Amico Nema 4 Master Alarm User Manual

Operating & Maintenance Manual
www.amico.com
Alert-2 Microprocessor Based Digital Alarm System v5.9
Contents
User Responsibility 5
Features
Description of the Alarm
Shipment Details The Alarm Back Box The Frame/Module Assembly Description of the Modules 7-10 Common to all Alarms System Power Supply Annunciator Module Blank Module Area Alarm Area Display Module 2 in 1 Display Module Compact Display Module Sensor Module Master Alarm Master/Nema 4 Status Module Computer Interface Module
Installation Guide 10 - 11
The Alarm Back Box For Local Sensor Only Standing Pressure Test Frame/Module Assembly Sensor Local Remote
Wiring 12 - 14
System Power Supply Annuciator Module Sensor Module Local Remote Area Display Module 2 in 1 Display Module
2 Amico Pipeline
2 Amico Pipeline
Area Display Module 2 in 1 Display Module Compact Display Module Master/NEMA 4 Status Module Computer Interface Module Closing the Frame Module Assembly
Annunciator Module 14
Noise Level Control Control of Remote Alarm Buzzer
Steps to Re-Calibrate the Sensor from Area Module v4.0 15
Area, 2 in 1, Compact Display Module 15 - 19
PSI/kPa/ BAR selection Inch Hg/kPa/BAR selections Common Settings for Pressure and Vacuum Setting Factory Default Setting Gas Identication Switches Chart of Gas Specic Settings of Dip-Switches
Master/NEMA 4 Status Module 19 - 21
Repeat Alarm Signal Input Selection Maintenance Mode
Troubleshooting Guide 22 - 24
Error Code Messages on the Display Module 24
Model Numbers 25 - 28
Area Alarm Master Alarm Compact Alarm NEMA 4 Alarm Compact Master Combination Alarm 2 in 1 Area Alarm
Spare Part Numbers 29 - 31
www.amico.com 3
Dimensions 32 - 37
Area Alarm Master Alarm Compact Alarm Compact Master Alarm Combination 2 in 1 Alarm NEMA 4
Appendix A - Wiring Diagram: Auto-Switching Power Supply 38
Appendix B - Wiring Diagram: Annunciator 39
Appendix C - Wiring Diagram: Automatic Voice/Pager Dialing System 40
Appendix D - Wiring Diagram: Area Display Module (Local Sensor) 41
Appendix E - Wiring Diagram: Area Display Module (Remote Sensor) 42
Appendix F - Wiring Diagram: 2 in 1 Display Module 43
Appendix G - Wiring Diagram: Compact Module 44
Appendix H - Wiring Diagram: Area Module to Master Module 45
Appendix I - Wiring Diagram: 2 in 1 Module to Master Module 46
Appendix J - Wiring Diagram: Abnormal Condition 47
Appendix K - Wiring Diagram: Area Slave 48
Appendix L - Wiring Diagram: Master/NEMA 4 Module 49
Appendix M - Wiring Diagram: Pressure Switch Connection to a Master Alarm 50
Appendix N - Wiring Diagram: Computer Interface Module 51
Appendix O - Wiring Diagram: Master to Slave Module 52
Appendix P - Technical Specication 53
Notes 54 - 55
4 Amico Pipeline
User Responsibility
Amico Microprocessor Based Alarm
USER RESPONSIBILITY
The information contained in this Installation and Operation Maintenance Manual, pertains only to the ALERT-2 microprocessor based digital alarm. This product will perform to conformity with the descriptions contained in this manual, when assembled, operated, maintained and serviced in accordance with the installation instructions provided.
The alarm must be checked periodically. Parts that are broken, missing, worn, distorted or contaminated, must be replaced immediately. Should such repair or replacement become necessary, please contact Amico Corporation or their distributors.
All alarms should not be repaired, or altered without prior written or verbal approval of Amico Corporation or it’s distributors. Failure to comply will void all warranty on the alarm.
Statements in this manual preceded by the words
WARNING, CAUTION,
DANGER and
NOTE are of special significance. Please read these sections
carefully.
WARNING: denotes steps which can prevent injury.
CAUTION: denotes steps which can prevent damage to equipment.
DANGER: denotes steps which can prevent electrical shock to equipment
or to prevent serious injury and/or death.
The information contained in this Installation and Operation Maintenance Manual, pertains only to the ALERT-2 micro­processor based digital alarm. This product will perform to conformity with the descriptions contained in this manual, when assembled, operated, maintained and serviced in accordance with the installation instructions provided.
The alarm must be checked periodically. Parts that are broken, missing, worn, distorted or contaminated, must be replaced immediately. Should such repair or replacement become necessary, please contact Amico Corporation or their distributors.
All alarms should not be repaired, or altered without prior written or verbal approval of Amico Corporation or its distributors. Failure to comply will void all warranty on the alarm.
Statements in this manual preceded by the words WARNING, CAUTION, DANGER and NOTE are of special signicance. Please read these sections carefully.
NOTE: Amico strongly recommends that alarms be checked annually by qualied sta.
WARNING: denotes steps which can prevent injury.
CAUTION: denotes steps which can prevent damage to
Introduction
The AMICO Medical Gas Alarm System (ALERT-2) incorporates the latest microprocessor technology for alarm and surveillance systems. The alarm has been designed to provide user exibility and reliability. This manual will enable the customer to install, use and maintain the alarm properly.
equipment.
DANGER: denotes steps which can prevent electrical shock to equipment or to prevent serious injury and/or death.
All Gases or Vacuum are displayed with large Red LED’s for clear visibility. To facilitate the monitoring function by hospital personnel, a trend bar is provided to show the direction of the gas/vacuum pressure. Under normal operation, the gas trend indicator will be in the GREEN - OK position. If the gas pressure approaches alarm condition, the trend indicator will display a YELLOW - Caution indicator. If an alarm condition occurs, a RED-Alarm indicator will be displayed and the buzzer will sound.
There are two buttons located on the front face of the Annunciator module. They are the “TEST” and “ALARM MUTE” buttons. The function of the “Test” button is to verify that the buzzer and all the alarm LED’s are in normal working condition. The function of the “Alarm Mute” button is to silence an alarm that has occurred.
A master status module monitors source equipment such as: Oxygen, Nitrous Oxide, Air compressors, Vacuum pumps, Air dryers, high/low pressure switches, etc. This module can be connected to a “Building Management System”, with a piggy-back computer interface board, that attaches to the master module.
www.amico.com 5
The Alert-2 microprocessor based digital alarm system complies with NFPA-99.
The Alert-2 microprocessor based digital alarm system is UL Listed to U.S. and Canadian safety standards.
FEATURES
Individual Microprocessor on each display, sensor and master module.
Gas specic sensors can be mounted locally or remote, up to 2,500 feet, [750m] utilizing 22 gauge twisted pair (shielded cable should be used).
DISS gas specic sensor housed in a tamper proof enclosure. The Sensor Module is housed in an anodized aluminum and nickle-plated brass enclosure to act as an interference barrier.
The Sensor Module is the smallest computer-calibrated temperature-compensated sensor in the industry.
True digital LED display and trend indicator for each service monitored.
