Amico Valve Alarm Combo Unit User Manual

Page 1
Installation and Maintenance Manual
www.amico.com
Alarm Valve Combo Unit Alert-1 v1.3
Page 2
Table of Contents
User Responsibility 4
Introduction 5
Features 5
Installation of Valve Boxes 6
Description of Modules 8
Common to All Alarms 8
System Power Supply 8 Annunciator Module 8 Alarm Valve Display Module 8 Sensor Module 8
Installation of Alarm 9-10
Local Sensor Only 9 Standing Pressure Test 9 Frame/Module Assembly 9 Sensor 10
Local 10 Remote 10
Wiring 11
System Power Supply 11 Annunciator Module 11 Sensor Module 11
Local 11 Remote 11
Annunciator Module 12
Noise Level Control 12 Control of Remote Alarm Buzzer 12
2 Amico Pipeline
Page 3
Table of Contents
The Display Module 13-16
Pressure Only 13
HIGH/LOW Alarm Set Point Adjustments 13 PSI/KPA/BAR selection 14
Vacuum Only 14
LOW Vacuum Alarm Set Point Adjustment 14 InchHg/KPA/BAR selections 15
Common Settings for Pressure and Vacuum 15
Repeat Alarm Enable/Disable 15 Setting Factory Default 15 Setting Gas Identication Switches 16 Chart of Gas Specic Settings of Dip-Switches 16
Troubleshooting Guide 17-19
Table of Error Codes 17-19 Error Code Messages on the Display Module 19
Model Numbers 20-21
Spare Parts Numbers 22-23
Dimensions 24-25
Appendix A - Wiring Diagram - Auto-Switching Power Supply 26 Appendix B - Wiring Diagram - Annunciator 27 Appendix C - Wiring Diagram - Alarm Valve Combo Unit 28 Appendix D - Wiring Diagram - Remote Alarm Valve Combo Unit 29 Appendix E - Wiring Diagram - Alarm Valve Combo Unit to Master Module 30 Appendix F - Technical Specications 31
www.amico.com 3
Page 4
User Responsibility
WARNING, CAUTION,
NOTE are of special significance. Please read these sections
WARNING: denotes steps which can prevent injury.
CAUTION: denotes steps which can prevent damage to equipment.
DANGER: denotes steps which can prevent electrical shock to equipment
or to prevent serious injury and/or death.
The information contained in this Installation and Operation Maintenance Manual pertains only to the Alarm Valve Combo Unit. This product will perform to conformity as described in this manual when assembled, operated, maintained and serviced in accordance with the installation instructions provided.
The Alarm Valve Combo Unit must be checked periodically. Parts that are broken, missing, worn, distorted or contaminated must be replaced immediately. Should such repair or replacement become necessary, please contact Amico Corporation or their distributors.
All alarms should not be repaired or altered without prior written or verbal approval of Amico Corporation or its distributors. Failure to comply will void all warranty on the alarm.
Statements in this manual preceded by the words WARNING, CAUTION, DANGER and NOTE are of special signicance. Please read these sections carefully.
WARNING: denotes steps which can prevent injury.
CAUTION: denotes steps which can prevent damage to equipment.
DANGER: denotes steps which can prevent electrical shock to
equipment or prevent serious injury and/or death.
4 Amico Pipeline
Page 5
Introduction
The Alarm Valve Combo Unit is a 2 in 1 design, which combines the Area Alarm and Zone Valve Box, to compensate for space restrictions.
Amico Shuto Valves are used to stop the ow of medical gas or vacuum in the medical gas distribution pipeline in cases of emergency or maintenance.
Valve Boxes must be installed to enclose the shuto valves when the valves are located in areas accessible to unauthorized personnel.
The Amico medical gas Alarm Valve Combo Unit incorporates the latest microprocessor technology for alarm and surveillance systems. The alarm has been designed to provide user exibility and reliability. This manual will enable the customer to install, use and maintain the alarm properly.
All gases or vacuum are displayed with large red LED’s for clear visibility. To facilitate the monitoring function by hospital personnel, a trend bar is provided to show the direction of the gas/vacuum pressure. Under normal operation, the gas trend indicator will be in the GREEN - OK position. If the gas pressure approaches alarm condition, the trend indicator will display a RED - Caution indicator. If an alarm condition occurs, the buzzer will sound.
Features
• Individual microprocessor on each display and sensor module.
• Gas specic sensors can be mounted locally or remotely, up to 2,500 feet (750 m), utilizing 22 gauge shielded twisted pair (2 shielded wires).
• The DISS gas specic sensor is housed in a tamper-proof enclosure. The Sensor Module is housed in an anodized aluminum and nickle-plated brass enclosure to act as an interference barrier.
• The Sensor Module is the smallest, computer-calibrated and temperature-compensated sensor in the industry.
• True digital LED display and trend indicator for each service monitored.
• Illuminated LED display that is visible at an angle or in dim lighting conditions.
• PSI, kPa or BAR display (switch selected).
• Self-diagnostic circuitry with error display for problem identication.
• Highly accurate solid state pressure piezoresistive transducer.
• Adjustable repeat alarm (1 to 60 minutes or o).
• Dry contacts for remote monitoring of High and Low alarm status.
• Modules are factory mounted on a hinged frame assembly for ease of installation and maintenance.
• Field programmable push buttons for adjustment of HI and LOW set-points on display module.
• Available in 1 to 7 display modules.
