Amperite HDOD Series Delay-On-Dropout Time Delay Relay Data Sheet

HDOD Series Delay-On-Dropout Time Delay Relay
TIMING DIAGRAM:
CONTACT INFORMATION
(Resistive);
ENVIRONMENTAL INFORMATION
True delay on dropout: Timing cycle after power removal DPDT (2 form C) isolated 4 ampere relay contacts Built-in timing adjust potentiometer Numerous models from 0.1 seconds to hours
Timing Mode
Upon the application of input voltage the relay immediately energizes. The timing cycle begins when input voltage is removed. When the timing cycle is complete, the relay will de-energize
Arrangement: 2 form C (DPDT) Contact material: Gold Clad Silver Alloy Rating: Maximum Switching Power - 1000 VA, 90W
Maximum Switching Voltage - 250V AC, 48V DC Maximum Switching Current - 4 Amperes Nominal Switching Capacity - 4A 250V AC, 3A 30V DC UL/CSA Rating - 4 A 1/20 HP 125, 250V AC, 3A 30V DC
Expected Life @ 25°C
Mechanical: 100 Million operations Electrical 100,000 operation at 4A 250V AC 200,000 operations at 3A 30V DC
temperature Range: Ambient: - 40°C to 65°C (-40° to +149°F)
OUTLINE DIMENSIONS
Timing Specifications
Fixed timing: 0.1 seconds to hour, tolerance 5%
MECHANICAL INFORMATION
consult factory for availability. Adjustable Timing Ranges: .1 to 1 sec; 1 to 10 sec; 10 to 100 sec; 1 to 10 min; 10 to 100 min. Availability of long delay time depends upon voltage; consult factory for details.
INITIAL DIELECTRIC STRENGTH:
Between open contacts: 750V RMS Between adjacent contacts: 1000V RMS Between contacts & coil: 1500V RMS
INPUT INFORMATION
Voltage: 12, 24, 48, 120 volts AC or DC Custom voltages are available Power requirements: 2 VA or Watts Transient: protection: 1 Joule MOV Polarity protection DC units
INPUT VOLTAGES & LIMITS:
Nominal Minimum Maximum 10V 11V 15V 24V 20V 28V 48V 20V 28V 110V 41V 55V 120V 95V 125V
WRING DIAGRAM
Termination: 1/4 inch quick-connect male terminals Enclosure: 21/2 by 3/4 inch, epoxy sealed Single 1/4 inch hole flat panel mounting.
Ordering Information
Definition of a part number for the Amperite
HDOD Series Time Delay Relay Example:
A: Denotes nominal input voltage. Voltages: 12, 24 and120V AC;
12, 24, 48, and 110V DC. B: Denotes type of input power: A = AC, D = DC C & D: Denotes timing range if knob adjustability. See Standard ranges.
For fixed units specify a single number. Costume timing available. E: Denotes unit of time delay: S = seconds; M = minutes
H = hours F: Denotes Amperite HDOD Series DPDT 4 ampere
delay-on-dropout TDR.
Loading...