Illuminated LED display that is visible at an angle and in dim lighting conditions.
PSI, kPa or BAR display (switch selected).
Self diagnostic circuitry with error display for problem identication.
Highly accurate Solid State Pressure piezo-resistive transducer.
Adjustable repeat alarm (1 to 60 minutes/or o) for the Area, 2 in 1 Alarm and Compact Alarm.
Adjustable repeat alarm (1, 12, 24 hours/or o) for the Master Alarm.
Dry contacts for remote monitoring of High and Low alarm status on the Area, 2 in 1 and Compact Alarm display module.
Modules are factory mounted on a hinged frame assembly for ease of installation and maintenance.
Field programmable push buttons for adjustment of HI and LOW set-points on display module.
Area alarms available in 1 to 6 display modules.
Compact alarms available in 1 to 12 display modules.
Master alarms available in 10 to 60 points.
2 in 1 alarms available in 1 to 6 display modules with 5 to 30 master points.
Area, 2 in 1, and Compact Modules can be intermixed with Master Modules to create a combination alarm.
Built-In relay for remote annunciator applications.
Area, 2 in 1 and Compact Module indication for calibration (ashing bar graph).
6 Amico Pipeline
Description of the Alarm
SHIPMENT DETAILS
When you receive an ALERT-2 series alarm from Amico Corporation, the package will consist of two main sections; the Alarm Back Box and the Frame/Module Assembly. The Frame/Module assembly will be pre-congured, with the appro­priate display modules, based upon the customer’s specications.
THE ALARM BACK BOX
The Alarm Back Box contains the auto-switchable System Power Supply with an ON/OFF switch, a built-in fuse and ter­minal blocks (115 VAC, or 220 VAC). The back box also incorporates the pipe stubs for applications that require locally (in box) mounted sensors.
THE FRAME/MODULE ASSEMBLY
The Frame/Module Assembly consists of the frame and all the modules that are pre-assembled to the customers speci­cation. The hinged frame is designed to swing down from the back box to facilitate installation and servicing of the alarm. This design will reduce installation time and eliminate the risk of improper installation since all the modules are connected and tested at the factory.
Description of the Modules
The ALERT-2 alarm is divided into 4 or 7 main modules:
COMMON TO ALL ALARMS
1. SYSTEM POWER SUPPLY
The System Power Supply has been pre-installed into the back box assembly. The System Power Supply converts the AC voltage supply to the alarm into two voltages: 5 VDC (regulated) required by the microprocessor hardware and 15 VDC (unregulated) required by the buzzer and the LED’s. This unit also contains the main ON/OFF power switch, the transformer, the heat sink, the main fuse and fuse cover, the rectifying circuitry, the terminal blocks and the low voltage DC power cable for connecting this unit to the annunciator module. The System Power Supply can be easily removed and reinstalled by unscrewing it from the back box.
www.amico.com 7
2. ANNUNCIATOR MODULE
DESCRIPTION OF MODULES
The ALERT-2 alarm is divided into (4) or (7) main modules:
COMMON TO ALL ALARMS
1. SYSTEM POWER SUPPLY
The System Power Supply has been pre-installed into the back box assembly. The System Power Supply converts the AC voltage supply to the alarm into two voltages: 5 VDC (regulated) required by the microprocessor hardware and 15 VDC (unregulated) required by the buzzer and the LED’s. This unit also contains the main ON/OFF power switch, the transformer, the heat sink, the main fuse and fuse cover, the rectifying circuitry, the terminal blocks and the low voltage DC power cable for connecting this unit to the annunciator module. The System Power Supply can be easily removed and reinstalled by unscrewing it from the back box.
2. ANNUNCIATOR MODULE
The Annunciator Module contains the buzzer, a “Power On” LED, the “TEST” and the “ALARM MUTE” buttons. The function of the “TEST” button is to verify that the buzzer and all the LED’s are in working condi- tion. An alarm will be heard when this button is pushed and all the LED’s will light up. When the button is released, the alarm will silence. The “ALARM MUTE” button is used to silence an alarm that has occurred. This module also contains a fail-safe relay that de-energizes when the buzzer is activated. This relay can be used with the Amico remote buzzer”, for applications requiring a remote audible alarm (see Appendix B), for connection to an other Amico Alarm or a Building Management System.
3. BLANK MODULE
The Annunciator Module contains the buzzer, a “Power On” LED, the “TEST” and the “ALARM MUTE” buttons. The function of the “TEST” button is to verify that the buzzer and all the LED’s are in working condition. An alarm will be heard when this button is pushed and all the LED’s will light up. When the button is released, the alarm will silence. The “ALARM MUTE” button is used to silence an alarm that has occurred. This module also contains a fail-safe relay that de-energizes when the buzzer is activated. This relay can be used with the “Amico remote buzzer”, for applications requiring a remote audible alarm (see Appendix B), for connection to another Amico Alarm or a Building Management System.
3. BLANK MODULE
The Blank Module is used as a ller board for future provisions of the alarm.
AREA ALARM
4. AREA DISPLAY MODULE
The Area Display Module provides a digital display of the actual pressure/vacuum of a gas being monitored. In addition a gas trend indicator bar with HIGH and LOW alarms are displayed. The trend bar has three coloured LED’s: Green for Normal condition, YELLOW for Caution condition, and RED for high and low Alarm conditions.
Each display module contains a gas specic colour coded label (USA or ISO colours are available). A space is also provided, at the base of the module, to identify the location that the display module monitors. The display module is eld adjustable for pressure/vacuum settings, repeat alarm, and units of measure. Whenever the module is in calibration mode, the bargraph is ashing, indicating the calibration mode. Dry contacts for high and low alarms are available for remote monitoring of each module.
5. 2 IN 1 DISPLAY MODULE
The 2 in 1 Display Module provides a digital display of the actual pressure/vacuum of the gas being monitored. In addition, a gas trend indicator bar with High and Low alarms are displayed. This module has two coloured LEDs - Green for Normal conditions and Red for High and Low alarm conditions. It is eld adjustable for pressure/vacuum settings, repeat alarms, and units of measure. Dry contacts for high and low alarms are available for remote monitoring of each module.
Each module will continuously monitor up to 5 signals from source equipment or pressure switches. If any of the signals being monitored go into an alarm condition, a Red LED will illuminate and the audible alarm will sound.
PLEASE NOTE: Contacts located on back of module are Dry Contacts only. DO NOT apply any voltage.
8 Amico Pipeline
6. COMPACT DISPLAY MODULE
The Compact Display Module shall have 2 displays in 1 board. The Compact Module provides a digital display of the actual pressure/vacuum of a gas being monitored. In addition a gas trend indicator bar with High and LOW alarms are displayed. The trend bar as two colored LED’s: GREEN for Normal and RED for High and Low condition.
Each display module contains a gas specic colour coded label (USA or ISO colours are available). The Display Module is eld adjustable for pressure/vacuum settings, repeat alarm, and unit of measure. Dry contacts for high and low alarms are available for remote monitoring of each module.