• Built-in relay for remote annunciator applications.
www.amico.com 5
Page 6
Installation of Alarm Valve Combo Unit Boxes
The Amico Valve Combo Unit is shipped in one container holding two separate packages. One package contains the Alarm Valve Combo. The other package contains the window and the frame assembly.
1. Recessed Valve Box: anchor the valve box rough-in to the studs so that the front edge will be ush or slightly recessed with the nished wall. The recommended mounting is 66" (1676 mm) from the top of the valve box to the nished oor.
NOTE: The Shuto Valve handles should be installed to point downstream for pressurized gases.
2. Before brazing, remove all box plugs as they could melt during brazing. Wrap wet rags around the tube extensions next to the valves to prevent overheating and possible damage to the valve seals. Connect copper tubing to the valve extensions (outside the valve box) using brazing methods and materials in accordance with NFPA-99 or CSA Z7396.1-06. Once valve extensions are cool, remove rags.
3. Test the system (per appropriate standards) to ensure that the intended gas and vacuum services are connected to the appropriate lines.
WARNING: Misconnection of the gases could lead to serious or fatal injury to patients. Following the initial installation of shuto valves, make certain that the intended services are correctly connected to the appropriate service lines.
4. Test the system for leaks (per appropriate standards)
NOTE: Pipe sealants should comply with the requirements of NFPA 99 or CSA Z7396.1-06. Use care to exclude pipe sealants from the valve cavity and from interior tube surfaces exposed to medical gas ow or vacuum service. Properly applied Teon tape is an alternative to pipe sealants. Check Shuto Valve handle operation for proper clearance from gauge (if installed).
5. After the wall is nished, remove the window by pulling the ring towards you and attach the aluminum frame to the alarm valve combo unit valve box with the No. 6 metal screws provided. Then put the window back in place.
6 Amico Pipeline
Page 7
Maintenance
Operate shuto valves periodically and repair them, if seals tend to stick or leak. Notify all concerned personnel before shutting o any gas supply.
WARNING: To protect the lives of patients, always notify the appropriate medical facility sta before shutting o the supply of medical gas or vacuum through a shuto valve. Do not close shuto valves except in cases of emergency or maintenance.
Clean the exterior of the valve boxes routinely with soap and water. Strong solvents may damage the Lexan window.
Authorized hospital personnel should close shuto valves in the event of re, explosion or damage to the pipeline systems or equipment.
In Alarm Valve Combo Unit boxes, the Shuto Valve handles become accessible after the window has been removed from the valve box.
To remove the window, grasp the ring and pull outwards. Turn valve handle towards you to shut o the ow of gas or vacuum.
Zone Valves have a swingout design body which makes changing the internal components of the ball valve easier.
All valve bodies can be accessed by loosening all bolts and nuts and removing only one bolt, at this point the valve body can be swung out for servicing.
www.amico.com 7
Page 8
Description of Modules: Common to All Alarms
System Power Supply
The System Power Supply has been pre-installed into the back box assembly. The System Power Supply converts the AC voltage supply to the alarm into two voltages: 5 VDC (regulated) required by the microprocessor hardware and 15 VDC (unregulated) required by the buzzer and the LED’s. This unit also contains the main ON/OFF power switch, the transformer, the heat sink, the main fuse and fuse cover, the rectifying circuitry, the terminal blocks and the low voltage DC power cable for connecting this unit to the annunciator module. The System Power Supply can be easily removed and reinstalled by unscrewing it from the back box.
Annunciator Module
The Annunciator Module contains the buzzer, a “Power On” LED as well as the “TEST” and “ALARM MUTE” buttons. The function of the “TEST” button is to verify that the buzzer and all the LED’s are in working condition. An alarm will be heard when this button is pushed and all the LED’s will light up. When the button is released, the alarm will silence. The “ALARM MUTE” button is used to silence an alarm that has occurred. This module also contains a fail-safe relay that de-energizes when the buzzer is activated. This relay can be used with the Amico remote buzzer, for applications requiring a remote audible alarm (see Appendix B), for connection to another Amico alarm or a building management system.
Alarm Valve Display Module
The module provides a digital display of the actual pressure/vacuum of a gas being monitored. In addition, a gas trend indicator bar with High and Low alarms are displayed. The trend bar has two coloured LED’s: GREEN for Normal and RED for High and Low conditions.
Each display module contains a gas specic, colour coded label (USA or ISO colours are available). The Display Module is eld adjustable for pressure/vacuum settings, repeat alarm and unit of measure. Dry contacts for high and low alarms are available for remote monitoring of each module.
Sensor Module
The Sensor Module contains the transducer which converts the gas/vacuum pressure source into a digital signal that is displayed on the display module. The sensor module shall be housed in an anodized aluminum and nickel-plated brass enclosure to act as an interference barrier. It is also temperature compensated.
Each sensor is clearly labeled and colour coded for the gas or vacuum being monitored. The sensor module contains a gas specic DISS tting to ensure correct connection of the proper sensor to the respective gas. Each sensor has been factory calibrated by a computer for the specic gas shown on the sensor housing. If it is not connected to the appropriate gas display module, an error message (EO2) will be displayed.
8 Amico Pipeline
Page 9
Installation of Alarm
For Local Sensor Only
If the sensors are to be mounted locally (inside the valve box), the pipe stubs must be connected to the pipeline. Using silver-brazing techniques, connect each pipe stub to its appropriate gas or vacuum while ensuring that the bottom of the pipe stub is wrapped with a damp cloth. BE CAREFUL not to damage the DISS check-valve by overheating. When the brazing of pipe stubs has been completed, the system can be pressure tested.
