table 1.
Parameter Value Unit Test Conditions/Comments
ACCURACY
Measurement Error
1
2
0.1 % of reading, typ Over a dynamic range of 500 to 1
Phase Error Between Channels
PF = 0.8 Capacitive ±0.05 Degrees, max Phase lead 37° PF = 0.5 Inductive ±0.05 Degrees, max Phase lag 60°
AC Power Supply Rejection
2
Output Frequency Variation 0.01 %, typ V1A = V1B = V2P = ±100 mV rms
DC Power Supply Rejection
2
Output Frequency Variation 0.01 %, typ V1A = V1B = V2P = ±100 mV rms
FAU LT D ETEC TION
2, 3
See the Fault Detection section
Fault Detection Threshold
Inactive Input <> Active Input 6.25 %, typ V1A or V1B active
Input Swap Threshold
Inactive Input <> Active Input 6.25 % of larger, typ V1A or V1B active
Accuracy Fault Mode Operation
V1A Active, V1B = AGND 0.1 % of reading, typ Over a dynamic range of 500 to 1
V1B Active, V1A = AGND 0.1 % of reading, typ Over a dynamic range of 500 to 1 Fault Detection Delay 3 Seconds, typ Swap Delay 3 Seconds, typ
MISSING NEUTRAL MODE
2, 4
See the Missing Neutral Detection section
Missing Neutral Detection Threshold
V2P − V
2N
59.4 mV peak, min
Accuracy Missing Neutral Mode
V1A Active, V1B = V2P = AGND 0.1 % of reading, typ Over a dynamic range of 500 to 1
V1B Active, V1A = V2P = AGND 0.1 % of reading, typ Over a dynamic range of 500 to 1 Missing Neutral Detection Delay 3 Seconds, typ
ANALOG INPUTS V1A − V1N, V1B − V1N, V2P − V
Maximum Signal Levels ±660 mV peak, max Differential input 660 mV peak, max Differential input MISCAL − V Input Impedance (DC) 400 kΩ, min Bandwidth (−3 dB) 7 kHz, typ ADC Offset Error
2
15 mV, typ Uncalibrated error, see the Terminology section for details Gain Error ±4 %, typ External 2.5 V reference Gain Error Match
2
±3 %, typ External 2.5 V reference
REFERENCE INPUT
REF
Input Voltage Range 2.7 V, max 2.5 V + 8%
IN/OUT
2.3 V, min 2.5 V − 8% Input Impedance 3 kΩ, min Input Capacitance 10 pF, max
ON-CHIP REFERENCE
Reference Error ±200 mV, max Temperature Coefficient 30 ppm/°C, typ Current Source 20 µA, min
ON-CHIP OSCILLATOR
Oscillator Frequency 450 kHz Oscillator Frequency Tolerance ±12 % of reading, typ Temperature Coefficient 30 ppm/°C, typ
MIN
to T
= −40°C to +85°C.
MAX
2N
2N
Rev. 0 | Page 3 of 24
ADE7761A
Parameter Value Unit Test Conditions/Comments
LOGIC INPUTS
PGA, SCF, S1, and S0
Input High Voltage, V Input Low Voltage, V Input Current, I Input Capacitance, C
LOGIC OUTPUTS
CF, REVP, and FAULT
Output High Voltage, V Output Low Voltage, V
F1 and F2
Output High Voltage, V Output Low Voltage, V
POWER SUPPLY For specified performance
V
DD
5.25 V, max 5 V + 5% V
DD
1
See plots in the Typical Performance Characteristics section.
2
See the Terminology section for explanation of specifications.
3
See the Fault Detection section for explanation of fault detection functionality.
4
See the Missing Neutral Detection section for explanation of missing neutral detection functionality.
5
Sample tested during initial release and after any redesign or process change that might affect this parameter.
TIMING CHARACTERISTICS
VDD = 5 V ± 5%, AGND = DGND = 0 V, on-chip reference, on-chip oscillator, T initial release and after any redesign or process change that might affect this parameter. See
Table 2.
Parameter Value Unit Test Conditions/Comments
1
t
1
t
2
t
3
1
t
4
t
5
t
6
1
The pulse widths of F1, F2, and CF are not fixed for higher output frequencies. See the Transfer Function section.
5
INH
INL
IN
IN
5
OH
OH
OH
OH
2.4 V, min VDD = 5 V ± 5%
0.8 V, max VDD = 5 V ± 5% ±3 µA, max Typical 10 nA, VIN = 0 V to V 10 pF, max
4 V, min VDD = 5 V ± 5% 1 V, max VDD = 5 V ± 5%
4 V, min VDD = 5 V ± 5%, I 1 V, max VDD = 5 V ± 5%, I
SOURCE
SINK
4.75 V, min 5 V − 5%
3 mA, max
MIN
to T
= −40°C to +85°C. Sample tested during
MAX
Figure 2.
120 ms F1 and F2 Pulse Width (Logic High). See Tab le 7 s Output Pulse Period. See the Transfer Function section. 1/2 t
2
s Time Between F1 Falling Edge and F2 Falling Edge. 90 ms CF Pulse Width (Logic High). See Tab le 8 s CF Pulse Period. See the Transfer Function section. CLKIN/4 s Minimum Time Between F1 and F2 Pulse.
t
1
DD
= 10 mA
= 10 mA
F1
t
6
t
2
t
F2
t
4
CF
3
t
5
05040-002
Figure 2. Timing Diagram for Frequency Outputs
Rev. 0 | Page 4 of 24
ADE7761A
ABSOLUTE MAXIMUM RATINGS
TA = 25°C, unless otherwise noted.
Table 3.
Parameter Rating
VDD to AGND −0.3 V to +7 V Analog Input Voltage to AGND
, V1B, V1N, V2N, V2P, MISCAL
V
1A
Reference Input Voltage to AGND −0.3 V to VDD + 0.3 V Digital Input Voltage to DGND −0.3 V to VDD + 0.3 V Digital Output Voltage to DGND −0.3 V to VDD + 0.3 V Operating Temperature Range
Industrial −40°C to +85°C Storage Temperature Range −65°C to +150°C Junction Temperature 150°C 20-Lead SSOP, Power Dissipation 450 mW θJA Thermal Impedance 112°C/W Lead Temperature, Soldering
Vapor Phase (60 sec) 215°C
Infrared (15 sec) 220°C
−6 V to +6 V
Stresses above those listed under Absolute Maximum Ratings may cause permanent damage to the device. This is a stress rating only; functional operation of the device at these or any other conditions above those listed in the operational sections of this specification is not implied. Exposure to absolute maximum rating conditions for extended periods may affect device reliability.
PERFORMANCE ISSUES THAT MAY AFFECT BILLING ACCURACY
The ADE7761A provides pulse outputs—CF, F1, and F2— intended to be used for the billing of active energy. Pulses are generated at these outputs in two different situations.
Case 1: When the analog input V conditions described in
Figure 34, CF, F1, and F2 frequencies are proportional to active power and can be used to bill active energy.
Case 2: When the analog input V the conditions described in measure active energy but a quantity proportional to kAh. This quantity is used to generate pulses on the same CF, F1, and F2. This situation is indicated when the FAULT pin is high.
Analog Devices, Inc. cautions users of the ADE7761A about the following:
Billing active energy in Case 1 is consistent with the
understanding of the quantity represented by pulses on CF, F1, and F2 outputs (watt-hour).
Billing active energy while the ADE7761A is in Case 2 must
be decided knowing that the entity measured by the ADE7761A in this case is ampere-hour and not watt-hour. Users should be aware of this limitation and decide if the ADE7761A is appropriate for their application.
– V2N complies with the
2P
– V2N does not comply with
2P
Figure 34, the ADE7761A does not
ESD CAUTION
ESD (electrostatic discharge) sensitive device. Electrostatic charges as high as 4000 V readily accumulate on the human body and test equipment and can discharge without detection. Although this product features proprietary ESD protection circuitry, permanent damage may occur on devices subjected to high energy electrostatic discharges. Therefore, proper ESD precautions are recommended to avoid performance degradation or loss of functionality.
