Datasheet ADE7752 Datasheet (Analog Devices)

Polyphase Energy Metering IC

FEATURES

High accuracy, supports 50 Hz/60 Hz IEC 687/61036 Less than 0.1% error over a dynamic range of 500 to 1 Compatible with 3-phase/3-wire delta and 3-phase/4-wire Wye
configurations
The ADE7752* supplies average real power on the frequency
outputs F1 and F2
High frequency output CF is intended for calibration and
supplies instantaneous real power
Logic output NEGP indicates a potential miswiring or negative
power for each phase
Direct drive for electromechanical counters and 2-phase stepper
motors (F1 and F2)
Proprietary ADCs and DSP provide high accuracy over large
variations in environmental conditions and time On-chip power supply monitoring On-chip creep protection (no load threshold) On-chip reference 2.4 V ±8% (20 ppm/°C typical) with external
overdrive capability Single 5 V supply, low power (60 mW typical) Low cost CMOS process
*Patent pending.
with Pulse Output
ADE7752

GENERAL DESCRIPTION

The ADE7752 is a high accuracy polyphase electrical energy measurement IC. The part specifications surpass the accuracy requirements as quoted in the IEC61036 standard. The only analog circuitry used in the ADE7752 is in the ADCs and reference circuit. All other signal processing (e.g., multiplication, filtering, and sum­mation) is carried out in the digital domain. This approach provides superior stability and accuracy over extremes in environ­mental conditions and over time.
The ADE7752 supplies average real power information on the low frequency outputs, F1 and F2. These logic outputs may be used to directly drive an electromechanical counter or to interface with an MCU. The CF logic output gives instantaneous real power informa­tion. This output is intended to be used for calibration purposes.
The ADE7752 includes a power supply monitoring circuit on the V
pin. The ADE7752 will remain inactive until the supply voltage
DD
on V
reaches 4 V. If the supply falls below 4 V, the ADE7752 will
DD
also be reset and no pulses will be issued on F1, F2, and CF.
Internal phase matching circuitry ensures that the voltage and current channels are phase matched. An internal no load threshold ensures the part does not exhibit any creep when there is no load.

FUNCTIONAL BLOCK DIAGRAM

5
IAP
IAN
6
16
VA P
IBP
7
8
IBN
15
VBP
9
ICP
10
ICN
VCP
14
13
VN
2.4V REF
11 12 4 18 21 22 23 24 1
AGND
Rev. B
Information furnished by Analog Devices is believed to be accurate and reliable. However, no responsibility is assumed by Analog Devices for its use, nor for any infringements of patents or other rights of third parties that may result from its use. Specifications subject to change without notice. No license is granted by implication or otherwise under any patent or patent rights of Analog Devices. Trademarks and registered trademarks are the property of their respective owners.
ADC
ADC
ADC
ADC
ADC
ADC
4k
REF
IN/OUT
HPF
Φ
PHASE
CORRECTION
HPF
Φ
PHASE
CORRECTION
HPF
Φ
PHASE
CORRECTION
Figure 1. Functional Block Diagram
The ADE7752 is available in a 24-lead SOIC package.
ADE7752
Σ
V
DD
3
POWER SUPPLY
MONITOR
2
DGND
19
CLKIN
CLKOUT
20
CFS1 F1F2S0SCFNEGP
02676-A-001
ABS
17
LPF
LPF
LPF
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A.
X
X
X
DIGITAL-TO-FREQUENCY CONVER TER
Tel: 781.329.4700 www.analog.com Fax: 781.326.8703 © 2003 Analog Devices, Inc. All rights reserved.
ADE7752
TABLE OF CONTENTS
Specifications..................................................................................... 3
Meter Connections..................................................................... 15
Timing Characteristics..................................................................... 4
Absolute Maximum Ratings............................................................ 5
Terminology ...................................................................................... 6
Pin Configuration and Function Descriptions............................. 7
Typical Performance Characteristics ............................................. 9
Test Circuit ......................................................................................11
Theory of Operation...................................................................... 12
Power Factor Considerations.................................................... 12
Nonsinusoidal Voltage and Current......................................... 13
Analog Inputs.................................................................................. 14
Current Channels....................................................................... 14
Voltage Channels........................................................................ 14
Typical Connection Diagrams ...................................................... 15
Current Channel Connection................................................... 15
Voltage Channels Connection .................................................. 15
Power Supply Monitor ................................................................... 17
HPF and Offset Effects .............................................................. 17
Digital-to-Frequency Conversion................................................ 18
Mode Selection of the Sum of the Three Active Energies .... 19
Power Measurement Considerations....................................... 19
Transfer Function........................................................................... 20
Frequency Outputs F1 and F2.................................................. 20
Frequency Output CF................................................................ 21
Selecting a Frequency for an Energy Meter Application........... 22
Frequency Outputs..................................................................... 22
No Load Threshold .................................................................... 23
Negative Power Information..................................................... 23
Outline Dimensions....................................................................... 24
Ordering Guide .......................................................................... 24
REVISION HISTORY
Location Page
9/03—Data Sheet Changed from Rev. A to Rev. B
Updated Format................................................................................................................................................................................................... Universal
Change to Figure 19 .........................................................................................................................................................................................................15
5/03—Data Sheet Changed from Rev. 0 to Rev. A
to F
Changed F
Change to Figure 6 ...........................................................................................................................................................................................................10
Changes to Frequency Outputs F1 and F2 section ......................................................................................................................................................13
Replaced Table II ..............................................................................................................................................................................................................13
Changes to Examples 1, 2, and 3.....................................................................................................................................................................................14
Replaced Table III.............................................................................................................................................................................................................14
Replaced Tables IV, V, and VI ..........................................................................................................................................................................................15
Changes to SELECTING A FREQUENCY FOR AN ENERGY METER APPLICATION section.......................................................................15
Changes to NO LOAD THRESHOLD section .............................................................................................................................................................16
Replaced Table VII............................................................................................................................................................................................................16
1–5
............................................................................................................................................................................................. Universal
1–7
Rev. B | Page 2 of 24
ADE7752