Standing Pressure Test
Perform a standing pressure test on the piping system as per NFPA-99 “Health Care Facilities” or CSA-Z305.1 “Non-ammable Medical Gas Piping Systems”. Inspect all joints for leaks and make certain each gas is piped to a correspondingly labeled gas service.
Frame/Module Assembly
Step #1 Remove the frame/valve window from its protective box
Step #2 Attach the Sensor wire to the display module (Sensor +, -)
Step #3 Close the valve window
www.amico.com 9
Page 10
250psi
Installation of Alarm
CAUTION: The microprocessor circuitry on the alarm valve unit contains sophisticated integrated semiconductors. If it becomes necessary to remove a module, PLEASE hold the boards by the edges. DO NOT TOUCH any of the components on the board. Static discharge can cause the modules to malfunction or become damaged.
Sensor
LOCAL (Inside the Back Box)
1. Locate the gas specic sensor module to be installed.
2. In the back box, there are colour coded gas labels located under the DISS Demand check valves. Each label identies where each sensor module is to be placed.
3. The sensor module contains a gas specic DISS tting. Push the sensor module hex-nut and nipple adapter up into the demand check-valve. With a wrench, tighten the nut so that it makes a good seal.
NOTE: Pressure on sensors is not to exceed 250 psi for pressure sensors and 30" for vacuum sensors
The sensor can reach pressure up to:
Mid Pressure 0-99 Psi
Hi Pressure 0-249 Psi
Vacuum 0-30" Hg
REMOTE (Outside the Back Box)
1. Connect a Tee (supplied by others) to the pipeline with a 1/4" NPT female connection that will accept the DISS Demand check-valve.
2. Locate the gas specic sensor module to be installed.
3. Thread the DISS Demand check-valve into the correct gas pipeline.
4. The sensor module contains a gas specic DISS tting. Push the sensor module hex-nut and nipple adapter up into the demand check-valve. With a wrench, tighten the nut so that it makes a good seal.
10 Amico Pipeline
Page 11
Wiring
WARNING, CAUTION,
NOTE are of special significance. Please read these sections
WARNING: denotes steps which can prevent injury.
CAUTION: denotes steps which can prevent damage to equipment.
System Power Supply
TURN OFF THE POWER SWITCH BEFORE CHANGING ANY MODULES AND/OR DISCONNECTING ANY CABLES, OR ELSE THE FUSE WILL BLOW TO PROTECT THE CIRCUITRY.
1. Ensure that the ON/OFF switch is in the OFF position.
2. Through the top left side of the back box, bring in the AC power wires. Knockouts are provided for making conduit connections to the box. All wiring is to be installed according to local and national codes.
3. Connect the AC power to the terminal blocks as shown in the wiring diagram in Appendices A and F.
Annunciator Module
1. The Annunciator Module has a female receptacle located at the top right side of the board (J1).
2. Connect the DC power cable from the System Power Supply into the receptacle connection located on the annunciator module. The connector is keyed and can only be plugged in one way, (Appendix B).
Sensor Module
LOCAL (Inside the Back Box)
1. The sensor module is provided with a 6"-8" (0.1 m-0.2 m) twisted pair of wires. One wire is red (positive) and the other wire is black (negative). Connect the wires to the display module as shown in Appendix C. Take the red wire from the sensor and attach it to terminal “Sensor +” on the display module. Take the black wire from the sensor and attach it to terminal “Sensor -”. The terminal block on the display module is clearly marked for proper connection of the sensor wires.
2. Repeat the above procedures with the remaining sensor modules.
REMOTE (Outside the Back Box)
1. The sensor module is provided with a 6" - 8" (0.1m - 0.2m) twisted pair of wires. Connect the wires to a junction box (not supplied) located near the sensor as per the wiring diagram in Appendix D.
2. Connect a shielded twisted pair cable from the junction box to the back box assembly. Knockouts are provided throughout the alarm back box. Up to 2,500 feet (750 m) of 22 Gauge, shielded twisted pair cable should be used.
3. Connect the red wire from the cable to the terminal on the display module marked ”Sensor +”. Connect the black wire to terminal “Sensor -” (see Appendix D).
4. Repeat the above procedures with the remaining sensor modules using the wiring diagram in Appendix D.
PLEASE NOTE: When remote sensors are used, a shielded or twisted pair cable is required (BELDEN #8451 or equivalent, supplied by others). Ensure that the proper gas sensor module is connected to its corresponding area display module, otherwise an error message (E02) will be displayed on the Display module.
www.amico.com 11
Page 12
Annunciator Module
J 6
ALRM
NORM
SILENCE
LVL 1 LVL 2 LVL 3
J5
SILENCE
Noise Level Control
Factory Default: 80 Decibels
To decrease noise level:
1. Locate jumper at J5. Move jumper to: LVL1 = 90 dBa. LVL2 = 80 dBa. LVL3 = 70 dBa.
Control of Remote Alarm Buzzer
Factory Default: Normal Condition
To silence remote alarm buzzer when silencing the annunciator module:
1. Locate jumper at J6. Move jumper to:
NORM = Remote alarm buzzer will silence when annunciator module is silenced.
ALRM = Remote alarm will not silence when annunciator module is silenced. The buzzer will only silence when an alarm condition has been cleared. Please refer to Appendix B.