Rev. 0 | Page 5 of 24
ADE7761A
PIN CONFIGURATION AND FUNCTION DESCRIPTIONS
1
V
DD
2
V
1A
3
V
1B
V
4
1N
V
5
ADE7761A
MISCAL
REF
V
AGND
IN/OUT
SCF
2N
2P
6
7
8
9
10
TOP VIEW
(Not to Scale)
Figure 3. Pin Configuration (SSOP)
Table 4. Pin Function Descriptions
Pin No. Mnemonic Description
1 V
DD
Power Supply. This pin provides the supply voltage for the digital circuitry in the ADE7761A. The supply voltage should be maintained at 5 V ± 5% for specified operation. This pin should be decoupled with a 10 µF capacitor in parallel with a ceramic 100 nF capacitor.
2, 3 V1A, V
1B
Analog Inputs for Channel 1 (Current Channel). These inputs are fully differential voltage inputs with maximum differential input signal levels of ±660 mV with respect to V at these pins is ±1 V with respect to AGND. Both inputs have internal ESD protection circuitry, and an overvoltage of ±6 V can also be sustained on these inputs without risk of permanent damage.
4 V
1N
Negative Input for Differential Voltage Inputs, V1A and V1B. The maximum signal level at this pin is ±1 V with respect to AGND. The input has internal ESD protection circuitry, and an overvoltage of ±6 V can also be sustained on this input without risk of permanent damage. The input should be directly connected to the burden resistor and held at a fixed potential, that is, AGND. See the
5 V
2N
Negative Input for Differential Voltage Inputs, V2P and MISCAL. The maximum signal level at this pin is ±1 V with respect to AGND. The input has internal ESD protection circuitry, and an overvoltage of ±6 V can also be sustained on this input without risk of permanent damage. The input should be held at a fixed potential, that is, AGND. See the
Analog Inputs section.
6 V
2P
Analog Input for Channel 2 (Voltage Channel). This input is a fully differential voltage input with maximum differential input signal levels of ±660 mV with respect to V this pin is ±1 V with respect to AGND. This input has internal ESD protection circuitry, and an overvoltage of ±6 V can also be sustained on this input without risk of permanent damage.
7 MISCAL
Analog Input for Missing Neutral Calibration. This pin can be used to calibrate the CF-F1-F2 frequencies in the missing neutral condition. This input is a fully differential voltage input with maximum differential input signal levels of 660 mV with respect to V
for specified operation. The maximum signal level at this pin is ±1 V with
2N
respect to AGND. This input has internal ESD protection circuitry, and an overvoltage of ±6 V can also be sustained on this input without risk of permanent damage.
8 AGND
This pin provides the ground reference for the analog circuitry in the ADE7761A, that is, ADCs and reference. This pin should be tied to the analog ground plane of the PCB. The analog ground plane is the ground reference for all analog circuitry, such as antialiasing filters, and current and voltage transducers. For good noise suppression, the analog ground plane should be connected only to the digital ground plane at the DGND pin.
9 REF
IN/OUT
This pin provides access to the on-chip voltage reference. The on-chip reference has a nominal value of
2.5 V ± 8% and a typical temperature coefficient of 30 ppm/°C. An external reference source can also be connected at this pin. In either case, this pin should be decoupled to AGND with a 1 F ceramic capacitor and 100 nF ceramic capacitor.
10 SCF
Select Calibration Frequency. This logic input is used to select the frequency on the calibration output CF. Table 7 shows how the calibration frequencies are selected.
11, 12 S1, S0
These logic inputs are used to select one of four possible frequencies for the digital-to-frequency conversion. This offers the designer greater flexibility when designing the energy meter. See the Energy Meter Application
section. 13 PGA This logic input is used to select the gain for the analog inputs, V1A and V1B. The possible gains are 1 and 16. 14 RCLKIN
To enable the internal oscillator as a clock source on the chip, a precise low temperature drift resistor at nominal value of 6.2 kΩ must be connected from this pin to DGND.
20
F1
19
F2
18
CF
17
DGND
16
REVP
15
FAU LT
14
RCLKIN
13
PGA
12
S0
11
S1
05040-003
for specified operation. The maximum signal level
1N
Analog Inputs section.
for specified operation. The maximum signal level at
2N
Selecting a Frequency for an
Rev. 0 | Page 6 of 24
ADE7761A
Pin No. Mnemonic Description
15 FAULT
16 REVP
17 DGND
18 CF
19, 20 F2, F1
This logic output goes active high when a fault or missing neutral condition occurs. A fault is defined as a condition under which the signals on V defined when the chip is powered up with no voltage at the input. The logic output is reset to zero when a fault or missing neutral condition is no longer detected. See the Fault Detection section and the Missing Neutral Mode section.
This logic output goes logic high when negative power is detected, that is, when the phase angle between the voltage and current signals is greater than 90°. This output is not latched and is reset when positive power is once again detected. The output goes high or low at the same time as a pulse is issued on CF.
This pin provides the ground reference for the digital circuitry in the ADE7761A, that is, multiplier, filters, and digital-to-frequency converters. This pin should be tied to the digital ground plane of the PCB. The digital ground plane is the ground reference for all digital circuitry, such as counters (mechanical and digital), MCUs, and indicator LEDs. For good noise suppression, the analog ground plane should be connected only to the digital ground plane at the DGND pin.
Calibration Frequency Logic Output. The CF logic output, active high, gives instantaneous active power information. This output is used for operational and calibration purposes. See the section.
Low Frequency Logic Outputs. F1 and F2 supply average active power information. The logic outputs can be used to directly drive electromechanical counters and 2-phase stepper motors.
and V1B differ by more than 6.25%. A missing neutral condition is
1A
Digital-to-Frequency Conversion
Rev. 0 | Page 7 of 24
ADE7761A
r
e
TERMINOLOGY
Measurement Error
The error associated with the energy measurement made by the ADE7761A is defined by
=
Percentag
⎛ ⎜ ⎜ ⎝
Phase Error Between Channels
The high-pass filter (HPF) in the current channel has a phase lead response. To offset this phase response and equalize the phase response among channels, a phase correction network is also placed in the current channel. The phase correction network ensures a phase match between the current channels and voltage channels to within ±0.1° over a range of 45 Hz to 65 Hz and ±0.2° over a range of 40 Hz to 1 kHz.
Power Supply Rejection (PSR)
PSR quantifies the ADE7761A measurement error as a percentage of reading when the power supplies are varied. For the ac PSR measurement, a reading at nominal supplies (5 V) is taken. A second reading is obtained with the same input signal levels when an ac (175 mV rms/100 Hz) signal is introduced onto the supplies. Any error introduced by this ac signal is expressed as a percentage of reading (see the Error
definition).
Erro
EnergyTrueADE7761AbyregisteredEnergy
EnergyTrue
Measurement
×
%100
⎟ ⎠
For the dc PSR measurement, a reading at nominal supplies (5 V) is taken. A second reading is obtained with the same input signal levels when the power supplies are varied ±5%. Any error introduced is again expressed as a percentage of reading.
ADC Offset Error
The dc offset associated with the analog inputs to the ADCs. With the analog inputs connected to AGND, the ADCs still see a dc analog input signal. The magnitude of the offset depends on the input gain and range selection (see the Characteristics the offset is removed from the current channels and the power calculation is not affected by this offset.
Gain Error
The gain error in the ADE7761A ADCs is defined as the difference between the measured output frequency (minus the offset) and the ideal output frequency. It is measured with a gain of 1 in Channel V percentage of the ideal frequency, which is obtained from the transfer function (see the
Gain Error Match
The gain error match is defined as the gain error (minus the offset) obtained when switching between a gain of 1 or 16. It is expressed as a percentage of the output ADC code obtained under a gain of 1.
section). However, when HPFs are switched on,
. The difference is expressed as a
1A
Transfer Functi on section).
