Amprobe ACDC-3400-IND Specifications

Data Sheet
1000V
600V
ACDC-3400 IND
CAT IV Industrial True RMS Clamp Meter
This CAT IV rated clamp is ideal for industrial applications and utilities that require an extra level of safety. Includes True RMS sensing for accuracy and dependability. Extra large jaw to accommodate wide diameter wires.
True RMS
Measures AC Current up to 1000 ACA, Voltage up to 750 VAC / 1000 VDC, Frequency, Resistance and Capacitance and Duty Cycle
Peak Hold
1000A DC Current
No hassle warranty
No waiting.
No shipping charges.
(note: $500 MSLP limit)
Relative Zero
Audible continuity
Auto and manual ranging
Auto power off
Data hold
Backlight
Diode Test
Duty Cycle
Accommodates conductors up to 2” (51mm) in diameter
Safety CAT IV 600 V, CAT III 1000 V
Test leads, battery (installed), Users Manual, and Carrying Case included with the product
Amprobe® Test Tools
www.Amprobe.com
ACDC-3400 IND CAT IV Industrial True RMS Clamp Meter
Specifications (valid for 23 °C ± 5 °C, for less than 75% relative humidity).
DC Volts Ranges Accuracy
660.0 mV, 6.600 V, 66.00 V, 660.0 V, 1000 V ± (0.5% rdg + 2 dgts) Input impedance 660 mV: >100 MΩ; 6.6 V:10 MΩ; 66 V to 1000 V: 9.1 MΩ Overload protection 1000 VDC or 750 VAC rms
AC Volts True RMS Ranges Frequency Accuracy
660.0 mV 50 to 100 Hz ± (1.5% rdg + 8 dgts)
6.600V, 66.00V 50 to 500 Hz ± (1.5% rdg + 8 dgts)
660.0V, 750V 50 to 500 Hz ± (1.5% rdg + 8 dgts) Frequency* 50 to 1 kHz ± (0.1% rdg + 5 dgts)
* Frequency: 10% to 100% of voltage range
Peak Hold Ranges Frequency Accuracy
66.00V, 660.0V, 750V 50 to 500 Hz ± (3.0% rdg + 300 dgts)
AC coupled TRMS 5% to 100% of range
Crest factor 3 Input impedance 660 mV: >100 MΩ; 6.6 V:10 MΩ; 66 V to 750 V: 9.1 MΩ Overload protection 1000 VDC or 750 VAC rms
AC Current True RMS Ranges Frequency Accuracy
660.0A 50 to 60 Hz ± (2.0% rdg + 10 dgts)
660.0A 61 to 400 Hz ± (3.0% rdg + 10 dgts) 1000 A 50 to 60 Hz ± (2.5% rdg + 10 dgts) 1000 A 61 to 400 Hz ± (3.5% rdg + 10 dgts) Frequency* 50 to 1kHz ± (0.1% rdg + 5 dgts) * Frequency: 10% to 100% of current range
Data Sheet
Peak Hold Ranges Frequency Accuracy
660.0A, 1000A 50 to 400 Hz ± (3.0% rdg + 200 dgts) AC coupled TRMS 5% to 100% of range Crest factor 3 Overload protection 1000A AC
DC Current Range Accuracy
660.0A ± (2.0% rdg + 5 dgts) 1000A ± (3.0% rdg + 5 dgts) Overload protection 1000A DC
Resistance Range Accuracy
660.0Ω, 6.600kΩ, 66.00kΩ, 660.0kΩ ± (1.0% rdg + 5 dgts)
6.600MΩ ± (2.0% rdg + 5 dgts)
66.00MΩ ± (3.5% rdg + 5 dgts)
Open circuit volts -0.8 Vdc typical , (-1.2 Vdc on 660 Ω range) Overload protection 1000 VDC or 750 VAC rms