TEST
LVL 1 LVL 2 LVL 3
J5
Steps to Re-Calibrate the Sensor from Area Module v4.0
1. Turn on Alarm
2. Set switches #8 and #10 the OFF position
3. Set switches #5 and #6 the ON position
4. The display will show the current reading of the pressure
5. Adjust the calibration, using the “UP” and “DOWN” push buttons, to the desired value.
6. Set switches #5 and #6 the OFF position
7. Turn on #10 if AIMS is connected (do not turn on #8)
When you have completed step #7, the display module will automatically go into “RESET” mode. This will store the data that you entered.
12 Amico Pipeline
Page 13
The Display Module
A dip-switch is located on the back of the display module which is used to identify the gas of the display module. The dip-switch contains ten switch settings.
Pressure Only
Factory Default:
High = 60 Psi, Low = 40 Psi
Repeat time = 30 min.
Compact Alarm Board
High Pressure/Nitrogen
Factory Default:
High = 195 Psi, Low = 140 Psi
Repeat time = 30 min.
During programming, the “Trend Bar” will ash!
1. Set switch #6, #7 and #8 to the ON position.
2. The LED will display (HI-), followed by the current set point. Indicating that the system is ready to accept a new High set point. Adjust set point, using the “UP” and “DOWN” push buttons, to the desired value.
3. Set switch #7 to the OFF position.
4. The LED will display (LO-), followed by the current set point. Indicating the system is ready to accept a new Low set point. Adjust set point, using the “UP” and “DOWN” push buttons, to the desired value.
5. Set switch #8 to the OFF position.
Dip-Switch
6. The LED will display (I-I-), followed by the current set point. Indicating the system is ready to accept a new Repeat Time set point. Adjust set point using the “UP” and “DOWN” push buttons, to the desired value. [(Display dd=Disabled) Range from 1 to 60 Minutes]
7. Set switch #6 to the OFF position.
When you have completed step #7, the display module will automatically go into “RESET” mode. This will store the data that you entered.
“UP” and “DOWN” Push Button
www.amico.com 13
Page 14
PSI
PSI
K
PA
B
AR
PSI / kPa / BAR Selection
Factory Default - PSI
For PSI mode, set the switch #4 to the ON position. The LED PSI indicator located next to the gas pressure reading will illuminate.
For kPa mode, set the switch #4 to the OFF position and switch #9 to the ON position. The LED kPa indicator located next to the gas pressure reading will illuminate.
For BAR set the switch #4 to the OFF and the switch #9 to the OFF position. The LED kPa indicator located next to the gas pressure reading will illuminate. (There is no separate indicator for BAR).
Vacuum Only
Vacuum alarm set-point adjustment
Factory Default:
High = 30"Hg, Low = 12"Hg
Repeat time = 30 min.
KPA
BAR
During programming, the “Trend Bar” will ash!
1. Set switch #6, #7 and #8 to the ON position.
2. The LED will display (HI-), followed by the current set point. Indicating the system is ready to accept a new High set point. Do not adjust this set point since the High set point is not used.
3. Set switch #7 to the OFF position.
4. The LED will display (LO-), followed by the current set point. Indicating the system is ready to accept a new Low set point. Adjust set point, using the “UP” and “DOWN” push buttons, to the desired value.
5. Set switch #8 to the OFF position.
6. The LED will display (I-I-), followed by the current set point. Indicating the system is ready to accept a new Repeat Time set point. Adjust set point using the “UP” and “DOWN” push buttons, to the desired value. [(Display dd=Disabled) Range from 1 to 60 Minutes].
7. Set switch #6 to the OFF position.
When you have completed step #7, the display module will automatically go into “RESET” mode. This will store the data that you entered.
14 Amico Pipeline
Page 15
InchHg
InchHg
K
PA
B
AR
InchHg / KPA / BAR Selections
Factory Default - InchHg
For InchHg mode, set the switch #4 to the ON position. The LED indicating InHg located next to the vacuum source reading will illuminate.
For KPA mode, set the switch #4 to the OFF position and the switch #9 to the ON position. The LED indicating KPA located next to the vacuum source reading will illuminate.
For BAR mode, the KPA indicating source must be changed to BAR by use of a label. Set the switch #4 to the OFF and the switch #9 to the OFF position. The LED indicating BAR located next to the vacuum source reading will illuminate.
Common Settings For Pressure and Vacuum
Repeat Alarm Enable/Disable
Factory Default - Disable
Disable
Set switch #5 to the OFF position to disable the repeat alarm.
KPA
BAR
NOTE: When the repeat alarm function is disabled, the alarm will not repeat.
Enable
Enable Mode: (Factory Default 30 min, when enabled).
Set switch #5 to the ON position.
PLEASE NOTE: The module with the lowest set Repeat Time is the one that controls the Repeat Time. For example, if one module is set for 5 minutes and one for 30 minutes and both are Repeat Alarm enabled, the alarm will now repeat every 5 minutes.
Setting Factory Default
To quickly reset the module (Pressure or Vacuum) to the factory default settings as follows:
• Pressure: High set-point 60 Psi, Low set-point 40 Psi.
• Nitrogen and HP Air: High set-point 195 Psi, Low set-point 140 Psi.
• Vacuum: Low set-point 12 inchHg.
• No Repeat alarm, but set for 30 min..
