Installation Sheet
RDM-2ZC Dual Zero Cross Module
2400 W
The RDM-2ZC Dual Zero Cross Module is a dual 2400 W zero-cross relay
built for long term, reliable switching of electronic fluorescent ballasts, electronic transformers and incandescent lamps. It is designed for use with the
RDA series of enclosures, in an AMX Lighting™ modular digital dimming
system. The module's 120, 240, and 277 VAC ratings are CE, UL, and CUL approved.
Mounting
points
Line in (hot)
High-voltage
connections
Load out
Zero cross relay A
Zero cross relay B
Low-voltage control
wiring: 4-pin connector
to AMX Lighting master
controller
• This module may require extra power from the AXlink connection or an
external power supply connected to the control card.
Connecting the RDM-2ZC to the AMX Lighting Master
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
RDM-2ZC 4-pin module connector
3 (-)
1 (+)
4-pin plug from RDM series module
NOTE: The 4-pin plugs from the module connector to
the 4-pin connector on the master (black plug cover facing up).
FIG. 2 RDM-2ZC connections
Lighting Application Drawing
All neutrals are common
to the Neutral block in the
enclosure. Provide a
separate neutral for
each load.
(B) Load
(B) Line in (HOT)
(A) Line in (HOT)
(A) Load
FIG. 1 RDM-2ZC
RDM-2ZC UL and C-UL Ratings
• 120-277 VAC, 2400 W
• 240/277 VAC, 2400 W
Suggested Switched Loads
• Incandescent
• Electronic transformers
• HID ballast
• Electronic and magnetic ballast
Specifications
• Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)
• Non-phase dependant
• Use wires rated at 75°C (167°F)
• Torque terminals to 7 in-lbs. (0.8 N/M)
• Max. wire size: 10 AWG (4 mm²)
• Wire stripping length: 0.28" (7 mm)
• Weight: 2.0 lbs. (0.91 kg)
• BTU/hr: 300
• Control current: 45 mA per relay (90 mA total) @ 12 VDC
Caution: Pre-Installation Notes
• All Class 1 wiring must be connected to proper terminals.
• All control wiring must be connected to proper terminals.
• Disconnect power while installing or connecting the unit.
• Keep top and bottom air vents clear at all times.
• Test loads for shorts before connecting.
• Use low voltage wires with a 300 volt rating or greater.
• Use field installed copper conductors.
• All electrical ratings are for continuous duty.
• For indoor use only.
Circuit breaker
panel
FIG. 3 RDM-2ZC wiring configuration
Fluorescent Ballast
Ballast
Load
Neutral
Safety ground
Neutral
Load
Neon lights
(cold-cathode, on/off)
AMX Corporation reserves the right to alter specifications without notice at any time.
For full warranty information, refer to the AMX Instruction Manual(s) associated with your Product(s).
The AMX logo is a trademark of AMX Corporation. AMX Cor poration reserves the right t o alter specifications without notice at any time.
3000 research drive, richardson, TX 75082 USA • 469.624.8000 • 800.2 22.0193 • fax 469.624.71 53 • technical support 800.932.6993