Alert-2 Microprocessor Based
Digital Alarm System v5.9
Contents
User Responsibility 5
Introduction 5 - 6
Features
Description of the Alarm
Shipment Details
The Alarm Back Box
The Frame/Module Assembly
Description of the Modules 7-10Common to all Alarms
System Power Supply
Annunciator Module
Blank Module
Area Alarm
Area Display Module
2 in 1 Display Module
Compact Display Module
Sensor Module
Master Alarm
Master/Nema 4 Status Module
Computer Interface Module
Installation Guide 10 - 11
The Alarm Back Box
For Local Sensor Only
Standing Pressure Test
Frame/Module Assembly
Sensor
Local
Remote
Wiring 12 - 14
System Power Supply
Annuciator Module
Sensor Module
Local
Remote
Area Display Module
2 in 1 Display Module
2 Amico Pipeline
2 Amico Pipeline
Area Display Module
2 in 1 Display Module
Compact Display Module
Master/NEMA 4 Status Module
Computer Interface Module
Closing the Frame Module Assembly
Annunciator Module 14
Noise Level Control
Control of Remote Alarm Buzzer
Steps to Re-Calibrate the Sensor from Area Module v4.0 15
Area, 2 in 1, Compact Display Module 15 - 19
PSI/kPa/ BAR selection
Inch Hg/kPa/BAR selections
Common Settings for Pressure and Vacuum
Setting Factory Default
Setting Gas Identication Switches
Chart of Gas Specic Settings of Dip-Switches
Master/NEMA 4 Status Module 19 - 21
Repeat Alarm
Signal Input Selection
Maintenance Mode
Troubleshooting Guide 22 - 24
Error Code Messages on the Display Module 24
Model Numbers 25 - 28
Area Alarm
Master Alarm
Compact Alarm
NEMA 4 Alarm
Compact Master Combination Alarm
2 in 1 Area Alarm
Spare Part Numbers 29 - 31
www.amico.com 3
Dimensions 32 - 37
Area Alarm
Master Alarm
Compact Alarm
Compact Master Alarm Combination
2 in 1 Alarm
NEMA 4
Appendix A - Wiring Diagram: Auto-Switching Power Supply 38
Appendix B - Wiring Diagram: Annunciator 39
Appendix C - Wiring Diagram: Automatic Voice/Pager Dialing System 40
Appendix D - Wiring Diagram: Area Display Module (Local Sensor) 41
Appendix E - Wiring Diagram: Area Display Module (Remote Sensor) 42
Appendix F - Wiring Diagram: 2 in 1 Display Module 43
Appendix G - Wiring Diagram: Compact Module 44
Appendix H - Wiring Diagram: Area Module to Master Module 45
Appendix I - Wiring Diagram: 2 in 1 Module to Master Module 46
Appendix L - Wiring Diagram: Master/NEMA 4 Module 49
Appendix M - Wiring Diagram: Pressure Switch Connection to a Master Alarm 50
Appendix N - Wiring Diagram: Computer Interface Module 51
Appendix O - Wiring Diagram: Master to Slave Module 52
Appendix P - Technical Specication 53
Notes 54 - 55
4Amico Pipeline
User Responsibility
Amico Microprocessor Based Alarm
USER RESPONSIBILITY
The information contained in this Installation and Operation MaintenanceManual, pertains only to the ALERT-2 microprocessor based digital alarm.This product will perform to conformity with the descriptions contained in thismanual, when assembled, operated, maintained and serviced in accordancewith the installation instructions provided.
The alarm must be checked periodically. Parts that are broken, missing,worn, distorted or contaminated, must be replaced immediately. Should suchrepair or replacement become necessary, please contact Amico Corporationor their distributors.
All alarms should not be repaired, or altered without prior written or verbalapproval of Amico Corporation or it’s distributors. Failure to comply will voidall warranty on the alarm.
Statements in this manual preceded by the words
WARNING,CAUTION,
DANGERand
NOTEare of special significance. Please read these sections
carefully.
WARNING:denotes steps which can prevent injury.
CAUTION: denotes steps which can prevent damage to equipment.
DANGER: denotes steps which can prevent electrical shock to equipment
or to prevent serious injury and/or death.
The information contained in this Installation and Operation Maintenance Manual, pertains only to the ALERT-2 microprocessor based digital alarm. This product will perform to conformity with the descriptions contained in this manual,
when assembled, operated, maintained and serviced in accordance with the installation instructions provided.
The alarm must be checked periodically. Parts that are broken, missing, worn, distorted or contaminated, must be
replaced immediately. Should such repair or replacement become necessary, please contact Amico Corporation or their
distributors.
All alarms should not be repaired, or altered without prior written or verbal approval of Amico Corporation or its distributors.
Failure to comply will void all warranty on the alarm.
Statements in this manual preceded by the words WARNING, CAUTION, DANGER and NOTE are of special signicance.
Please read these sections carefully.
NOTE: Amico strongly recommends that alarms be checked annually by qualied sta.
WARNING: denotes steps which can prevent injury.
CAUTION: denotes steps which can prevent damage to
Introduction
The AMICO Medical Gas Alarm System (ALERT-2) incorporates the latest microprocessor technology for alarm and
surveillance systems. The alarm has been designed to provide user exibility and reliability. This manual will enable the
customer to install, use and maintain the alarm properly.
equipment.
DANGER: denotes steps which can prevent electrical
shock to equipment or to prevent serious injury and/or
death.
All Gases or Vacuum are displayed with large Red LED’s for clear visibility. To facilitate the monitoring function by hospital
personnel, a trend bar is provided to show the direction of the gas/vacuum pressure. Under normal operation, the gas
trend indicator will be in the GREEN - OK position. If the gas pressure approaches alarm condition, the trend indicator
will display a YELLOW - Caution indicator. If an alarm condition occurs, a RED-Alarm indicator will be displayed and the
buzzer will sound.
There are two buttons located on the front face of the Annunciator module. They are the “TEST” and “ALARM MUTE”
buttons. The function of the “Test” button is to verify that the buzzer and all the alarm LED’s are in normal working condition.
The function of the “Alarm Mute” button is to silence an alarm that has occurred.
A master status module monitors source equipment such as: Oxygen, Nitrous Oxide, Air compressors, Vacuum pumps,
Air dryers, high/low pressure switches, etc. This module can be connected to a “Building Management System”, with a
piggy-back computer interface board, that attaches to the master module.
www.amico.com 5
The Alert-2 microprocessor based digital alarm system complies with NFPA-99.
The Alert-2 microprocessor based digital alarm system is UL Listed to U.S. and Canadian safety standards.
FEATURES
Individual Microprocessor on each display, sensor and master module.
Gas specic sensors can be mounted locally or remote, up to 2,500 feet, [750m] utilizing 22 gauge twisted pair
(shielded cable should be used).
DISS gas specic sensor housed in a tamper proof enclosure. The Sensor Module is housed in an anodized aluminum
and nickle-plated brass enclosure to act as an interference barrier.
The Sensor Module is the smallest computer-calibrated temperature-compensated sensor in the industry.
