AMX RDM-ZC User Manual

Installation Sheet
RDM-ZC Zero Cross Module
2400 W
The RDM-ZC Zero Cross Module is a 2400 W zero-cross relay built for long term, reliable switching of electronic fluorescent ballasts, electronic trans­formers and incandescent lamps. It is designed for use with the RDA series of enclosures, in an AMX Lighting™ modular digital dimming system. The RDM-ZC module's 120, 240, and 277 VAC ratings are CE, UL, and C-UL approved.
Mounting points
Line in (hot) Load out
Zero cross relay
High-voltage connections
Low-voltage control wiring: 4-pin connector to AMX Lighting master controller
• This module may require extra power from the AXlink connection or an external power supply connected to the control card.

Connecting the RDM-ZC to the AMX Lighting Master

Pin 4 (GND) Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
RDM-ZC 4-pin module connector
3 (-)
1 (+)
4-pin plug from RDM series module
NOTE: The 4-pin plugs from the module connector to the 4-pin connector on the master (black plug cover facing up).
FIG. 2 RDM-ZC connections

Lighting Application Drawing

All neutrals are common to the Neutral block in the enclosure. Provide a separate neutral for each load.
Neutral
Line in (HOT)
Load
Zone 1
Incandescent track
lighting
FIG. 1 RDM-ZC

RDM-ZC UL and C-UL Ratings

• 120-277 VAC, 50/60 Hz, 2400 W
• 240/277 VAC, 50/60 Hz, 2400 W

Suggested Switched Loads

• Incandescent
• Electronic transformers
• HID ballast
• Electronic and magnetic ballast

Specifications

• Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)
• Non-phase dependant
• Use wires rated at 75°C (167°F)
• Torque terminals to 7 in-lbs. (0.8 N/M)
• Max. wire size: 10 AWG (4 mm²)
• Wire stripping length: 0.28" (7 mm)
• Weight: 1.5 lbs. (0.68 kg)
• BTU/hr: 150
• Control current: 45 mA @ 12 VDC

Caution: Pre-Installation Notes

• All Class 1 wiring must be connected to proper terminals.
• All control wiring must be connected to proper terminals.
• Disconnect power while installing or connecting the unit.
• Keep top and bottom air vents clear at all times.
• Test loads for shorts before connecting.
• Use low voltage wires with a 300 volt rating or greater.
• Use field installed copper conductors.
• All electrical ratings are for continuous duty.
• For indoor use only.
Circuit breaker panel
FIG. 3 RDM-ZC wiring configuration
Fluorescent Ballast
BALLAST
BALLAST
Neutral
Load
Neutral
Load
Neon lights
(cold-cathode, on/off)
AMX Corporation reserves the right to alter specifications without notice at any time.
For full warranty information, refer to the AMX Instruction Manual(s) associated with your Product(s).
The AMX logo is a trademark of AMX Corporation. AMX Cor poration reserves the right t o alter specifications without notice at any time.
3000 research drive, richardson, TX 75082 USA • 469.624.8000 • 800.2 22.0193 • fax 469.624.71 53 • technical support 800.932.6993
043-019-2213 8/01 ©2001 AMX Corporation. All rights re served.
Loading...