7. SENSOR MODULE
The Sensor Module contains the transducer which converts the pressure/vacuum pres­sure source into a digital signal that is displayed on the Display Module. The sensor module shall be housed in an anodized aluminum and nickel-plated brass enclosure to act as an interference barrier also it is temperature compensated. Each sensor is clearly labeled and colour coded for the gas or vacuum being monitored. The sen­sor module contains a gas specic DISS tting to ensure correct connection of the proper sensor to the respective gas. Each sensor has been factory calibrated by computer for the specic gas shown on the sensor housing. If it is not connected to the appropriate gas display module, an error message (EO2) will be displayed.
MASTER ALARM
8. MASTER/NEMA 4 STATUS MODULE
Each Master Status Module will continuously monitor up to 10 signals from source equipment and pressure switches. If any of the signals being monitored go into an alarm condition, a Red LED will illuminate and the audible alarm will sound. The module has a slow and a rapid ashing LED rate. The last alarm condition always ashes at a rapid rate, while the previously acknowledged alarms always ash at a slow rate.
PLEASE NOTE: Contacts located on back of module are Dry Contacts only. DO NOT apply any voltage.
For Annual Test
• Reset power to make sure all LED’s light up
• Push and hold the ‘Test’ button to light up all LED’s and the audible alarm
www.amico.com 9
9. COMPUTER INTERFACE MODULE
MASTER ALARM
7. MASTER/NEMA 4 STATUS MODULE
Each Master Status Module will continuously monitor up to 10 signals from source equipment and pressure switches. If any of the signals being monitored go into an alarm condition, a red LED will illuminate and the audible alarm will sound. The module has a slow and a rapid flashing LED rate. The last alarm condition always flashes at a rapid rate, while the previously acknowledged alarms always flash at a slow rate.
PLEASE NOTE: Contacts located on back of module are Dry Contacts only. DO NOT apply any voltage.
8. COMPUTER INTERFACE MODULE
The Computer Interface Module is a piggyback board that fits on top of the master status module. This module plugs into the status module via a connector, located at the bottom end of the status module. There are three mounting screws provided to secure this module to the status module.
This module provides dry contacts for interface to a Building Manage- ment System”. The module is “Fail- Safe”, closed circuit monitoring.
NOTE: The computer interface module is not compatible with the 2 in 1 board.
The Computer Interface Module is a piggyback board that ts on top of the master status module. This module plugs into the status module via a connector, located at the bottom end of the status module. There are three mounting screws provided to secure this module to the status module. This module provides dry contacts for interface to a “Build­ing Management System”. The module is “Fail-Safe”, closed circuit monitoring.
PLEASE NOTE: The computer interface module is not compatible with the 2 in 1 board.
Installation
THE ALARM BOX
Install the back-box to the studs of the wall at the desired height. Ensure that the box is securely in place. The mounting brackets are adjustable to suit the thickness of the wall. MAKE SURE the box is parallel, squared and ush with the nished wall surface, to ensure that the frame assembly will t properly.
FOR LOCAL SENSOR ONLY
If the sensors are to be mounted locally (inside the back box), the pipe stubs must be connected to the pipeline. Using silver-brazing techniques, connect each pipe stub to it’s appropriate gas or vacuum while ensuring that the bottom of the pipe stub is wrapped with a damp cloth. BE CAREFUL not to damage the DISS check-valve by overheating the lower portion of the copper pipe. When the brazing of pipe stubs has been completed, the system can be pressure tested.
STANDING PRESSURE TEST
Perform a standing pressure test on the piping system as per NFPA-99 “Health Care Facilities”. Inspect all joints for leaks and make certain each gas is piped to a correspondingly labelled gas service.
FRAME/MODULE ASSEMBLY
Step #1 Remove the frame/module assembly from its protective box.
Step #2 Remove screws from the frame section (6 screws).
Step #3 Attach the at head screws (provided with frame in plastic bag) to the hinge. This will line up with holes
on the box.
Step #4 Attach the frame wire with 2 dome head screws (provided with frame in plastic bag).
Step #5 Close the frame panel and tighten the screws on the frame plate.
Step #6 Carefully place the front frame over the fastened plate. Refasten the screws that were removed in Step #2.
10 Amico Pipeline
CAUTION: The microprocessor circuitry on the ALERT-2 alarm contains sophisticated integrated semiconductors. If it
250psi
for Vacuum sensors
250psi
becomes necessary to remove a module, PLEASE hold the boards by the edges. DO NOT TOUCH any of the components on the board. Static discharge can cause the modules to malfunction, or become damaged.
SENSOR
LOCAL (Inside the Back Box)
1. Locate the gas specic sensor module to be installed.
2. In the back box, there are colour coded gas labels located
under the DISS Demand check valves. Each label identies where each sensor module is to be placed.
3. The sensor module contains a gas specic DISS tting. Push the sensor module hex-nut and nipple adapter up into the
demand check-valve. With a wrench, tighten the nut so that it makes a good seal.
NOTE: Pressure on sensors are not to exceed 250psi for Pressure
sensors and 30” for vacuum sensors.
The new style sensors can read pressure up to: Mid Pressure 99 Psi Hi Pressure 249 Psi Vacuum 30” Hg
REMOTE (Outside the Back Box)
1. Connect a Tee (supplied by others) to the pipeline with a 1/4” NPT female connection that will accept the DISS Demand check-valve.
OLD LOOK
NEW LOOK
2. Locate the gas specic sensor module to be installed.
3. Thread the DISS Demand check-valve into the correct gas
pipe line.
4. The sensor module contains a gas specic DISS tting. Push the sensor module hex-nut and nipple adapter up into the
demand check-valve. With a wrench, tighten the nut so that it makes a good seal.
OLD LOOK
NEW LOOK
www.amico.com 11
Wiring
Amico Microprocessor Based Alarm
USER RESPONSIBILITY
The information contained in this Installation and Operation Maintenance Manual, pertains only to the ALERT-2 microprocessor based digital alarm. This product will perform to conformity with the descriptions contained in this manual, when assembled, operated, maintained and serviced in accordance with the installation instructions provided.
The alarm must be checked periodically. Parts that are broken, missing, worn, distorted or contaminated, must be replaced immediately. Should such repair or replacement become necessary, please contact Amico Corporation or their distributors.
All alarms should not be repaired, or altered without prior written or verbal approval of Amico Corporation or it’s distributors. Failure to comply will void all warranty on the alarm.
Statements in this manual preceded by the words
WARNING, CAUTION,
DANGER and
NOTE are of special significance. Please read these sections
carefully.
WARNING: denotes steps which can prevent injury.
SYSTEM POWER SUPPLY
TURN OFF THE POWER SWITCH BEFORE CHANGING ANY MODULES AND/OR DISCONNECTING ANY CABLES, OR ELSE THE FUSE WILL BLOW TO PROTECT THE CIRCUITRY.
1. Ensure that the ON/OFF switch is in the OFF position.
2. Through the top left side of the back box, bring in the AC power wires. Knockouts are
provided for making conduit connections to the box. All wiring is to be installed according to local and national codes.
3. Connect the AC power to the terminal blocks as shown in the wiring diagram in Appendix A and as specied in the technical specication in Appendix P.
ANNUNCIATOR MODULE
1. The Annunciator Module has a female receptacle located at the top right side of the board (J1).
2. Connect the DC power cable from the System Power Supply into the receptacle connection located on
the annunciator module. The connector is keyed and can only be plugged in one way, (Appendix B).