1. Set switch #8 to the ON position.
2. Turn the power o (wait 5 seconds) then back on.
3. Set switch #8 to the OFF position.
The module is now in the default mode.
www.amico.com 15
Page 16
Alert - 2 Series
SETTING GAS IDENTIFICATION SWITCHES
NOTE: DO NOT TAMPER WITH SWITCHES #1, 2 AND 3 ON THE DIP-SWITCH. TAMPERING WITH THESE POSITIONS WILL RESULT IN AN ERROR MESSAGE BEING DISPLAYED (EO2) AND WILL DISABLE THE ELECTRICAL INTERLOCK FROM THE GAS SPECIFIC SENSOR.
CHANGES TO THESE SWITCHES SHOULD ONLY BE DONE BY PROPERLY TRAINED PERSONNEL, WHEN CIRCUIT BOARDS HAVE TO BE CHANGED IN THE FIELD.
Switches # 1, 2 and 3 are used for the gas identification of the display module. These will be set at the factory and should not be tampered with in the field.
CHART OF GAS SPECIFIC SETTINGS OF DIP-SWITCHES
O N
O N
O N
O N
O N
O N
O N
O N
4444444
43333333322222222111111115555555566666666777777778888888899999999
1010101010
10
#2 - off
#3 - off
#1 - off
#2 - off
#3 - off
Oxygen
Vacuum
Medical Air
Nitrous Oxide
Setting Gas Identication Switches
WARNING, CAUTION,
NOTE are of special significance. Please read these sections
WARNING: denotes steps which can prevent injury.
CAUTION: denotes steps which can prevent damage to equipment.
PLEASE NOTE: DO NOT tamper with switches #1, 2 and 3 on the dip-switch. Tampering with these positions will result in an error message being displayed (E02) and will disable the electrical interlock from the gas specic sensor.
Changes to these switches should only be done by properly trained personnel, when circuit boards have to be changed in the eld.
Switches #1, #2 and #3 are used for the gas identication of the display module. These will be set at the factory and should not be tampered with in the eld.
Chart of Gas Specic Settings of Dip-Switches
#1 - off #2 - off #3 - on
#1 - off #2 - on #3 - off
#1 - on
#3 - on
#2 - on #3 - on
10
Instrument Air/
Nitrogen
#1 - off #2 - off #3 - off
Carbon Dioxide
#1 - on #2 - on #3 - on
10
16 Amico Pipeline
WAGD
#1 - on #2 - on
HP Air
#1 - on
Page 17
Troubleshooting Guide
Symptom Cause Corrective Action
An error code appears on one or more display modules
The microprocessor detected a fault and has shut down
Turn power switch to OFF position. Wait for at least 5 seconds before turning on the power. The program will reset itself.
No power on the alarm (no LED’s illuminated)
Faulty wire connection between the sensor and display module
AC power not available Ensure that the ON/OFF switch on the power
Fuse is blown Check the fuse. The fuse is located on the upper
DC power plug not connected to the annunciator module
Check error codes at the end of this section.
supply module is turned ON
AC wiring not connected
Check the building electrical breaker to ensure that the power is ON
Check the voltage at the terminal block above the transformer. Ensure that 115 VAC or 220 VAC is being supplied.
right corner of the system power supply. Replace the fuse if it is defective. See Appendix A.
Ensure that the DC power plug is rmly in its socket on the annunciator module.
Replace System Power Supply unit if all the above steps fail to resolve the problem.
Defective ribbon cable Replace the ribbon cable
www.amico.com 17
Page 18
Troubleshooting Guide
Symptom Cause Corrective Action
Power light on the annunciator module is ON but LED’s on other modules are not on
No audible alarm and LED’s are not illuminating
Audible signal will not silence Faulty display module Disconnect the ribbon cable from the back of the
DC power cable is not connected to the annunciator module
DC power cable is disconnected or loose
Ensure that the DC power cable is rmly in its socket on the annunciator module
Ensure that the module(s) on the Frame/Module assembly are all connected to the ribbon-cable
Replace the annunciator module
Ensure that the DC power cable from the system power supply is connected to the annunciator module snugly
Depress “TEST” button. If the LED’s come on and there is no audible alarm, replace the annunciator module. If this does not work, try solutions to problem #2.
faulty display modules) and replace the module(s)
Alarm condition exists but LED’s are not illuminating
Connection of the DC power cable from system power supply to annunciator module is loose
Faulty annunciator module Replace annunciator module
Display module not properly calibrated
Faulty display module Replace the display module.
Disconnect the DC power cable from the annunciator module and then reconnect. If the audible signal still persists, replace the System Power Supply unit.
Ensure that the system was properly ordered.
Factory default settings:
Mid Pressure:
Hi Pressure 60 Psi
Low Pressure 40 Psi
Vacuum:
Low Vacuum 12 inHg
High Pressure:
Hi: Nitrogen & Air 195 Psi
Low: Nitrogen & Air 140 Psi
If calibration is required, refer to setting HIGH and LOW calibration procedure on page 13-14
18 Amico Pipeline
Page 19
Troubleshooting Guide
Symptom Cause Corrective Action
Gas reading incorrect Loose connection of DISS ttings Ensure that the sensor module is properly
connected to the DISS demand check-valve
Sensor module is not properly wired to the display module
Defective sensor or requires calibration Replace the sensor module
The ribbon cable is not properly connected to the display module
Defective display module Replace the display module
Ensure that the sensor module is properly wired to the display module by using wiring diagram in Appendix C or D
Pull out the ribbon cable and connect it back in again, while ensuring that it is seated properly
Error Code Messages on the Display Module
System Cause Corrective Action Page
E01 No sensor is connected. Connect a sensor 28/29
E02 Sensor and Display Module mismatched. Ensure that the Sensor and Display Module are for the
same gas
E03 The High set-point was set below the Low set-point
or vice versa.
