AMX RDM-HDC User Manual

Installation Sheet
RDM-HDC Heavy Duty DC Module
2400 W, 0-12 VDC
The RDM-HDC Heavy Duty DC Module is a heavy-duty 2400 W module for dimming of fluorescent ballast loads. It uses a 0 to 12 VDC current sinking or sourcing for use with all four-wire ballasts. It is designed for use with the RDA series of enclosures, in an AMX Lighting™ modular digital dimming system. The module’s 120, 240, and 277 VAC ratings are CE, UL, and C-UL approved.
Mounting points
Neutral
High voltage
Line in
Load
Relay
- out (LV)
+ out (LV)
Low-voltage

Caution: Pre-Installation Notes

• All Class 1 wiring must be connected to proper terminals.
• All control wiring must be connected to proper terminals.
• Disconnect power while installing or connecting the unit.
• Keep top and bottom air vents clear at all times.
• Use low-voltage wires with a 300 volt rating or greater.
• Use field installed copper conductors.
• All electrical ratings are for continuous duty.
• For indoor use only.
• Test loads for shorts before connecting.
• This module may require extra power from the AXlink connection or an external power supply connected to the control card.

Connecting the RDM-HDC to the AMX Lighting Master

Pin 4 (GND)
Pin 3 (RLY) Pin 2 (DIM)
Pin 1 (+12 V)
RDM-HDC 4-pin module connector
GND 3 (-)
2 (DIM) 1 (+)
4-pin plug from RDM series module
Note: The 4-pin plugs from the module connector to the 4-pin connector on the master (black plug cover facing up).
FIG. 1 RDM-HDC

RDM-HDC UL and C-UL Ratings

• 120 VAC, 50/60 Hz, 2400 W
• 240/277 VAC, 50/60 Hz, 2400 W
• Control Out: 50 mA, 12 VDC sourcing/sinking

Suggested Dimmed Loads

• Four-wire dimmable ballasts
• All low-voltage DC controlled ballasts

Specifications

• Dimensions (HW): 10" x 2.75" (25.4 cm x 6.99 cm)
• Non-phase dependant
• Use wires rated at 75°C (167°F)
• Torque terminals to 20 in-lbs. (2.3 N/M)
• Max. wire size: 10 AWG (4 mm²)
• Wire stripping length: 0.28" (7 mm)
• Weight: 1.3 lbs. (0.590 kg)
• BTU/hr: 150
• Control current: 150 mA @ 12 VDC
Low-voltage control wiring: 4-pin connector to AMX Lighting master controller
FIG. 2 Connecting the RDM-HDC and AMX Lighting Master

Lighting Application Drawings

Neutral Line in (HOT)
Circuit breaker panel
FIG. 3 RDM-HDC application wiring
RDM-HDC
LOAD LINE NEUT CON
­+
Florescent Ballast
Ballast
Load
Neutral
Low-voltage wire rated to 300 V
Warning: Failure to ground the ballast may cause ballast failure
AMX Corporation reserves the right to alter specifications without notice at any time.
For full warranty information, refer to the AMX Instruction Manual(s) associated with your Product(s).
The AMX logo is a trademark of AMX Corporation. AMX Corporation reserves the right to alter specifications without notice at any time.
3000 research drive, richardson, TX 75082 USA • 469.624.8000 • 800.222.0193 • fax 469.624.7153 • technical support 800.932.6993
043-019-2240 10/01 ©2001 AMX Corporation. All rights reserved.