The RDM-HFDB Heavy Duty FDB Module is a heavy-duty, 2400 W positive
air gap relay and dimmer, built for strength and for reliable switching/dimming of Lutron FDB ballasts. It is designed for use with the RDA series of
enclosures, in a AMX Lighting™ modular digital dimming system. The
RDM-HFDB module's 120, 240, and 277 VAC ratings are CE, UL, and C-UL
approved.
Mounting points
High
voltage
connections
FIG. 1 RDM-HFDB
Line in (hot)
Positive air
gap relay
Neutral
Switched out
Dimmed out
Solid state relay
Low-voltage control
wiring: 4-pin connector
to AMX Lighting master
controller
High
voltage
connections
RDM-HFDB UL and C-UL Ratings
• 120 VAC, 2400 W
• 240/277 VAC, 2400 W
Suggested Dimmed Loads
• Lutron© FDB Ballasts
• Lutron ECO-10
for more information)
®
Ballasts (refer to the AMX Lighting instruction manual
Specifications:
• Dimensions (HW): 10.0" x 2.75" (25.4 cm x 6.99 cm)
• Phase dependant
• Use wires rated at 75°C (167°F)
• Torque terminals to 20 in-lbs. (2.3 N/M)
• Max. wire size: 10 AWG (4 mm²)
• Wire stripping length: 0.28" (7 mm)
• Weight: 1.50 lbs. (0.680 kg)
• BTU/hr: 150
• Control current: 135 mA @ 12 VDC
• Use Dimming Curve 6 (refer to the Programming AMX Lighting
instruction manual for more information).
• For use with FDB ballasts.
Caution: Pre-Installation Notes
• All Class 1 wiring must be connected to proper terminals.
• All control wiring must be connected to proper terminals.
• Disconnect power while installing or connecting the unit.
• Keep top and bottom air vents clear at all times.
• Test loads for shorts before connecting. Use low-voltage wires with a
300 volt rating or greater.
• Use field installed copper conductors.
• All electrical ratings are for continuous duty.
• For indoor use only.
• This module may require extra power from the AXlink connection or an
external power supply connected to the control card.
Connecting the RDM-HFDB to the AMX Lighting Master
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
RDM-HFDB 4-pin module connector
3 (-)
2 (AC)
1 (+)
4-pin plug from RDM series module
Note: The 4-pin plugs from the module connector to the 4-pin
connector on the master (black plug cover facing up).
FIG. 2 Connecting the RDM-HFDB and AMX Lighting Master
Lighting Application Drawings
All neutrals are common
to the Neutral block in
the enclosure. Provide
a separate neutral for each
load.
Florescent Ballast
Ballast
Switched
Dimmed
Line in (HOT)
Neutral
Circuit breaker
panel
FIG. 3 RDM-HDC application wiring
RDM-HFDB
NEUTRAL LINE SWITCHED DIMMED
Neutral
AMX Corporation reserves the right to alter specifications without notice at any time.
For full warranty information, refer to the AMX Instruction Manual(s) associated with your Product(s).
The AMX logo is a trademark of AMX Corporation. AMX Corporat ion reserves the right to alter specifications without notice at any time.
3000 research drive, richardson, TX 75082 USA • 469.624.8000 • 800.222.0193 • fax 469.624.7153 • technical support 800.932.6993