True digital LED display and trend indicator for each service monitored.
Illuminated LED display that is visible at an angle and in dim lighting conditions.
PSI, kPa or BAR display (switch selected).
Self diagnostic circuitry with error display for problem identication.
Highly accurate Solid State Pressure piezo-resistive transducer.
Adjustable repeat alarm (1 to 60 minutes/or o) for the Area, 2 in 1 Alarm and Compact Alarm.
Adjustable repeat alarm (1, 12, 24 hours/or o) for the Master Alarm.
Dry contacts for remote monitoring of High and Low alarm status on the Area, 2 in 1 and Compact Alarm display
module.
Modules are factory mounted on a hinged frame assembly for ease of installation and maintenance.
Field programmable push buttons for adjustment of HI and LOW set-points on display module.
Area alarms available in 1 to 6 display modules.
Compact alarms available in 1 to 12 display modules.
Master alarms available in 10 to 60 points.
2 in 1 alarms available in 1 to 6 display modules with 5 to 30 master points.
Area, 2 in 1, and Compact Modules can be intermixed with Master Modules to create a combination alarm.
Built-In relay for remote annunciator applications.
Area, 2 in 1 and Compact Module indication for calibration (ashing bar graph).
6 Amico Pipeline
Description of the Alarm
SHIPMENT DETAILS
When you receive an ALERT-2 series alarm from Amico Corporation, the package will consist of two main sections; the
Alarm Back Box and the Frame/Module Assembly. The Frame/Module assembly will be pre-congured, with the appropriate display modules, based upon the customer’s specications.
THE ALARM BACK BOX
The Alarm Back Box contains the auto-switchable System Power Supply with an ON/OFF switch, a built-in fuse and terminal blocks (115 VAC, or 220 VAC). The back box also incorporates the pipe stubs for applications that require locally
(in box) mounted sensors.
THE FRAME/MODULE ASSEMBLY
The Frame/Module Assembly consists of the frame and all the modules that are pre-assembled to the customers specication. The hinged frame is designed to swing down from the back box to facilitate installation and servicing of the
alarm. This design will reduce installation time and eliminate the risk of improper installation since all the modules are
connected and tested at the factory.
Description of the Modules
The ALERT-2 alarm is divided into 4 or 7 main modules:
COMMON TO ALL ALARMS
1. SYSTEM POWER SUPPLY
The System Power Supply has been pre-installed into the back box assembly. The System Power Supply converts the
AC voltage supply to the alarm into two voltages: 5 VDC (regulated) required by the microprocessor hardware and 15
VDC (unregulated) required by the buzzer and the LED’s. This unit also contains the main ON/OFF power switch, the
transformer, the heat sink, the main fuse and fuse cover, the rectifying circuitry, the terminal blocks and the low voltage
DC power cable for connecting this unit to the annunciator module. The System Power Supply can be easily removed
and reinstalled by unscrewing it from the back box.
www.amico.com 7
2. ANNUNCIATOR MODULE
DESCRIPTION OF MODULES
The ALERT-2 alarm is divided into (4) or (7) main modules:
COMMON TOALL ALARMS
1.SYSTEM POWER SUPPLY
The System Power Supply has been pre-installed into the back boxassembly. The System Power Supply converts the AC voltage supply tothe alarm into two voltages: 5 VDC (regulated) required by themicroprocessor hardware and 15 VDC (unregulated) required by thebuzzer and the LED’s. This unit also contains the main ON/OFF powerswitch, the transformer, the heat sink, the main fuse and fuse cover, therectifying circuitry, the terminal blocks and the low voltage DC powercable for connecting this unit to the annunciator module. The SystemPower Supply can be easily removed and reinstalled by unscrewing itfrom the back box.
2.ANNUNCIATOR MODULE
The Annunciator Module contains the buzzer, a “Power On” LED, the“TEST” and the “ALARM MUTE” buttons. The function of the “TEST”button is to verify that the buzzer and all the LED’s are in working condi-tion. An alarm will be heard when this button is pushed and all the LED’swill light up. When the button is released, the alarm will silence. The“ALARM MUTE” button is used to silence an alarm that has occurred. Thismodule also contains a fail-safe relay that de-energizes when the buzzeris activated. This relay can be used with the “Amico remote buzzer”, forapplications requiring a remote audible alarm (see Appendix B), forconnection to an other Amico Alarm or a Building Management System.
3.BLANK MODULE
The Annunciator Module contains the buzzer, a “Power On” LED, the “TEST” and the
“ALARM MUTE” buttons. The function of the “TEST” button is to verify that the buzzer and all
the LED’s are in working condition. An alarm will be heard when this button is pushed and
all the LED’s will light up. When the button is released, the alarm will silence. The “ALARM MUTE”
button is used to silence an alarm that has occurred. This module also contains a fail-safe relay
that de-energizes when the buzzer is activated. This relay can be used with the “Amico remote
buzzer”, for applications requiring a remote audible alarm (see Appendix B), for connection to
another Amico Alarm or a Building Management System.
3. BLANK MODULE
The Blank Module is used as a ller board for future provisions of the alarm.
AREA ALARM
4. AREA DISPLAY MODULE
The Area Display Module provides a digital display of the actual pressure/vacuum of a
gas being monitored. In addition a gas trend indicator bar with HIGH and LOW alarms
are displayed. The trend bar has three coloured LED’s: Green for Normal condition, YELLOW
for Caution condition, and RED for high and low Alarm conditions.
Each display module contains a gas specic colour coded label (USA or ISO colours are
available). A space is also provided, at the base of the module, to identify the location that
the display module monitors. The display module is eld adjustable for pressure/vacuum
settings, repeat alarm, and units of measure. Whenever the module is in calibration mode,
the bargraph is ashing, indicating the calibration mode. Dry contacts for high and low
alarms are available for remote monitoring of each module.
5. 2 IN 1 DISPLAY MODULE
The 2 in 1 Display Module provides a digital display of the actual pressure/vacuum of the
gas being monitored. In addition, a gas trend indicator bar with High and Low alarms are
displayed. This module has two coloured LEDs - Green for Normal conditions and Red for
High and Low alarm conditions. It is eld adjustable for pressure/vacuum settings, repeat
alarms, and units of measure. Dry contacts for high and low alarms are available for remote
monitoring of each module.
Each module will continuously monitor up to 5 signals from source equipment or pressure
switches. If any of the signals being monitored go into an alarm condition, a Red LED will
illuminate and the audible alarm will sound.
PLEASE NOTE: Contacts located on back of module are Dry Contacts only.
DO NOT apply any voltage.
8 Amico Pipeline
6. COMPACT DISPLAY MODULE
The Compact Display Module shall have 2 displays in 1 board. The Compact Module
provides a digital display of the actual pressure/vacuum of a gas being monitored. In
addition a gas trend indicator bar with High and LOW alarms are displayed. The trend bar
as two colored LED’s: GREEN for Normal and RED for High and Low condition.
Each display module contains a gas specic colour coded label (USA or ISO colours are
available). The Display Module is eld adjustable for pressure/vacuum settings, repeat
alarm, and unit of measure. Dry contacts for high and low alarms are available for remote
monitoring of each module.