E04 Incorrect type of Sensor connected
(e.g. 250 psi sensor on a 100 psi range)
E06 Cable between the sensor and display module
shorted out or reversed polarity
E07 Out of calibration / Sensor not reading gas Replace the sensor module 28/29
Recalibrate the High and Low setpoint to proper values
Connect the correct Sensor to the matching Display Module
Reverse polarity or replace cable if defective 28/29
16
13/14
www.amico.com 19
Page 20
Model Numbers
Alarm Valve Combo Unit
AVCLN-XXGXXGXXGXXGXXGXXGXXG
The “L” denes
the language:
U = English (NFPA)
E = English (CSA)
S = Spanish
F = French
Notes:
• The power supply requires 1 gang per box.
• Example: English, 3 valves, 1/2" Oxygen, 3/4" Medical Air and 1-1/4" Medical Vacuum. Will be in a 4 gang box, not a 3 gang: AVCU3-05O05A12V
• The 1-1/2" valve will have an empty space above the valve.
• Example: a box with a 1/2" Oxygen, 3/4" Medical Air and 1-1/2" Medical Vacuum and a power supply will require a 5 gang box not a 4 gang box.
• The 2" valve will be assembled in a 6-1/2" deep box and shall accommodate up to a maximum of four gases. The 2" valve shall be positioned on the bottom of the assembly. The height measurements of the 6-1/2" deep valve box are the same as the 3-7/8" deep valve box. When comparing height measurements, consider the gap above the 2" valve.
• Example: a valve box with 1/2" valve, 2" valve and a power supply would be in a 3 gang, 6-1/2" deep box, which would be the same height as the 4 gang, 3-7/8" valve box.
• 2-1/2" and 3" valve assemblies are only oered as singles.
The “N” denes the # of valves:
1 = 1 Valve
2 = 2 Valves
3 = 3 Valves
4 = 4 Valves
5 = 5 Valves
6 = 6 Valves
The “G” denes the gas:
O = Oxygen
A = Medical Air
V = MedVac
2 = Nitrous Oxide
N = Nitrogen
C = Carbon Dioxide
W/E = WAGD/AGSS
I = Instrument Air
Replace “XX” with the valve size required:
1/2" = 05
3/4" = 07
1" = 10
1-1/4" = 12
1-1/2" = 15
2" = 20F
2-1/2" = 25
3" = 30
20 Amico Pipeline
Page 21
Model Numbers
Alarm Valve Combo Unit
AVCHLN-XXGXXGXXGXXGXXGXXGXXG
Horizontal
Notes:
• The power supply shall be located on the left side of the assembly.
• Valves are to be assembled vertically, with medical gas ow direction from the bottom to the top.
• The 2-1/2" and 3" valve assemblies are only oered as singles.
The “L” denes
the language:
U = English (NFPA)
E = English (CSA)
S = Spanish
F = French
The “N” denes the # of valves:
1 = 1 Valve
2 = 2 Valves
3 = 3 Valves
4 = 4 Valves
5 = 5 Valves
6 = 6 Valves
The “G” denes the gas
O = Oxygen
A = Medical Air
V = MedVac
2 = Nitrous Oxide
N = Nitrogen
C = Carbon Dioxide
W/E = WAGD/AGSS
I = Instrument Air
Replace “XX” with the valve size required:
1/2" = 05
3/4" = 07
1" = 10
1-1/4" = 12
1-1/2" = 15
2" = 20F
2-1/2" = 25
3" = 30
www.amico.com 21
Page 22
Spare Parts Numbers
Model Number Description
A2P-ANNU-CB
A2P-POWER-V2
A2P-SENS-E-AIR
A2P-SENS-E-CO2
A2P-SENS-E-EVA
A2P-SENS-E-N2O
A2P-SENS-E-NIT
A2P-SENS-E-OXY
A2P-SENS-E-VAC
A2P-SENS-U-AIR
A2P-SENS-U-OXY
A2P-SENS-U-VAC
A2P-SENS-U-WAG
A2P-SENS-U-IAR
A2P-AVCDIS-CB
A2P-AVCDIS-E-AIRB
A2P-AVCDIS-E-OXYB
A2P-AVCDIS-E-VACB
A2P-AVCDIS-E-NITB
A2P-AVCDIS-E-N2OB
A2P-AVCDIS-E-CO2B
A2P-AVCDIS-E-AGSB
A2P-AVCDIS-U-OXYB
A2P-AVCDIS-U-AIRB
A2P-AVCDIS-U-VACB
A2P-AVCDIS-U-WAGB
A2P-AVC-MYLA-E-O
A2P-AVC-MYLA-E-A
A2P-AVC-MYLA-E-V
A2P-AVC-MYLA-E-N
A2P-AVC-MYLA-E-2
A2P-AVC-MYLA-E-C
A2P-AVC-MYLA-E-E
A2P-AVC-MYLA-U-O
A2P-AVC-MYLA-U-V
A2P-AVC-MYLA-U-A
A2P-AVC-MYLA-U-W
A2X-AVC-RIBBON2
A2X-AVC-RIBBON3
A2X-AVC-RIBBON4
ANNUNCIATOR CIRCUIT BOARD ASSEMBLY
POWER SUPPLY MODULE ALERT-2
SENSOR MODULE ISO-AIR ENG. ALERT-2
SENSOR MODULE ISO-CO2 ENG. ALERT-2
SENSOR MODULE ISO-EVA ENG. ALERT-2
SENSOR MODULE ISO-N2O ENG. ALERT-2
SENSOR MODULE ISO-NIT ENG. ALERT-2
SENSOR MODULE ISO-OXY ENG. ALERT-2
SENSOR MODULE ISO-VAC ENG. ALERT-2
SENSOR MODULE USA-AIR ENG. ALERT-2
SENSOR MODULE USA-OXY ENG. ALERT-2
SENSOR MODULE USA-VAC ENG. ALERT-2
SENSOR MODULE USA-WAG ENG. ALERT-2
SENSOR MODULE USA-INSTRUMENT AIR ALERT-2
ALARM VALVE COMBO CIRCUIT BOARD ASS. -ALL GASES
ALARM VALVE COMBO DIS. MODU ISO-AIR ENG.
