AMX RDM-MDM User Manual

Installation Sheet
RDM-MDM Multimode Dimmer Module
2400 W
The RDM-MDM Multimode Dimmer Module is ideally used in situations where the load is not specified or the load may change at the last moment. This unit is a unique combination 2400 W Incandescent dimmer,
2400 W Switch, or 2400 W FDB fluorescent dimmer. It consists of a heavy duty SSR construction for dimming and a heavy duty positive air gap relay for switching. The RDM-MDM module's 120 and 240-277 VAC ratings are CE, UL, and C-UL approved.
Mounting points
Neutral
Line
Dimmed Switched
350 µS Choke
Mechanical Relay
2400 W power device
High-voltage connections

Caution Pre-Installation Notes:

• All Class 1 wiring must be connected to proper terminals.
• All control wiring must be connected to proper terminals.
• Disconnect power while installing or connecting the unit.
• Keep top and bottom air vents clear at all times.
• Test loads for shorts before connecting.
• Use low-voltage wires with a 300 volt rating or greater.
• Use field-installed copper conductors.
• Run all low-voltage and control wires away from heat producing parts of the dimmer.
• Each dimming circuit must have a separate neutral connection.
• All electrical ratings are for continuous duty.
• For indoor use only.
• AC lighting loads only.
• This module may require extra power from the AXlink connection or an external power supply connected to the control card.

Connecting RDM Series Modules to the RDM-MDM:

Pin 4 (GND) Pin 3 (RLY)
Pin 2 (DIM) Pin 1 (+12 V)
RDM-MDM four-pin module connector
4-pin plug from a RDM series module
Note: The 4-pin plugs from the module connector to the 4-pin connector on the master (black plug cover facing up).
Low-voltage control wiring: four-pin connector to AMX Lighting master controller
FIG. 1 RDM-MDM

RDM-MDM UL and C-UL Ratings:

• 120 VAC, 50/60 Hz, 2400 W per circuit
• 240/277 VAC, 50/60 Hz, 2400 W per circuit

Specifications:

• Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)
• Phase dependant dimming
• Use wires rated at 75°C (167°F)
• Torque terminals to 7 in-lbs (0.8 N/M)
• Max. wire size: 10 AWG (4 mm²)
• Wire stripping length: 0.28" (7 mm)
• Weight: 4.5 lbs (2.04 kg)
• BTU/hr: 300
• Control current: 190 mA @ 12 VDC

Suggested Loads:

• Incandescent • Two-wire, phase-controlled ballast
• Low-voltage • Three-wire, phase-controlled ballast
• Neon, cold-cathode • Switched fluorescent ballast
FIG. 2 Connecting RDM series modules to the RDM-MDM
Switch configuration
FIG. 3 Method A

Lighting Application Drawings

Method A
120 VAC, 1Ø /
FIG. 4 Method B
Three-wire (FDB) configuration
FIG. 5 Method C
Method B
120 VAC, 1Ø /
Dimming configuration
Method C
120 VAC, 1Ø /
AMX Corporation reserves the right to alter specifications without notice at any time.
For full warranty information, refer to the AMX Instruction Manual(s) associated with your Product(s).
The AMX logo is a trademark of AMX Corporation. AMX Corporation reserves the right to alter specifications without notice at any time.
3000 research drive, richardson, TX 75082 USA • 469.624.8000 • 800.222.0193 • fax 469.624.7153 • technical support 800.932.6993
043-019-2299 10/01 ©2001 AMX Corporation. All rights reserved.
Loading...