SPECIFICATIONS

Table 1. VDD = 5 V± 5%, AGND = DGND = 0 V, On-Chip Reference, CLKIN = 10 MHz, T
Parameter Conditions Min Typ Max Unit
ACCURACY
Measurement Error on Current
Channel
Phase Error between Channels
1, 2
PF = 0.8 Capacitive PF = 0.5 Capacitive
Voltage Channel with Full-Scale Signal (±500 mV), 25°C, Over a Dynamic Range of 500 to 1 0.1 % Reading
AC Power Supply Rejection SCF = 0; S0 = S1 = 1
Output Frequency Variation (CF)
IA = IB = IC = 100 mV rms, VA = VB = VC = 100 mV rms, @ 50 Hz, Ripple on VDD of 200 mV rms @ 100 Hz
DC Power Supply Rejection S1 = 1; S0 = SCF = 0
Output Frequency Variation (CF)
V1 = 100 mV rms, V2 = 100 mV rms, V
= 5 V ±250 mV 0.1
DD
ANALOG INPUTS See Analog Inputs Section
Maximum Signal Levels VAP–VN, VBP–VN, VCP–VN, IAP–IAN, IBP–IBN, ICP–ICN ±0.5 V peak Diff.
Input Impedance (DC) CLKIN = 10 MHz 370 410 kΩ
Bandwidth (–3 dB) CLKIN/256, CLKIN = 10 MHz 14 kHz
ADC Offset Error
1, 2
Gain Error External 2.5 V Reference, IA = IB = IC = 500 mV dc ±9
REFERENCE INPUT
REF
Input Voltage Range 2.4 V + 8%
IN/OUT
Input Impedance
Input Capacitance
2.4 V – 8% 2.2
ON-CHIP REFERENCE Nominal 2.4 V
Reference Error
Temperature Coefficient CLKIN All Specifications for CLKIN of 10 MHz
Input Clock Frequency LOGIC INPUTS3
ACF, S0, S1, and ABS
Input High Voltage, V Input Low Voltage, V
V
INH
V
INL
= 5 V ±5% 2.4
DD
= 5 V ±5%
DD
Input Current, IIN Typically 10 nA, VIN = 0 V to VDD Input Capacitance, CIN
LOGIC OUTPUTS3
F1 and F2
Output High Voltage, VOH I Output Low Voltage, VOL I
CF and NEGP
Output High Voltage, VOH V Output Low Voltage, VOL V
= 10 mA, V
SOURCE
= 10 mA, VDD = 5 V
SINK
= 5 V 4.5
DD
= 5 V, I
DD
= 5 V, I
DD
= 5 mA 4
SOURCE
= 5 mA
SINK
POWER SUPPLY For Specified Performance
VDD 5 V ±5% 4.75
IDD
1
See section for explanation of specifications. Terminology
2
See plots in Typi . cal Performance Characteristics
3
Sample tested during initial release and after any redesign or process change that may affect this parameter.
MIN
to T
= –40°C to+ 85°C
MAX
±0.1 °(Degrees) ±0.1 °(Degrees)
0.01 % Reading
3.3
±25 mV
2.6 V
10 pF
% Reading
% Ideal
V kΩ
±200 mV
25 ppm/°C
10 MHz
0.8 V ±3 µA
V
10 pF
0.5 V
0.5 V
V
V
5.25 V
12 16 mA
Rev. B | Page 3 of 24
ADE7752

TIMING CHARACTERISTICS

Table 2. VDD = 5 V ± 5%, AGND = DGND = 0 V, On-Chip Reference, CLKIN = 10 MHz, T
MIN
to T
= –40°C to +85°C
MAX
Parameter Conditions Unit
3
t
275 F1 and F2 Pulse Width (Logic High) ms
1
t2 See Table 6 Output Pulse Period. See Transfer Function section. sec t3 1/2 t2 Time between F1 Falling Edge and F2 Falling Edge sec
3, 4
t
96 CF Pulse Width (Logic High) ms
4
5
t
See Table 7 CF Pulse Period. See Transfer Function section. sec
5
t6 CLKIN/4 Minimum Time between F1 and F2 Pulse sec
1
Sample tested during initial release and after any redesign or process change that may affect this parameter.
2
See . Figure 2
3
The pulse widths of F1, F2, and CF are not fixed for higher output frequencies. See Fre section. quency Outputs
4
CF is not synchronous to F1 or F2 frequency outputs.
5
The CF pulse is always 1 µs in the high frequency mode. See section.
Frequency Outputs
t
1
F1
t
6
t
2
t
F2
3
1, 2
t
4
CF
t
5
02676-A-003
Figure 2. Timing Diagram for Frequency Outputs
Rev. B | Page 4 of 24
ADE7752

ABSOLUTE MAXIMUM RATINGS

Table 3. TA = 25°C, unless otherwise noted
Parameter Rating
VDD to AGND –0.3 V to +7 V VDD to DGND –0.3 V to +7 V Analog Input Voltage to AGND
VAP, VBP, VCP, VN, IAP, IAN, IBP, IBN,
ICP, and ICN –6 V to +6 V Reference Input Voltage to AGND –0.3 V to VDD + 0.3 V Digital Input Voltage to DGND –0.3 V to VDD + 0.3 V Digital Output Voltage to DGND –0.3 V to VDD + 0.3 V Operating Temperature Range
Industrial –40°C to +85°C Storage Temperature Range –65°C to +150°C Junction Temperature 150°C 24-Lead SOIC, Power Dissipation 88 mW θJA Thermal Impedance 250°C/W Lead Temperature, Soldering
Vapor Phase (60 sec) 215°C
Infrared (15 sec) 220°C
Stresses above those listed under Absolute Maximum Ratings may cause permanent damage to the device. This is a stress rating only; functional operation of the device at these or any other conditions above those listed in the operational sections of this specification is not implied. Exposure to absolute maximum rating conditions for extended periods may affect device reliability.
ESD CAUTION
ESD (electrostatic discharge) sensitive device. Electrostatic charges as high as 4000 V readily accumulate on the human body and test equipment and can discharge without detection. Although this product features proprietary ESD protection circuitry, permanent damage may occur on devices subjected to high energy electrostatic discharges. Therefore, proper ESD precautions are recommended to avoid performance degradation or loss of functionality.
Rev. B | Page 5 of 24
ADE7752

TERMINOLOGY

Measurement Error
The error associated with the energy measurement made by the ADE7752 is defined by the following formula:
=
ErrorPercentage 100
 
7752
EnergyTrue
Error between Channels
The HPF (high-pass filter) in the current channel has a phase lead response. To offset this phase response and equalize the phase response between channels, a phase correction network is also placed in the current channel. The phase correction net­work ensures a phase match between the current channels and voltage channels to within ±0.1° over a range of 45 Hz to 65 Hz and ±0.2° over a range of 40 Hz to 1 kHz. See Figure 25 and Figure 26.
Power Supply Rejection
This quantifies the ADE7752 measurement error as a percentage of reading when the power supplies are varied.
For the ac PSR measurement, a reading at a nominal supply (5 V) is taken. A 200 mV rms/100 Hz signal is then introduced onto the supply and a second reading is obtained under the
EnergyTrueADE by Registered Energy
%
×
 
same input signal levels. Any error introduced is expressed as a percentage of reading. See definition for Measurement Error.
For the dc PSR measurement, a reading at nominal supplies (5 V) is taken. The supply is then varied ±5% and a second reading is obtained with the same input signal levels. Any error introduced is again expressed as a percentage of reading.
ADC Offset Error
This refers to the dc offset associated with the analog inputs to the ADCs. It means that with the analog inputs connected to AGND, the ADCs still see an analog input signal offset. However, as the HPF is always present, the offset is removed from the current channel and the power calculation is not affected by this offset.
Gain Error
The gain error of the ADE7752 is defined as the difference between the measured output frequency (minus the offset) and the ideal output frequency. The difference is expressed as a percentage of the ideal frequency. The ideal frequency is obtained from the ADE7752 transfer function. See the Transfer Function section.
Rev. B | Page 6 of 24
ADE7752