7. SENSOR MODULE
The Sensor Module contains the transducer which converts the pressure/vacuum pressure source into a digital signal that is displayed on the Display Module. The sensor
module shall be housed in an anodized aluminum and nickel-plated brass enclosure
to act as an interference barrier also it is temperature compensated. Each sensor is
clearly labeled and colour coded for the gas or vacuum being monitored. The sensor module contains a gas specic DISS tting to ensure correct connection of the proper
sensor to the respective gas. Each sensor has been factory calibrated by computer for the
specic gas shown on the sensor housing. If it is not connected to the appropriate gas
display module, an error message (EO2) will be displayed.
MASTER ALARM
8. MASTER/NEMA 4 STATUS MODULE
Each Master Status Module will continuously monitor up to 10 signals from source equipment
and pressure switches. If any of the signals being monitored go into an alarm condition, a
Red LED will illuminate and the audible alarm will sound. The module has a slow and
a rapid ashing LED rate. The last alarm condition always ashes at a rapid rate, while the
previously acknowledged alarms always ash at a slow rate.
PLEASE NOTE: Contacts located on back of module are Dry Contacts only.
DO NOT apply any voltage.
For Annual Test
•Reset power to make sure all LED’s light up
•Push and hold the ‘Test’ button to light up all LED’s and the audible alarm
www.amico.com 9
9. COMPUTER INTERFACE MODULE
MASTERALARM
7.MASTER/NEMA 4 STATUS MODULE
Each Master Status Module will continuously monitor up to 10 signals fromsource equipment and pressure switches. If any of the signals beingmonitored go into an alarm condition, a red LED will illuminate and theaudible alarm will sound. The module has a slow and a rapidflashing LEDrate. The last alarm condition always flashes at a rapidrate, while thepreviously acknowledged alarms always flash at a slowrate.
PLEASE NOTE:Contacts located on back of module are Dry Contactsonly. DO NOT apply any voltage.
8.COMPUTER INTERFACE MODULE
The Computer Interface Module is a piggyback board that fits on top of themaster status module. This module plugs into the status module via aconnector, located at the bottom end of the status module. There are threemounting screws provided to secure this module to the status module.
This module provides dry contactsfor interface to a “Building Manage-ment System”. The module is “Fail-Safe”, closed circuit monitoring.
NOTE: The computer interfacemodule is not compatible with the 2in 1 board.
The Computer Interface Module is a piggyback board that ts on top of the master
status module. This module plugs into the status module via a connector, located at the
bottom end of the status module. There are three mounting screws provided to secure this
module to the status module. This module provides dry contacts for interface to a “Building Management System”. The module is “Fail-Safe”, closed circuit monitoring.
PLEASE NOTE: The computer interface module is not compatible with the 2 in 1 board.
Installation
THE ALARM BOX
Install the back-box to the studs of the wall at the desired height. Ensure that the box is securely in place. The mounting
brackets are adjustable to suit the thickness of the wall. MAKE SURE the box is parallel, squared and ush with the nished wall
surface, to ensure that the frame assembly will t properly.
FOR LOCAL SENSOR ONLY
If the sensors are to be mounted locally (inside the back box), the pipe stubs must be connected to the pipeline. Using
silver-brazing techniques, connect each pipe stub to it’s appropriate gas or vacuum while ensuring that the bottom of
the pipe stub is wrapped with a damp cloth. BE CAREFUL not to damage the DISS check-valve by overheating the lower
portion of the copper pipe. When the brazing of pipe stubs has been completed, the system can be pressure tested.
STANDING PRESSURE TEST
Perform a standing pressure test on the piping system as per NFPA-99 “Health Care Facilities”. Inspect all joints for leaks
and make certain each gas is piped to a correspondingly labelled gas service.
FRAME/MODULE ASSEMBLY
Step #1 Remove the frame/module assembly from its protective box.
Step #2 Remove screws from the frame section (6 screws).
Step #3 Attach the at head screws (provided with frame in plastic bag) to the hinge. This will line up with holes
on the box.
Step #4 Attach the frame wire with 2 dome head screws (provided with frame in plastic bag).
Step #5 Close the frame panel and tighten the screws on the frame plate.
Step #6 Carefully place the front frame over the fastened plate. Refasten the screws that were removed in Step #2.
10 Amico Pipeline
CAUTION: The microprocessor circuitry on the ALERT-2 alarm contains sophisticated integrated semiconductors. If it
250psi
for Vacuum sensors
250psi
becomes necessary to remove a module, PLEASE hold the boards by the edges. DO NOT TOUCH any of the components
on the board. Static discharge can cause the modules to malfunction, or become damaged.
SENSOR
LOCAL (Inside the Back Box)
1. Locate the gas specic sensor module to be installed.
2. In the back box, there are colour coded gas labels located
under the DISS Demand check valves. Each label identies
where each sensor module is to be placed.
3. The sensor module contains a gas specic DISS tting. Push
the sensor module hex-nut and nipple adapter up into the
demand check-valve. With a wrench, tighten the nut so that
it makes a good seal.
NOTE: Pressure on sensors are not to exceed 250psi for Pressure
sensors and 30” for vacuum sensors.
The new style sensors can read pressure up to:
Mid Pressure 99 Psi
Hi Pressure 249 Psi
Vacuum 30” Hg
REMOTE (Outside the Back Box)
1. Connect a Tee (supplied by others) to the pipeline with a
1/4” NPT female connection that will accept the DISS Demand
check-valve.
OLD LOOK
NEW LOOK
2. Locate the gas specic sensor module to be installed.
3. Thread the DISS Demand check-valve into the correct gas
pipe line.
4. The sensor module contains a gas specic DISS tting. Push
the sensor module hex-nut and nipple adapter up into the
demand check-valve. With a wrench, tighten the nut so that
it makes a good seal.
OLD LOOK
NEW LOOK
www.amico.com 11
Wiring
Amico Microprocessor Based Alarm
USER RESPONSIBILITY
The information contained in this Installation and Operation MaintenanceManual, pertains only to the ALERT-2 microprocessor based digital alarm.This product will perform to conformity with the descriptions contained in thismanual, when assembled, operated, maintained and serviced in accordancewith the installation instructions provided.
The alarm must be checked periodically. Parts that are broken, missing,worn, distorted or contaminated, must be replaced immediately. Should suchrepair or replacement become necessary, please contact Amico Corporationor their distributors.
All alarms should not be repaired, or altered without prior written or verbalapproval of Amico Corporation or it’s distributors. Failure to comply will voidall warranty on the alarm.
Statements in this manual preceded by the words
WARNING,CAUTION,
DANGERand
NOTEare of special significance. Please read these sections
carefully.
WARNING:denotes steps which can prevent injury.
SYSTEM POWER SUPPLY
TURN OFF THE POWER SWITCH BEFORE CHANGING ANY MODULES AND/OR DISCONNECTING ANY CABLES, OR ELSE
THE FUSE WILL BLOW TO PROTECT THE CIRCUITRY.