Typical Performance
Rev. 0 | Page 8 of 24
ADE7761A
%
R
%
R
TYPICAL PERFORMANCE CHARACTERISTICS
1.0 PF = 1
ON-CHIP REF ERENCE
0.8
0.6
0.4
0.2
0
–0.2
% ERROR
–0.4
–0.6
–0.8
–1.0
CURRENT (% of Fu ll Scale)
–40°C
+25°C
+85°C
Figure 4. Active Power Error as a Percentage of Reading
with Gain = 1 and Internal Reference
1.5 PF = DIFFERENT VALUES
ON-CHIP REF ERENCE
1.0
0.5
0
% ERROR
–0.5
–1.0
–40°C; PF = 0.5
+25°C; PF = 1
+85°C; PF = 0.5
CURRENT (% of Fu ll Scale)
+25°C; PF = 0.5
Figure 5. Active Power Error as a Percentage of Reading over Power Factor with Gain = 1 and Internal Reference
1.0 PF = 1. GAIN = 16
ON-CHIP REF ERENCE
0.8
0.6
0.4
0.2
0
ERRO
–0.2
–0.4
–0.6
–0.8
–1.0
0.10 1 10 100
+25°C
+85°C
–40°C
CURRENT (% Full Scale)
Figure 6. Active Power Error as a Percentage of Reading
with Gain = 16 and Internal Reference
100.00.1 1.0 10.0
05040-004
1000.1 1.0 10
05040-005
05040-034
1.0 GAIN = 16
ON-CHI P REFE RENCE
0.8
0.6
0.4
0.2
0
ERRO
–0.2
–0.4
–0.6
–0.8
–1.0
0.10 1 10 100
PF = –0.5
PF = +1
PF = +0.5
CURRENT (% Full Scale)
Figure 7. Active Power Error as a Percentage of Reading
over Power Factor with Gain = 16 and Internal Reference
1.0 PF = 1
ON-CHIP REF ERENCE
0.8
0.6
0.4
0.2
0
–0.2
% ERROR
–0.4
–0.6
–0.8
–1.0
5.25V
5.00V
4.75V
CURRENT (% of Fu ll Scale)
Figure 8. Active Power Error as a Percentage of Reading
over Power Supply with Gain = 1 and Internal Reference
2.0 ON-CHIP REF ERENCE
1.5
1.0
0.5
0
% ERROR
–0.5
–1.0
–1.5
–2.0
+25°C
CURRENT (% of Fu ll Scale)
+85°C
–40°C
Figure 9. Ampere Hour Error as a Percentage of Reading
in Missing Neutral Mode with Gain = 1 and Internal Reference
05040-035
100.00.1 1.0 10.0
05040-006
100.00.1 1.0 10.0
05040-007
Rev. 0 | Page 9 of 24
ADE7761A
V
V
TEST CIRCUIT
DD
+
220
40A TO 80mA
RB = 18
1M
10µF
I
RB
RB
33nF1k
560k
100k
1k
33nF
1k
33nF
1k
33nF
1k
33nF
33nF
100nF
2
3
4
5
6
7
1
V
DD
V
1A
V
1B
V
1N
V
2N
V
2P
MISCAL
ADE7761A
AGND DGNDPGA
RCLKIN
REF
FAU LT
SCF
IN/OUT
1713 8
10k
100nF
PS2501-1
1
2
4
3
+
TO FREQ . COUNTE R
10µF
2k
18
CF
2k
15
6.2k
14
12
S0
11
S1
10
9
05040-008
Figure 10. Test Circuit for Performance Curves
Rev. 0 | Page 10 of 24
ADE7761A
V
V
V
OPERATION
V1
V
V1
V2
V
V
CM
MISCAL
MISCAL
V
V
CM
AGND
1A
1N
1B
V
2P
2N
2N
POWER SUPPLY MONITOR
The ADE7761A continuously monitors the power supply (VDD) with its on-chip, power supply monitor. If the supply is less than 4 V ± 5%, the ADE7761A goes into an inactive state, that is, no energy is accumulated and the CF, F1, and F2 outputs are disabled. This is useful to ensure correct device operation at power-up and during power-down. The power supply monitor has built-in hysteresis and filtering, which provides a high degree of immunity to false triggering due to noisy supplies.
The power supply and decoupling for the part should be such that the ripple at V
does not exceed 5 V ± 5% as specified for
DD
normal operation.
DD
5V 4V
0V
ADE7761A
REVP - FAULT - CF -
F1 - F2 OUTPUTS
INACTIVE ACTIVE
Figure 11. On-Chip, Power Supply Monitoring
TIME
INACTIVE
ANALOG INPUTS
Channel V1 (Current Channel)
The voltage outputs from the current transducers are connected to the ADE7761A at Channel V1. It has two voltage inputs, V and V
. These inputs are fully differential with respect to V1N.
1B
However, at any one time, only one is selected to perform the power calculation (see the
The maximum peak differential signal on V
Fault Detection section).
− V1N and V1B − V1N
1A
is ±660 mV. However, Channel 1 has a programmable gain amplifier (PGA) with user-selectable gains of 1 or 16 (see Table 5). This gain facilitates easy transducer interfacing.
Table 5. Channel 1 Dynamic Range
PGA Gain Maximum Differential Signal (mV)
0 1 660 1 16 41
Figure 12 shows the maximum signal levels on V1A, V1B, and
. The maximum differential voltage is ±660 mV divided by
V
1N
the gain selection. The differential voltage signal on the inputs must be referenced to a common mode (usually AGND).
1A
DIFFERENTIAL INPUT A
±660mV MAX PEAK
COMMON MO DE
±100mV MAX
DIFFERENTIAL INPUT B
±660mV MAX PEAK V
AGND
V
CM
+660mV
GAIN
–660mV
GAIN
+ V
+ V
V
, V
1A
1B
CM
V
CM
CM
Figure 12. Maximum Signal Levels, Channel 1
Channel V2 (Voltage Channel)
The output of the line voltage transducer is connected to the ADE7761A at this analog input. Channel V2 is a single-ended, voltage input. The maximum peak differential signal on Channel 2 is ±660 mV with respect to V
. Figure 13 shows the maximum
2N
signal levels that can be connected to Channel 2.
2
+660mV + V
–660mV + V
05040-009
CM
V
CM
CM
DIFFERENTIAL INPUT
±660mV MAX PEAK
COMMON MODE
±100mV MAX
Figure 13. Maximum Signal Levels, Channel 2
The differential voltage V2P − V2N must be referenced to a common mode (usually AGND). The analog inputs of the ADE7761A can be driven with common-mode voltages of up to 100 mV with respect to AGND. However, the best results are achieved using a common mode equal to AGND.
MISCAL Input
The input for the power calibration in missing neutral mode is connected to the ADE7761A at this analog input. MISCAL is a single-ended, voltage input. It is recommended to use a dc signal derived from the voltage reference to drive this pin. The maximum peak differential signal on MISCAL is 660 mV with respect to V
. Figure 14 shows the maximum signal levels that
2N
can be connected to the MISCAL pin.
MISCAL
+660mV + V
CM
V
CM
DIFFERENTIAL INPUT
±660mV MAX PEAK
COMMON MODE
±100mV MAX
Figure 14. Maximum Signal Levels, MISCAL
05040-010
05040-011
05040-012
Rev. 0 | Page 11 of 24
ADE7761A
V
V
A
A
The differential voltage MISCAL − V2N must be referenced to a common mode (usually AGND). The analog inputs of the ADE7761A can be driven with common-mode voltages of up to 100 mV with respect to AGND. However, best results are achieved using a common mode equal to AGND.
Typical Connection Diagrams
Figure 15 shows a typical connection diagram for Channel V1. The analog inputs are used to monitor both the phase and neutral currents. Because of the large potential difference between the phase and neutral, two current transformers (CTs) must be used to provide the isolation. Note that both CTs are referenced to analog ground (AGND); therefore, the common­mode voltage is 0 V. The CT turns ratio and burden resistor (RB) are selected to give a peak differential voltage of ±660 mV/gain.