PIN CONFIGURATION AND FUNCTION DESCRIPTIONS

Table 4. Pin Function Descriptions
Pin No. Mnemonic Description
1 CF
Calibration Frequency Logic Output. The CF logic output gives instantaneous real power information. This output is intended to be used for calibration purposes. See the SCF pin description.
2 DGND
This provides the ground reference for the digital circuitry in the ADE7752, i.e., multiplier, filters, and digital-to­frequency converter. Because the digital return currents in the ADE7752 are small, it is acceptable to connect this pin to the analog ground plane of the whole system.
3 VDD
Power Supply. This pin provides the supply voltage for the digital circuitry in the ADE7752. The supply voltage should be maintained at 5 V ± 5% for specified operation. This pin should be decoupled to DGND with a 10 µF capacitor in parallel with a 100 nF ceramic capacitor.
4 NEGP
This logic output will go logic high when negative power is detected on any of the three phase inputs, i.e., when the phase angle between the voltage and the current signals is greater than 90°. This output is not latched and will be reset when positive power is once again detected. See the section.
5, 6; 7, 8; 9, 10
IAP, IAN; IBP, IBN; ICP, ICN
Analog Inputs for Current Channel. This channel is intended for use with the current transducer and is referenced in this document as the current channel. These inputs are fully differential voltage inputs with maximum differential input signal levels of ±0.5 V. See the Analog Inputs section. Both inputs have internal ESD protection circuitry; in addition, an overvoltage of ±6 V can be sustained on these inputs without risk of permanent damage.
11 AGND
This pin provides the ground reference for the analog circuitry in the ADE7752, i.e., ADCs, temperature sensor, and reference. This pin should be tied to the analog ground plane or the quietest ground reference in the system. This quiet ground reference should be used for all analog circuitry, e.g., antialiasing filters, current and voltage transducers, and so on. To keep ground noise around the ADE7752 to a minimum, the quiet ground plane should only connect to the digital ground plane at one point. It is acceptable to place the entire device on the analog ground plane.
12 REF
IN/OUT
This pin provides access to the on-chip voltage reference. The on-chip reference has a nominal value of 2.4 V ± 8% and a typical temperature coefficient of 20 ppm/°C. An external reference source may also be connected at this pin. In either case, this pin should be decoupled to AGND with a 1 µF ceramic capacitor.
13–16
VN, VCP, VBP, VAP
Analog Inputs for the Voltage Channel. This channel is intended for use with the voltage transducer and is referenced in this document as the voltage channel. These inputs are single-ended voltage inputs with a maximum signal level of ±0.5 V with respect to VN for specified operation. All inputs have internal ESD protection circuitry; in addition, an overvoltage of ± 6 V can be sustained on these inputs without risk of permanent damage.
17
This logic input is used to select the way the three active energies from the three phases are summed. This
ABS
offers the designer the capability to do the arithmetical sum of the three energies (ABS the absolute values (ABS
18 SCF
Select Calibration Frequency. This logic input is used to select the frequency on the calibration output CF. Table 7 shows how the calibration frequencies are selected.
19 CLKIN
Master Clock for ADCs and Digital Signal Processing. An external clock can be provided at this logic input. Alternatively, a parallel resonant AT crystal can be connected across CLKIN and CLKOUT to provide a clock source for the ADE7752. The clock frequency for specified operation is 10 MHz. Ceramic load capacitors of between 22 pF and 33 pF should be used with the gate oscillator circuit. Refer to the crystal manufacturer’s data sheet for load capacitance requirements.
23
22
21
20
19
18
17
16
15
14
13
F1
F2
S1
S0
CLKOUT
CLKIN
SCF
ABS
VAP
VBP
VCP
VN
02676-A-003
REF
124
CF
2
DGND
V
3
DD
4
NEGP
5
IAP
ADE7752
6
IAN
TOP VIEW
(Not to Scale)
7
IBP
8
IBN
9
ICP
10
ICN
11
AGND
12
IN/OUT
Figure 3. Pin Configuration
Negative Power Information
logic high) or the sum of
logic low). See the section.
Mode Selection of the Sum of the Three Active Energies
Rev. B | Page 7 of 24
ADE7752
Pin No. Mnemonic Description
20 CLKOUT
21, 22 S0, S1
24, 23 F1, F2
A crystal can be connected across this pin and CLKIN as described previously to provide a clock source for the ADE7752. The CLKOUT pin can drive one CMOS load when an external clock is supplied at CLKIN or when a crystal is being used.
These logic inputs are used to select one of four possible frequencies for the digital-to-frequency conversion. This offers the designer greater flexibility when designing the energy meter. See the an Energy Meter Application
Low Frequency Logic Outputs. F1 and F2 supply average real power information. The logic outputs can be used to drive electromechanical counters and 2-phase stepper motors directly. See the Transfer Function section.
Selecting a Frequency for
section.
Rev. B | Page 8 of 24
ADE7752

TYPICAL PERFORMANCE CHARACTERISTICS

1
0.5
WYE CONNECTION ON-CHIP REFERENCE
0.4
0.3
0.2
0.1
PHASE B
0
–0.1
–0.2
ERROR (% of Reading)
–0.3
–0.4
–0.5
0.1 1
PHASE C
A
ASE
P
H
CURRENT CHANNEL (% of Full Scale)
PHASE A + B + C
Figure 4. Error as a Percent of Reading
with Internal Reference (Wye Connection)
1.0
WYE CONNECTION ON-CHIP REFERENCE
0.8
0.6
0.4
0.2
0
–0.2
–0.4
ERROR (% of Reading)
–0.6
–0.8
–1.0
0.1 1
+85°C PF = +0.5
5
2
+
°
C
P
F = +
4
0
°
C
P
+
F
=
CURRENT CHANNEL (% of Full Scale)
1
0
.5
+25°C PF = –0.5
Figure 5. Error as a Percent of Reading over Power Factor
with Internal Reference (Wye Connection)
0.5
WYE CONNECTION EXTERNAL REFERENCE
0.4
0.3
0.2
0.1
0
–0.1
–0.2
ERROR (% of Reading)
–0.3
–0.4
–0.5
0.1 1
+85°C PF = +0.5
+25°C
P
F = +
1
4
0
°
C
P
0
.5
+
F
=
+25°C PF = –0.5
CURRENT CHANNEL (% of Full Scale)
Figure 6. Error as a Percent of Reading over Power Factor
with External Reference (Wye Connection)
02676-A-004
10010
02676-A-005
10010
02676-A-006
10010
1.0
WYE CONNECTION ON-CHIP REFERENCE
0.8
0.6
0.4
0.2
0
–0.2
–0.4
ERROR (% of Reading)
–0.6
–0.8
–1.0
0.1 1
+85°C PF = 1
F
=
+25°C PF = 1
1
4
0
°
C
P
CURRENT CHANNEL (% of Full Scale)
Figure 7. Error as a Percent of Reading over Temperature
with Internal Reference (Wye Connection)
0.5
0.4
0.3
0.2
0.1
0
–0.1
–0.2
ERROR (% of Reading)
–0.3
–0.4
–0.5
0.1 1
DELTA CONNECTION ON-CHIP REFERENCE
PF = –0.5
PF = +1
0
P
.5
+
F
=
CURRENT CHANNEL (% of Full Scale)
Figure 8. Error as a Percent of Reading over Power Factor
with Internal Reference (Delta Connection)
0.5
WYE CONNECTION EXTERNAL REFERENCE
0.4
0.3
0.2
0.1
0
–0.1
–0.2
ERROR (% of Reading)
–0.3
–0.4
–0.5
0.1 1
+85°C PF = 1
5
2
+
°
C
P
F = 1
4
0
°
C
P
1
F
=
CURRENT CHANNEL (% of Full Scale)
Figure 9. Error as a Percent of Reading over Temperature
with External Reference (Wye Connection)
02676-A-007
10010
02676-A-008
10010
02676-A-009
10010
Rev. B | Page 9 of 24
ADE7752
0.5
0.4
0.3
0.2
0.1
0
–0.1
–0.2
ERROR (% of Reading)
–0.3
–0.4
–0.5
45
Figure 10. Error as a Percent of Reading over Frequency
0.5
WYE CONNECTION EXTERNAL REFERENCE
0.4
0.3
0.2
0.1
0
–0.1
–0.2
ERROR (% of Reading)
–0.3
–0.4
–0.5
0.1 1
Figure 11. Error as a Percent of Reading over Power Supply
WYE CONNECTION ON-CHIP REFERENCE
PF = 1
F = 0
P
.5
FREQUENCY (Hz)
with an Internal Reference (Wye Connection)
4.75V
5
V
5
V
5
.2
CURRENT CHANNEL (% of Full Scale)
with External Reference (Wye Connection)
N: 88
18
MEAN: 4.48045 SD: 3.23101 MIN: –2.47468 MAX: 12.9385 RANGE: 15.4132
15
12
9
6
3
60 655550
02676-A-010
0
–20 –10–15
CH_I PhA OFFSET (mV)
02676-A-012
2015105–5 0
Figure 12. Channel 1 Offset Distribution
0.5
WYE CONNECTION ON-CHIP REFERENCE
0.4
0.3
0.2
0.1
–0.1
–0.2
ERROR (% of Reading)
–0.3
–0.4
02676-A-011
10010
–0.5
4.75V
0
5
V
5
.2
0.1 1
CURRENT CHANNEL (% of Full Scale)
V
5
02676-A-013
10010
Figure 13. Error as a Percent of Reading over Power Supply
with Internal Reference (Wye Connection)
Rev. B | Page 10 of 24
ADE7752

