Installation Guide
RE-DM4 Radia Eclipse 4-Channel Dimmer Module (120 or 240 volts)
Overview
The RE-DM4 RADIA Eclipse 4-Channel Integrated Dimmer Module (120 VAC:
FG706-01; 240 VAC: FG706-02) controls up to six circuits with four 1200-watt onboard
dimmers and two satellite connectors for RDM series dimmer or switch modules
(FIG. 1). The RE-DM4 is designed for use with the RDA series of enclosures in an
AMX Lighting™ modular digital dimming system. The RE-DM4 is controlled by AXLink
or by dry (contact) closures.
Mounting
points
Power Devices
Jumper
High
Voltage
Connections
Load out
Class 1 wiring
Class 2 wiring
AXLink
Address
DIP Switch
Mounting
points
FIG. 1 RE-DM4 4-Channel Integrated Dimmer Module
AXlink Connector
Dry Closures
Specifications
RE-DM4 Specifications
Dimensions (HW) 5.75" x 10.0" (146.05 mm x 254.00 mm)
Weight 4.5 lbs (2.04 kg)
Line Input • 120, 240 VAC, single phase, 2W+G, 50/60 Hz, 2400 W,
Output • 1200 W max. per channel @120, 240 VAC
Wire rating Use only copper wires rated at 75°C (167°F) min.
Torque terminals To 20 in-lbs (2.3 N/M)
Maximum wire size 10 AWG (4 mm²)
Wire stripping length 0.5" (13 mm)
AXLink Port 4-pin 3.5mm black captive wire connector. AXLink
Aux Power 2-pin 3.5mm green captive wire connector. This is a
Dry Contacts • Emergency fire alarm relay connection - Closed relay
BTU/hr 300 single feed (2400 W); 600 dual feed (4800 W)
one feed
• 120, 120/240, 240 VAC, single phase, 3W+G, 50/60
Hz, 4800 W, dual feed
• 2400 W max. total, all four channels on with single
2400 W feed
• 4800 W max. total, all four channels on with dual
2400 W feeds
• Line input #1 goes to dimmer 1 and 3; line input #2
goes to dimmer 2 and 4
• All electrical ratings are for continuous duty
communication signaling with 12VDC power in.
12VDC power input that supplies additional power to the
Radia PCB and connected Radia modules.
activates preset 126. Other control is locked out until
relay opens. Supports daisy chaining of up to 20
dimmers for this connection, with a maximum current
requirement of 200mA when daisy-chained.
• Failsafe connection - Works with a toggle switch opening the switch triggers preset 128, closing the
switch triggers preset 127. Supports daisy chaining of
up to 20 dimmers for this connection with a maximum
current requirement of 200mA when daisy-chained.
Line In
Neutral
Chokes
4-Pin Connectors
to RDM series
Modules
External +12V
Aux Power
RE-DM4 Specifications (Cont.)
Idle current draw 75 mA @ 120 VAC, 50 mA @ 240 VAC, 100 mA @ 13.5
RDM control current 2 at 200 mA @ 12 VDC with no additional power supply
Certifications • FCC
Operating Temp Range • 0° to 40°C (32° to 104°F)
Included Accessories • 2 4-pin 3.5mm captive wire connector (41-5047)
Required Enclosures • RDA-ENC2 (FG606-10)
VDC
•CE
• UL North America
• IEC-60950 Safety
• 4 #8-32x1/2” F-point mounting screws
• RDA-ENC4 (FG606-11)
• RDA-ENC6/6B (FG606-12/13/15)
• RDA-ENC12B (FG606-14/16)
Suggested Loads
Dimmed Switched
Incandescent Motors
Neon, cold-cathode Fans
Caution: Pre-Installation Notes
WARNING: This unit should be installed only by qualified electrical personnel, and in
compliance with all national electrical codes, local codes and ordinances.To prevent
possible personal injury or death, disconnect power to the enclosure at the breaker
box before attempting to work with any AMX Lighting modules.
• All Class 1 and 2 wiring must be connected to their dedicated terminals.