SENSOR MODULE
LOCAL (Inside the Back Box)
1. The sensor module is provided with a 6”-8” [0.1m-0.2m] twisted pair of wires. One wire is Red (positive) and the other wire is Black (negative). Connect the wires to the display module as shown in Appendix D. Take the Red
wire fromthe sensor and attach it to terminal “Sensor +” on the display module. Take the Black wire from the sensor and attach it to terminal “Sensor -”. The terminal block on the display module is clearly marked for proper connection of the sensor wires.
2. Repeat the above procedures with the remaining sensor modules.
REMOTE (Outside the Back Box)
1. The sensor module is provided with a 6” - 8” [0.1m - 0.2m] twisted pair of wires. Connect the wires to a junction box (not supplied) located near the sensor as per the wiring diagram in Appendix E.
2. Connect a shielded twisted pair cable from the junction box to the back box assembly. Knockouts are provided throughout the alarm back box. Up to 2,500 feet [750m] of 22 Gauge, shielded twisted pair cable can be used.
12 Amico Pipeline
3. Connect the Red wire from the cable to the terminal on the display module marked ”Sensor +”. Connect the
black wire to terminal “Sensor -” (see Appendix D).
4. Repeat the above procedures with the remaining sensor modules using the wiring diagram in Appendix E.
PLEASE NOTE: When remote sensors are used, a shielded or twisted pair cable is required (BELDEN #8451 or equivalent,
supplied by others). Ensure that the proper gas sensor module is connected to its corresponding area display module, otherwise an error message (E02) will be displayed on the Area Display module.
AREA DISPLAY MODULE
1. If the dry contacts for High and Low alarm are to be used for remote monitoring, connect the wires to the appropriate
terminals, Com (Common), NO (Normally Open) or NC (Normally Closed), using the diagram in Appendix H.
2. See Appendix P for contact rating.
2 IN 1 DISPLAY MODULE
1. If the dry contacts for High and Low alarms are to be used for remote monitoring, connect the wires to the appropriate
terminals, COM (Common), NC (Normally Closed), or NO (Normally Open), using the diagram in Appendix F.
2. Pull the remote signal wires into the alarm panel. Make the connections to the terminal blocks located on the side of the status module. The wiring fail-safe normally closed (NC) connections from the source equipment. The signal level is 5 VDC. Please refer to Appendix I.
3. ENSURE that the unused terminals are jumpered. If this is not done, the terminals that have not been jumpered will go into alarm.
COMPACT DISPLAY MODULE
1. If the dry contacts for high and low are to be used for remote monitoring, connect the wires to the appropriate
terminals, Com (Common), NO (Normally Open), NC (Normally Closed), using the diagram in Appendix G.
2. See Appendix P for contact rating.
MASTER/NEMA 4 STATUS MODULE
1. Pull the remote signal wires into the alarm panel. Make the connections to the terminal blocks located on the side
of the status module. The wiring is fail-safe normally closed (NC) connections from the source equipment. The signal level is 5 VDC.
2. Make the appropriate wiring connections as per the wiring diagram in APPENDIX M and N.
3. For Version 3 ENSURE that the unused terminals in the master module are jumpered. If this is not done, the terminals
that have not been jumpered will go into alarm.
For Version 4, turn o switches for any unused points (SW2).
www.amico.com 13
COMPUTER INTERFACE MODULE
SILENCE
J
6
ALRM
NORM
SILENCE
LVL1 LVL2 LVL3
J5
1. Pull the remote signal wires from the “Building management system” into the alarm panel. Make the connections to the terminal blocks located on the side of the module. The wiring is fail-safe normally open, held closed, dry contacts to the monitoring equipment.
2. Make the appropriate wiring connections as per wiring diagram in Appendix N.
CLOSING THE FRAME/MODULE ASSEMBLY
1. Swing up the frame assembly, ensuring that the stopper wires are folded into the back box.
2. Screw in the frame module to the top of the back box assembly by using the screws provided with the frame/module
assembly. The alarm is now ready for use!
Annunciator Module
NOISE LEVEL CONTROL
Factory Default: 90 Decibels
To decrease noise level:
LVL1 LVL2 LVL3
J5
1. Locate jumper at J5. Move jumper to:
LVL1 = 90 dBa. LVL2 = 80 dBa. LVL3 = 70 dBa.
CONTROL OF REMOTE ALARM BUZZER
Factory Default: Normal Condition
To silence remote alarm buzzer, when silencing the annunciator module:
1. Locate jumper at J6. Move jumper to:
NORM =
TEST
Remote alarm buzzer will silence when annunciator module is silenced.
ALRM = Remote alarm will not silence when annunciator module is silenced. The buzzer will only silence when alarm condition has been cleared. Please refer to Appendix B.
14 Amico Pipeline
Steps to Re-Calibrate the Sensor from Area Module v4.0
1. Turn on Alarm
2. Set switches #8 & #10 the OFF position
3. Set switches #5 & #6 the ON position
4. The display will show the current reading of the pressure
5. Adjust the calibration, using the “UP” and “DOWN” push buttons, to the desired value.
6. Set switches #5 & #6 the OFF position
7. Turn on #10 if Aims is connected (do not turn on #8)
When you have completed step #7, the display module will automatically go into a “RESET” mode. This will store the data that you had entered.
Area, 2 in 1, Compact Display Module
A dip-switch is located on the back of the display module which is used to identify the gas of the display module. The dip-switch contains ten switch settings.
PRESSURE ONLY Factory Default: High = 60 Psi, Low = 40 Psi Repeat time = 30 min.
Dip-Switch
Dip-Switch
Dip-Switch
HIGH PRESSURE/NITROGEN Factory Default: High = 195 Psi, Low = 140 Psi Repeat time = 30 min.
2 in 1 Alarm
Board
During programming, the “Trend Bar” will Flash!
1. Set switch #6, #7 and #8 to the ON position.
2. The LED will display (HI-), followed by the current set point. Indicating the system is ready to accept a
new High set point. Adjust set point, using the “UP” and “DOWN” push buttons, to the desired value.
3. Set switch #7 to the OFF position.
4. The LED will display (LO-), followed by the current set point. Indicating the system is ready to accept a
new Low set point. Adjust set point, using the “UP” and “DOWN” push buttons, to the desired value.
5. Set switch #8 to the OFF position.
6. The LED will display (I-I-), followed by the current set point. Indicating the system is ready to accept a
new Repeat time set point. Adjust set point using the “UP” and “DOWN” push buttons, to the desired value. [(Display dd=Disabled) Range from 1 to 60 Minutes]
7. Set switch #6 to the OFF position.
Area Alarm
Board
Dip-Switches
Compact Alarm
Board (v2.02)
Compact Alarm
Board (v2.01)
www.amico.com 15
When you have completed step #7, the display module
PSI
Alert - 2 Series
2 in 1 Alarm
Board
Area Alarm
Board
will automatically go into a “RESET” mode. This will store the data that you had entered.
PSI / kPa / BAR selection
Factory Default - PSI
For PSI mode, set the switch #4 to the ON position. The LED PSI indicator located next to the GAS pressure reading will illuminate.
