AMX RDD-DM4 User Manual

Installation Sheet
RDD-DM4 4-Channel Integrated Dimmer Module 120,240,277 VAC
The RDD-DM4 Four-Channel Integrated Dimmer Module controls up to six dimmed channels with four 1200 W onboard dimmers and two satellite connectors (for RDM series dimmer or switching modules). It is designed for use with the RDA series of enclosures, in an AMX Lighting™ modular digital dimming system. The RDD-DM4 is controlled by AXlink, PROlink, or by dry (contact) closures. The RDD-DM4’s 120, 240, or 277 VAC ratings are CE, UL, and C-UL approved.
Mounting points
Powe r device
Bridge Line In
High-voltage connections
Load out
AXlink
address
DIP switch
PROlink address DIP
switch
Low-voltage control wiring: 4-pin connectors to RDM series modules
Dry Closures
AXlink connector
PROlink
Neutral
Chokes
Reset button
Memory Protect jumper
External +12 V power connector (optional)
FIG. 1 RDD-DM4 4-channel Integrated Dimmer Module

RDD-DM4 UL and C-UL Ratings: (per circuit)

Input
• 120, 240, 277 VAC, single phase, 3-wire, 50/60 Hz, 2400 W, one feed
• 120 ,240, 277 VAC, single phase, 4-wire, 50/60 Hz, 4800 W, dual feed
Output
• 1200 W max. per channel @120, 240, 277 VAC
• 2400 W max. total, all four channels on with 2400 W feed
• 4800 W max. total, all four channels on with dual 2400 W feeds
• Feed circuit #1 goes to dimmer 1 and 3; feed circuit #2 goes to dimmer 2 and 4.

Specifications

• Dimensions (HW): 5.87" x 10.0" (149.00 mm x 254.00 mm)
• Use wires rated at 75°C (167°F)
• Torque terminals to 20 in-lbs (2.3 N/M)
• Max. wire size: 10 AWG (4 mm²)
• Wire stripping length: 0.35" (9 mm)
• Weight: 4.5 lbs (2.04 kg)
• BTU/hr: 300 single feed (2400 W); 600 dual feed (4800 W)
• Power consumption: 50 mA @ 120 VAC, 25 mA @ 240 VAC, 22 mA @ 277 VAC
• Control port current: 200 mA @ 12 VDC

Loads:

Suggested Loads
Dimmed Switched (at 600 W)
Incandescent Fans
Low-voltage Florescent ballast
Neon, cold-cathode Motors

Button/Jumper Information:

• RESET button: By pressing the RESET button, located on the RDD-DM4 circuit board, it is possible to restart the processor without having to power-down the unit or disconnect AXlink or PROlink. RESET does not affect any saved presets or curve settings.
• MEMORY PROTECT on/off jumper: The MEMORY PROTECT jumper is set to Off by default. When put in the On position, saved curve settings and presets are protected in case of a power failure.

Caution: Pre-Installation Notes

• All Class 1 wiring must be connected to proper terminals.
• All control wiring must be connected to proper terminals.
• Disconnect power while installing or connecting the unit.
• Keep top and bottom air vents clear at all times.
• Test loads for shorts before connecting.
• Use low-voltage wires with a 300 volt rating or greater.
• Use field-installed copper conductors.
• All electrical ratings are for continuous duty.
• For indoor use only.
• AC lighting loads only.
• This module may require extra power from the AXlink connection or an external power supply connected to the control card.

Connecting the RDD-DM4 to the AMX Lighting Master

Pin 4 (GND) Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
RDD-DM4 4-pin module connector
3 (-)
1 (+)
4-pin plug from RDM series module
NOTE: The 4-pin plugs from the module connector to the 4-pin connector on the master (black plug cover facing up).
FIG. 2 RDD-DM4 connections

Connecting AXlink:

Connect the 4-pin captive-wire AXlink from the RDD-DM4 to the Central Controller for AXlink control of the dimming system.
(optional)
RDD-DM4
PWR
AXP AXM
GND
PWR AXP
AXM GND
Central Controller
FIG. 3 Connecting AXlink

Connecting PROlink:

Connect the orange 4-pin captive-wire PROlink connector from the RDD-DM4 to a PRO-DP8 PROlink wall panel.
PRO-DP8 Pack 1 Pack 2
+12
PR+ PR-
GND
FIG. 4 Connecting PROlink
+12
PR+ PR-
GND

Line-in Connections:

20 A
FIG. 5 Line-in Connections
Dual 20 A Inputs
Bridged 20 A Input
Using two feeds for line 1 and line 2 provides two, 20 A inputs.
Bridging line 1 and line 2 provides a single 20 A input.

Connecting Dry Closures:

Use the 8 (+ common) dry closures with a WPD8 eight-button wall panel.
1
2
5
78
3
6
4
COM
Each contact (1 - 8) is pre­programmed with a default preset.
Refer to the AMX Lighting Control System instruction manual for details on dry closure default presets and recording new presets.
FIG. 6 Dry closures connection
Each contact closure connection (1 - 8) is pre-programmed with a default preset. The table below shows the default presets for each contact closure.

Lighting Application Drawings

Dry Closure Default Presets
Contact Closure Default Function
1 Channel 1 at 100% in 1 second
2 Channel 2 at 100% in 1 second
3 Channel 3 at 100% in 1 second
4 Channel 4 at 100% in 1 second
5 Channel 5 at 100% in 1 second
6 Channel 6 at 100% in 1 second
7 Pack on (channels 1-6)
8 Pack off (channels 1-6
All other channels are undefined.

Setting AXlink and PROlink Address Numbers:

AXlink Address PROlink Address
Set the AXlink address number (1-255) for the RDD-DM4. This number must match the device number in your Axcess program.
Use the PROlink DIP switch to set the PROlink address number for the RDD-DM4 (1-10).
Pin 8 on the PROlink DIP switch is a test switch that turns all circuits on to full.
FIG. 7 Setting AXlink and PROlink address numbers
Te st
FIG. 8 Method A
Method A
120 VAC 1Ø /
Single-phase, four load
Method B
Typical 120 VAC
Single-pahse, four-wire
dual-feed
FIG. 9 Method B
AMX Corporation reserves the right to alter specifications without notice at any time.
For full warranty information, refer to the AMX Instruction Manual(s) associated with your Product(s).
The AMX logo is a trademark of AMX Corporation. AMX reserves the right to alter specifications without notice at any time.
3000 research drive, richardson, TX 75082 USA • 469.624.8000 • 800.222.0193 • fax 469.624.7153 • technical support 800.932.6993
043-019-2194 8/02 ©2002 AMX Corporat ion. All rights reserved.