• Class 1 wiring should be connected through the top of the enclosure, and Class
2 wiring through the bottom.
• Load conductors must be same size as line conductors, regardless of
connected load.
• Disconnect power while installing or connecting the unit.
• Keep top and bottom air vents clear at all times, and maintain 12” (30.48 cm)
clearance around the top and bottom.
• Test loads for shorts before connecting.
• Class 2 wiring must be rated 300V or higher.
• For indoor use only.
• AC lighting loads only.
• This module may require extra power from the AXLink connection or an external
power supply connected to the control card.
• For more information, refer to the RE-DM4 instruction manual available at
www.amx.com.
Radia Lighting System Configuration Pages
The AMX Radia Web pages provide a simple interface for users of the Radia Duet
module. The web pages reside on the AMX master when running the Radia Duet
module and may be accessed through Internet Explorer or Mozilla Firefox. The REDM4 may also be configured using NetLinx code or a terminal. For more information,
refer to the RE-DM4 instruction manual available at www.amx.com.
High-Voltage Connections
Each AMX Lighting module has its high-voltage connectors marked on its circuit
board. Line, load, and neutrals are also clearly marked.
Load
High-voltage connections
FIG. 2
Line in
Load
Neutral
Line-in Connections
• Using two feeds for Line 1 and Line 2 provides two 2400 W inputs.
• With a jumper, Line 1 and Line 2 provides a single 2400 W input (FIG. 3).
Dual 2400 W Inputs without jumper
Single 2400 W Input with jumper
FIG. 3 Line-in Connections
Low-Voltage Connections
The low-voltage area in the AMX Lighting controllers contain connections and DIP
switches for AXLink, dry closures, and RDM module connectors. On the controller
cards, low-voltage power for the board is supplied either by line power, optional
auxiliary power supply (RDA-PSM), or the +12 VDC pin on the AXLink connector.
AXLink address DIP switch
AXlink connector
FIG. 4 Low-voltage connections and DIP switches
WARNING: Disconnect the main power to the AMX Lighting controller at the
breaker box if rewiring the low voltage connections.
Module connector/LED (CH6)
Module connector/LED (CH5)
Dry contact closures
Auxiliary power IN
Dry Closure Connections
Dry contact closures from other equipment can be connected to the Radia Eclipse
dimmer module to provide direct manual control of lighting loads (FIG. 5).
FAILSAF E
RE-DM4
FIG. 5 Dry Closure Connections
GND
EMERGENCY
GND
Failsafe switch
Alarm system
Lighting Application Drawings
Each dry contact closure has two pins: ground and contact. To activate each dry
closure, connect the ground and contact.
Setting AXLink Address Numbers
Set the AXLink address number (1-255) for the RE-DM4. This number must match
the device number in your Axcess program.
Note: By turning all switches off, all circuits will go to 100 percent so that the installer
can test the high-voltage connections without having connections to a control
system.
Connecting AXLink
Connect the 4-pin captive-wire AXLink from the RE-DM4 to the Central Controller for
AXLink control of the dimming system.
PWR
RE-DM4
FIG. 6 Connecting AXlink
AXP
AXM
GND
PWR
AXP
AXM
GND
Central
Controller
RE-DM4 4-pin module connector (male)
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
FIG. 7 RE-DM4 module connector
FIG. 8 Example A
FIG. 9 Example B
Example A
Single input
120 or 240 VAC 1
Ø
Single-phase, four load
Example B
Dual Input
120, 120/240, or 240 VAC 1
Single-phase, four load
Ø
For full warranty information, refer to the AMX Instruction Manual(s) associated with your Product(s).
©2007 AMX. All rights reserved. AMX and the AMX logo are registered trademarks of AMX.
3000 RESEARCH DRIVE, RICHARDSON, TX 75082 • 800.222.0193 • fax 469.624.7153 • technical support 800.932.6993 • www.amx.com
AMX reserves the right to alter specifications without notice at any time.
8/07
93-0706-01 REV: C