Amtrol WX-401, WX-401C, WX-403, WX-403C, WX-404 Installation & Operation Instructions

...
WELL-X-TROL
®
COMMERCIAL PRE-PRESSURIZED WELL TANKS
INSTALLATION & OPERATION INSTRUCTIONS
Models WX-401(C) through WX-407(C)
Models WX-421 through WX-427
Models WX-447(C) through WX-463C
Models WX-35L(CL) through WX-600-L(CL)
NOTE: Inspect for shipping damage and notify freight carrier or store where purchased immediately if damage is present. To avoid risk of personal
injury and property damage, if the product appears to be malfunctioning or shows signs of corrosion, call a licensed professional immediately. Current copies of the Product manual can be viewed at www.amtrol.com. Use proper safety equipment when installing.
THIS IS THE SAFETY ALERT SYMBOL. IT IS USED TO ALERT YOU TO POTENTIAL PERSONAL INJURY AND OTHER HAZARDS. OBEY ALL SAFETY MESSAGES THAT FOLLOW THIS SYMBOL TO REDUCE THE RISK OF PERSONAL INJURY AS WELL AS PROPERTY DAMAGE.
READ CAREFULLY THE PRODUCT
INSTALLATION & OPERATION INSTRUCTIONS. FAILURE TO FOLLOW THE INSTRUCTIONS AND WARNINGS IN THE MANUAL MAY RESULT IN SERIOUS OR FATAL INJURY AND/OR PROPERTY DAMAGE, AND WILL VOID THE PRODUCT WARRANTY. THIS PRODUCT MUST BE INSTALLED BY A LICENSED PROFESSIONAL. FOLLOW ALL APPLICABLE LOCAL AND STATE CODES AND REGULATIONS, IN THE ABSENCE OF SUCH CODES, FOLLOW THE CURRENT EDITIONS OF THE NATIONAL PLUMBING CODE AND NATIONAL ELECTRIC CODE, AS APPLICABLE. EXPLOSION OR RUPTURE HAZARD. THE EXPANSION TANK MUST BE OPERATED SO THAT THE PRESSURE DOES NOT EXCEED THE MAXIMUM WORKING PRESSURE.
EXPLOSION HAZARD. Failure to follow the
instructions in the accompanying product manual can cause a rupture or explosion; possibly causing serious or fatal injury, leaking or flooding and/or property damage.
Use only with potable water system. Do not
operate in a setting with freezing temperatures or where the temperature can exceed 200°F and do not exceed the maximum working pressure specified for this Product in the Manual. Mount vertically only.
Chlorine & Aggressive Water: The water quality
can significantly influence the life of this Product. You should test for corrosive elements, acidity, total solids and other relevant contaminants, including chlorine and treat your water appropriately to insure satisfactory performance and prevent premature failure.
explode, causing serious or fatal injury, leaking or flooding and/or property damage. To minimize risk, a licensed professional must install and periodically inspect and service the Product. A drip pan connected to an adequate drain must be installed if leaking or flooding could cause property damage. Do not locate in an area where leakage of the tank or connections could cause property damage to the area adjacent to the appliance or to lower floors of the structure.
excess of local code requirement or maximum working pressure designated in the Product Manual, whichever is less. Do not expose Product to freezing temperatures or temperatures in excess of 200° F. Do not adjust the pre-charge or re-pressure this Product except for any adjustments required at the time of initial installation, especially if Product corroded, damaged or with diminished integrity. Adjustments to pre­charge must be done at ambient temperature only. Failure to properly size the Product or follow these instructions may result in excessive strain on the system lead to Product failure, serious or fatal personal injury, leakage and/or property damage.
cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
This Product, like most Products under pressure, may over time corrode. weaken and burst or
EXPLOSION OR RUPTURE HAZARD A relief valve must be installed to prevent pressure in
This product can expose you to chemicals including lead, which is known to the State of California to
PLEASE READ THE FOLLOWING INSTRUCTIONS CAREFULLY
IMPORTANT GENERAL SAFETY INFORMATION -
ADDITIONAL SPECIFIC SAFETY ALERTS APPEAR IN THE FOLLOWING INSTRUCTIONS.
DANGER! EXPLOSION HAZARD. WHEN THE
CHANGE TO A HIGHER PRE-CHARGE PRESSURE IS NECESSARY DUE TO A REQUIRED CHANGE IN THE PRESSURE SWITCH SETTING, FAILURE TO FOLLOW INSTRUCTIONS BELOW CAN CAUSE A RUPTURE OR EXPLOSION, POSSIBLY CAUSING SERIOUS OR FATAL PERSONAL INJURY, AND/OR PROPERTY DAMAGE.
 •DO NOT ADJUST OR ADD PRESSURE IF THERE HAS BEEN A
LOSS OF AIR.
 •DO NOT ADJUST THE PRE-CHARGE PRESSURE IF THERE IS
VISIBLE EXTERIOR CORROSION.
