Meaning
Default Value
Fan speed at high speed in cooling
Fan speed at medium speed in cooling
Fan speed at low speed in cooling
Fan speed at high speed in heating
Fan speed at medium speed in heating
Fan speed at low speed in heating
Fan speed at super low speed in heating
Motorized water valve
Memory function
Setting Range
450-2000
450-2000
450-2000
450-2000
450-2000
450-2000
450-2000
1400
1200
1000
1250
1000
750
550
1
2
3
4
5
6
7
8
9
Parameter
Due to the limitation of the display,we will use two digits and
symbol of “℃” to show fan speed.
for example ,13 sta nds for 1300rpm,while 13℃ Stands 1350 rpm.
0:Without water valve
1:Wit h w ate r v alve
0:Without memory function
1:With memory function
1
1
Failuer code
Description Solution
E0
E1
E2
E3
E4
PCB and wired controller can't
communication properly
air inlet temperature sensor fails
inlet water temperature sensor fails,
limitation for water inlet temperature
stops
fan motor fails or fan motor cable not
well connecte
d
air outlet temperature sensor fails
Check if the cable between PC B
and wired controller gets loose,
if yes, fasten it.If not,change
PCB or wired controller.
Check if the sensor cable gets
loose, if so, fasten it. if not,
change the sensor
Check if the fan motor cable gets
loose, if so, fasten it, if not,
change the motor.
Check if the sensor cable gets
loose, if so, fasten it. if not,
change the sensor
Check if the sensor cable gets
loose, if so, fasten it. if not,
change the sensor