AMS Quick Start Guide: ValveLink Mobile | AMS, Quick Start Guide: ValveLink Mobile Manuals & Guides

Quick Start Guide
D103408X012
ValveLink™ Mobile Software
ValveLink Mobile Software Version 6.1
January 2020
ValveLink Mobile software lets you configure, calibrate, and troubleshoot FIELDVUE™ DVC6200, DVC6200f, DVC2000, DVC6000, and DVC6000f digital valve controllers using Emerson's AMS Trex
, ValveLink DTM, or ValveLink PLUG-IN for PRM® applications to be
analyzed and archived.
Hardware Requirements
The HART® or FOUNDATION™ Fieldbus communicator needs to be licensed for ValveLink Mobile software and licensed for HART of Fieldbus communications.
AMS Trex Device Communicator
475 Field Communicator
Note: 475 Field Communicators are no longer available for sale and software updates will not be supported after October 2020.
Upgrade studio is required to be installed to use the Trex communicator file transfer utility to create export files, which can be imported into ValveLink software.
Easy Upgrade option and System Software Version 3.8 are required to install ValveLink Mobile 6.1. Requires Bluetooth transfer data files. To transfer data files using Bluetooth, the Field Communicator must be ordered with the Bluetooth option. Both HART and F
OUNDATION™ fieldbus communications are supported.
®
or an IrDA® interface on the PC to
www.Fisher.com
ValveLink Mobile Software Version 6.1
January 2020
Quick Start Guide
D103408X012
AMS Trex Device Communicator
Installation
AMS Trex Device Communicator
ValveLink Mobile is automatically installed and unlocked when the device is registered and ValveLink Mobile is licensed.
Field Communicator
ValveLink Mobile 6.1 on Field Communicators v 3.8 or 3.9 must be updated using the Card Updater Utility found in Easy Upgrade for the 475
Field Communicator (available at Emerson Handheld Communicators Support).
Connecting to the Digital Valve Controller
The Trex communicator or Field Communicator may be connected to the loop wiring or directly
475 Field Communicator
to the digital valve controller. To connect directly to the digital valve controller, attach the clipon wires to the Loop + and  terminals located in the digital valve controller terminal box.
Launching ValveLink Mobile Software
Select the ValveLink Mobile icon from the main menu to launch the software. Select HART or F
OUNDATION Fieldbus communications to start a
session.
Establishing a Connection
With ValveLink Mobile software, you can navigate through the menu structure without being connected to a device. This can be used to explore the menu structure, review diagnostic data, or transfer diagnostic data files to a PC while offline.
2
Quick Start Guide
D103408X012
ValveLink Mobile Software Version 6.1
January 2020
Y
B
Home Screen
Select the Fieldbus or HART Connect icon from the home screen to communicate with a field instrument.
Navigation Tips
List controls are scrolled with grab‐and‐drag input as shown in the list control navigation screen shot.
Once you find a variable that you want to change, you can hit the selection button (>). The selection button may not be visible if you are not connected to a device. Parameters that cannot be changed will have a symbol next to the selection button. This will usually happen when the instrument mode is In Service for HART devices or AUTO for fieldbus devices.
List Control Navigation
The command bar located at the bottom of the screen has two soft keys. The left Done soft key is used to go back one screen. The right soft key displays instrument mode (In Service, Out of Service, or Not Connected for HART devices; AUTO, MAN, OOS, or Not Connected for fieldbus devices). Select this key to change the instrument mode.
Most tasks will display a green highlighted bar to indicate that the task has completed successfully. For offline diagnostic tests, wait for the green Completed highlight to appear on the graph before moving on to the next task.
Graph Controls
Graphs are displayed in real time or statically after a test has completed. Graph areas can be zoomed in by dragging a selection rectangle around the desired region of interest. Axes can be translated by grabbing the scale and sliding it to the desired position. Zooming and translation are shown in the figure below. To return back to the default view, tap the graph.
3
ValveLink Mobile Software Version 6.1
January 2020
Zoom
Y
Translate
B
Quick Start Guide
D103408X012
B
Graph Zoom and Translate Controls
Y
When graphs are being drawn in real time, you can zoom in on the data or translate the axes. When this occurs, updates to the display will be paused but data will continue to be collected in the background. Tap the graph to restart the real time display.
Crosshairs can be displayed by selecting the directional pad (up, down, left, right arrows) “Enter” or Checkmark key until the crosshairs appear. Crosshairs can be moved by grabbing and dragging any point on the screen. XY coordinates are displayed in the lower right corner. To clear the crosshairs, press the directional pad “Enter” or Checkmark key again.
Graph Crosshairs and Coordinates
PD graphs can display up to four variables on two graphs. The second graph can be viewed by grabbing a graph anywhere except the yaxis scale and sliding the display up or down. Alternatively, graphs can be moved by pressing the up or down directional pad arrow keys.
4
PD Real Time Graphs
Quick Start Guide
D103408X012
ValveLink Mobile File Transfer on AMS Trex Device Communicator
Connect your Trex communicator to the PC you wish to export the files to with the USB connection.
Note
Ensure ValveLink Mobile software is closed and will not be accessed for the entirety of this transfer.
Navigate to Trex File Transfer Utility on the PC.
ValveLink Mobile Software Version 6.1
January 2020
Transfer ValveLink Mobile Dataset
Note
Upgrade Studio must be installed from the Trex installation CD before you can tranfer files from the Trex.
Click the Transfer button next to ValveLink Mobile Dataset.
These .exp files can then be individually imported in to ValveLink software.
Note
This process does not delete the files from the Trex communicator. Files must be deleted from the ValveLink Mobile application, at Utilities > Data Set Explorer.
5