1. Ensure that the ON/OFF switch is in the OFF position.
2. Through the top left side of the back box, bring in the AC power wires. Knockouts are
provided for making conduit connections to the box. All wiring is to be installed according
to local and national codes.
3. Connect the AC power to the terminal blocks as shown in the wiring diagram in Appendix
A and as specied in the technical specication in Appendix P.
ANNUNCIATOR MODULE
1. The Annunciator Module has a female receptacle located at the top right side of the board (J1).
2. Connect the DC power cable from the System Power Supply into the receptacle connection located on
the annunciator module. The connector is keyed and can only be plugged in one way, (Appendix B).
SENSOR MODULE
LOCAL (Inside the Back Box)
1. The sensor module is provided with a 6”-8” [0.1m-0.2m] twisted pair of wires. One wire is Red (positive) and the
other wire is Black (negative). Connect the wires to the display module as shown in Appendix D. Take the Red
wire fromthe sensor and attach it to terminal “Sensor +” on the display module. Take the Black wire from the sensor
and attach it to terminal “Sensor -”. The terminal block on the display module is clearly marked for proper
connection of the sensor wires.
2. Repeat the above procedures with the remaining sensor modules.
REMOTE (Outside the Back Box)
1. The sensor module is provided with a 6” - 8” [0.1m - 0.2m] twisted pair of wires. Connect the wires to a junction box
(not supplied) located near the sensor as per the wiring diagram in Appendix E.
2. Connect a shielded twisted pair cable from the junction box to the back box assembly. Knockouts are provided
throughout the alarm back box. Up to 2,500 feet [750m] of 22 Gauge, shielded twisted pair cable can be used.
12 Amico Pipeline
3. Connect the Red wire from the cable to the terminal on the display module marked ”Sensor +”. Connect the
black wire to terminal “Sensor -” (see Appendix D).
4. Repeat the above procedures with the remaining sensor modules using the wiring diagram in Appendix E.
PLEASE NOTE: When remote sensors are used, a shielded or twisted pair cable is required (BELDEN #8451 or equivalent,
supplied by others). Ensure that the proper gas sensor module is connected to its corresponding area display module,
otherwise an error message (E02) will be displayed on the Area Display module.
AREA DISPLAY MODULE
1. If the dry contacts for High and Low alarm are to be used for remote monitoring, connect the wires to the appropriate
terminals, Com (Common), NO (Normally Open) or NC (Normally Closed), using the diagram in Appendix H.
2. See Appendix P for contact rating.
2 IN 1 DISPLAY MODULE
1. If the dry contacts for High and Low alarms are to be used for remote monitoring, connect the wires to the appropriate
terminals, COM (Common), NC (Normally Closed), or NO (Normally Open), using the diagram in Appendix F.
2. Pull the remote signal wires into the alarm panel. Make the connections to the terminal blocks located on the side
of the status module. The wiring fail-safe normally closed (NC) connections from the source equipment. The signal
level is 5 VDC. Please refer to Appendix I.
3. ENSURE that the unused terminals are jumpered. If this is not done, the terminals that have not been jumpered will
go into alarm.
COMPACT DISPLAY MODULE
1. If the dry contacts for high and low are to be used for remote monitoring, connect the wires to the appropriate
terminals, Com (Common), NO (Normally Open), NC (Normally Closed), using the diagram in Appendix G.
2. See Appendix P for contact rating.
MASTER/NEMA 4 STATUS MODULE
1. Pull the remote signal wires into the alarm panel. Make the connections to the terminal blocks located on the side
of the status module. The wiring is fail-safe normally closed (NC) connections from the source equipment. The
signal level is 5 VDC.
2. Make the appropriate wiring connections as per the wiring diagram in APPENDIX M and N.
3. For Version 3 ENSURE that the unused terminals in the master module are jumpered. If this is not done, the terminals
that have not been jumpered will go into alarm.
For Version 4, turn o switches for any unused points (SW2).
www.amico.com 13
COMPUTER INTERFACE MODULE
SILENCE
J
6
ALRM
NORM
SILENCE
LVL1LVL2LVL3
J5
1. Pull the remote signal wires from the “Building management system” into the alarm panel. Make the connections
to the terminal blocks located on the side of the module. The wiring is fail-safe normally open, held closed, dry
contacts to the monitoring equipment.
2. Make the appropriate wiring connections as per wiring diagram in Appendix N.
CLOSING THE FRAME/MODULE ASSEMBLY
1. Swing up the frame assembly, ensuring that the stopper wires are folded into the back box.
2. Screw in the frame module to the top of the back box assembly by using the screws provided with the frame/module
assembly. The alarm is now ready for use!
Annunciator Module
NOISE LEVEL CONTROL
Factory Default: 90 Decibels
To decrease noise level:
LVL1
LVL2
LVL3
J5
1. Locate jumper at J5. Move jumper to:
LVL1 = 90 dBa.
LVL2 = 80 dBa.
LVL3 = 70 dBa.
CONTROL OF REMOTE ALARM BUZZER
Factory Default: Normal Condition
To silence remote alarm buzzer, when silencing the
annunciator module:
1. Locate jumper at J6. Move jumper to:
NORM =
TEST
Remote alarm buzzer will silence when annunciator
module is silenced.
ALRM =
Remote alarm will not silence when annunciator
module is silenced. The buzzer will only silence when
alarm condition has been cleared. Please refer to
Appendix B.
14 Amico Pipeline
Steps to Re-Calibrate the Sensor from Area Module v4.0
1. Turn on Alarm
2. Set switches #8 & #10 the OFF position
3. Set switches #5 & #6 the ON position
4. The display will show the current reading of the pressure
5. Adjust the calibration, using the “UP” and “DOWN” push buttons, to the desired value.
6. Set switches #5 & #6 the OFF position
7. Turn on #10 if Aims is connected (do not turn on #8)
When you have completed step #7, the display module will automatically go into a “RESET” mode. This will store the
data that you had entered.
Area, 2 in 1, Compact Display Module
A dip-switch is located on the back of the display module which is used to identify the gas of the display module. The
dip-switch contains ten switch settings.
PRESSURE ONLY
Factory Default:
High = 60 Psi, Low = 40 Psi
Repeat time = 30 min.
Dip-Switch
Dip-Switch
Dip-Switch
HIGH PRESSURE/NITROGEN
Factory Default:
High = 195 Psi, Low = 140 Psi
Repeat time = 30 min.
2 in 1 Alarm
Board
During programming, the “Trend Bar” will Flash!
1. Set switch #6, #7 and #8 to the ON position.
2. The LED will display (HI-), followed by the current set point. Indicating the system is ready to accept a
new High set point. Adjust set point, using the “UP” and “DOWN” push buttons, to the desired value.
3. Set switch #7 to the OFF position.
4. The LED will display (LO-), followed by the current set point. Indicating the system is ready to accept a
new Low set point. Adjust set point, using the “UP” and “DOWN” push buttons, to the desired value.