For kPa mode, set the switch #4 to the OFF position and switch #9 to the ON position. The LED kPa indicator located next to the GAS pressure reading will illuminate.
For BAR set the switch #4 to the OFF and the switch #9 to the OFF position. The LED kPa indicator located next to the GAS pressure reading will illuminate. (There is no separate indicator for BAR).
VACUUM ONLY Vacuum alarm set-point adjustment Factory Default: High = 30”Hg, Low = 12”Hg Repeat time = 30 min.
KPA
BAR
During programming, the “Trend Bar” will Flash!
1. Set switch #6, #7 and #8 to the ON position.
2. The LED will display (HI-), followed by the current set point. Indicating the system is ready to
accept a new High set point. Do not adjust this set point since the High set point is not used.
3. Set switch #7 to the OFF position.
4. The LED will display (LO-), followed by the current set point. Indicating the system is ready
to accept a new Low set point. Adjust set point, using the “UP” and “DOWN” push buttons, to the desired value.
5. Set switch #8 to the OFF position.
6. The LED will display (I-I-), followed by the current set point. Indicating the system is ready to
accept a new Repeat time set point. Adjust set point using the “UP” and “DOWN”push buttons, to the desired value. [(Display dd=Disabled) Range from 1 to 60 Minutes]
7. Set switch #6 to the OFF position.
When you have completed step #7, the display module will automatically go into a “RESET” mode. This will store the data that you had entered.
16 Amico Pipeline
InchHg / KPA / BAR selections
InchHg
Factory Default - InchHg
For InchHg mode, set the switch #4 to the ON position. The LED indicating InHg located next to the VACUUM source reading will illuminate.
For KPA mode, set the switch #4 to the OFF position and the switch #9 to the ON position. The LED indicating KPA located next to the VACUUM source reading will illuminate.
For BAR mode, the KPA indicating source must be changed to BAR by use of a label. Set the switch #4 to the OFF and the switch #9 to the OFF position. The LED indicating BAR located next to the VACUUM source reading will illuminate.
KPA
BAR
COMMON SETTINGS FOR PRESSURE AND VACUUM
Repeat Alarm Enable/Disable
Factory Default - Disable
Disable
Set switch #5 to the OFF position to disable the repeat alarm.
NOTE: When the repeat alarm function is disabled, the alarm will not repeat.
Enable
Enable Mode: (Factory Default 30 min, when enabled).
Set switch #5 to the ON position.
PLEASE NOTE: The Module with the Lowest set Repeat Time is the one that controls the Repeat Time. For example if one Module is set for 5min and one for 30min and both are Repeat Alarm en­abled, the Alarm will now Repeat every 5min.
www.amico.com 17
SETTING FACTORY DEFAULT
Amico Microprocessor Based Alarm
USER RESPONSIBILITY
The information contained in this Installation and Operation Maintenance Manual, pertains only to the ALERT-2 microprocessor based digital alarm. This product will perform to conformity with the descriptions contained in this manual, when assembled, operated, maintained and serviced in accordance with the installation instructions provided.
The alarm must be checked periodically. Parts that are broken, missing, worn, distorted or contaminated, must be replaced immediately. Should such repair or replacement become necessary, please contact Amico Corporation or their distributors.
All alarms should not be repaired, or altered without prior written or verbal approval of Amico Corporation or it’s distributors. Failure to comply will void all warranty on the alarm.
Statements in this manual preceded by the words
WARNING, CAUTION,
DANGER and
NOTE are of special significance. Please read these sections
carefully.
WARNING: denotes steps which can prevent injury.
To quickly reset the module (Pressure or Vacuum) to the factory default settings as follows:
- Pressure: High set-point 60 Psi, Low set-point 40 Psi.
- Nitrogen & HP Air: High set-point 195 Psi, Low set-point 140 Psi.
- Vacuum: Low set-point 12 inchHg.
- No Repeat alarm, but set for 30 min..
1. Set switch #8 to the ON position.
2. Turn the power o (wait 5 seconds) then back on.
3. Set switch #8 to the OFF position.
The module is now in the default mode.
SETTING GAS IDENTIFICATION SWITCHES
PLEASE NOTE: DO NOT tamper with switches #1, #2 and #3 on the dip-switch. Tampering with these positions will
result in an error message being displayed (EO2) and will disable the electrical interlock from the gas specic sensor.
Changes to these switches should only be done by properly trained personnel, when circuit boards have to be changed in the eld.
Switches # 1, #2 and #3 are used for the gas identication of the display module. These will be set at the factory and should not be tampered with in the eld.
18 Amico Pipeline
CHART OF GAS SPECIFIC SETTINGS OF DIP-SWITCHES
Alert - 2 Series
SETTING GAS IDENTIFICATION SWITCHES
NOTE: DO NOT TAMPER WITH SWITCHES #1, 2 AND 3 ON THE DIP-SWITCH. TAMPERING WITH THESE POSITIONS WILL RESULT IN AN ERROR MESSAGE BEING DISPLAYED (EO2) AND WILL DISABLE THE ELECTRICAL INTERLOCK FROM THE GAS SPECIFIC SENSOR.
CHANGES TO THESE SWITCHES SHOULD ONLY BE DONE BY PROPERLY TRAINED PERSONNEL, WHEN CIRCUIT BOARDS HAVE TO BE CHANGED IN THE FIELD.
Switches # 1, 2 and 3 are used for the gas identification of the display module. These will be set at the factory and should not be tampered with in the field.
CHART OF GAS SPECIFIC SETTINGS OF DIP-SWITCHES
O N
O N
O N
O N
O N
O N
O N
O N
4444444
43333333322222222111111115555555566666666777777778888888899999999
1010101010
10
#2 - off
#3 - off
#1 - off
#2 - off
#3 - off
Oxygen
Vacuum
Medical Air
Nitrous Oxide
#1 - off #2 - off #3 - on
#1 - off #2 - on #3 - off
#1 - off #2 - off #3 - off
Master/NEMA 4 Status Module
REPEAT ALARM
10
Nitrogen
10
Carbon Dioxide
#1 - on #2 - on #3 - on
#1 - on #3 - on
WAGD
#1 - on #2 - on
#2 - on #3 - on
HP Air
#1 - on
Factory Default - Disable
Version
3 4
3 4
Version
Disable Set switch #1 to the OFF position.
Set switch #2 to the OFF position.
Enable Set switch #1 to the ON position.
Enable 12 HR Set switch #1 to the OFF position.
5 min 1 HR
Set switch #2 to the OFF position.
15 min 12 HR
1 HR
12
HR
Set switch #2 to the ON position.
Enable 24 HR Set switch #1 to the ON position.
30 min 24 HR
24
HR
Set switch #2 to the ON position.
PLEASE NOTE: The above repeat alarm only applies to the Master/NEMA 4 alarm, for the 2 in 1 please refer to page 17.
www.amico.com 19
SIGNAL INPUT SELECTION
1 HR
12
HR
24
HR
Version
3 4
Factory Default - Normally Closed as per NFPA 99.
The Amico alarm can detect eld devices in the Normally Open or Normally Closed position.