 •DONOT ADJUST THE PRE-CHARGE PRESSURE IF THERE HAS
BEEN A REDUCTION OF THE PUMP CYCLE TIME OR THE PRE­CHARGE PRESSURE COMPARED TO ITS INITIAL SETTING. THIS IS BECAUSE REDUCTION IN PUMP CYCLE TIME CAN RESULT FROM LOSS OF TANK AIR PRESSURE WHICH IN TURN CAN MEAN THERE MAY BE INTERNAL CORROSION AND ANY RE-PRESSURIZATION OR ADDITIONAL PRESSURE COULD RESULT IN RUPTURE OR EXPLOSION.
pressure for the Well-X-Trol line. Should pressures exceed 125 psig, proper selection and sizing of an ASME constructed Well-X-Trol should be made.
pressures (75 psig or more). This will protect the Well-X-Trol and other system components should the pressure switch malfunction and fail to shut the pump off. The relief valve should be installed at the connection of the Well-X-Trol to the system piping and have a discharge equal to the pump’s capacity at 75 psig.
YOUR WELL TANK, ESPECIALLY DURING TIMES OF NON-USE. CONSULT YOUR LOCAL PLUMBING OFFICIAL REGARDING ANY STEPS YOU MAY WISH TO TAKE TO SAFELY DISINFECT YOUR HOME’S PLUMBING SYSTEM.
WELL TANK HAS BEEN IN SERVICE AND A
MAXIMUM WORKING PRESSURES. Every Well-X-Trol is
air tested to 125 psig, the maximum working
RELIEF VALVE REQUIRED. A relief valve should be installed which is set to open at excessive
AS IN ALL PLUMBING PRODUCTS AND WATER STORAGE VESSELS, BACTERIA CAN GROW IN
A water test must be taken before installation of any water treatment equipment.
DANGER! EXPLOSION HAZARD. IF YOU
ADJUST THE PRE-CHARGE PRESSURE OR ADD PRESSURE TO A TANK THAT IS CORRODED OR DAMAGED OR WITH DIMINISHED INTEGRITY THE TANK CAN BURST OR EXPLODE, POSSIBLY CAUSING SERIOUS OR FATAL PERSONAL INJURY AND/ OR PROPERTY DAMAGE.
 •ONLY ADJUST THE PRE-CHARGE AS DESCRIBED IN THIS
MANUAL WHEN THE TANK IS NEW OR WHEN THE INTEGRITY OF THE TANK AND LACK OF INTERNAL OR EXTERNAL CORROSION IS CONFIRMED.
 •ONLYLICENSEDPROFESSIONALSSHOULDCHECK,ADJUSTOR
RE-CHARGE THE PRE-CHARGE OF TANKS.
For your safety, the information in this manual must
be followed to minimize the risk of electric shock, property damage or personal injury.
•Properlygroundtoconformwithallgoverningcodesandordinances.
Do not install in direct sunlight. Excessive sun heat
may cause distortion or other damage to non­metallic parts.
Use only lead-free solder and flux for all sweat-solder
connections, as required by state and federal codes.
Maximum allowable inlet water pressure is 125 psig.
If daytime pressure is over 80 psig, nighttime pressure may exceed the maximum. Use a pressure-reducing valve to reduce the flow if necessary.
ELECTROCUTION AND EXPLOSION HAZARD.
before work is performed on the tank, turn off the power to the pump and release all water pressure in the tank and pumping system.
Pre-Installation
Proper WELL-X-TROL® Location
The surface which supports the Well-X-Trol should be capable of supporting its operating weight (including the weight of water).
The Well-X-Trol should be installed as close as possible to the pressure switch. This will reduce the adverse effects of added friction loss and differences in elevation between Well-X-Trol and/ or water supply main and switch.
1. Adjacent to pump. This is the location chosen most often. The
Well-X-Trol tank can be used whether pumps are above or below the surface. In either case, it protects the pump by reducing surge, dampening pressure spikes, offering a point of pressure control, and providing minimum run time. This location also permits all equipment to be placed in an area that’s both serviceable and secure.
2. At the end of long pipe runs. Sometimes it’s better to put the
Well-X-Trol tank at the end of a long run of pipe so it can provide rapid system response and adequate protection. When this location is chosen, the pressure switch should either be relocated with the Well-X-Trol tank or the setting should be adjusted to compensate for any line pressure drop.
3. Adjacent to shock creating components. If you want to use the
Well-X-Trol tank to control shock or pressure fluctuations, then you should locate the tank as close to the cause as possible. This should be done when and where you have back flow preventors, check valves, solenoid, mixing and meter valves, pumps and other system controls which can contribute to system shock.
Do not use for shock with flow velocities greater than 10 FPS.
DO NOT LOCATE IN AN AREA WHERE
LEAKAGE OF THE TANK OR CONNECTIONS
COULD CAUSE PROPERTY DAMAGE TO THE AREA ADJACENT TO THE APPLIANCE OR TO LOWER FLOORS.
System Connection
The connecting pipe between the Well-X-Trol tank and the system should be as short as possible with a minimum of bends. It should also be as large in diameter as possible, consistent with system piping. You should never bush down from the Well-X-Trol tank (Figure A).
Figure A