5. Set switch #8 to the OFF position.
6. The LED will display (I-I-), followed by the current set point. Indicating the system is ready to accept a
new Repeat time set point. Adjust set point using the “UP” and “DOWN” push buttons, to the desired
value. [(Display dd=Disabled) Range from 1 to 60 Minutes]
7.Set switch #6 to the OFF position.
Area Alarm
Board
Dip-Switches
Compact Alarm
Board (v2.02)
Compact Alarm
Board (v2.01)
www.amico.com 15
When you have completed step #7, the display module
PSI
Alert - 2 Series
2 in 1 Alarm
Board
Area Alarm
Board
will automatically go into a “RESET” mode. This will store the
data that you had entered.
PSI / kPa / BAR selection
Factory Default - PSI
For PSI mode, set the switch #4 to the ON position. The LED PSI indicator located next to the GAS
pressure reading will illuminate.
For kPa mode, set the switch #4 to the OFF position and switch #9 to the ON position. The LED kPa
indicator located next to the GAS pressure reading will illuminate.
For BAR set the switch #4 to the OFF and the switch #9 to the OFF position. The LED kPa indicator
located next to the GAS pressure reading will illuminate. (There is no separate indicator for BAR).
VACUUM ONLY
Vacuum alarm set-point adjustment
Factory Default:
High = 30”Hg, Low = 12”Hg
Repeat time = 30 min.
KPA
BAR
During programming, the “Trend Bar” will Flash!
1. Set switch #6, #7 and #8 to the ON position.
2. The LED will display (HI-), followed by the current set point. Indicating the system is ready to
accept a new High set point. Do not adjust this set point since the High set point is not used.
3. Set switch #7 to the OFF position.
4. The LED will display (LO-), followed by the current set point. Indicating the system is ready
to accept a new Low set point. Adjust set point, using the “UP” and “DOWN” push buttons, to
the desired value.
5. Set switch #8 to the OFF position.
6. The LED will display (I-I-), followed by the current set point. Indicating the system is ready to
accept a new Repeat time set point. Adjust set point using the “UP” and “DOWN”push buttons,
to the desired value. [(Display dd=Disabled) Range from 1 to 60 Minutes]
7. Set switch #6 to the OFF position.
When you have completed step #7, the display module will automatically go into a “RESET” mode.
This will store the data that you had entered.
16 Amico Pipeline
InchHg / KPA / BAR selections
InchHg
Factory Default - InchHg
For InchHg mode, set the switch #4 to the ON position. The LED indicating InHg located next to the
VACUUM source reading will illuminate.
For KPA mode, set the switch #4 to the OFF position and the switch #9 to the ON position. The LED
indicating KPA located next to the VACUUM source reading will illuminate.
For BAR mode, the KPA indicating source must be changed to BAR by use of a label. Set the switch
#4 to the OFF and the switch #9 to the OFF position. The LED indicating BAR located next to the
VACUUM source reading will illuminate.
KPA
BAR
COMMON SETTINGS FOR PRESSURE AND VACUUM
Repeat Alarm Enable/Disable
Factory Default - Disable
Disable
Set switch #5 to the OFF position to disable the repeat alarm.
NOTE: When the repeat alarm function is disabled, the alarm will not repeat.
Enable
Enable Mode: (Factory Default 30 min, when enabled).
Set switch #5 to the ON position.
PLEASE NOTE: The Module with the Lowest set Repeat Time is the one that controls the Repeat
Time. For example if one Module is set for 5min and one for 30min and both are Repeat Alarm enabled, the Alarm will now Repeat every 5min.
www.amico.com 17
SETTING FACTORY DEFAULT
Amico Microprocessor Based Alarm
USER RESPONSIBILITY
The information contained in this Installation and Operation MaintenanceManual, pertains only to the ALERT-2 microprocessor based digital alarm.This product will perform to conformity with the descriptions contained in thismanual, when assembled, operated, maintained and serviced in accordancewith the installation instructions provided.
The alarm must be checked periodically. Parts that are broken, missing,worn, distorted or contaminated, must be replaced immediately. Should suchrepair or replacement become necessary, please contact Amico Corporationor their distributors.
All alarms should not be repaired, or altered without prior written or verbalapproval of Amico Corporation or it’s distributors. Failure to comply will voidall warranty on the alarm.
Statements in this manual preceded by the words
WARNING,CAUTION,
DANGERand
NOTEare of special significance. Please read these sections
carefully.
WARNING:denotes steps which can prevent injury.
To quickly reset the module (Pressure or Vacuum) to the factory default settings as follows:
- Pressure: High set-point 60 Psi, Low set-point 40 Psi.
- Nitrogen & HP Air: High set-point 195 Psi, Low set-point 140 Psi.
- Vacuum: Low set-point 12 inchHg.
- No Repeat alarm, but set for 30 min..
1. Set switch #8 to the ON position.
2. Turn the power o (wait 5 seconds) then back on.
3. Set switch #8 to the OFF position.
The module is now in the default mode.
SETTING GAS IDENTIFICATION SWITCHES
PLEASE NOTE: DO NOT tamper with switches #1, #2 and #3 on the dip-switch. Tampering with these positions will
result in an error message being displayed (EO2) and will disable the electrical interlock from the gas specic sensor.
Changes to these switches should only be done by properly trained personnel, when circuit
boards have to be changed in the eld.
Switches # 1, #2 and #3 are used for the gas identication of the display module. These will be set at the factory and
should not be tampered with in the eld.
18 Amico Pipeline
CHART OF GAS SPECIFIC SETTINGS OF DIP-SWITCHES
Alert - 2 Series
SETTING GAS IDENTIFICATION SWITCHES
NOTE: DO NOT TAMPER WITH SWITCHES #1, 2 AND 3ON THE DIP-SWITCH. TAMPERING WITH THESEPOSITIONS WILL RESULT IN AN ERROR MESSAGEBEING DISPLAYED (EO2) AND WILL DISABLE THEELECTRICAL INTERLOCK FROM THE GAS SPECIFICSENSOR.
CHANGES TO THESE SWITCHES SHOULD ONLY BEDONE BY PROPERLY TRAINED PERSONNEL, WHENCIRCUIT BOARDS HAVE TO BE CHANGED IN THE FIELD.
Switches # 1, 2 and 3 are used for the gas identification of thedisplay module. These will be set at the factory and should notbe tampered with in the field.
PLEASE NOTE: The above repeat alarm only applies to the Master/NEMA 4 alarm, for the 2 in 1 please
refer to page 17.
www.amico.com 19
SIGNAL INPUT SELECTION
1 HR
12
HR
24
HR
Version
3 4
Factory Default - Normally Closed as per NFPA 99.
The Amico alarm can detect eld devices in the Normally Open or Normally Closed position.
For Normally Closed Set switch #3 to the OFF position.
For Normally Open Set switch #3 to the ON position.
PLEASE NOTE: The above signal input selection, applies to both alarm systems - the Master/NEMA 4
and the 2 in 1.
MAINTENANCE MODE
Factory Default - Disabled
The Maintenance (or Latch) mode is used to allow hospital personnel to identify loose wiring or faulty source equipment.
