Amprobe AF-600 Specifications

AF-600 A-Frame
Ground Fault Locator
Save time and money by pinpointing leakage points
Ground faults are a common problem with electrical cables. Find any fault with the AF-600 A-Frame cable ground fault locator, specically designed for use with the Amprobe UAT-600 Series.
Set up the UAT-600-T Transmitter to apply a fault nd signal to the utility under test, the AF-600 A-Frame receives the signal and locates the place of the fault. The AF-600 will pinpoint where a cable metal conductor (either a sheath or a metallic conductor of the wire) touches the ground and can also detect other conductors to ground faults such as pipeline coating defects.
AF-600-A-Frame
Ground Fault Locator
LCD Display with auto backlight
amprobe.com
Features and Highlights Specifications
• Identify any point of leakage around a cable
• Locate cable and wire ground faults, sheath
faults or pipeline coating defects, where the utility is in direct contact with the ground
• Find the exact point where metal is touching the ground and power is leaking, ie, a shield is rusted or a rubber buffer is broken, creating noise on a cable
• Advanced technology and digital signal processing makes pinpointing process fast,
accurate and clear:
- Compass guidance with numeric fault eld strength indicates the direction of the fault
- Distance sensitive left and right arrows guides the user to precisely follow the path of the buried utility
- Automatic gain control quickly detects tracing signal and precisely adjusts the A-Frame sensitivity
- Adjustable volume controls
Tracing mode (de-energized) 8 kHz Locating mode Ground fault locating
Sensitivity (typical)
Display backlight Automatic Audio indication Speaker indicates left/right by pulsed/continuous tone Compatible transmitter UAT-600-T Transmitter Display 1.28 in, 128 x 128 BW outdoor LCD display with auto backlight Update rate Instantaneous Operating temperature and humidity -4 °F to 122 °F (-20 °C to 50 °C), 90% RH Storage temperature and humidity -40 °F to 140 °F (-40 °C to 60 °C), 90% RH Operating altitude < 6561 ft (< 2000 m) Pollution degree 2 Water and dust resistance IP54 Drop proof 3.28 ft (1 m) Power supply (6) 1.5 V AA alkaline batteries Auto power off 15 minutes idle Battery life Approx. 60 hours at 70 °F (21 °C) (Typical)
Certications
Safety compliance IEC 61010-1, CSA/UL 61010-1 Size (H x W x L) Approx. 14 x 9 x 4.7 in (355 x 230 x 120 mm) Weight Approx. 4.2 lb (1.9 kg) (batteries installed)
AF-600 A-Frame includes: A-Frame Receiver, (6) 1.5 V AA (IEC LR6) Batteries, Carrying Case, User Manual
AF-600 A-Frame
Cable locate mode at 1 meter depth: 10 uA
Fault locate mode: up to 2 MΩ fault
The AF-600 comes complete with batteries and a carrying case
Clearly view the LCD display in bright sunlight Pinpoint fault location by using the AF-600
with the UAT-600 Transmitter
©2018 Amprobe® For detailed specications and ordering go to amprobe.com 6011240 AAmprobe® | info@amprobe.com | Fluke Corporation, Everett, WA 98203 | Tel: 877-AMPROBE (267-7623)
Loading...