AMX NXF-MINI User Manual

Installation Guide
Rear

Overview

The NXF-MINI NetLinx Mini CardFrame (FG2104) provides up to 4 expansion card slots that accept any combination of compatible NetLinx Control Cards (see Specifications table below).
front
rear
FIG. 1 NXF-MINI NetLinx Mini CardFrame
This unit is ideal for expansion or distributed systems needing additional IR, Relay, and Volume Control capabilities. Current features include:
• Flexibility and custom control options.
• Supports for up to four NetLinx Control Cards.
• Front access to all four card slots.
• Ease of use and installation.
Multiple MINIs can be connected using ICSNet Hubs.

Specifications

NXF-MINI Specifications
Dimensions (HWD): • 1.75" x 17.00" x 9.56" (4.45 cm x 43.18 cm x 24.28 cm)
•1 RU
Power: • 25 mA @ 12 VDC
Weight: • 6.20 lbs (2.81 kg)
Enclosure: • Metal with black matte finish
Front Panel: • NetLinx Control Card Slots 1- 4: Accept up to 4 compatible
Rear Panel: • CardFrame Number DIP Switch: Sets the starting address
Included Accessories:
Optional Accessories:
Note: The NXF-MINI requires a local 12 VDC Power Supply.
NetLinx Cards: such as the NXC-COM2, NXC-I/O10, etc.
• Rack-mount brackets: Provides an installation option for the NXF-MINI to be mounted into an equipment rack.
for the Control Cards in the CardFrame. The 8-position DIP switch address range is 1-3064. (Factory default
CardFrame DIP switch value = 0). The Control Card address range is 1-3064.
• NetLinx Control Card Connectors (1-4): Four 20-pin (male) connectors that bridge the gap between the Control Cards in the CardFrame and external equipment.
• ICSNet Connector: Single RJ-45 connector for ICSNet interface.
• Power Port: 2-pin 3.5 mm mini-Phoenix (male) connector.
• Removable rack ear set (62-2104-03). Allows for tabletop, under-counter, and front/rear rack mounting
• Quick Start Guide (93-2104)
• Three faceplate screws (80-0181)
• One 2-pin mini-Phoenix PWR connector (41-5025)
• Installation Kit (KA2104):
- 4 screws (#10-32 x 0.625)
- 4 washers (#10 Black Nylon)
• PSN6.5 power supply (FG423-41)
• Accepts up to 4 compatible NetLinx Control Cards: NXC-COM2 Dual COM Port Control Card (FG2022) NXC-I/O10 Input/Output Control Card (FG2021) NXC-IRS4 4-Port IR/S Control Card (FG2023) NXC-REL10 Relay Control Card (FG2020) NXC-VAI4 Analog Voltage Control Card (FG2025) NXC-VOL4 Volume Control Card (FG2024)
NXF-MINI NetLinx
®
Mini-CardFrame

Connections and Wiring

FIG. 2 shows the layout of the connectors and components on the rear of the NXF-MINI.
Rack ears
CARDFRAME #
ON
CardFrame DIP switch
SLOT 4
14171920 18 1615 10
1213 11 9 8 7 564231
SLOT 3
2019 18
1516 14 1213 11 978564 2021 171918 1516 14 10
17
Slot 1-4 connectors
SLOT 2
13310
1211 897 3564 12 20 1819 17 131516 14 1112 10
FIG. 2 Rear NXF-MINI connectors and components

Inserting NetLinx Cards into the NetLinx Control Card Slots

The optional NetLinx Cards can be installed horizontally into the NXF-MINI through the card slot openings on the front of the enclosure. To install a NetLinx Card:
1. Discharge the static electricity from your body by touching a grounded metal object and unplug all the connectors from the unit.
2. Remove the three (3) screws by turning them in a counter-clockwise direction and remove the front faceplate.
3. Align the edges of the card with the internal guide slots and gently slide the card all the way in until you feel the rear edge of the card lightly snap into place.
4. Re-secure the faceplate by inserting the three (3) screws by turning them in a clockwise direction and securing the front faceplate to the NXF-MINI.
5. Re-apply power and other connections as necessary.

Setting the MINI’s Control Card starting Card Address

The 8-position CardFrame Number DIP switch, located on the lower-left rear of the CardFrame, sets the starting address (the device number in the D:P:S specification) for the Control Cards installed in the unit.
The Control Card address range is 1-3064. The factory default CardFrame DIP switch value = 0 (All CardFrame DIP switches in the OFF position).
The formula for setting the starting address is:
(DIP switch value) + Card slot Number (1-4) = Card Address
For example:
For DIP switch setting, 00010101:
(0 + 0 + 0 + 96 + 0 + 384 + 1536) + SLOT #(ex:1) = 2017. A card in slot number 1 = device address 2018.
Set the CardFrame Number DIP switch based on the table below.
Position 12345678
Value 12 24 48 96 192 384 768 1536
Cycle power to the unit for approximately 5 seconds. This allows the unit to read the new device number settings.

Using the PSN NetLinx connector for power

To supply power from the local power supply to the rear 2-pin mini-Phoenix power jack; the incoming PWR and GND cables from the power supply must be connected to the corresponding location on the NXF-MINI 2-pin 3.5 mm mini­Phoenix connector (FIG. 3).
PWR +
GND -
To the NXF-MINI
(terminal end)
FIG. 3
NetLinx power connector wiring diagram
1. Insert the PWR and GND wires into the terminal end of the PSN 2-pin
3.5 mm mini-Phoenix cable.
2. Tighten the clamp to secure the two wires.
3. Verify the connection of the other end to the mini-Phoenix connector on the power supply.
NXF-MINI
SLOT 1
6897534 12
ICSNet
PWR
12VDC
ICSNet
PWR
ON position
12 VDC Power Supply
(PSN6.5)

ICSNet Connections/Wiring

This connector uses a standard CAT5 Ethernet cable to provide communication between the CardFrame and the NetLinx control system processor. The following table shows the signal and pinout information associated with the ICSNet connections.
ICSNet Signals and Pinouts
Pin Signal-Master Signal-Device
1TX + RX +
2TX - RX -
3N/A N/A
4GND GND
5N/A N/A
6N/A N/A
7 RX + TX +
8 RX - TX -
Note: ICSHub cable information is used when connecting an NXF-MINI (from the rear ICSNet connector) to an external Hub (ex: ICSHub connector port on an NXC-NH).

ICSHub Connections/Wiring

The following table shows the ICSHub pinout wiring, coloring, and functionality.
ICSHub Pinout Information (EIA/TIA 568 B)
Pin Wire Color Polarity Function
1 Orange/White + Transmit
2 Orange - Transmit
3 Green/White - -
4Blue - -
5White/Blue + -
6Green + -
7 White/Brown + Receive
8 Brown - Receive
1 2 3 4 5 6 7 8
TIA 568B
1 2 3 4 5 6 7 8
(female) (male)
RJ-45 connector - pin configurations
For full warranty information, refer to the AMX Instruction Manual(s) associated with your Product(s).
©2009 AMX. All rights reserved. AMX and the AMX logo are registered trademarks of AMX.
3000 RESEARCH DRIVE, RICHARDSON, TX 75082 • 800.222.0193 • fax 469.624.7153 • technical support 800.932.6993 • www.amx.com
AMX reserves the right to alter specifications without notice at any time.
1/09
93-2104 REV: B