TEST CIRCUIT

V
DD
1k
33nF
1k
33nF
100nF
V
DD
5
IAP
ADE7752
6
IAN
IBP
7
8
IBN
ICP
9
10
ICN
16
VAP
15
VBP
VCP
14
VN AGND DGND
13 11
1k
33nF
3
17
ABS
CLKOUT
CLKIN
REF
IN/OUT
NEGP
F1
F2
CF
S0
S1
SCF
2
24
23
825
1
20
10MHz
19
21
22
18
12
100nF 10µF
4
NOT CONNECTED
22pF
22pF
1k
PS2501-1
V
DD
K7
TO FREQ. COUNTER
K8
02676-A-014
220V
1M
1k
LOAD
I
33nF
10µF
RB
SAME AS IAP, IAN
SAME AS IAP, IAN
SAME AS VAP
SAME AS VAP
Figure 14. Test Circuit for Performance Curves
Rev. B | Page 11 of 24
ADE7752

THEORY OF OPERATION

The six voltage signals from the current and voltage transducers are digitized with ADCs. These ADCs are 16-bit second order ∑-∆ with an oversampling rate of 833 kHz. This analog input structure greatly simplifies transducer interface by providing a wide dynamic range for direct connection to the transducer and also simplifying the antialiasing filter design. A high-pass filter in the current channel removes the dc component from the current signal. This eliminates any inaccuracies in the real power calculation due to offsets in the voltage or current signals—see HPF and Offset Effects section.
The real power calculation is derived from the instantaneous power signal. The instantaneous power signal is generated by a direct multiplication of the current and voltage signals of each phase. In order to extract the real power component (i.e., the dc component), the instantaneous power signal is low-pass filtered on each phase. Figure 15 illustrates the instantaneous real power signal and shows how the real power information can be extracted by low-pass filtering the instantaneous power signal. This method is used to extract the real power information on each phase of the polyphase system. The total real power information is then obtained by adding the individual phase real power. This scheme correctly calculates real power for nonsinusoidal current and voltage waveforms at all power factors. All signal processing is carried out in the digital domain for superior stability over temperature and time.
The low frequency output of the ADE7752 is generated by accumulating the total real power information. This low frequency inherently means a long accumulation time between output pulses. The output frequency is therefore proportional to the average real power. This average real power information can, in turn, be accumulated (e.g., by a counter) to generate real energy information. Because of its high output frequency and therefore shorter integration time, the CF output is proportional to the instantaneous real power. This pulse is useful for system calibration purposes that would take place under steady load conditions.

POWER FACTOR CONSIDERATIONS

The method used to extract the real power information from the individual instantaneous power signal (i.e., by low-pass filtering) is still valid when the voltage and current signals of each phase are not in phase. Figure 16 displays the unity power factor condition and a DPF (displacement power factor) = 0.5, i.e., current signal lagging the voltage by 60°, for one phase of the polyphase. If we assume the voltage and current waveforms are sinusoidal, the real power componen of the instantaneous power signal (i.e., the dc term) is given by:
×
1V
 
2
 
()
°×
60cos
p(t) = i(t) × v(t)
V × I
V × I
IAP IAN
VA P
IBP IBN
VBP
ICP ICN
VCP
VN
2
TIME
WHERE:
v(t) = V × cos (ωt) i(t) = I × cos (ωt) p(t) =
V × I
{1+ cos (2ωt)}
2
INSTANTANEOUS
POWER SIGNAL - p(t)
HPF
ADC
MULTIPLIER
ADC
HPF
ADC
MULTIPLIER
ADC
HPF
ADC
MULTIPLIER
ADC
V × I
2
LPF
LPF
LPF
INSTANTANEOUS
REAL POWER SIGNAL
ABS
|X|
|X|
|X|
Σ
VA × IA + VB × IB +
VC×IC
2
INSTANTANEOUS
TOTAL
POWER SIGNAL
DIGITAL-TO-
FREQUENCY
Σ
DIGITAL-TO-
FREQUENCY
Σ
CF
F1 F2
02676-A-015
Figure 15. Signal Processing Block Diagram
Rev. B | Page 12 of 24
ADE7752
φ×=
This is the correct real power calculation.
INSTANTANEOUS POWER SIGNAL
INSTANTANEOUS REAL POWER SIGNAL
()
O
n
=
0
n
(
tnIVIti βω××+=
sin2
)
(2)
n
V× I
2
0V
CURRENT
VO LTA G E
V× I
INSTANTANEOUS POWER SIGNAL
× cos(60°)
2
0V
VO LTA G E
Figure 16. DC Component of Instantaneous Power Signal
Conveys Real Power Information PF < 1
INSTANTANEOUS REAL POWER SIGNAL
60°
CURRENT

NONSINUSOIDAL VOLTAGE AND CURRENT

The real power calculation method also holds true for nonsin­usoidal current and voltage waveforms. All voltage and current waveforms in practical applications will have some harmonic content. Using the Fourier Transform, instantaneous voltage and current waveforms can be expressed in terms of their harmonic content:
()
n
=
0
where:
v(t) is the instantaneous voltage V
is the average value
O
Vn is the rms value of voltage harmonic n
and
α
is the phase angle of the voltage harmonic
n
sin2
no
(
tnVVtv α+ω××+=
)
(1)
n
where:
i(t) is the instantaneous current I
is the dc component
O
I
is the rms value of current harmonic n
n
β
is the phase angle of the current harmonic
n
Using Equations 1 and 2, the real power, P, can be expressed in terms of its fundamental real power (P power (P
).
H
P = P
) and harmonic real
1
+ PH
1
where:
cos
IVP
1111
(3)
111
cos
IVP
φ×=
n
nn
nn
(4)
n
βα=φ
=
1
βα=φ
02676-A-016
H
n
As can be seen from Equation 4, a harmonic real power compo­nent is generated for every harmonic, provided that harmonic is present in both the voltage and current waveforms. The power factor calculation has been shown to be accurate in the case of a pure sinusoid. Therefore, the harmonic real power must also correctly account for power factor since it is made up of a series of pure sinusoids.
Note that the input bandwidth of the analog inputs is 14 kHz with a master clock frequency of 10 MHz.
Rev. B | Page 13 of 24
ADE7752

ANALOG INPUTS

CURRENT CHANNELS

The voltage outputs from the current transducers are connected to the ADE7752 current channels, which are fully differential voltage inputs. IAP, IBP, and ICP are the positive inputs for IAN, IBN, and ICN, respectively.