ALARM VALVE COMBO DIS. MODU ISO-OXY ENG.
ALARM VALVE COMBO DIS. MODU ISO-VAC ENG.
ALARM VALVE COMBO DIS. MODU ISO-NIT ENG.
ALARM VALVE COMBO DIS. MODU ISO-N2O ENG.
ALARM VALVE COMBO DIS. MODU ISO-CO2 ENG.
ALARM VALVE COMBO DIS. MODU ISO-AGS ENG.
ALARM VALVE COMBO DIS. MODU USA-OXY ENG.
ALARM VALVE COMBO DIS. MODU USA-AIR ENG.
ALARM VALVE COMBO DIS. MODU USA-VAC ENG.
ALARM VALVE COMBO DIS. MODU USA-WAG ENG.
ALARM VALVE COMBO MYLAR ENG. OXY ISO
ALARM VALVE COMBO MYLAR ENG. AIR ISO
ALARM VALVE COMBO MYLAR ENG. VAC ISO
ALARM VALVE COMBO MYLAR ENG. NIT ISO
ALARM VALVE COMBO MYLAR ENG. N2O ISO
ALARM VALVE COMBO MYLAR ENG. CO2 ISO
ALARM VALVE COMBO MYLAR ENG. AGS ISO
ALARM VALVE COMBO MYLAR ENG. OXY NFPA
ALARM VALVE COMBO MYLAR ENG. VAC NFPA
ALARM VALVE COMBO MYLAR ENG. AIR NFPA
ALARM VALVE COMBO MYLAR ENG. WAG NFPA
2 STN RIB CABLE FOR ALRM/VALVE COMBO
3 STN RIB CABLE FOR ALRM/VALVE COMBO
4 STN RIB CABLE FOR ALRM/VALVE COMBO
22 Amico Pipeline
Page 23
Spare Parts Numbers
Model Number Description
A2X-AVC-RIBBON5
A2X-AVC-RIBBON6
A2X-AVC-RIBBON7
A2X-AVC-DVPLATE
A2X-AVC-DVPLAT2
A2X-AVC-DVPLAT3
A2X-AVC-DVPLAT4
A2X-AVC-DVPLAT5
A2X-AVC-DVPLAT6
A2X-AVC-BRKT-2F
A2X-AVC-PLT-02N
A2X-P-SW-AVCCAP
S-DIS-KIT-OXY
S-DIS-KIT-AIR
S-DIS-KIT-VAC
S-DIS-KIT-N2O
S-DIS-KIT-NIT
S-DIS-KIT-CO2
S-DIS-KIT-EVA
S-DIS-DEMC-AIR
S-DIS-DEMC-OXY
S-DIS-DEMC-VAC
S-DIS-DEMC-N2O
S-DIS-DEMC-NIT
S-DIS-DEMC-CO2
S-DIS-DEMC-EVA
5 STN RIB CABLE FOR ALRM/VALVE COMBO
6 STN RIB CABLE FOR ALRM/VALVE COMBO
7 STN RIB CABLE FOR ALRM/VALVE COMBO
DIVIDER PLATE FOR 1GAS ALARM VALVE COMBO
DIVIDER PLATE FOR 2GAS ALARM VALVE COMBO
DIVIDER PLATE FOR 3GAS ALARM VALVE COMBO
DIVIDER PLATE FOR 4GAS ALARM VALVE COMBO
DIVIDER PLATE FOR 5GAS ALARM VALVE COMBO
DIVIDER PLATE FOR 6GAS ALARM VALVE COMBO
P/S COVER FOR ALARM VALVE COMBO
DIVIDER PLATE FOR ALARM VALVE COMBO
ALARM VALVE COMBO KEYCAP - GRAY
DISS DEMAND CHECK, NUT & NIPPLE – OXY
DISS DEMAND CHECK, NUT & NIPPLE – AIR
DISS DEMAND CHECK, NUT & NIPPLE – VAC
DISS DEMAND CHECK, NUT & NIPPLE – N2O
DISS DEMAND CHECK, NUT & NIPPLE – NIT
DISS DEMAND CHECK, NUT & NIPPLE – CO2
DISS DEMAND CHECK, NUT & NIPPLE – EVA
DISS DEMAND CHECK VALVE 1/4"MNPT - AIR
DISS DEMAND CHECK VALVE 1/4"MNPT - OXY
DISS DEMAND CHECK VALVE 1/4"MNPT - VAC
DISS DEMAND CHECK VALVE 1/4"MNPT – N2O
DISS DEMAND CHECK VALVE 1/4"MNPT - NIT
DISS DEMAND CHECK VALVE 1/4"MNPT – CO2
DISS DEMAND CHECK VALVE 1/4"MNPT - EVA
www.amico.com 23
Page 24
Dimensions
Vertical Alarm Valve Combo Unit
Inch [mm]
24 Amico Pipeline
Remote Sensor
DISS
CONNECTOR
1/2"-14 NPSM [13]
(see thread specs.)