For Normally Closed Set switch #3 to the OFF position.
For Normally Open Set switch #3 to the ON position.
PLEASE NOTE: The above signal input selection, applies to both alarm systems - the Master/NEMA 4 and the 2 in 1.
MAINTENANCE MODE
Factory Default - Disabled
The Maintenance (or Latch) mode is used to allow hospital personnel to identify loose wiring or faulty source equipment. By putting the master module into “Latch” mode, any alarms received; even transient ones, will be latched-on so that maintenance personnel can identify the source of the problem. The Maintenance mode will disable the automatic reset, if a fault condition has been rectied. The alarm indicator can only be turned-o by pushing the “alarm silence” button on the annunciator module twice. The “Maintenance” LED will illuminate whenever the maintenance mode is enabled.
Disable Set switch #4 to the OFF position.
Enable Set switch #4 to the ON position.
20 Amico Pipeline
THE MASTER
MODULE SWITCH
5U6U
THE MASTER
MODULE SWITCH
THE 2 IN 1 SWITCH
2U
U4
U3
U4
123
4
NO
S1
----------
++++++++++
1HC2HC3HC4HC5HC6HC7HC8HC9HC01HC
Version 3 Version 4
MASTERBOARD 10-CHANNEL ACTIVATION DIP-SWITCHES
The 10 Channel dip-switch is responsible for activating and deactivating each individual corresponding channel on the Masterboard.
ALL CHANNELS
ACTIVATED
ALL CHANNELS
DEACTIVATED
NOTE:
Version 3: Jumper any unused points on
the Master module
Version 4: Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
www.amico.com 21
Troubleshooting Guide
SYMPTOM CAUSE CORRECTIVE ACTION
1. An error code appears on one or more display modules.
2. No power on the alarm. (No LED’s illuminated).
a. The Microprocessor detected a fault and has shutdown.
b. Faulty wire connection between the sensor and display module.
a. AC power not available.
1. Turn power switch to OFF position. Wait for at least 5 seconds before turning on the power. The program will reset itself.
2. Check error codes at the end of this section.
1. Ensure that the ON/OFF switch on the power supply module is turned ON.
2. AC wiring not connected.
3. Check the building electrical breaker to ensure that the power is ON.
4. Check the voltage at the terminal block above the transformer. Ensure that 115 VAC or 220 VAC is being supplied.
b. Fuse is blown.
c. DC power plug not connected to the annunciator module.
d. Defective Ribbon cable.
1. Check the fuse. The fuse is located on the upper-right corner of the system power supply. Replace the fuse if it is defective. See Appendix A and P.
1. Ensure that the DC power plug is rmly in it’s socket on the annunciator module.
2. Replace System Power Supply unit if all the above steps fail to resolve the problem.
1. Replace the ribbon cable.
22 Amico Pipeline
SYMPTOM CAUSE CORRECTIVE ACTION
3. Power light on the annunciator module is ON but LED’s on other modules are not on.
4. No audible alarm and LED ’s are not illuminating.
5. Audible signal will not silence.
a. DC power cable is not connected to the annunciator module.
a. DC power cable is disconnected or loose.
a. Faulty display module.
1. Ensure that the DC power cable is rmly in it’s socket on the annunciator module.
2. Ensure that the module(s) on the Frame/Module assembly are all connected to the ribbon cable.
3. Replace the annunciator module.
1. Ensure that the DC power cable from the system power supply is connected to the annunciator module snugly.
2. Depress “TEST” button. If the LED’s come on and there is no audible, replace the annunciator module. If this does not work, try solutions to problem #2.
1. Disconnect the ribbon cable from the back of the faulty display module(s) and replace the module(s).
6. Alarm condition exists but LED’s are not illuminating.
b. Connection of the DC power cable from system power supply to annunciator module is loose.
c. Faulty annunciator module.
a. Display module not properly calibrated.
1. Disconnect the DC power cable from the annunciator module and then reconnect. If audible alarm still persists, replace the System Power Supply unit.
1. Replace annunciator module.
1. Ensure that the system was properly ordered.
Factory default settings: Mid Pressure: Hi Pressure 60 Psi Low Pressure 40 Psi Vacuum: Low Vacuum 12 inHg High Pressure: Hi: Nitrogen & Air 195 Psi Low: Nitrogen & Air 140 Psi
www.amico.com 23
SYMPTOM CAUSE CORRECTIVE ACTION
2. If calibration is required, refer to setting HIGH and LOW calibration procedure on page 18/19.
7. Gas reading incorrect.
b. Faulty display module.
a. Loose connection of DISS ttings.
b. Sensor module is not properly wired to the display module.
c. Defective sensor or requires calibration.
d. The ribbon cable not properly connected to the display module.
e. Defective display module.
1. Replace the display module.
1. Ensure that the sensor module is properly connected to the DISS demand check-valve.
1. Ensure that the sensor module is properly wired to the display module by using wiring diagram in Appendix D or E.
1. Replace the sensor module.
1. Pull out the ribbon cable and connect it back in again, while ensuring that it is seated properly.
1. Replace the display module.
Error Code Messages on the Display Module
SYSTEM CAUSE CORRECTIVE ACTION PAGE
E01
E02
E03
E04
E06
E07
No sensor is connected.
Sensor and Display Module mismatched.
The High set-point was set below the Low set-point or vice versa.
Incorrect type of Sensor connected, (i.e. 250 Psi sensor on a 100 Psi range).
Cable between the sensor and display module shorted out or reversed polarity.
Out of Calibration / Sensor not reading gas
Connect a sensor.
Ensure that the Sensor and Display Module are for the same gas.
Recalibrate the High and Low setpoint to proper values.
Connect the correct Sensor to the match­ing Display Module.
Reverse polarity or replace cable if defective.
Replace the sensor module
41 / 42
19
15/16
41 / 42
41 / 42
24 Amico Pipeline
Model Numbers
AREA ALARM
1 module = A2AR-E-X 2 gang back box
1 module = A2AR-E-X 3 gang back box
2 modules = A2AR-E-XX 3 gang back box
1 module = A2AR-E-X 4 gang back box
2 modules = A2AR-E-XX 4 gang back box
3 modules = A2AR-E-XXX 4 gang back box
4 modules = A2AR-E-XXXX 5 gang back box
4 modules = A2AR-E-XXXX 7 gang back box
5 modules = A2AR-E-XXXXX 7 gang back box
6 modules = A2AR-E-XXXXXX 7 gang back box
A2AR-L-XXXXXX
The Letter “L” Represents the Langauge:
U = English (NFPA) E = English (CSA) F = French (CSA) S = Spanish (NFPA)
R = Remote/Local Sensors C = Conversion
The Letter “X” Denes the Type of Gas:
Oxygen = O Medical Air = A MedVac = V Nitrous Oxide = 2 Nitrogen = N Carbon Dioxide = C WAGD = W AGSS = E Instrument Air = I
Example: 4 Gases, English ISO, Remore/Local pressure sensors, Oxygen, MedVac, Medical Air and Nitrous Oxide = A2AR-E-OVA2
NOTE: Please specify the gang back box on each alarm.
