Amperite CI Series TDR Data Sheet

Page 1
CI Series
… Solid state analog circuitry
TDR
Timing Mode:
Relay contacts transfer and timing cycle begins, upon application of power. At the end of the timing cycle, the relay contacts return to the De-Energized position. Reset occurs upon removal of the input power.
… One-shot timing mode (interval on) … DPDT (2 form C) isolated 10 ampere relay contacts … Timing selection: Knob adjustable or Fixed … Numerous models timing from 0.1 secs. to 480 secs. … UL File #E96739 (M) … CSA File #LR62586-3
Timing Diagram:
Contact Information:
Arrangement: 2 form C (DPDT) - Diagrams C & D Contact Material: Silver - Cadmium Oxide Rating (Resistive): 10A @ 240V AC Resistive 15A @ 30V DC Resistive 15A @ 120V AC Resistive 1/3 HP @ 120V AC 1/2 HP @ 250V AC Expected Life @ 25°C: 10 Million operations, Mechanical 100,000 operations minimum at rated loads
Page 2
Environmental Information: Temperature Range: Storage: -60°C to +105°C (-76°F to +221°F) Operating: 45°C to +70C (-49°F to +158°F)
Mechanical Information: Termination: 8 Pin Octal Style Plug or 11-Pin Spade Terminal (Dia. C&D) Enclosure: White plastic case. Knob adjustable models have a dial scale for reference only "LCI" version has a black case. Weight: 4 oz (114g) approx.
Outline Dimensions:
Timing Specifications:
Timing - Fixed: 0.1 through 480 secs. Timing Ranges: 0.1 - 60, 60 - 120, 120 - 180, 180 - 240, 240 - 300, 300 - 480 secs. Custom timing is available. Timing Adjustment: Knob adjustable potentiometer. Timing Tolerance: Fixed Units: ±5% Adjustable Units: -0 to +25% of maximum specified delay time. Minimum specified value or less at low end. Repeatability: ±5% Release Time: 60 ms typical, 100 ms maximum.
Initial Dielectric Strength: Between open contacts: 1000V RMS, between adjacent contacts: 1500V RMS, Between contacts & coil: 1500 RMS.
Input Information: Voltage: AC units- 12V, 24V, and l20V DC units- 12V, 24V, 48V & 110V. Other voltages are available.
Page 3
Power Requirement: AC units: 3 VA or less, DC units: 3 Watts or less. Transient Protection: 1 JOULE MOV. Polarity Protection: On DC units - Yes.
Input Voltages & Limits:
Nominal Minimum
Maximum
12V AC 10V 14V
24V AC 20V 28V
120V AC
105V 130V
12V DC 11V 14V
24V DC 20V 32V
48V DC 41V 55V
110V DC
55V 125V
Wiring Diagrams:
Ordering Information:
Definition of a part number for the Amperite CI Series Time Delay Relay. Example:
A: Denotes nominal input voltage. Voltages available: 12, 24, & 120V AC; 12, 24, 48 & 110V DC. Custom voltages are available. B: Denotes type of input current required for operation. A=AC - Alternating current;
Page 4
D=DC - Direct current.
C: Denotes contact form: P= DPDT - 2 form C. D & E: Denotes range of knob adjustability for timing (in seconds) where:
D= Minimum time delay. E= Maximum time delay for adjustable TDR'S. Note: 1.) Ranges available: 0.1 - 60, 60 - 120, 120 - 180, 180 - 240, 240 - 300 & 300 ­480 secs. Custom Timing is available.
2.) Both values (D & E) can be replaced by a single value for a factory preset time delay in seconds from 0.1 through 480 secs.
F: Enter "L" if optional 11-pin spade terminals are required (Dia. B &D). G: Denotes use of solid state analog circuitry of CI Series.
Solving Your Relay Requirements Since 1922