1.88 [48]
(approximate, can vary)
Wrench Flats
1
[25]
1/2" Conduit
Connection
Page 25
Dimensions
Horizontal Alarm Valve Combo Unit
Inch [mm]
Remote Sensor
DISS
Connector
(approximate, can vary)
1.88 [48]
1/2"-14 NPSM [13]
(see thread specs.)
Wrench Flats
1
[25]
1/2" Conduit
Connection
www.amico.com 25
Page 26
Appendix A
Wiring Diagram – Auto-Switching Power Supply
Toggle Switch
AC Supply 115 to 220 VAC
G
N
L
L - Live N - Neutral G - Ground
Fuse (1 AMPw)
Ground
26 Amico Pipeline
DC Power Cable: Connect to Annunciator Module
Page 27
Appendix B
Wiring Diagram – Annunciator
www.amico.com 27
Page 28
Appendix C
Wiring Diagram – Alarm Valve Combo Unit
Sensor Module
Sensor Module
SENSOR
REMOTE
+ -
+ -
COM NC NO
LOW
ALARM
COM NC NO
HIGH
ALARM
BlackRed
L - Live N - Neutral G - Ground
AC Supply 115 to 220 VAC
Sensor Module
SENSOR
REMOTE
+ -
+ -
COM NC NO
LOW
ALARM
COM NC NO
HIGH
ALARM
BlackRed
Ground
L
N
G
Power Supply
Annunciator
Toggle Switch
Module
#22 Gauge twisted pair shielded cable 6"-8” [0.1 m-0.2 m] supplied
SENSOR
REMOTE
+ -
+ -
COM NC NO
LOW
ALARM
COM NC NO
HIGH
ALARM
BlackRed
28 Amico Pipeline
Page 29
Appendix D
Wiring Diagram – Remote Alarm Valve Combo Unit
Sensor Module
Ribbon
Cable
DISS
OXYGEN
#22 Gauge twisted pair shielded cable 6"-8” [0.1 m-0.2 m] supplied
Junction Box
(by others)
Compact
Module
L - Live N - Neutral G - Ground
AC Supply 115 to 220 VAC
L
G
N
Power Supply
Ground
Toggle Switch
Annunciator Module
Red
SENSOR
+ -
REMOTE
+ -
COM NC NO
LOW
ALARM
Black
COM NC NO
HIGH
ALARM
www.amico.com 29
Page 30
Appendix E
Wiring Diagram - Alarm Valve Combo Unit to Master Module
Sensor Module
DISS
#22 Gauge twisted pair shielded cable 6"-8” [0.1 m-0.2 m]
OXYGEN
supplied
Junction Box
(by others)
L - Live N - Neutral G - Ground
AC Supply 115 to 220 VAC
G
N
Power Supply
Ribbon
Cable
Compact
Module
Dry contacts only
No voltage
+
-
+
-
+
-
SENSOR
Ground
L
Annunciator
Toggle Switch
Module
#22 Gauge wire
To Amico: Master Module or Building Management
+ -
REMOTE
+ -
System
COM NC NO
LOW
ALARM
COM NC NO
HIGH
ALARM
Equipment
Source
+
-
+
-
+
-
+
-
+
-
+
-
+
-
SW-2
Master
Note
Version 3 and 4: Jumper any unused points on the Master module
Version 4: Turn OFF dip-switches for any unused points (location SW-2)
30 Amico Pipeline
Page 31
Appendix F
Technical Specications
Supply Voltage: 115 to 220 VAC - 50 to 60 Hz
Current Draw: 1 Amp. Max.
Fuse (1/4 * 1-1/4): Fast Blow 1 Amp.
Cable Requirements
AVC Display Module to Remote Sensor:
Distance: Maximum 2,500 feet (750 m)
Cable: Belden # 8451 or equivalent. #22 gauge shielded, twisted pair (For multiple sensors a multi-conductor shielded twisted pair cable should be used).
Signal: 30 VDC - 1.0 Amps. 60 VDC - 0.3 Amps. 125 VAC - 0.5 Amps.
AVC Display Module to Master Module
Distance: Maximum 10,000 feet (3,000 m)
Cable: Minimum #22 gauge wire (does not have to be shielded, twisted pair)
Signal: 5 VDC, < 5 µA
www.amico.com 31
Page 32
www.amico.com
Amico Pipeline | www.amico.com
85 Fulton Way, Richmond Hill
Ontario, L4B 2N4, Canada
71 East Industry Court, Deer Park NY 11729, U.S.A
Toll Free Tel: 1.877.462.6426 Toll Free Fax: 1.866.440.4986 Tel: 905.764.0800
Fax: 905.764.0862 Email: info@amico.com
C US LISTED
APEIMALMVLVCMB 04.09.2014
Loading...