MASTER ALARM
10 functions = A2M-E-10 2 gang back box
10 functions = A2M-E-10 3 gang back box
20 functions = A2M-E-20 3 gang back box
10 functions = A2M-E-10 4 gang back box
30 functions = A2M-E-30 4 gang back box
40 functions = A2M-E-40 5 gang back box
40 functions = A2M-E-40 7 gang back box
50 functions = A2M-E-50 7 gang back box
C = Conversion
A2M(C)-L-20
The Letter “L” Represents the Langauge:
E = English (CSA/NFPA) F = French (CSA) S = Spanish (NFPA)
20 functions = A2M-E-20 4 gang back box
Example: 2 Modules, English (20 Functions) = A2M-E-20
NOTE: Please specify the gang back box on each alarm.
60 functions = A2M-E-60 7 gang back box
www.amico.com 25
COMPACT ALARM
1 module = A2ADR-L-X 2 gang back box
3 modules = A2ADR-L-XXXXXX 4 gang back box
R = Remote/Local Sensors C = Conversion Series
1 module = A2ADR-L-XX 3 gang back box
2 modules = A2ADR-L-XXXX 3 gang back box
1 module = A2ADR-L-XX 4 gang back box
2 modules = A2ADR-L-XXXX 4 gang back box
NOTE: Please specify the gang back box on each alarm.
4 modules = A2ADR-L-XXXXXXXX 5 gang back box
4 modules = A2ADR-L-XXXXXXXX 7 gang back box
5 modules = A2ADR-L-XXXXXXXXXX 7 gang back box
6 modules = A2ADR-L-XXXXXXXXXXXX 7 gang back box
The Letter “L” Represents the Langauge:
U = English (NFPA) E = English (CSA) F = French (CSA) S = Spanish (NFPA)
A2ADR-L-XXXXXXXXXXXX
The Letter “X” Denes the Type of Gas:
Oxygen = O Medical Air = A MedVac = V Nitrous Oxide = 2 Nitrogen = N Carbon Dioxide = C WAGD = W AGSS = E Instrument Air = I
Example: English NFPA - Oxygen, Medical Air, MedVac, Nitrous Oxide, Nitrogen, Carbon Dioxide = A2ADR-U-OAV2NC
NEMA 4 ALARM
A2MN-L-XX
The Letter “L” Represents the Langauge:
E = English (CSA/NFPA) F = French (CSA) S = Spanish (NFPA)
26 Amico Pipeline
1
2
3
4
5
6
“X’’ indicates the order of gases, as shown above.
The Letters “XX” Denes the Number of Functions:
10 = 10 Functions
20 = 20 Functions
7
8
9
101112
COMPACT MASTER COMBINATION ALARM
Use the Model number for the Area Alarm and add “M” for each Master module.
Example: 3 Gases, English ISO, Remote/Local Sensors, Oxygen, Vacuum, Medical Air and 2 Master Modules = A2ADR-E-OVAMM.
2 modules = A2ADR-U-XXM 3 gang back box
2 modules = A2ADR-U-XXM 4 gang back box
3 modules = A2ADR-U-XXMM 4 gang back box
3 modules = A2ADR-U-XXXXM 4 gang back box
NOTE: Please specify the gang back box on each alarm
1
3
5
7
9
4 modules = A2ADR-U-XXXXMM 5 gang back box
4 modules = A2ADR-U-XXXXMM 7 gang back box
5 modules = A2ADR-U-XXXXXXMM 7 gang back box
6 modules = A2ADR-U-XXXXXXMMM 7 gang back box
2
4
R = Remote/Local Sensors C = Conversion
U = English (NFPA) E = English (CSA) F = French (CSA) S = Spanish (NFPA)
6
8
101112
Each “M” Stands for 10 Functions
A2ADR-U-XXXXXXMMM
The Letter “X” Denes the Type of Gases::
Oxygen = O Medical Air = A MedVac = V Nitrous Oxide = 2 Nitrogen = N Carbon Dioxide = C WAGD (NFPA) = W AGSS (ISO) = E Instrument Air = I
www.amico.com 27
2 in 1 Area Alarm
1 MODULE= A2AR-E-1 2 gang back box
1 MODULE= A2AR-E-1 3 gang back box
2 MODULES= A2AR-E-11 3 gang back box
1 MODULE= A2AR-E-1 4 gang back box
2 MODULES= A2AR-E-11 4 gang back box
Example: 4 Gases, English CSA, Remote/Local pressure sensors, Oxygen, Medical Air, MedVac, Nitrous Oxide = A2AR-E-1111 (O,A,V,2)
3 MODULES= A2AR-E-111 4 gang back box
4 MODULES= A2AR-E-1111 5 gang back box
4 MODULES= A2AR-E-1111 7 gang back box
5 MODULES= A2AR-E-11111 7 gang back box
6 MODULES= A2AR-E-111111 7 gang back box
NOTE: Please specify the gang back box on each alarm.
R = Remote/Local Sensors C = Conversion Series
A2AR-L-1111
The Letter “L” Represents the Langauge:
U = English (NFPA) E = English (CSA) F = French (CSA) S = Spanish (NFPA)
The Number of the Digit “1” Denes the Number of Gases:
1 = 1 Gas 11 = 2 Gases 111 = 3 Gases 111111 = 6 Gases
The Letter “X” Denes the Type of Gas:
Oxygen = O Medical Air = A MedVac = V Nitrous Oxide = 2 Nitrogen = N Carbon Dioxide = C WAGD = W AGSS = E Instrument Air = I
28 Amico Pipeline
Spare Part Numbers
MODEL NUMBER DESCRIPTION
A2-MAN-ALM-ENG Alert-2 alarm manual English A2P-ANNU-CB Annunciator circuit board assembly A2P-ANNU-EB Annunciator module English Alert-2 A2P-POWER-V2 Power supply module Alert-2 A2P-AREA-E-AIR Area alarm module ISO-AIR Eng. Alert-2 A2P-AREA-E-CO2 Area alarm module ISO-CO2 Eng. Alert-2 A2P-AREA-E-EVA Area alarm module ISO-EVA Eng. Alert-2 A2P-AREA-E-N2O Area alarm module ISO-N2O Eng. Alert-2 A2P-AREA-E-NIT Area alarm module ISO-NIT Eng. Alert-2 A2P-AREA-E-OXY Area alarm module ISO-OXY Eng. Alert-2 A2P-AREA-E-VAC Area alarm module ISO-VAC Eng. Alert-2 A2P-AREA-U-AIR Area alarm module USA - AIR Alert-2 A2P-AREA-U-ARG Area alarm module USA-ARGON Eng. Alert-2 A2P-AREA-U-DAI Area alarm module DENTAL-AIR Eng. Alert-2 A2P-AREA-U-HELB Area alarm module USA-HELIUM Alert-2 A2P-AREA-U-HEO Area alarm module