VOLTAGE CHANNELS

The output of the line voltage transducer is connected to the ADE7752 at this analog input. Voltage channels are a pseudo­differential voltage input. VAP, VBP, and VCP are the positive inputs with respect to VN.
The maximum peak differential signal on the current channel should be less than ±500 mV (353 mV rms for a pure sinusoidal signal) for the specified operation.
IAP–IAN
+500mV
V
CM
–500mV
DIFFERENTIAL INPUT
±500mV MAX PEAK
COMMON-MODE
±25mV MAX
AGND
Figure 17. Maximum Signal Levels, Current Channel
IAP
IA
IAN
V
CM
02676-A-017
Figure 17 illustrates the maximum signal levels on IAP and IAN. The maximum differential voltage between IAP and IAN is ±500 mV. The differential voltage signal on the inputs must be referenced to a common mo de, e.g., AGND. The maximum common-mode signal shown in Figure 17 is ±25 mV.
The maximum peak differential signal on the voltage channel is ±500 mV (353 mV rms for a pure sinusoidal signal) for specified operation.
Figure 18
illustrates the maximum signal levels that can be
connected to the ADE7752’s voltage channels.
VA P– V N
+500mV
V
CM
–500mV
DIFFERENTIAL INPUT
±500mV MAX PEAK
COMMON-MODE
±25mV MAX
AGND
Figure 18. Maximum Signal Levels, Voltage Channel
VA
VCM
VA P
VN
02676-A-018
Voltage channels must be driven from a common-mode voltage, i.e., the differential voltage signal on the input must be referenced to a common mode (usually AGND). The analog inputs of the ADE7752 can be driven with common-mode voltages of up to 25 mV with respect to AGND. However, best results are achieved using a common mode equal to AGND.
Rev. B | Page 14 of 24
ADE7752
(
)
(
(
(
)
φ+ω
φ××
=

TYPICAL CONNECTION DIAGRAMS

CURRENT CHANNEL CONNECTION

Figure 19 channel (IA). A CT (current transformer) is the current trans­ducer selected for this example. Notice the common-mode voltage for the current channel is AGND and is derived by center tapping the burden resistor to AGND. This provides the complementary analog input signals for IAP and IAN. The CT turns ratio and burden resistor Rb are selected to give a peak differential voltage of ±500 mV at maximum load.
IP
shows a typical connection diagram for the current
CT
NEUTRALPHASE
Figure 19. Typical Connection for Current Channels
Rf
R
±500mV
b
Rf
IAP
Cf
IAN
Cf

VOLTAGE CHANNELS CONNECTION

Figure 20 The first option uses a PT (potential transformer) to provide complete isolation from the main voltage. In the second option, the ADE7752 is biased around the neutral wire, and a resistor divider is used to provide a voltage signal proportional to the line voltage. Adjusting the ratio of Ra, Rb, and VR is also a convenient way of carrying out a gain calibration on the meter.
shows two typical connections for the voltage channel.
PT
±500mV
AGND
NEUTRALPHASE
Ra
NEUTRALPHASE
Figure 20. Typical Connections for Voltage Channels
Cf
*
Rb
*
±500mV
VR
*
Ra >> Rf + VR;*Rb + VR = Rf
*
Rf
Rf
Rf
VA P
Cf
VN
Cf
VA P
VN
Cf
02676-A-019
02676-A-018

METER CONNECTIONS

In 3-phase service, two main power distribution services exist: 3-phase 4-wire or 3-phase 3-wire. The additional wire in the 3-phase 4-wire arrangement is the neutral wire. The voltage lines have a phase difference of ±120° (±2π/3 radians) between each other. See Equation 5.
where V
()
()
()
, VB, and VC represent the voltage rms values of the
A
AA
BB
CC
different phases.
The current inputs are represented by Equation 6:
()
()
()
where I each phase and ϕ
, IB, and IC represent the rms value of the current of
A
cos2
AA
cos2
BB
cos2
CC
, ϕB, and ϕC represent the phase difference of
A
the current and voltage channel of each phase.
The instantaneous powers can then be calculated as follows:
P
A
P
P
Then:
)
()
()
As shown in Equation 7, in the ADE7752, the real power calcu­lation per phase is made when current and voltage inputs of one phase are connected to the same channel (A, B, or C). Then the summation of each individual real power calculation gives the total real power information, P(t) = PA(t) + PB(t) + PC(t).
tVtV
cos2
ω××=
()
l
2
cos2
 
cos2
 
l
 
l
 
l
π
tVtV
+ω××=
l
3
4
π
tVtV
+ω××=
l
3
tItI
φ+ω×=
A
2
π
tItI
+ω×=
3
4
π
tItI
+ω×=
3
(t) = VA(t) × IA(t) (t) = VB(t) × IB(t)
B
(t) = VC(t) × IC(t)
C
)
()
()
××
AAAAAA
BBBBBB
CCCCCC
(5)
 
  
(6)
φ+
B
φ+
C
tIVIVtP
2coscos
A
l
π
4
tIVIVtP
+ω××φ××=
2coscos
l
+ω××φ××=
tIVIVtP
2coscos
l
φ+
B
3
π
8
φ+
C
3
(7)
Rev. B | Page 15 of 24
ADE7752
Figure 21 inputs with the power lines in a 3-phase 3-wire Delta service.
PHASE A
SOURCE
PHASE B
Note that only two current inputs and two voltage inputs of the ADE7752 are used in this case. The real power calculated by the ADE7752 does not depend on the selected channels.
shows the connections of the ADE7752’s analog
Cf
Ra*
Rb*
VR*
Ra*
Rb*
VR*
Rb*
CT
PHASE C
Cf
Ra >> Rf + VR;*Rb + VR = Rf
*
CT
Rb*
ANTIALIASING
FILTERS
Rf
ANTIALIASING
FILTERS
Figure 21. 3-Phase 3-Wire Meter Connection with ADE7752
VA P
IAP
IAN
VN
Cf
IBP
IBN
VBP
LOAD
Figure 22 shows the connections of the ADE7752’s analog inputs with the power lines in a 3-phase 4-wire Wye service.
Cf
Ra*
Rb*
CT
VAP IAP
IAN
ANTIALIASING
Rb*
FILTERS
ICP
ICN
VCP
LOAD
IBP IBN
VBP
02676-A-022
VR*
Rb*
CT
PHASE A
SOURCE
02676-A-021
PHASE B
PHASE C
Cf
Ra*
Rb*
VR*
Rf
VN
Ra >> Rf + VR;*Rb + VR = Rf
CF
*
Ra*
Rb*
VR*
CT
ANTIALIASING
Cf
Rb*
FILTERS
ANTIALIASING
FILTERS
Figure 22. 3-Phase 4-Wire Meter Connection with ADE7752
Rev. B | Page 16 of 24
ADE7752
L
V

