AMX RADIA DIMMER ENCLOSURES WITH BREAKERS User Manual

Installation Sheet
RDA-ENC6B and ENC12B Dimmer Enclosures w/Breakers
The RDA-ENC6B (FG606-13) and RDA-ENC12B (FG606-14) enclosures provide secure mounting for all AMX Lighting and PROlink controllers, and lighting modules. The enclosures also contain circuit breakers.
0.75"
(19.05 mm)
6.0"
(152.4 mm)
RDA-ENC12B
Top, side, and bottom views are the same for both enclosures.
RDA-ENC6B
24.0"
(610 mm)
TOP VIEW
SIDE VIEW
18.0"
(457.2 mm)
24.0"
(610 mm)
These enclosures are CE, UL, and C-UL approved. They include circuit breakers and terminals for multi-phase wiring. They also provide 18 knockouts for 1/2", 3/4", and 1" conduits.
RDA-ENC6B Configurations:
- ENC6B/120 20 A Breakers
- ENC6B/240 10 A Breakers
RDA-ENC12B Configurations:
- ENC12B/120 20 A Breakers
- ENC12B/240 10 A Breakers
RDK Configurations:
- RDK-ENC6B with 1 RDC-PDC
- RDK-ENC12B/240 2 RDC-PDC
Sample RDK-ENC12B kit shown with 2 RDC-PDC
Note:
LINE INPUTS: 140 A MAX PER ENCLOSURE
Use 75° C copper conductors only. Torque terminals to 44 in-lbs.
BOTTOM VIEW
FIG. 1
Top, front, bottom, and side views of the RDA-ENC6B and RDA-ENC12B enclosures
• For indoor use only.
• Mount on vertical surface only.
• Maintain 12" (304.88 mm) minimum clearance above and below the enclosure.
• Route class 1 conductors through upper conduit knockouts.
• Route class 2 conductors through lower conduit knockouts.
• Use 75°C (167°F) copper conductors only.
• Install filler plate #28-10500 (RDA-EFP) in all unused openings.
• Install only UL approved modules (see the UL Number Cross Reference to AMX Lighting ID table on page 2).

Enclosure Weights:

• RDA-ENC6B: 16.5 lbs. (7.48 kg)
• RDA-ENC12B: 17.5 lbs. (7.94 kg)

Dimensions between center lines (from FIG. 2):

RDA-ENC6B:
• A to B = 16.0" (406.4 mm)
• B to C = 22.88" (581.2 mm)
RDA-ENC12B:
• A to B = 16.0" (406.4 mm)
• B to C = 22.88" (581.2 mm)
Radia enclosures must be mounted on a vertical surface with a minimum of 12" (304.8 mm) clearance above and below the enclosure.
Configuration for right and left mounting brackets for all Radia enclosures.
Maximum mounting screw size: #12
Bracket configuration
FIG. 2
Top s l o t
Bottom slot
A to B
B to C

Specifications

• Maximum input wire #1/0 AWG (50mm²)
• Maximum line input is 140 A (per enclosure )
• Torque input wire to 44 in-lbs. (5.0 N/m)
• Wire stripping length: 0.67 inches (17 mm)
• Input 1 feeds channels 1, 4, 7, and 10
• Input 2a feeds channels 5 and 11
• Input 2b feeds channels 2 and 8
• Input 3 feeds channels 3, 6, 9, and 12
• Breakers are UL 489 listed 10,000 AIC, 100% Switching Duty, Hydraulic-Magnetic
The following section cross references the UL ID module numbers and AMX Lighting module IDs.
The modules identified are the only ones that can be used in the RDA­ENC6B and RDA-ENC12B enclosures.
UL Number Cross Reference to AMX Lighting ID
UL ID AMX ID UL ID AMX ID UL ID AMX ID
28-10100 RDC-DC/120 28-10200 RDM-INC 28-10300 RDM-MR60
28-10110 RDC-DC/240 28-10210 RDM-2INC 28-10310 RDM-MDM
28-10120 RDC-DC/277 28-10220 RDM-INC50 28-10340 RDA-CHK
28-10130 RDC-PDC/120 28-10230 RDM-ZC,
28-10133 RDC-PDC/240 28-10240 RDM-ZC50 28-10360 RDM-DPSM
RDM-2ZC
28-10350 RDM-FDB
RDM-2FDB RDM-3FDB RDM-HFDB

Lighting Application Drawings

UL Number Cross Reference to AMX Lighting ID (Cont.)
UL ID AMX ID UL ID AMX ID UL ID AMX ID
28-10140 RDD-DM6/120 28-10260 RDM-SWM,
28-10150 RDD-DM6/240 28-10270 RDM-HSW,
28-10160 RDD-DM6/277
28-10170 RDA-PSM/120
RDM-2SWM, RDM-3SWM
RDM-2HSW, RDM-3HSW
28-10370 RDM-DC,
RDM-2DC, RDM-3DC RDM-HDC
Note:
LINE INPUTS: 140 A MAX PER ENCLOSURE
Use 75° C copper conductors only. Torque terminals to 44 in-lbs.
FIG. 3 ENC6B and ENC12B Power Distribution
FIG. 4 ENC6B and ENC12B Input Terminal Block Wiring
AMX Corporation reserves the right to alter specifications without notice at any time.
For full warranty information, refer to the AMX Instruction Manual(s) associated with your Product(s).
The AMX logo is a trademark of AMX Corporation. AMX reserves the right to alter specifications without notice at any time.
3000 RESEARCH DRIVE, RICHARDSON, TX 75082 • 800.222.0193 • fax 469.624.7153 • technical support 800.932.6993 • www.amx.com
043-019-2246 6/04 ©2002 AMX Corporat ion. All rights reserved.
93-0606-13
REV: A
Loading...