By putting the master module into “Latch” mode, any alarms received; even transient ones, will be latched-on so that
maintenance personnel can identify the source of the problem. The Maintenance mode will disable the automatic reset,
if a fault condition has been rectied. The alarm indicator can only be turned-o by pushing the “alarm silence” button
on the annunciator module twice. The “Maintenance” LED will illuminate whenever the maintenance mode is enabled.
Disable Set switch #4 to the OFF position.
Enable Set switch #4 to the ON position.
20Amico Pipeline
THE MASTER
MODULE SWITCH
5U6U
THE MASTER
MODULE SWITCH
THE 2 IN 1 SWITCH
2U
U4
U3
U4
123
4
NO
S1
----------
++++++++++
1HC2HC3HC4HC5HC6HC7HC8HC9HC01HC
Version 3Version 4
MASTERBOARD 10-CHANNEL ACTIVATION DIP-SWITCHES
The 10 Channel dip-switch is responsible for activating and
deactivating each individual corresponding channel on the
Masterboard.
ALL CHANNELS
ACTIVATED
ALL CHANNELS
DEACTIVATED
NOTE:
Version 3:Jumper any unused points on
the Master module
Version 4:Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
www.amico.com 21
Troubleshooting Guide
SYMPTOMCAUSECORRECTIVE ACTION
1. An error code appears on one or
more display modules.
2. No power on the alarm.
(No LED’s illuminated).
a. The Microprocessor detected a
fault and has shutdown.
b. Faulty wire connection between
the sensor and display module.
a. AC power not available.
1. Turn power switch to OFF position.
Wait for at least 5 seconds before
turning on the power. The program
will reset itself.
2. Check error codes at the end of this
section.
1. Ensure that the ON/OFF switch on the
power supply module is turned ON.
2. AC wiring not connected.
3. Check the building electrical breaker
to ensure that the power is ON.
4. Check the voltage at the terminal
block above the transformer. Ensure
that 115 VAC or 220 VAC is being
supplied.
b. Fuse is blown.
c. DC power plug not connected
to the annunciator module.
d. Defective Ribbon cable.
1. Check the fuse. The fuse is located on
the upper-right corner of the system
power supply. Replace the fuse if it
is defective. See Appendix A and P.
1. Ensure that the DC power plug is
rmly in it’s socket on the annunciator
module.
2. Replace System Power Supply unit if
all the above steps fail to resolve the
problem.
1. Replace the ribbon cable.
22 Amico Pipeline
SYMPTOMCAUSECORRECTIVE ACTION
3. Power light on the annunciator
module is ON but LED’s on other
modules are not on.
4. No audible alarm and LED ’s are
not illuminating.
5. Audible signal will not silence.
a. DC power cable is not connected
to the annunciator module.
a. DC power cable is disconnected
or loose.
a. Faulty display module.
1. Ensure that the DC power cable is
rmly in it’s socket on the annunciator
module.
2. Ensure that the module(s) on the
Frame/Module assembly are all
connected to the ribbon cable.
3. Replace the annunciator module.
1. Ensure that the DC power cable from
the system power supply is connected
to the annunciator module snugly.
2. Depress “TEST” button. If the LED’s
come on and there is no audible,
replace the annunciator module.
If this does not work, try solutions
to problem #2.
1. Disconnect the ribbon cable from
the back of the faulty display module(s)
and replace the module(s).
6. Alarm condition exists but
LED’s are not illuminating.
b. Connection of the DC power
cable from system power supply
to annunciator module is loose.
c. Faulty annunciator module.
a. Display module not properly
calibrated.
1. Disconnect the DC power cable from
the annunciator module and then
reconnect. If audible alarm still persists,
replace the System Power Supply unit.
1. Replace annunciator module.
1. Ensure that the system was properly
ordered.
Factory default settings:
Mid Pressure:
Hi Pressure 60 Psi
Low Pressure 40 Psi
Vacuum:
Low Vacuum 12 inHg
High Pressure:
Hi: Nitrogen & Air 195 Psi
Low: Nitrogen & Air 140 Psi
www.amico.com 23
SYMPTOMCAUSECORRECTIVE ACTION
2. If calibration is required, refer to
setting HIGH and LOW calibration
procedure on page 18/19.
7. Gas reading incorrect.
b. Faulty display module.
a. Loose connection of DISS
ttings.
b. Sensor module is not properly
wired to the display module.
c. Defective sensor or requires
calibration.
d. The ribbon cable not properly
connected to the display module.
e. Defective display module.
1. Replace the display module.
1. Ensure that the sensor module
is properly connected to the DISS
demand check-valve.
1. Ensure that the sensor module is
properly wired to the display module
by using wiring diagram in Appendix
D or E.
1. Replace the sensor module.
1. Pull out the ribbon cable and connect
it back in again, while ensuring that it
is seated properly.
1. Replace the display module.
Error Code Messages on the Display Module
SYSTEMCAUSECORRECTIVE ACTIONPAGE
E01
E02
E03
E04
E06
E07
No sensor is connected.
Sensor and Display Module mismatched.
The High set-point was set below the Low
set-point or vice versa.
Incorrect type of Sensor connected, (i.e. 250
Psi sensor on a 100 Psi range).
Cable between the sensor and display
module shorted out or reversed polarity.
Out of Calibration / Sensor not reading gas
Connect a sensor.
Ensure that the Sensor and Display Module
are for the same gas.
Recalibrate the High and Low setpoint to
proper values.
Connect the correct Sensor to the matching Display Module.
Reverse polarity or replace cable if defective.
Replace the sensor module
41 / 42
19
15/16
41 / 42
41 / 42
24Amico Pipeline
Model Numbers
AREA ALARM
1 module =
A2AR-E-X
2 gang back box
1 module =
A2AR-E-X
3 gang back box
2 modules =
A2AR-E-XX
3 gang back box
1 module =
A2AR-E-X
4 gang back
box
2 modules =
A2AR-E-XX
4 gang back
box
3 modules =
A2AR-E-XXX
4 gang back
box
4 modules =
A2AR-E-XXXX
5 gang back box
4 modules =
A2AR-E-XXXX
7 gang back box
5 modules =
A2AR-E-XXXXX
7 gang back box
6 modules =
A2AR-E-XXXXXX
7 gang back box
A2AR-L-XXXXXX
The Letter “L” Represents
the Langauge:
U = English (NFPA)
E = English (CSA)
F = French (CSA)
S = Spanish (NFPA)
R = Remote/Local Sensors
C = Conversion
The Letter “X” Denes
the Type of Gas:
Oxygen = O
Medical Air = A
MedVac = V
Nitrous Oxide = 2
Nitrogen = N
Carbon Dioxide = C
WAGD = W
AGSS = E
Instrument Air = I
Example: 4 Gases, English ISO, Remore/Local pressure sensors,
Oxygen, MedVac, Medical Air and Nitrous Oxide = A2AR-E-OVA2
NOTE: Please specify the gang back box on each alarm.