R
±660mV
GAIN
±660mV
GAIN
R
F
F
CT
RB
INIP
AGND
RB
PHASE
NEUTRAL
CT
Figure 15. Typical Connection for Channel 1
1A
C
F
V
1N
C
F
V
1B
05040-013
Figure 16 shows two typical connections for Channel V2. The first option uses a potential transformer (PT) to provide complete isolation from the main voltage. In the second option, the ADE7761A is biased around the neutral wire, and a resistor divider is used to provide a voltage signal that is proportional to the line voltage. Adjusting the ratio of RA and RB + VR is a convenient way to carry out a gain calibration on the meter.
R
±660mV
R
NEUTRAL
PHASE
AGND
2P
F
C
F
V
2N
F
C
F
Adjusting the level of MISCAL to calibrate the meter in missing neutral mode can be done by changing the ratio of RC and RD + VR1. When the internal reference is used, the values of RC, RD, and VR1 must be chosen to limit the current sourced by the internal reference sourcing current to below the specified 20 μA. Therefore, because V
internal = 2.5 V, RC + RD +
REF
VR1 > 600 kΩ.
REF
RC
IN/OUT
C
RD
VR1
F
MISCAL
R
F
C
F
Figure 17. Typical Connection for MISCAL
V
2N
05040-015
INTERNAL OSCILLATOR
The nominal internal oscillator frequency is 450 kHz when used with the recommended R between RCLKIN and DGND (see
The internal oscillator frequency is inversely proportional to the value of this resistor. Although the internal oscillator operates when used with an R
resistor value between 5 kΩ and 12 kΩ,
OSC
it is recommended to choose a value within the range of the nominal value.
The output frequencies on CF, F1, and F2 are directly propor­tional to the internal oscillator frequency; therefore, the resistor R
must have a low tolerance and low temperature drift. A low
OSC
tolerance resistor limits the variation of the internal oscillator frequency. A small variation of the clock frequency and consequently of the output frequencies from meter to meter contributes to a smaller calibration range of the meter.
A low temperature drift resistor directly limits the variation of the internal clock frequency over temperature. The stability of the meter to external variation is then better ensured by design.
DE7761
resistor value of 6.2 kΩ
OSC
Figure 18).
1
RA
C
F
V
2P
V
R
2N
F
C
T
05040-014
NEUTRAL
PHASE
1
RB + VR = RF.
RB
VR
1
1
Figure 16. Typical Connection for Channel 2
Figure 17 shows a typical connection for the MISCAL input. The voltage reference input (REF
) is used as a dc reference
IN/OUT
to set the MISCAL voltage.
REFERENCE
3k
2.5V
9
IN/OUT
INTERNAL
OSCILLATOR
14 17
R
OSC
Figure 18. Internal Oscillator Connection
DGNDRCLKINREF
05040-016
Rev. 0 | Page 12 of 24
ADE7761A
A
A
A
A
ANALOG-TO-DIGITAL CONVERSION
The analog-to-digital conversion in the ADE7761A is carried out using second-order, Σ-Δ ADCs. order, Σ-Δ ADC (for simplicity). The converter is made up of two parts: the Σ-Δ modulator and the digital low-pass filter.
ANALOG
LOW-PASS FILTER
R
C
INTEGRATOR
V
REF
Figure 19. First-Order, Σ-Δ ADC
A Σ-Δ modulator converts the input signal into a continuous serial stream of 1s and 0s at a rate determined by the sampling clock. In the ADE7761A, the sampling clock is equal to CLKIN. The 1-bit DAC in the feedback loop is driven by the serial data stream. The DAC output is subtracted from the input signal. If the loop gain is high enough, the average value of the DAC output (and, therefore, the bit stream) approaches that of the input signal level. For any given input value in a single sampling interval, the data from the 1-bit ADC is virtually meaningless. Only when a large number of samples are averaged is a meaningful result obtained. This averaging is carried out in the second part of the ADC, the digital low-pass filter. By averaging a large number of bits from the modulator, the low-pass filter can produce 24-bit data-words that are proportional to the input signal level.
The Σ-Δ converter uses two techniques to achieve high resolution from what is essentially a 1-bit conversion technique. The first is oversampling, which means that the signal is sampled at a rate (frequency) that is many times higher than the bandwidth of interest. For example, the sampling rate in the ADE7761A is CLKIN (450 kHz) and the band of interest is 40 Hz to 1 kHz. Oversampling has the effect of spreading the quantization noise (noise due to sampling) over a wider bandwidth. With the noise spread more thinly over a wider bandwidth, the quantization noise in the band of interest is lowered (see
However, oversampling alone is not an efficient enough method to improve the signal-to-noise ratio (SNR) in the band of interest. For example, an oversampling ratio of 4 is required just to increase the SNR by only 6 dB (1 bit). To keep the oversampling ratio at a reasonable level, it is possible to shape the quantization noise so that the majority of the noise lies at the higher frequencies. This is what happens in the Σ-Δ modulator; the noise is shaped by the integrator, which has a high-pass type response for the quantization noise. The result is that most of the noise is at the higher frequencies, where it can be removed by the digital low­pass filter. This noise shaping is also shown in
Figure 19 shows a first-
MCLK
LATCHED COMPAR­ATO R
....10100101....
1-BIT DAC
Figure 20).
DIGITAL
LOW-PASS FILTER
1 24
Figure 20.
NTIALIAS FILTER (RC)
SIGN
L
NOISE
0 1 225 450
SIGN
L
NOISE
04407-017
0 1 225 450
DI G ITA L F ILT E R
FREQUENCY (kHz)
HIGH RESOLUTION
OUTPUT FROM
DIGITAL LFP
FREQUENCY (kHz)
Figure 20. Noise Reduction due to Oversampling and
Noise Shaping in the Analog Modulator
SAMPLING FREQUENCY
SHAPED NOISE
05040-018
Antialias Filter
Figure 20 also shows an analog low-pass filter (RC) on input to the modulator. This filter is present to prevent aliasing. Aliasing is an artifact of all sampled systems, which means that frequency components in the input signal to the ADC that are higher than half the sampling rate of the ADC appear in the sampled signal frequency below half the sampling rate.
Figure 21 illustrates
the effect.
In
Figure 21, frequency components (arrows shown in black) above half the sampling frequency (also known as the Nyquist frequency), that is, 225 kHz, are imaged or folded back down below 225 kHz (arrows shown in gray). This happens with all ADCs no matter what the architecture. In the example shown, only frequencies near the sampling frequency (450 kHz) move into the band of interest for metering (40 Hz to 1 kHz). This fact allows the use of a very simple low-pass filter to attenuate these frequencies (near 250 kHz) and thereby prevent distortion in the band of interest. A simple RC filter (single pole) with a corner frequency of 10 kHz produces an attenuation of approximately 33 dB at 450 kHz (see
Figure 21). This is
sufficient to eliminate the effects of aliasing.
NTIALIASING EFFECTS
SAMPLING
IMAGE
FREQUENCIES
0 1 225 450
FREQUENCY (kHz)
Figure 21. ADC and Signal Processing in Current Channel or Voltage Channel
FREQUENCY
05040-019
Rev. 0 | Page 13 of 24
ADE7761A
ACTIVE POWER CALCULATION
The ADCs digitize the voltage signals from the current and voltage transducers. A high-pass filter in the current channel removes any dc component from the current signal. This eliminates any inaccuracies in the active power calculation due to offsets in the voltage or current signals (see the Offset Effects
section).
The active power calculation is derived from the instantaneous power signal. The instantaneous power signal is generated by a direct multiplication of the current and voltage signals. To extract the active power component (dc component), the instantaneous power signal is low-pass filtered. illustrates the instantaneous active power signal and shows how the active power information can be extracted by low-pass filtering the instantaneous power signal. This scheme correctly calculates active power for nonsinusoidal current and voltage waveforms at all power factors. All signal processing is carried out in the digital domain for superior stability over temperature and time.