POWER SUPPLY MONITOR

The ADE7752 contains an on-chip power supply monitor. The power supply (VDD) is continuously monitored by the ADE7752. If the supply is less than 4 V ± 5%, the outputs of the ADE7752 will be inactive. This is useful to ensure correct device startup at power-up and power-down. The power supply monitor has built-in hysteresis and filtering. This gives a high degree of immunity to false triggering due to noisy supplies.
As can be seen from F , the trigger level is nominally set
igure 23 at 4 V. The tolerance on this trigger level is about ±5%. The power supply and decoupling for the part should be such that the ripple at V
does not exceed 5 V ± 5% as specified for
DD
normal operation.
V
DD
5V
4V
0V
TIME
INTERNA
RESET
INACTIVE
ACTIVE INACTIVE
× I
OS
OS
V × I
2
Figure 24. Effect of Channel Offset on the Real Power Calculation
The HPF in the current channels have an associated phase response that is compensated for on-chip. Figure 25 and F
show the phase error between channels with the com-
26 pensation network. The ADE7752 is phase compensated up to 1 kHz as shown. This ensures correct active harmonic power calculation even at low power factors.
0.07
0.06
0.05
DC COMPONENT (INCLUDING ERRORTERM) IS EXTRACTED BYTHE LPF FOR REAL POWER CALCULATION
IOS× V
V
× I
OS
0
ω
FREQUENCY – RAD/S
2ω
02676-A-024
igure
02676-A-023
Figure 23. On-Chip Power Supply Monitor

HPF AND OFFSET EFFECTS

Figure 24 shows the effect of offsets on the real power calcula­tion. As can be seen, an offset on the current channel and voltage channel contribute a dc component after multiplication. Since this dc component is extracted by the LPF and is used to generate the real power information for each phase, the offsets will have contributed a constant error to the total real power calculation. This problem is easily avoided by the HPF in the current channels. By removing the offset from at least one channel, no error component can be generated at dc by the multiplication. Error terms at cos(ωt) are removed by the LPF and the digital-to-frequency conversion. See the Digital-to­Frequency Conversion section.
()
{}
IV
×
2
IV
×
+
2
()
2cos
t
ω×
()
{}
coscos
ItIVtV
=+ω×+ω
OSOS
() ()
coscos
tVItIVIV
OSOSOSOS
ω×+ω×+×+
0.04
0.03
0.02
PHASE (Degrees)
0.01
0
–0.01
100 300 500 700 900
0 1000200 400 600 800
FREQUENCY (Hz)
02676-A-025
Figure 25. Phase Error between Channels (0 Hz to 1 kHz)
0.010
0.008
0.006
0.004
0.002
PHASE (Degrees)
0
–0.002
–0.004
40 7045 50
55 60 65
FREQUENCY (Hz)
02676-A-026
Figure 26. Phase Error bet ween Channels (40 Hz to 70 Hz)
Rev. B | Page 17 of 24
ADE7752

DIGITAL-TO-FREQUENCY CONVERSION

As previously described, after multiplication the digital output of the low-pass filter contains the real power information of each phase. However since this LPF is not an ideal “brick wall” filter implementation, the output signal also contains attenuated components at the line frequency and its harmonics, i.e., cos(hωt), where h = 1, 2, 3, …
The magnitude response of the filter is given by
()
||
Where the –3 dB cutoff frequency of the low-pass filter is 8 Hz. For a line frequency of 50 Hz, this would give an attenuation of the 2ω (100 Hz) component of approximately –22 dB. The dom­inating harmonic will be twice the line frequency, i.e., cos(2ωt), due to the instantaneous power signal. F shows the instantaneous real power signal at the output of the CF, which still contains a significant amount of instantaneous power infor­mation, i.e., cos (2
This signal is then passed to the digital-to-frequency converter where it is integrated (accumulated) over time to produce an output frequency. This accumulation of the signal will suppress or average out any non-dc component in the instantaneous real
1
=ffH (8)
1
2
+
8
igure 27
ωt).
power signal. The average value of a sinusoidal signal is zero. Thus, the frequency generated by the ADE7752 is proportional to the average real power. F shows the digital-to-
igure 27 frequency conversion for steady load conditions, i.e., constant voltage and current.
As can be seen in the diagram, the frequency output CF varies over time, even under steady load conditions. This frequency variation is primarily due to the cos(2ωt) components in the instantaneous real power signal. The output frequency on CF can be up to 160 times higher than the frequency on F1 and F2. The higher output frequency is generated by accumulating the instantaneous real power signal over a much shorter time, while converting it to a frequency. This shorter accumulation period means less averaging of the cos(2ωt) component. As a conse­quence, some of this instantaneous power signal passes through the digital-to-frequency conversion. This will not be a problem in the application. Where CF is used for calibration purposes, the frequency should be averaged by the frequency counter. This will remove any ripple. If CF is being used to measure energy, e.g., in a microprocessor based application, the CF output should also be averaged to calculate power. Because the outputs F1 and F2 operate at a much lower frequency, much more averaging of the instantaneous real power signal is carried out. The result is a greatly attenuated sinusoidal content and a virtually ripple-free frequency output.
MULTIPLIER
MULTIPLIER
MULTIPLIER
VA
VB
VC
ABS
LPF
|X|
IA
LPF
|X|
IB
LPF
|X|
IC
Figure 27. Real Power-to-Frequency Conversion
Σ
LPF TO EXTRACT
REAL POWER
(DC TERM)
DIGITAL-TO-
FREQUENCY
Σ
DIGITAL-TO-
FREQUENCY
Σ
V× I
2
0
INSTANTANEOUS REAL POWER SIGNAL
F1
F1 F2
FREQUENCY
TIME
CF
CF
FREQUENCY
TIME
cos(2ωt)
ATTENUATED BY LPF
ω
FREQUENCY – RAD/S
(FREQUENCY DOMAIN)
2ω
02676-A-027
Rev. B | Page 18 of 24
ADE7752

MODE SELECTION OF THE SUM OF THE THREE ACTIVE ENERGIES

The ADE7752 can be configured to execute the arithmetic sum of the three active energies, Wh = Wh sum of the absolute value of these energies, Wh = |Wh
| + |WhϕC| The selection between the two modes can be
|Wh
ϕB
made by setting the on the
pin correspond to the arithmetic sum and the sum
ABS
pin. Logic high and logic low applied
ABS
of absolute values, respectively.
When the sum of the absolute values is selected, the active energy from each phase is always counted positive in the total active energy. It is particularly useful in 3-phase 4-wire installa­tion where the sign of the active power should always be the same. If the meter is misconnected to the power lines, i.e., CT connected in the wrong direction, the total active energy recorded without this solution can be reduced by two-thirds.
+ WhϕB + WhϕC, or the
ϕA
| +
ϕA
The sum of the absolute values assures that the active energy recorded represents the actual active energy delivered. In this mode, the reverse power pin still detects when negative power is present on any of the three phase inputs.

