ANALOG DEVICES 6B50 Service Manual

www.BDTIC.com/ADI
Isolated, Field Configurable Digital I/O
FEATURES
Single-channel isolated signal-conditioning modules. Accepts outputs from Thermocouple, millivolt, volt and
current signals. Complete microcomputer-based data acquisition systems. Can be remotely reconfigured for various sensor types and
input ranges.
APPLICATIONS
Process Monitoring & Control Test Stand Automation Machine Monitoring Material Testing Remote Energy Mangement Laboratory Data Acquisition
PRODUCT OVERVIEW
The 6B Series delivers sensor-to-host signal-conditioning for remote applications. Software-configurable for a wide variety of sensor types, including: analog input, analog output, and digital I/O, the 6B Series is intended for remote data acquisition, machine monitoring, remote energy management and process monitoring and control applications.
Including transformer-based isolation, ranging, linearization, A/d conversion and RS-232C/RS-485 serial communication for up to 256 channels per serial port, the 6B Series modules and boards are a complete, low-cost interface between computers and analog signals.
All 6B Series input/output modules are fully encapsulated and identical in pin-out and size, facilitating their ability to be mixed and matched with all other 6B Series modules on the same backplane. The 6B Series is fully rated over the industrial temperature range of -25
Each 6B Series module and board is a complete microcontroller-based process monitoring and control system, with all calibration, address and linearizing parameters stored in non-volatile memory. Being microcontroller-based, 6b Series modules can be configured for various sensor types, including RTD and thermocouple, and a wide variety of input ranges. This reduces the number of different modules that need to be used
o
C to +85oC.
6B50-1 / 6B50-2
in a given application and carried in inventory.
FUNCTIONAL BLOCK DIAGRAM
Figure 1. 6B50-1 & 6B50-2 Functional Block Diagram
Designed for industrial applications, the 6B Series modules incorporate transformer-based isolation with surface-mount manufacturing technology – providing increased reliability at low cost. The compact, rugged 6B Series analog modules can be mixed and matched on a 16-channel backplane for high density, remote process monitoring and control.
Communications between backplanes, modules and host is in ASCII over an RS-232C link or RS-485 bi-directional serial bus. Circuitry to convert RS-232C to RS485 is built into the 6B backplane. Baud rates are software programmable, with speeds up to 19.2 K Baud.
The 6B Series digital subsystem communication is compatible with the overall 6B Series communication protocol. Each digital I/O board can be configured for its address, baud rate and checksum status. Connection to the 16 and 24-channel solid state relay backplanes is by a 50-conductor ribbon cable. This enables interfacing with input and outputs from 4 V to 240 V. Power control modules are also available that can switch up to 3A and come with a variety of ratings for low voltage DC up to 280 VAC.
Rev. 0
Information furnished by Analog Devices is believed to be accurate and reliable. However, no responsibility is assumed by Analog Devices for its use, nor for any infringements of patents or other rights of third parties that may result from its use. Specifications subject to change without notice. No license is granted by implication or otherwise under any patent or patent rights of Analog Devices. Trademarks and registered trademarks are the property of their respective companies.
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A. Tel: 781.329.4700 Fax: 781.326.8703 © 2004 Analog Devices, Inc. All rights reserved.
www.analog.com
www.BDTIC.com/ADI
GENERAL DESCRIPTION
The 6B50-1 and 6B50-2 are 24-channel digital I/O boards which are compatible with the 6B Series Signal-Conditioning Modules at the network level. Each converts commands from the host computer into logic levels suitable for interfacing with industry-standard opto-isolated digital I/O panels. All I/O channels can be configured for input or output, using bit or byte addressing. In addition, the status of the port can be read back by the host to confirm the I/O configuration
Synchronized Sampling – The synchronized sampling command allows data to be sampled simultaneously from all 6B11, 6B11HV, 6B12, 6B12HV modules and all 6B50 boards in a 6B Series system. Each module or board stores the data in a separate register within its microcontroller and can access the data with a separate command.
Software Configuration – The 6B50-1 and 6B50-2 can be
.
6B50-1 / 6B50-2
software-configured for address, baud rate, data format, checksum status and I/O configuration. All programmable parameters are stored in the nonvolatile memory of each digital I/O board.
An on-board microcontroller communicates with the host through an RS-232C port (Model 6B50-2 or with a 6B Series backplane through an RS 485 port (Model 6B50-1) to exchange command and status information.
An included EEPROM stores system parameters (address, baud rate, checksum, etc.) as well as I/O configuration information. The microcontroller is interfaced to 8-bit latches and buffers a maximum of 24 digital i/o channels. Each channel can be individually set as either an input or output. The 6B50-1 and 6B50-2 are 3.47-inch x 6.5-inch open boards that can be panel or rack mounted.
Figure 2
.
Rev. 0 | Page 2 of 8
www.BDTIC.com/ADI
6B50-1 / 6B50-2
6B50-1 AND 6B50-2 Models Available
Model Host PC
Communications
6B50-1 N/A RS-485 24 Channels
6B50-2 RS-232C RS-485 24 Channels
Expansion & Module
Communications
Digital I/O
(Software Configurable)
6B50-1 and 6B50-2 Specifications
(typical @ +23°C ±5°C and Vs = +24 V dc)
Description Model 6B50-1 and 6B50-2
Digital I/O
Number of I/O Channels 24 (Software Configurable for Input or Output)
I/O Circuit Configuration
Digital Inputs
High-Level Input +3.5 V minimum; +5.25 V maximum
Low Level Output 0.8 V maximum
Digital Outputs
High Level Output Current 50 µA @ +5 V
Low Level Output Current 100 mA @ +1.1 V
High-Level Output Voltage +5.25 V maximum
Connector Male, 50-Pin
Model 6B50-2
Protocol RS-232C
Baud Rates, Software Selectable 300K, 600K, 1.2K, 2.4K, 4.8K, 9.6K,19.2K
Distance From Host PC and 6B50-2 50 feet maximum
Connector Male, DB-25
LED Indicators Data and Enable
Synchronized Sampling Command Yes
Conversion Time 1 ms maximum
Model 6B50-1
Protocol RS-485
Baud Rates, Software Selectable 300K, 600K, 1.2K, 2.4K, 4.8K, 9.6K, 19.2K
Distance From 6B Backplane and 6B50-1 4000 feet maximum
Connector 6 Screw Terminals
LED Indicators Data and Enable
Synchronized Sampling Command
Conversion Time 1 ms maximum
Open Collector Outputs with 47 k Pullups to +5 V
Communications
Ye s
Rev. 0 | Page 3 of 8
Loading...
+ 5 hidden pages