CH1
CH2
V × I
PGA
TIME
ADC
HPF
MULTIPLIER
ADC
INSTANTANEOUS
POWER SIGNAL –p(t)
p(t) = i(t).v(t) WHERE: v(t) = V × cos(ωt) i(t) = I × cos(ωt)
V × I
p(t) =
2
{1 + cos (2ωt)}
LPF
INSTANTANEOUS
ACTIVE POWER SIGNAL
V × I
2
Figure 22. Signal Processing Block Diagram
The low frequency output of the ADE7761A is generated by accumulating this active power information. This low frequency inherently means a long accumulation time between output pulses. The output frequency is, therefore, proportional to the average active power. This average active power information can, in turn, be accumulated (for example, by a counter) to generate active energy information. Because of its high output frequency and, therefore, shorter integration time, the CF output is proportional to the instantaneous active power. This is useful for system calibration purposes that take place under steady load conditions.
HPF and
Figure 22
DIGITAL-TO-
FREQUENCY
DIGITAL-TO-
FREQUENCY
F1 F2
CF
05040-020
Power Factor Considerations
The method used to extract the active power information from the instantaneous power signal (by low-pass filtering) is still valid even when the voltage and current signals are not in phase.
Figure 23 displays the unity power factor condition and a displacement power factor (DPF = 0.5), that is, current signal lagging the voltage by 60°.
V × I
2
V × I
2
0V
× cos(60°)
0V
INSTANTANEOUS POWER SIGNAL
CURRENT VOLTAGE
INSTANTANEOUS POWER SIGNAL
VOLTAGE
60°
Figure 23. Active Power Calculation over PF
INSTANTANEOUS ACTIVE POWER SIGNAL
INSTANTANEOUS ACTIVE POWE R SIGNAL
CURRENT
If one assumes that the voltage and current waveforms are sinusoidal, the active power component of the instantaneous power signal (dc term) is given by
(
V × I/2) × cos(60°)
This is the correct active power calculation.
Nonsinusoidal Voltage and Current
The active power calculation method also holds true for nonsinusoidal current and voltage waveforms. All voltage and current waveforms in practical applications have some harmonic content. Using the Fourier transform, instantaneous voltage and current waveforms can be expressed in terms of their harmonic content
O
h
0hh
(1)
)sin(2)(
thVVtv α+ω××+=
where:
v(t) is the instantaneous voltage.
V
is the average value.
O
V
is the rms value of voltage harmonic h.
h
αh is the phase angle of the voltage harmonic.
05040-021
Rev. 0 | Page 14 of 24
ADE7761A
β
O
h
0hh
)sin(2)(
thIIti β+ω××+=
(2)
The HPF in Channel 1 has an associated phase response that is compensated for on-chip. phase error between channels with the compensation network
where:
i(t) is the instantaneous current.
I
is the dc component.
O
is the rms value of current harmonic h.
I
h
is the phase angle of the current harmonic.
β
h
Using Equation 1 and Equation 2, the active power P can be expressed in terms of its fundamental active power (P harmonic active power (P
+ P
P = P
1
H
).
H
) and
1
activated. The ADE7761A is phase compensated up to 1 kHz as shown, which ensures a correct active harmonic power calculation even at low power factors.
V1 × I
1
2
where:
= V1 × I1 cos(Φ1)
P
1
= α1 − β1 (3)
Φ
1
0ϖ
Figure 24. Effect of Channel Offsets on the Active Power Calculation
and
IVP
H
2
h
=
α=Φ (4)
hhh
)cos(
Φ××=
hhh
0.30
0.25
0.20
Figure 25 and Figure 26 show the
DC COMPONENT (INCLUDING ERRO R TERM) IS EXTRACTE D BY THE LPF FOR ACTIVE POWER CALCULATION
V1 × I
0
V0 × I
1
FREQUENCY (RAD/ S)
2ω
05040-022
As can be seen in Equation 4, a harmonic active power component is generated for every harmonic provided that the harmonic is present in both the voltage and current waveforms. The power factor calculation was previously shown to be accurate in the case of a pure sinusoid; therefore, the harmonic active power must also correctly account for the power factor because it is made up of a series of pure sinusoids.
Note that the input bandwidth of the analog inputs is 7 kHz with an internal oscillator frequency of 450 kHz.
HPF and Offset Effects
Equation 5 shows the effect of offsets on the active power calculation.
Figure 24 shows the effect of offsets on the active
power calculation in the frequency domain.
)()(
tItV
=×
1010
IV
×
IV
+×
10
11
2
As can be seen in Equation 5 and
))cos(())cos((
tIItVV
=ω×+×ω×+
0110
Figure 24, an offset on Channel 1
(5)
)cos()cos(
tIVtIV
ω××+ω××+
and Channel 2 contributes a dc component after multiplication. Because this dc component is extracted by the LPF and used to generate the active power information, the offsets contribute a constant error to the active power calculation. This problem is easily avoided in the ADE7761A with the HPF in Channel 1. By removing the offset from at least one channel, no error component can be generated at dc by the multiplication. Error terms at cos(ωt) are removed by the LPF and the digital-to-frequency conversion (see the
Digital-to-Frequency Conversion section).
0.15
0.10
0.05
PHASE (Degrees)
0
–0.05
–0.10
0 100
200 300 400 500 600 700 80 0 900 1000
FREQUENCY (Hz)
05040-023
Figure 25. Phase Error Between Channels (0 Hz to 1 kHz)
0.30
0.25
0.20
0.15
0.10
0.05
PHASE (Degrees)
0
–0.05
–0.10
40
45 50 55 60 65 70
FREQUENCY (Hz)
05040-024
Figure 26. Phase Error Between Channels (40 Hz to 70 Hz)
Rev. 0 | Page 15 of 24
ADE7761A
××××
DIGITAL-TO-FREQUENCY CONVERSION
As previously described, the digital output of the low-pass filter after multiplication contains the active power information. However, because this LPF is not an ideal brick wall filter implementation, the output signal also contains attenuated components at the line frequency and its harmonics, that is, cos(hωt), where h = 1, 2, 3, …, and so on. The magnitude response of the filter is given by
)(ffH
=
For a line frequency of 50 Hz, this gives an attenuation of the 2ω (100 Hz) component of approximately −26.9 dB. The dominating harmonic is at twice the line frequency, cos(2ωt), due to the instantaneous power signal.
1
=
(6)
2
)Hz5.4/(1
F1
The output frequency on CF can be up to 2048 times higher than the frequency on F1 and F2. This higher output frequency is generated by accumulating the instantaneous active power signal over a much shorter time while converting it to a frequency. This shorter accumulation period means less averaging of the cos(2ωt) component. As a consequence, some of this instantaneous power signal passes through the digital-to-frequency conversion. This is not a problem in the application.
Where CF is used for calibration purposes, the frequency should be averaged by the frequency counter, which removes any ripple. If CF is being used to measure energy, such as in a microprocessor-based application, the CF output should also be averaged to calculate power. Because the outputs, F1 and F2, operate at a much lower frequency, a lot more averaging of the instantaneous active power signal is carried out. The result is a greatly attenuated sinusoidal content and a virtually ripple-free frequency output.
DIGITAL-TO-
FREQUENCY
V
MULTIPLIER
I
LPF TO EXTRACT ACTIVE POWER (DC TERM)
0 ω 2ω
FREQUENCY (Rad/s)
INSTANTANEOUS ACTIVE POWE R SIGNAL (FREQUENC Y DOMAIN)
Figure 27. Active Power to Frequency Conversion
LPF
DIGITAL-TO-
FREQUENCY
F1 F2
FOUT
CF
TIME
FREQUENCY FRE QUENCY
TIME
Figure 27 shows the instantaneous active power signal output of the LPF, which still contains a significant amount of instantaneous power information, cos(2ωt). This signal is then passed to the digital-to-frequency converter, where it is integrated (accumulated) over time to produce an output frequency. This accumulation of the signal suppresses or averages out any non-dc components in the instantaneous active power signal. The average value of a sinusoidal signal is zero. Therefore, the frequency generated by the ADE7761A is proportional to the average active power.