POWER MEASUREMENT CONSIDERATIONS

Calculating and displaying power information will always have some associated ripple that will depend on the integration period used in the MCU to determine average power as well as the load. For example, at light loads, the output frequency may be 10 Hz. With an integration period of 2 seconds, only about 20 pulses will be counted. The possibility of missing one pulse always exists since the ADE7752 output frequency is running asynchronously to the MCU timer. This would result in a 1-in­20 or 5% error in the power measurement.
Rev. B | Page 19 of 24
ADE7752
(
)
×
=
×

TRANSFER FUNCTION

FREQUENCY OUTPUTS F1 AND F2

The ADE7752 calculates the product of six voltage signals (on current channel and voltage channel) and then low-pass filters this product to extract real power information. This real power information is then converted to a frequency. The frequency information is output on F1 and F2 in the form of active high pulses. The pulse rate at these outputs is relatively low, e.g.,
29.32 Hz maximum for ac signals with SCF = 1; S0 = S1 = 1. (See Table 6.) This means that the frequency at these outputs is generated from real power information accumulated over a relatively long period of time. The result is an output frequency that is proportional to the average real power. The averaging of the real power signal is implicit to the digital-to-frequency conversion. The output frequency or pulse rate is related to the input voltage signals by the following equation:
Freq
922.5
=
AAN
BBN
2
V
REF
where:
Freq = Output frequency on F1 and F2 (Hz) V
and VCN = Differential rms voltage signal on voltage
AN, VBN,
channels (Volts)
and IC = Differential rms voltage signal on current
I
A, IB,
channels (Volts)
= The reference voltage (2.4 V ± 8%) (Volts)
V
REF
= One of seven possible frequencies selected by using the
F
1–7
logic inputs SCF, S0, and S1. See Table 5.
Table 5. F
SCF S1 S0 F
Frequency Selection1
1–7
1–7
(Hz)
0 0 0 1.27 1 0 0 1.19 0 0 1 5.09 1 0 1 4.77 0 1 0 19.07 1 1 0 19.07 0 1 1 76.29 1 1 1 0.60
1
F
is a fraction of the master clock and therefore will vary if the specified
1–7
CLKIN frequency is altered.
Example 1
Thus, if full-scale differential dc voltages of +500 mV are applied to VA, VB, VC, IA, IB, and IC, respectively (500 mV is the maximum differential voltage that can be connected to current and voltage channels), the expected output frequency is calculated as follows:
FIVIVIV
××+×+××
CCN
71
F
= 0.60 Hz, SCF = S0 = S1 = 1
1–7
= VBN = VCN = IA = IB = IC
V
AN
= 500 mV dc = 0.5 V(rms of dc = dc)
= 2.4 V (nominal reference value)
V
REF
Note that if the on-chip reference is used, actual output fre­quencies may vary from device to device due to reference tolerance of ±8%.
××
60.05.05.0922.5
×=
3
2
4.2
=
HzFreq 462.0
Example 2
In this example, with ac voltages of ±500 mV peak applied to the voltage channels and current channels, the expected output frequency is calculated as follows:
SSSCFHzF
110,60.0
AN
REF
71
BN
CN
500
()
4.2
=
===
ICIBIAVVV
=====
5.0
==
2
VrmsACpeakmV
valuereferencenominalVV
Note that if the on-chip reference is used, actual output fre­quencies may vary from device to device due to reference tolerance of ±8%.
596.05.05.0922.5
×=
3
××
2
4.222
××
HzFreq 23.0
=
As can be seen from these two example calculations, the maximum output frequency for ac inputs is always half of that for dc input signals. The maximum frequency also depends on the number of phases connected to the ADE7752. In a 3-phase 3-wire Delta service, the maximum output frequency is different from the maximum output frequency in a 3-phase 4-wire Wye service. The reason is that there are only two phases connected to the analog inputs, but also that in a Delta service, the current channel input and voltage channel input of the same phase are not in phase in normal operation.
Example 3
In this example, the ADE7752 is connected to a 3-phase 3-wire Delta service as shown in F . The total real energy
igure 21 calculation processed in the ADE7752 can be expressed as
Total Re a l P o w e r = (V
Where V
, VB, and VC represent the voltage on phase A, B, and
A
C, respectively. I
and IB represent the current on phase A and B,
A
– VC) × IA + (VB – VC) × IB
A
respectively.
Rev. B | Page 20 of 24
ADE7752
()()(
)
z
As the voltage and current inputs respect Equations 5 and 6, the total real power (P) is
()
 
 
A
A
B
B
()
l
cos2
tI
ω×××
()
l
cos2
 
cos2
tI
l
cos2cos2
C
2
π
+ω××+
l
3
2
π
+ω×××
3
×+=
IBNIBPVCVBIANIAPVCVAP
π
4
  
C
+ω××ω××=
tVtVP
l
3
4
cos2
 
π
tVvtV
+ω××
l
3
For simplification, we assume that ϕA = ϕB = ϕC = 0 and
= VB = VC = V. The preceding equation becomes:
V
A
2
π
sin2
×××=
A
sin2
×××+
B
sin
3
π
  
()
3
2
π
  
()
cos
ttIVP
+ω×
3
ω×
 
cossin
ll
(9)
π
2
  
+ω×π+ω×
ttIV
ll
3
P then becomes:
π
2
××=
sin
A
××+
B
3
π
sin
3
2sin
2sin
π
2
+ω+
tIVANP
l
3
(10)
π
+ω+
tIVBN
l
3
where VA N = V × sin(2π/3) and VBN = V × sin(π/3).
As the LPF on each channel eliminates the 2
ω
component of
l
the equation, the real power measured by the ADE7752 is
3
AAN
2
3
××+××=
IVIVP
BBN
2
If full-scale ac voltage of ±500 mV peak is applied to the voltage channels and current channels, the expected output frequency is calculated as follows:
110,60.0
SSSCFH
F
71
BN
AN
ICV
0
CN
REF
==
4.2
=
====
500
5.0
======
rmsVacpeakVmICIBIAVV
2
value referencenominal VV
Note that if the on-chip reference is used, actual output fre­quencies may vary from device to device due to reference tolerance of ±8%.
2
×=
Table 6
shows a complete listing of all maximum output fre-
×××
2
4.222
××
quencies when using all three channel inputs.
Table 6. Maximum Output Frequency on F1 and F2
 
SCF S1 S0
0 0 0 0.49 0.98 1 0 0 0.46 0.91 0 0 1 1.95 3.91 1 0 1 1.83 3.67 0 1 0 7.33 14.66 1 1 0 7.33 14.66 0 1 1 29.32 58.65 1 1 1 0.23 0.46
Max Frequency for AC Inputs (Hz)

FREQUENCY OUTPUT CF

The pulse output CF (calibration frequency) is intended for use during calibration. The output pulse rate on CF can be up to 160 times the pulse rate on F1 and F2. The lower the F quency selected, the higher the CF scaling. shows how the two frequencies are related, depending on the states of the logic inputs S0, S1, and SCF. Because of its relatively high pulse rate, the frequency at this logic output is proportional to the instantaneous real power. As is the case with F1 and F2, the frequency is derived from the output of the low-pass filter after multiplication. However, because the output frequency is high, this real power information is accumulated over a much shorter time. Thus, less averaging is carried out in the digital-to­frequency conversion. With much less averaging of the real power signal, the CF output is much more responsive to power fluctuations. See Figure 15.
Table 7. Maximum Output Frequency on CF
SCF S1 S0 F
0 0 0 1.27 160 × F1, F2 = 78.19 1 0 0 1.19 8 × F1, F2 = 3.66 0 0 1 5.09 160 × F1, F2 = 312.77 1 0 1 4.77 16 × F1, F2 = 29.32 0 1 0 19.07 16 × F1, F2 = 117.3 1 1 0 19.07 8 × F1, F2 = 58.65 0 1 1 76.29 8 × F1, F2 = 234.59 1 1 1 0.60 16 × F1, F2 = 3.67
(Hz) CF Max for AC Signals (Hz)
1–7
3
60.05.05.0922.5
=×
2
Max Frequency for DC Inputs (Hz)
Table 7
HzFreq 134.0
fre-
1–7
Rev. B | Page 21 of 24
ADE7752