MASTER ALARM
10 functions =
A2M-E-10
2 gang back box
10 functions =
A2M-E-10
3 gang back box
20 functions =
A2M-E-20
3 gang back box
10 functions =
A2M-E-10
4 gang back box
30 functions =
A2M-E-30
4 gang back box
40 functions =
A2M-E-40
5 gang back box
40 functions =
A2M-E-40
7 gang back box
50 functions =
A2M-E-50
7 gang back box
C = Conversion
A2M(C)-L-20
The Letter “L” Represents
the Langauge:
E = English (CSA/NFPA)
F = French (CSA)
S = Spanish (NFPA)
20 functions =
A2M-E-20
4 gang back box
Example: 2 Modules, English (20 Functions) = A2M-E-20
NOTE: Please specify the gang back box on each alarm.
60 functions =
A2M-E-60
7 gang back box
www.amico.com 25
COMPACT ALARM
1 module =
A2ADR-L-X
2 gang back box
3 modules =
A2ADR-L-XXXXXX
4 gang back box
R = Remote/Local Sensors
C = Conversion Series
1 module =
A2ADR-L-XX
3 gang back box
2 modules =
A2ADR-L-XXXX
3 gang back box
1 module =
A2ADR-L-XX
4 gang back box
2 modules =
A2ADR-L-XXXX
4 gang back box
NOTE: Please specify the gang back box on each alarm.
4 modules =
A2ADR-L-XXXXXXXX
5 gang back box
4 modules =
A2ADR-L-XXXXXXXX
7 gang back box
5 modules =
A2ADR-L-XXXXXXXXXX
7 gang back box
6 modules =
A2ADR-L-XXXXXXXXXXXX
7 gang back box
The Letter “L” Represents
the Langauge:
U = English (NFPA)
E = English (CSA)
F = French (CSA)
S = Spanish (NFPA)
A2ADR-L-XXXXXXXXXXXX
The Letter “X” Denes
the Type of Gas:
Oxygen = O
Medical Air = A
MedVac = V
Nitrous Oxide = 2
Nitrogen = N
Carbon
Dioxide = C
WAGD = W
AGSS = E
Instrument Air = I
Example: English NFPA - Oxygen, Medical Air, MedVac, Nitrous Oxide,
Nitrogen, Carbon Dioxide = A2ADR-U-OAV2NC
NEMA 4 ALARM
A2MN-L-XX
The Letter “L” Represents
the Langauge:
E = English (CSA/NFPA)
F = French (CSA)
S = Spanish (NFPA)
26Amico Pipeline
1
2
3
4
5
6
“X’’ indicates the order of gases, as shown above.
The Letters “XX” Denes the
Number of Functions:
10 = 10 Functions
20 = 20 Functions
7
8
9
101112
COMPACT MASTER COMBINATION ALARM
Use the Model number for the Area Alarm and add “M” for each Master module.
Example: 3 Gases, English ISO, Remote/Local Sensors, Oxygen, Vacuum, Medical Air and 2 Master Modules = A2ADR-E-OVAMM.
2 modules = A2ADR-U-XXM
3 gang back box
2 modules = A2ADR-U-XXM
4 gang back box
3 modules = A2ADR-U-XXMM
4 gang back box
3 modules = A2ADR-U-XXXXM
4 gang back box
NOTE: Please specify the gang back box on each alarm
1
3
5
7
9
4 modules = A2ADR-U-XXXXMM
5 gang back box
4 modules = A2ADR-U-XXXXMM
7 gang back box
5 modules = A2ADR-U-XXXXXXMM
7 gang back box
6 modules = A2ADR-U-XXXXXXMMM
7 gang back box
2
4
R = Remote/Local Sensors
C = Conversion
U = English (NFPA)
E = English (CSA)
F = French (CSA)
S = Spanish (NFPA)
6
8
101112
Each “M” Stands for 10
Functions
A2ADR-U-XXXXXXMMM
The Letter “X” Denes the
Type of Gases::
Oxygen = O
Medical Air = A
MedVac = V
Nitrous Oxide = 2
Nitrogen = N
Carbon Dioxide = C
WAGD (NFPA) = W
AGSS (ISO) = E
Instrument Air = I
www.amico.com 27
2 in 1 Area Alarm
1 MODULE=
A2AR-E-1
2 gang back box
1 MODULE=
A2AR-E-1
3 gang back box
2 MODULES=
A2AR-E-11
3 gang back box
1 MODULE=
A2AR-E-1
4 gang back box
2 MODULES=
A2AR-E-11
4 gang back box
Example: 4 Gases, English CSA, Remote/Local pressure sensors, Oxygen, Medical Air, MedVac, Nitrous Oxide = A2AR-E-1111
(O,A,V,2)
3 MODULES=
A2AR-E-111
4 gang back box
4 MODULES=
A2AR-E-1111
5 gang back box
4 MODULES=
A2AR-E-1111
7 gang back box
5 MODULES=
A2AR-E-11111
7 gang back box
6 MODULES=
A2AR-E-111111
7 gang back box
NOTE: Please specify the gang back box on each alarm.
R = Remote/Local Sensors
C = Conversion Series
A2AR-L-1111
The Letter “L” Represents
the Langauge:
U = English (NFPA)
E = English (CSA)
F = French (CSA)
S = Spanish (NFPA)
The Number of the Digit “1”
Denes the Number of Gases:
Relays on the annunciator are fail safe for
version 3.1 or newer.
Relays are not fail safe for version 3.0 or older.
www.amico.com 39
Appendix C
Wiring Diagram Automatic Voice/Pager Dialing System
Annunciator
Module
NOTE:
Relays on the annunciator are fail safe for
version 3.1 or newer.
1
K
SILENCETEST
5
U
2
U
NO NC COM GND +12V
4
U
M
R
O
3
N
U
O
IS
DC Power cable
from Power Supply
1
U
NOTE:
Relays on the annunciator are failsafe for Version 3.1 or newer.
1
J
Relays are not fail safe for Versions
3.0 or older.
Relays are not fail safe for version 3.0 or older.
40 Amico Pipeline
Appendix D
Wiring Diagram Area Display Module - Local Sensor
OXYGEN
# 22 Gauge twisted
pair shielded cable
6”-8” [0.1m-0.2m] supplied
www.amico.com 41
2,500750
Appendix E
Wiring Diagram Area Display Module - Remote Sensor
NOTE:
For multiple sensors, a multi-conductor
twisted pair, shielded cable should be used.