Figure 27 also shows the digital-to-frequency conversion for steady load conditions: constant voltage and current. As can be
Figure 27, the frequency output CF varies over time,
seen in even under steady load conditions. This frequency variation is primarily due to the cos(2ωt) component in the instantaneous active power signal.
TRANSFER FUNCTION
Frequency Outputs F1 and F2
The ADE7761A calculates the product of two voltage signals (on Channel 1 and Channel 2) and then low-pass filters this product to extract active power information. This active power information is then converted to a frequency. The frequency information is output on F1 and F2 in the form of active high pulses. The pulse rate at these outputs is relatively low, for example, 0.34 Hz maximum for ac signals with S0 = S1 = 0
Table 8). This means that the frequency at these outputs is
(see generated from active power information accumulated over a relatively long period. The result is an output frequency that is
05040-025
proportional to the average active power. The averaging of the active power signal is implicit to the digital-to-frequency conversion. The output frequency or pulse rate is related to the input voltage signals by
70.5
FrequencyFF
21
= (7)
2
V
REF
FV2V1Gain
41rmsrms
where:
F
F2 Frequency is the output frequency on F1 and F2 (Hz).
1
is the differential rms voltage signal on Channel 1 (V).
V1
rms
is the differential rms voltage signal on Channel 2 (V).
V2
rms
Gain is 1 or 16, depending on the PGA gain selection made
using the logic input PGA.
V
is the reference voltage (2.5 V ± 8%) (V).
REF
F
is one of four possible frequencies selected by using the
1–4
logic inputs S0 and S1 (see
Tabl e 6).
Rev. 0 | Page 16 of 24
ADE7761A
Table 6. F
S1 S0 F
0 0 1.72 OSC/2 0 1 3.44 OSC/2 1 0 6.86 OSC/2 1 1 13.7 OSC/2
1
Values are generated using the nominal frequency of 450 kHz.
2
F
are a binary fraction of the master clock and, therefore, vary with the
1–4
internal oscillator frequency (OSC).
Frequency Output CF
The pulse output calibration frequency (CF) is intended for use during calibration. The output pulse rate on CF can be up to 2048 times the pulse rate on F1 and F2. The lower the F frequency selected, the higher the CF scaling. how the two frequencies are related, depending on the states of the logic inputs S0, S1, and SCF. Because of its relatively high pulse rate, the frequency at this logic output is proportional to the instantaneous active power. As with F1 and F2, the frequency is derived from the output of the low-pass filter after multiplication. However, because the output frequency is high, this active power information is accumulated over a much shorter time. Therefore, less averaging is carried out in the digital-to-frequency conversion. With much less averaging of the active power signal, the CF output is much more responsive to power fluctuations (see
Table 7. Relationship Between CF and F1, F2 Frequency Outputs
SCF S1 S0 F
1 0 0 1.72 128 × F1, F2 0 0 0 1.72 64 × F1, F2 1 0 1 3.44 64 × F1, F2 0 0 1 3.44 32 × F1, F2 1 1 0 6.86 32 × F1, F2 0 1 0 6.86 16 × F1, F2 1 1 1 13.7 16 × F1, F2 0 1 1 13.7 2048 × F1, F2
Example
In this example, if ac voltages of ±660 mV peak are applied to V1 and V2, then the expected output frequency on CF, F1, and F2 is calculated as
Frequency Selection
1–4
1–4
(Hz)
1
Figure 22).
(Hz) CF Frequency Output
1–4
Gain = 1, PGA = 0
F
= 1.7 Hz, SCF = S1 = S0 = 0
1–4
V1
= rms of 660 mV peak ac = 0.66/√2 V
rms
V2
= rms of 660 mV peak ac = 0.66/√2 V
rms
V
= 2.5 V (nominal reference value)
REF
F
= OSC/2
1−4
18
17
16
15
Table 7 shows
n 2
1–4
Note that if the on-chip reference is used, actual output frequencies can vary from device to device due to a reference tolerance of ±8%.
Hz72.166.066.070.5
FrequencyFF
21
CF Frequency = F
=
F2 × 64 = 22.0 Hz
1
×××
2
5.222
××
Hz34.0
=
As can be seen from these two example calculations, the maximum output frequency for ac inputs is always half of that for dc input signals.
Table 8 shows a complete listing of all
maximum output frequencies for ac signals.
Table 8. Maximum Output Frequencies on CF, F1, and F2 for AC Inputs
SCF S1 S0
F1, F2 Maximum Frequency (Hz)
CF Maximum Frequency (Hz)
CF-to­F1 Ratio
1 0 0 0.34 43.52 128 0 0 0 0.34 21.76 64 1 0 1 0.68 43.52 64 0 0 1 0.68 21.76 32 1 1 0 1.36 43.52 32 0 1 0 1.36 21.76 16 1 1 1 2.72 43.52 16 0 1 1 2.72 5570 2048
FAULT DETECTION
The ADE7761A incorporates a novel fault detection scheme that warns of fault conditions and allows the ADE7761A to continue accurate billing during a fault event. The ADE7761A does this by continuously monitoring both the phase and neutral (return) currents. A fault is indicated when these currents differ by more than 6.25%. However, even during a fault, the output pulse rate on F1 and F2 is generated using the larger of the two currents. Because the ADE7761A looks for a difference between the voltage signals on V important that both current transducers be closely matched.
On power-up, the output pulse rate of the ADE7761A is proportional to the product of the voltage signals on V Channel 2. If the difference between V greater than 6.25%, the fault indicator (FAULT) becomes active after about 1 sec. In addition, if V ADE7761A selects V
as the input. The fault detection is
1B
is greater than V1A, the
1B
automatically disabled when the voltage signal on Channel 1 is less than 0.3% of the full-scale input range. This eliminates false detection of a fault due to noise at light loads.
and V1B, it is
1A
and
1A
and V1B on power-up is
1A
Rev. 0 | Page 17 of 24
ADE7761A
Fault with Active Input Greater than Inactive Input
If V1A is the active current input (that is, being used for billing), and the voltage signal on V of V
, the fault indicator becomes active. Both analog inputs
1A
(inactive input) falls below 93.75%
1B
are filtered and averaged to prevent false triggering of this logic output. As a consequence of the filtering, there is a time delay of approximately 3 sec on the logic output FAULT after the fault event. The FAULT logic output is independent of any activity on outputs F1 or F2. FAULT becomes active. Because V still greater than V swap to the V
V
V
0V
V1B < 93.75% OF V
FAULT
<0
6.25% OF ACTIV E INPUT
Figure 28. Fault Conditions for Active Input Greater than Inactive Input
Figure 28 shows one condition under which
is the active input and it is
1A
, billing is maintained on V1A, that is, no
1B
input occurs. V1A remains the active input.
1B
A
B
FILTER
AND
COMPARE
1A
1B
AGND
1A
V
1A
V
1A
V
1N
V
1B
V
1B
>0
ACTIVE POINT – INACTIVE INPUT
FAULT
TO MULTIPLIER
Fault with Inactive Input Greater than Active Input
Figure 29 illustrates another fault condition. If the difference between V is, being used for billing), becomes greater than 6.25% of V the FAULT indicator becomes active and a swap over to the V input occurs. The analog input V
, the inactive input, and V1A, the active input (that
1B
becomes the active input.
1B
,
1B
1B
Again, a time constant of about 3 sec is associated with this swap. V greater than V this order—becomes greater than 6.25% of V FAULT indicator becomes inactive as soon as V
6.25% of V between V
0V
does not swap back to the active channel until V1A is
1A
and the difference between V1A and V1B—in
1B
. However, the
1A
is within
1A
. This threshold eliminates potential chatter
1B
and V1B.