SELECTING A FREQUENCY FOR AN ENERGY METER APPLICATION

As shown in , the user can select one of seven frequen-
Table 5 cies. This frequency selection determines the maximum frequency on F1 and F2. These outputs are intended to be used to drive the energy register (electromechanical or other). Since only seven different output frequencies can be selected, the available frequency selection has been optimized for a 3-phase 4-wire service with a meter constant of 100 imp/kWhr and a maximum current of between 10 A and 100 A. T shows the output frequency for several maximum currents (I
able 8
MAX
) with a line voltage of 220 V (phase neutral). In all cases, the meter constant is 100 imp/kWhr
Table 8. V. F1 and F2 Frequency at 100 imp/kWhr
I
(A) F1 and F2 (Hz)
MAX
10 0.10 25 0.25 40 0.40 60 0.60 80 0.80 100 1.00
The F
frequencies allow complete coverage of this range of
1–7
output frequencies on F1 and F2. When designing an energy meter, the nominal design voltage on the voltage channels should be set to half scale to allow for calibration of the meter constant. The current channel should also be no more than half scale when the meter sees maximum load. This will allow overcurrent signals and signals with high crest factors to be accommodated. shows the output frequency on F1 and
Table 9
F2 when all six analog inputs are half scale.
Table 9. F1 and F2 Frequency with Half-Scale AC Inputs
Frequency on F1 and F2
SCF S1 S0 F
0 0 0 1.27 0.24 1 0 0 1.19 0.23 0 0 1 5.09 0.98 1 0 1 4.77 0.92 0 1 0 19.07 3.67 1 1 0 19.07 3.67 0 1 1 76.29 14.66 1 1 1 0.60 0.11
1–7
(Half-Scale AC Inputs)
When selecting a suitable F frequency output at I
(maximum load) with a 100 imp/kWhr
MAX
meter constant should be compared with Column 5 of T The frequency that is closest in will determine the best choice of frequency (F
). For example, if a 3-phase 4-wire Wye
1–7
meter with a 25 A maximum current is being designed, the output frequency on F1 and F2 with a 100 imp/kWhr meter constant is 0.25 Hz at 25 A and 220 V (from ). Looking at Table 9
, the closest frequency to 0.25 Hz in Column 5 is 0.24 Hz.
Therefore, F
= 1.27 Hz is selected for this design.
1–7

FREQUENCY OUTPUTS

Figure 2 shows a timing diagram for the various frequency outputs. The outputs F1 and F2 are the low frequency outputs that can be used to directly drive a stepper motor or electro­mechanical impulse counter. The F1 and F2 outputs provide two alternating high going pulses. The pulse width (t 275 ms, and the time between the rising edges of F1 and F2 (t is approximately half the period of F1 (t period of F1 and F2 falls below 550 ms (1.81 Hz), the pulse width of F1 and F2 is set to half of their period. The maximum output frequencies for F1 and F2 are shown in . Table 6
The high frequency CF output is intended to be used for com­munications and calibration purposes. CF produces a 96 ms­wide active high pulse (t power. The CF output frequencies are given in Table 7. As in the case of F1 and F2, if the period of CF (t CF pulse width is set to half the period. For example, if the CF frequency is 20 Hz, the CF pulse width is 25 ms. One exception to this is when the mode is S0 = 1, SCF = S1 = 0. In this case, the CF pulse width is 66% of the period.
) at a frequency proportional to active
4
frequency for a meter design, the
1–7
able 9
Table 9
Table 8
) is set at
1
). If, however, the
2
) falls below 192 ms, the
5
)
3
Rev. B | Page 22 of 24
ADE7752

NO LOAD THRESHOLD

The ADE7752 also includes no load threshold and start-up cur­rent features that eliminate any creep effects in the meter. The ADE7752 is designed to issue a minimum output frequency. Any load generating a frequency lower than this minimum fre­quency will not cause a pulse to be issued on F1, F2, or CF. The minimum output frequency is given as 0.005% of the full-scale output frequency for each of the F approximately 0.00204% of the F For example, for an energy meter with a 100 imp/kWhr meter constant using F F1 or F2 would be 9.15 × 10
(4.77 Hz), the minimum output frequency at
1–7
–5
at CF (16 × F1 Hz). In this example, the no load threshold would be equivalent to 3.3 W of load or a start-up current of
13.75 mA at 240 V.
Table 10. CF, F1, and F2 Minimum Frequency at No Load Threshold
SCF S1 S0 F1, F2 Min (mHz) CF Min (mHz)
0 0 0 2.44 × 10–5 3.91 × 10–3 1 0 0 2.29 × 10–5 1.83 × 10–4 0 0 1 9.77 × 10–5 1.56 × 10–2 1 0 1 9.16 × 10–5 1.47 × 10–3 0 1 0 3.67 × 10–4 5.86 × 10–3 1 1 0 3.67 × 10–4 2.93 × 10–3 0 1 1 1.47 × 10–3 1.17 × 10–2 1 1 1 1.15 × 10–5 1.83 × 10–4
frequency selections or
1–7
frequency (see ).
1–7
Table 10
Hz. This would be 1.46 × 10–6 Hz

NEGATIVE POWER INFORMATION

The ADE7752 detects when the current and voltage channels of any of the three phase inputs have a phase difference greater than 90°, i.e., ϕ wrong connection of the meter or generation of active energy. The NEGP pin output will go active high when negative power is detected on any of the three phase inputs. If positive active energy is detected on all the three phases, NEGP pin output is low. The NEGP pin output changes state at the same time as a pulse is issued on CF. If several phases measure negative power, the NEGP pin output will stay high until all the phases measure positive power. If a phase has gone below the NO LOAD threshold, NEGP detection on this phase is disabled. NEGP detection on this phase resumes when the power returns out of NO LOAD condition. See the No Load Threshold section.
or ϕB or ϕC > 90°. This mechanism can detect
A
Rev. B | Page 23 of 24
ADE7752
Y

OUTLINE DIMENSIONS

15.60 (0.6142)
15.20 (0.5984)
24 13
1
0.30 (0.0118)
0.10 (0.0039)
COPLANARIT
0.10
1.27 (0.0500) BSC
CONTROLLING DIMENSIONS ARE IN MILLIMETERS; INCH DIMENSIONS (IN PARENTHESES) ARE ROUNDED-OFF MILLIMETER EQUIVALENTS FOR REFERENCE ONLY AND ARE NOT APPROPRIATE FOR USE IN DESIGN
COMPLIANT TO JEDEC STANDARDS MS-013AD
0.51 (0.020)
0.31 (0.012)
7.60 (0.2992)
7.40 (0.2913)
12
2.65 (0.1043)
2.35 (0.0925)
SEATING PLANE
10.65 (0.4193)
10.00 (0.3937)
0.33 (0.0130)
0.20 (0.0079)
0.75 (0.0295)
0.25 (0.0098)
8° 0°
×
45°
1.27 (0.0500)
0.40 (0.0157)
Figure 28. 24-Lead Standard Small Outline Package [SOIC] Wide Body (RW-24)
Dimensions shown in millimeters and (inches)

ORDERING GUIDE

Model Package Description Package Option
ADE7752AR SOIC Package RW-24 ADE7752ARRL SOIC Package RW-24 on 13" Reels EVAL-ADE7752EB ADE7752 Evaluation Board
1
RW = Small Outline Wide Body Package in Tubes
1
© 2003 Analog Devices, Inc. All rights reserved. Trademarks and registered trademarks are the property of their respective companies.
C02676–0–9/03(B)
Rev. B | Page 24 of 24
Loading...