42Amico Pipeline
Appendix F
Wiring Diagram 2 in 1 Display Module
OXYGEN
Dry contacts for
remote monitoring of
High and Low alarms
2 in 1
Module
Sensor
Module
BlackRed
NO NC COM NO NCCOM
- +
# 22 Gauge twisted
pair shielded cable
6”-8” [0.1m-0.2m] supplied
Source Equipment
C
NC
C
NC
C
NC
C
-----
HC2HC3HC4HC5HC
+++++
1
NC
C
NC
Dry contacts
only, no
voltage
Note:
Jumper any
unused points
www.amico.com 43
Appendix G
2,500750
Wiring DiagramCompact Module
NOTE:
Version 3:Jumper any unused points on
the Master module
Version 4:Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
44Amico Pipeline
Appendix H
2,500750
Wiring Diagram Area Module to Master Module
NOTE:
Version 3:Jumper any unused points on
the Master module
Version 4:Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
www.amico.com 45
Appendix I
2,500750
Wiring Diagram 2 in 1 Module to Master Module
NOTE:
Version 3:Jumper any unused points on
the Master module
Version 4:Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
46Amico Pipeline
Appendix J
Wiring Diagram Abnormal Condition
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
Source
Equipment
NOTE:
Version 3:Jumper any unused points on
the Master module
Version 4:Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
SW-2
www.amico.com 47
Appendix K
Wiring Diagram Area Slave
Alarm #1
SLAVE
SENSOR LOW ALARM
- + - +
NO NC COM
HIGH ALARM
NO NC COM
OXYGENMEDICAL AIRMEDVAC
SLAVE
SENSOR LOW ALARM
- + - +
U12 U11
HIGH ALARM
NO NC COM
NO NC COM
U2
K1 K2
U4
UP
S1
DOWN
S2
S3
ON
1
2
3
4
5
U1
U3
6
7
8
U3
R41
R42
R19
SLAVE
SENSOR LOW ALARM
HIGH ALARM
NO NC COM
NO NC COM
- + - +
U2
K1 K2
U4
UP
S1
DOWN
S2
S3
ON
1
2
3
4
5
U1
U12 U11
R43
U3
6
7
8
U3
R41
R42
R19
SLAVE
- + - +
U12 U11
R43
SENSOR LOW ALARM
NO NC COM
U2
HIGH ALARM
NO NC COM
K1 K2
U4
UP
S1
DOWN
S2
S3
ON
1
2
3
4
5
U1
U3
6
7
8
U3
R43
R41
R42
R19
Alarm #2
SLAVE
SENSOR LOW ALARM
- + - +
NO NC COM
Note: Set the gas specific
dip switch on each area
slave panel
HIGH ALARM
NO NC COM
U10
SLAVE
- + - +
U12 U11
U10
U6U7U8
PAL1
PAL2
SENSOR LOW ALARM
NO NC COM
U2
U4
U1
U6U7U8
PAL1
PAL2
U9
U9
HIGH ALARM
NO NC COM
U3
U6U7U8
U10
PAL1
PAL2
SLAVE
U12 U11
- + - +
SENSOR LOW ALARM
NO NC COM
U2
U9
U13
HIGH ALARM
NO NC COM
K1 K2
U4
UP
S1
DOWN
S2
S3
ON
1
2
3
4
5
U1
U3
6
7
8
U3
R43
R41
R42
R19
U13
K1 K2
UP
S1
DOWN
S2
S3
ON
1
2
3
4
5
6
7
8
U3
R43
R41
R42
R19
U6U7U8
U10
PAL1
PAL2
U13
U9
U13
U10
U10
U12 U11
SLAVE
- + - +
U6U7U8
PAL1
PAL2
SENSOR LOW ALARM
NO NC COM
U2
U4
U1
U6U7U8
PAL1
PAL2
U9
U13
HIGH ALARM
NO NC COM
K1 K2
UP
S1
DOWN
S2
S3
ON
1
2
3
4
5
U3
6
7
8
U3
R43
R41
R42
R19
U9
U13
NOTE: “The slave alarm does not work with A2P-POWER-CONV, both Alarm must be attached the A2P-POWER-V2”
48 Amico Pipeline
Appendix L
Wiring Diagram Master/NEMA 4 Module
Source
Equipment
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
NOTE:
Version 3:Jumper any unused points on
the Master module
Version 4:Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
Note: Turn OFF dip-switches for any unused points(Location SW-2)
Dry Contacts only
No Voltage
SW-2
www.amico.com 49
Appendix M
Wiring Diagram Pressure Switch Connection to a Master Alarm
Master
Module
l a n g i S m r a l A w o L
Source
Equipment
C
NO
e l p r u P
Blue
Red
Vacuum
Green
(for Ground)
wiring code
Ground - Green
Common - Purple
Normally Closed -Red
Normally Open -Blue
Nitrogen
Switch for
High Alarm
NO
C
C NO NCC NO NC
Switch for
Low Alarm
n w o r B
e g n a r O
C
NC
l a n g i S m r a l A h g i H
wiring code
Circuit #1 for Low Circuit #2 for High
Common - Purple Common - Brown
Normally Closed - Blue Normally Closed - Orange
Normally Open - Red Normally Open - Yellow
e l p r u P
l a n g i S m r a l A w o L
d e R
Six Leads
18” Long (Approx.)
NO C
3/4” NPT Conduit
Connection
Circuit No. 1
Calibrated Dial
Circuit No. 2
Calibrated Dial
9/32” x 5/8”
Mounting
Hole (Typ.)
1/4” NPT
Gas Service
Connection
not required
e u l B
2 - 1/2”
3 - 1/2”
w o l l e Y
Green
(for Ground)
(OXY, AIR, N2O, CO2)
Circuit No. 1Circuit No. 2
Blue
Purple
Red
C
NO
Gas
Brown
Orange
NC
C
Yellow
NOTE: There are 2 NIT switches, one for high alarm and one for low alarm.
50Amico Pipeline
Appendix N
Wiring Diagram Computer Interface Module
Computer
Interface
Module
Source
Equipment
Dry contacts for interface with:
Building Management System.
Contacts are Common
and NC, open on Alarm.
Ratings:
24VDC 0.1A
Master
Module
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
NOTE:
Version 3:Jumper any unused points on
the Master module
Version 4:Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
SW-2
www.amico.com 51
Appendix O
Wiring Diagram Master to Slave Module
"Master 1" "Master 2"
+
-
0 1 H C
+
-
9 H C
+
-
8 H C
+
-
7 H C
+
6 H C
-
+
-
5 H C
+
4 H C
-
+
3 H C
-
+
2 H C
-
+
-
1 H C
+
-
0 1 H C
+
-
9 H C
+
-
8 H C
+
-
7 H C
+
-
6 H C
+
-
5 H C
+
-
4 H C
+
-
3 H C
+
-
2 H C
+
-
1 H C
NOTE:
Version 3:Jumper any unused points on
the Master module
Version 4:Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
52Amico Pipeline
Source
Equipment
(typical)
C
NC
Appendix P
Technical Specication
Supply Voltage: 115 to 220 VAC - 50 to 60 Hz
Current Draw: 1 Amp.Max.
Fuse (1/4 * 1-1/4): Fast Blow 1 Amp.
Cable requirement:
Area Display Module to Remote Sensor:
Distance: Maximum 2,500 feet [750 m]
Cable: Belden # 8451 or equivalent.
#22 gauge shielded, twisted pair. (For multiple sensors a multi-conductor
twisted pair, shielded cable should be used).
Signal: 30 VDC - 1.0 Amps.
60 VDC - 0.3 Amps.
125 VAC - 0.5 Amps.
Master Module to Source equipment:
Distance: Maximum 10,000 feet [3,000 m]
Cable: Minimum #22 gauge wire (does not have to be shielded, twisted pair).