1A
FAULT
A
B
FILTER
AND
COMPARE
TO MULTIPLIER
V
1A
V
1B
AGND
V1A < 93.75% OF V
FAULT + SWA P
<0
6.25% OF I NACTIVE I NPUT
1B
V
1A
V
1A
V
1N
V
1B
V
1B
>0
ACTIVE PO INT – INACT IVE INPUT
Figure 29. Fault Conditions for Inactive Input Greater than Active Input
05040-026
05040-027
Calibration Concerns
Typically, when a meter is being calibrated, the voltage and current circuits are separated, as shown in
Figure 30. This
means that current passes through only the phase or neutral
Figure 30 shows current being passed through the phase
circuit. circuit. This is the preferred option because the ADE7761A starts billing on the input V CT is connected to V
1A
on power-up. The phase circuit
1A
in Figure 30. Because there is no current in the neutral circuit, the FAULT indicator comes on under these conditions. However, this does not affect the accuracy of the calibration and can be used as a means to test the functionality of the fault detection.
V
1A
C
F
V
1N
C
F
V
1B
V
2P
V
2N
TEST
CURRENT
1
RB + VR = RF.
R
IB
IB
PHASE
240V rms
CT
RB
AGND
RB
CT
NEUTRAL
1
RA
C
1
RB
1
VR
V
F
V
1A
0V
R
F
F
R
F
C
T
Figure 30. Conditions for Calibration of Channel B
If the neutral circuit is chosen for the current circuit in the arrangement shown in
Figure 30, this may have implications for
the calibration accuracy. The ADE7761A powers up with the
input active as normal. However, because there is no
V
1A
current in the phase circuit, the signal on V
is zero. This
1A
causes a fault to be flagged and the active input to be swapped
(neutral). The meter can be calibrated in this mode, but
to V
1B
the phase and neutral CTs may differ slightly. Because under no-fault conditions all billing is carried out using the phase CT, the meter should be calibrated using the phase circuit. Of course, both phase and neutral circuits can be calibrated.
MISSING NEUTRAL MODE
The ADE7761A integrates a novel fault detection that warns and allows the ADE7761A to continue to bill in case a meter is connected to only one wire (see operation of the ADE7761A in this mode, the V ADE7761A must be maintained within the specified range (5 V ± 5%). The missing neutral detection algorithm is designed to work over a line frequency of 45 Hz to 55 Hz.
Figure 31). For correct
pin of the
DD
05040-028
Rev. 0 | Page 18 of 24
ADE7761A
V
V1AV1NV
V
V
A
244V rms
POWER
GENERATOR
LOAD
1
RB + VR = RF.
RA
RB
VR
CT
CT
1
1
1
IB
RB
RB
R
1A
F
C
F
V
1A
V
1N
0V
C
F
V
R
1B
F
C
F
V
2P
V
R
2N
F
C
T
Figure 31. Missing Neutral System Diagram
The ADE7761A detects a missing neutral condition by continuously monitoring the voltage channel input (V
− V2N).
2P
The FAULT pin is held high when a missing neutral condition is detected. In this mode, the ADE7761A continues to bill the energy based on the signal level on the current channel (see Figure 32). The billing rate or frequency outputs can be adjusted by changing the dc level on the MISCAL pin.
Analog Devices, Inc. cautions users of the ADE7761A about the following:
Billing active energy in Case 1 is consistent with the
understanding of the quantity represented by pulses on CF, F1, and F2 outputs (watt-hour).
Billing active energy while the ADE7761A is in Case 2 must
be decided knowing that the entity measured by the ADE7761A in this case is ampere-hour and not watt-hour. Users should be aware of this limitation and decide if the ADE7761A is appropriate for their application.
Missing Neutral Detection
05040-029
The ADE7761A continuously monitors the voltage input and detects a missing neutral condition when the voltage input peak value is smaller than 9% of the analog full scale or when no zero crossings are detected on this input (see
2P
AGND
V2
V
2N
ADC
Figure 33).
FILTERAND
THRESHOLD
MISSING NEUTRAL
ADC
A > B
HPF
1B
MISCAL
ADC
ADC
B > A B <> A
MISSI NG NEUTRA L
GAIN ADJUSM TENT
ZERO
CROSSING
DETECTIO N
LPF
DIGITAL-TO -
FREQUENCY
CONVERTERS
F1 F2
CF
Figure 32. Energy Calculation in Missing Neutral Mode
Important Note for Billing of Active Energy
The ADE7761A provides pulse outputs—CF, F1, and F2— intended to be used for the billing of active energy. Pulses are generated at these outputs in two different situations.
Case 1: When the analog input V
conditions described in
Figure 34, CF, F1, and F2 frequencies
– V2N complies with the
2P
are proportional to active power and can be used to bill active energy.
Case 2: When the analog input V
the conditions described in
– V2N does not comply with
2P
Figure 34, the ADE7761A does not measure active energy but a quantity proportional to kAh. This quantity is used to generate pulses on the same CF, F1, and F2. This situation is indicated when the FAULT pin is high.
|V2|
< 9% OF FULL SCALE
PEAK
V
2P–V2N
9% OF FS
0V
V2P–V
FSFS
0V
NO ZERO CROS SING ON V2OR
2N
V2P– V
FS
0V
2N
05040-031
Figure 33. Missing Neutral Detection
05040-030
The ADE7761A leaves the missing neutral mode for normal operation when both conditions are no longer valid, that is, a voltage peak value of greater than 9% of full scale and zero crossing on the voltage channel is detected (see
2P
FILTERAND
THRESHOLD
GND
V2
V
2N
|V2|
PEAK
ZERO CROSSING ON V2
+9% OF FS
–9% OF FS
ADC
> 9% OF FULL SCALE
AND
V2P– V
2N
FS
Figure 34. Return to Normal Mode after Missing Neutral Detection
Figure 34).
MISSING NEUTRAL
05040-032
Rev. 0 | Page 19 of 24
ADE7761A
×
y
F
F
Missing Neutral Gain Calibration
When the ADE7761A is in missing neutral mode, the energy is bill based on the active current input signal level. The frequency outputs in this mode can be calibrated with the MISCAL analog input pin. In this mode, applying a dc voltage of 330 mV on MISCAL is equivalent to applying, in normal mode, a pure sine wave on the voltage input with a peak value of 330 mV. The MISCAL input can vary from 0 V to 660 mV (see the Inputs
section). When set to 0 V, the frequency outputs are
Analog
close to zero. When set to 660 mV dc, the frequency outputs are twice that when MISCAL is at 330 mV dc. In other words, Equation 7 can be used in missing neutral mode by replacing
by MISCAL
V2
rms
,
21
Frequenc
rms
/√2.
=
2/170.5
rmsrms
2
V
REF
(8)
××××
FMISCALVGain
41
where:
, F2 Frequency is the output frequency on F1 and F2 (Hz).
F
1
is the differential rms voltage signal on Channel 1 (V).
V1
rms
MISCAL
is the differential rms voltage signal on the MISCAL
rms
pin (V). Gain is 1 or 16, depending on the PGA gain selection made
using logic input PGA.
is the reference voltage (2.5 V ± 8%) (V).
V
REF
F
is one of four possible frequencies selected by using the
1-4
logic inputs S0 and S1 (see
Tabl e 6).
Example
In normal mode, ac voltages of ±330 mV peak are applied to V1 and V2, and then the expected output frequency on F
and F2 is
1
calculated as:
Gain =1 ; PGA =0
F
= 1.7 Hz, SCF = S1 = S0 = 0
1–4
V1 = rms of 330 mV peak ac = 0.33/√2 V
V2 = rms of 330 mV peak ac = 0.33/√2 V
V
= 2.5 V (nominal reference value)
REF
Hz7.133.033.070.5
,
21
CF Frequency = F
=FrequencyFF
F2 Frequency × 64 = 5.4 Hz
1
××
2
5.222
××
Hz084.0
=
In missing neutral mode, the ac voltage of ±330 mV peak is applied to V1, no signal is connected on V2, and a 330 mV dc input is applied to MISCAL. With the ADE7761A in the same configuration as the previous example, the expected output frequencies on CF, F
,
21
CF Frequency = F
, and F2 are
1
=FrequencyFF
, F2 Frequency × 64 = 5.4 Hz
1
2
5.22
×
Hz7.12/33.033.070.5
×××
Hz084.0
=
Rev. 0 | Page 20 of 24
ADE7761A
r
APPLICATIONS
INTERFACING TO A MICROCONTROLLER FOR ENERGY MEASUREMENT
The easiest way to interface the ADE7761A to a microcontroller is to use the CF high frequency output with the output frequency scaling set to 2048 × F1, F2. This is done by setting SCF = 0 and S0 = S1 = 1 (see analog inputs, the output frequency on CF is approximately
5.5 kHz.
Figure 35 illustrates one scheme that could be used to digitize the output frequency and carry out the necessary averaging mentioned in the
CF
AVERAGE
FREQUENCY
ADE7761A
REVP
FAU LT
1
REVP MUST BE USED IF THE ME TER IS BIDI RECTIONAL OR DIRECTION OF ENERGY FLOW IS NEEDED.
2
FAULT MUST BE USED TO RECO RD ENERGY IN F AULT CONDITION.
Figure 35. Interfacing the ADE7761A to an MCU
As shown in Figure 35 the frequency output CF is connected to an MCU counter or port, which counts the number of pulses in a given integration time, determined by an MCU internal timer. The average power, proportional to the average frequency, is
The energy consumed during an integration period is
For the purpose of calibration, this integration time could be 10 sec to 20 sec to accumulate enough pulses to ensure correct averaging of the frequency. In normal operation, the integration time could be reduced to 1 sec or 2 sec depending on, for example, the required update rate of a display. With shorter integration times on the MCU, the amount of energy in each update may still have a small amount of ripple, even under steady load conditions. However, over a minute or more, the measured energy has no ripple.
Table 8). With full-scale ac signals on the
Frequency Output CF section.
FREQUENCY
RIPPLE
TIME
MCU
COUNTER
CF
1
2
TimePowerAverageEnergy =×=×=
UP/DOWN
PowerActiveAverageFrequencyAverage ==
Counter
Time
LOGIC
Counter
Time
±10%
05040-033
CounterTime
SELECTING A FREQUENCY FOR AN ENERGY METER APPLICATION
As shown in Ta ble 6, the user can select one of four frequencies. This frequency selection determines the maximum frequency on F1 and F2. These outputs are intended to be used to drive the energy register (electromechanical or other). Because only four different output frequencies can be selected, the available frequency selection was optimized for a meter constant of 100 impulses/kWh with a maximum current of between 10 A and 120 A. maximum currents (I cases, the meter constant is 100 impulses/kWh.
Table 9. F1 and F2 Frequency at 100 Impulses/kWh
I
MAX
12.5 0.083 25 0.166 40 0.266 60 0.4 80 0.533 120 0.8
The F output frequencies on F1 and F2. When designing an energy meter, the nominal design voltage on Channel 2 (voltage) should be set to half-scale to allow for calibration of the meter constant. The current channel should also be no more than half­scale when the meter sees maximum load, which accommodates overcurrent signals and signals with high crest factors. shows the output frequency on F1 and F2 when both analog inputs are half-scale. The frequencies listed in well with those listed in
Table 10. F1 and F2 Frequency with Half-Scale AC Inputs
S0 S1 F
0 0 1.72 0.085 0 1 3.44 0.17 1 0 6.86 0.34 1 1 13.5 0.68
When selecting a suitable F frequency output at I of 100 impulses/kWh should be compared with Column 4 of Table 10 . The frequency that is closest in Table 10 determines the best choice of frequency (F a maximum current of 40 A is being designed, the output frequency on F1 and F2 with a meter constant of 100 impulses per kWh is 0.266 Hz at 40 A and 240 V (see
Tabl e 9 shows the output frequency for several
) with a line voltage of 240 V. In all
MAX
(A) F1 and F2 (Hz)
frequencies allow complete coverage of this range of
1–4
Table 1 0 align
Table 9 for maximum load.
Frequency on F1 and F2, Ch 1 and Ch 2,
(Hz)
1–4
Half-Scale AC Inputs (Hz)
frequency for a meter design, the
1–4
(maximum load) with a meter constant
MAX
). For example, if a meter with
1-4
Table 9).
Table 10
Rev. 0 | Page 21 of 24
ADE7761A
Looking at Table 10, the closest frequency to 0.266 Hz in Column 4 is 0.17 Hz. Therefore, F2 (3.4 Hz; see
Table 6) is
selected for this design.
Frequency Outputs
Figure 2 is a timing diagram for the various frequency outputs. The high frequency CF output is intended for communication and calibration purposes. CF produces a 90 ms wide, active high pulse (t power. The CF output frequencies are given in F1 and F2, if the period of CF (t
) at a frequency that is proportional to active
4
Table 8. As with
) falls below 180 ms, the CF
5
pulse width is set to half the period. For example, if the CF frequency is 20 Hz, the CF pulse width is 25 ms.
No-Load Threshold
The ADE7761A includes a no-load threshold and start-up current feature that eliminates creep effects in the meter. The ADE7761A is designed to issue a minimum output frequency. Any load generating a frequency lower than this minimum frequency does not cause a pulse to be issued on F1, F2, or CF. The minimum output frequency is given as 0.0045% of the full­scale output frequency. (See
Table 8 for maximum output
frequencies for ac signals).
For example, an energy meter with a meter constant of 100 impulses per kWh on F1, F2 using SCF = 1, S1 = 0, and S0 = 1, the maximum output frequency at F1 or F2 is 0.68 Hz and 43.52 Hz on CF. The minimum output frequency at F1 or F2 is 0.0045% of 0.68 Hz or 3.06 × 10
–3
10
Hz at CF (64 × F1 Hz).
–5
Hz. This is 1.96 ×
In this example, the no-load threshold is equivalent to 1.1 W of load or a startup current of 4.6 mA at 240 V. Compare this value to the IEC 32053-21 specification, which states that the meter must start up with a load equal to or less than 0.4% of I 5 A (I
B) meter, 0.4% of I
B
is equivalent to 20 mA. B
B
. For a
B
B
Note that the no-load threshold is not enabled when using the high CF frequency mode: SCF = 0, S1 = S0 = 1.
NEGATIVE POWER INFORMATION
The ADE7761A detects when the current and voltage channels have a phase shift greater than 90 a wrong connection of the meter or the generation of negative power. The REVP pin output goes active high when negative power is detected and active low when positive power is detected. The REVP pin output changes state as a pulse is issued on CF.
°. This mechanism can detect
Rev. 0 | Page 22 of 24
ADE7761A
OUTLINE DIMENSIONS
7.50
7.20
6.90
0.38
0.22
11
5.60
5.30
8.20
5.00
7.80
1.85
1.75
1.65
SEATING PLANE
7.40
0.25
0.09
8° 4° 0°
0.95
0.75
0.55
060106-A
10
2.00 MAX
0.05 MIN
COPLANARITY
0.10
20
1
0.65 BSC
COMPLIANT TO JEDEC STANDARDS MO-150-AE
Figure 36. 20-Lead Shrink Small Outline Package [SSOP]
(RS-20)
Dimensions shown in millimeters
ORDERING GUIDE
Model Temperature Range Package Description Package Option
ADE7761AARS –40°C to +85°C 20-Lead Shrink Small Outline Package (SSOP) RS-20 ADE7761AARS-RL –40°C to +85°C 20-Lead Shrink Small Outline Package (SSOP) RS-20 ADE7761AARSZ ADE7761AARSZ-RL ADE7761AARS-REF Reference Board
1
Z = Pb-free part.
1
1
–40°C to +85°C 20-Lead Shrink Small Outline Package (SSOP) RS-20 –40°C to +85°C 20-Lead Shrink Small Outline Package (SSOP) RS-20
Rev. 0 | Page 23 of 24
ADE7761A
NOTES
©2006 Analog Devices, Inc. All rights reserved. Trademarks and registered trademarks are the property of their respective owners. D05040-0-7/06(0)
Rev. 0 | Page 24 of 24
Loading...