USA-HELIOX Alert-2 A2P-AREA-U-HPA Area alarm module HP-AIR Eng. Alert-2 A2P-AREA-U-LAI Area alarm module LAB-AIR Eng. Alert-2 A2P-AREA-U-OXY Area alarm module USA - OXY Alert-2 A2P-AREA-U-VAC Area alarm module USA - VAC Alert-2 A2P-AREA-U-WAG Area alarm module USA - WAG Eng. Alert-2 A2P-AREA-CB-AIR Area circuit board assembly - AIR A2P-AREA-CB-CO2 Area circuit board assembly - CO2 A2P-AREA-CB-EVA Area circuit board assembly - EVA A2P-AREA-CB-N2O Area circuit board assembly - N2O A2P-AREA-CB-NIT Area circuit board assembly - NIT A2P-AREA-CB-OXY Area circuit board assembly - OXY A2P-AREA-CB-VAC Area circuit board assembly - VAC A2P-SENS-E-AIR Sensor module ISO-AIR Eng. Alert-2 A2P-SENS-E-CO2 Sensor module ISO-CO2 Eng. Alert-2 A2P-SENS-E-EVA Sensor module ISO-EVA Eng. Alert-2 A2P-SENS-E-N2O Sensor module ISO-N2O Eng. Alert-2 A2P-SENS-E-NIT Sensor module ISO-NIT Eng. Alert-2 A2P-SENS-E-OXY Sensor module ISO-OXY Eng. Alert-2 A2P-SENS-E-VAC Sensor module ISO-VAC Eng. Alert-2
www.amico.com 29
MODEL NUMBER DESCRIPTION
A2P-SENS-U-AIR Sensor module USA-AIR Eng. Alert-2 A2P-SENS-U-ARG Sensor module USA-ARGON Eng. Alert-2 A2P-SENS-U-DAI Sensor module USA-DENTAL AIR Eng. Alert-2 A2P-SENS-U-HEL Sensor module USA-HEL Eng. Alert-2 A2P-SENS-U-HEO Sensor medule USA-HELIOX Alert-2 A2P-SENS-U-HPA Sensor module HP-AIR Eng. Alert-2 A2P-SENS-U-LAI Sensor module USA LAB AIR Eng. Alert-2 A2P-SENS-U-OXY Sensor module USA-OXY Eng. Alert-2 A2P-SENS-U-VAC Sensor module USA-VAC Eng. Alert-2 A2P-SENS-U-WAG Sensor module USA-WAG Eng. Alert-2 A2P-MAST-E-AME Master alarm module - English 10 points A2P-MAST-E-ISO Master alarm module - ISO English10 points A2P-MAST-CB Master circuit board Assembly Alert-2 A2P-BLANK Alert-2 alarm module blank (ller) A2P-BOXASS-2 Alarm back box Assembly 2-station Alert-2 A2P-BOXASS-3 Alarm back box Assembly 3-satation Alert-2 A2P-BOXASS-4 Alarm back box Assembly 4-station Alert-2 A2P-BOXASS-5 Alarm back box Assembly 5-station Alert-2 A2P-BOXASS-7 Alarm back box Assembly 7-station Alert-2 A2P-COMP-10 Computer interface Module English 10-pts. A2P-FRMASS-2B Alarm frame assembly 2-station Alert-2 A2P-FRMASS-3B Alarm frame assembly 3-station Alert-2 A2P-FRMASS-4B Alarm frame assembly 4-station Alert-2 A2P-FRMASS-5B Alarm frame assembly 5-station Alert-2 A2P-FRMASS-7B Alarm frame assembly 7-station Alert-2 A2P-PIPE Pressure module pipe assembly (Alert-2) A2P-RIBBON-3 Ribbon cable assembly 3-station Alarm A2P-RIBBON-4 Ribbon cable assembly 4-station Alarm A2P-RIBBON-7 Ribbon cable assembly 7-station Alarm A2P-RIBBON-8 Ribbon cable assembly 8-station for 7 gas alarm A2P-RIB-COMP-03 RIBBON CABLE ASSY 1 STN COMPACT ALARM A2P-RIB-COMP-05 RIBBON CABLE ASSY 2 STN COMPACT ALARM A2P-RIB-COMP-07 RIBBON CABLE ASSY 3 STN COMPACT ALARM A2P-RIB-COMP-09 RIBBON CABLE ASSY 4 STN COMPACT ALARM A2P-RIB-COMP-13 RIBBON CABLE ASSY 6 STN COMPACT ALARM A2P-RIB-COMP-15 RIBBON CABLE ASSY 7 STN COMPACT ALARM A2P-COMB-E-AGS Combo Board Alarm Module ISO - AGSS A2P-COMB-E-AIR Combo Board Alarm Module ISO - AIR
30 Amico Pipeline
MODEL NUMBER DESCRIPTION
A2P-COMB-E-CO2 Combo Board Alarm Module ISO - CO2 A2P-COMB-E-EVA Combo Board Alarm Module ISO - EVA A2P-COMB-E-N2O Combo Board Alarm Module ISO - N2O A2P-COMB-E-NIT Combo Board Alarm Module ISO - NIT A2P-COMB-E-OXY Combo Board Alarm Module ISO - OXY A2P-COMB-E-VAC Combo Board Alarm Module ISO - VAC A2P-COMB-U-AIR Combo Board Alarm Module USA - AIR A2P-COMB-U-OXY Combo Board Alarm Module USA - OXY A2P-COMB-U-VAC Combo Board Alarm Module USA - VAC A2P-COMB-U-WAG Combo Board Alarm Module USA - WAGD A2P-COMBO-CB Combo Circuit Board Assem. - ALL GASES A2X-BOX-2-FILL Alarm box Filler Frame 2 Station A2X-BOX-3-FILL Alarm Box Filler Frame 3 Station A2X-BOX-4-FILL Alarm Box Filler Frame 4 Station A2X-BOX-5-FILL Alarm Box Filler Frame 5 Station A2X-BOX-7-FILL Alarm Box Filler Frame 7 Station A2X-PLATE-RETR3 Retro-t Plate Filler for 3 Function A2X-PLATE-RETR4 Retro-t Plate Filler for 4 Function A2X-PLATE-RETR5 Retro-t Plate Filler for 5 Function A2X-PLATE-RETR7 Retro-t Plate Filler for 7 Function A2P-COMPACT-CB Compact Area Circuit Board Assembly-All Gases A2P-MYLCPB-E-AGS Compact Board Mylar Bottom (ISO) - AGS A2P-MYLCPB-E-AIR Compact Board Mylar Bottom (ISO) - AIR A2P-MYLCPB-E-CO2 Compact Board Mylar Bottom (ISO) - CO2 A2P-MYLCPB-E-N2O Compact Board Mylar Bottom (ISO) - N2O A2P-MYLCPB-E-NIT Compact Board Mylar Bottom (ISO) - NIT A2P-MYLCPB-E-OXY Compact Board Mylar Bottom (ISO) - OXY A2P-MYLCPB-E-VAC Compact Board Mylar Bottom (ISO) - VAC A2P-MYLCPB-E-IAIR Compact Board Mylar Bottom (ISO) -IAIR A2P-MYLCPB-U-AIR Compact Board Mylar Bottom (NFPA) - AIR A2P-MYLCPB-U-OXY Compact Board Mylar Bottom (NFPA) - OXY A2P-MYLCPB-U-VAC Compact Board Mylar Bottom (NFPA) - VAC A2P-MYLCPB-U-WAG Compact Board Mylar Bottom (NFPA) - WAG A2P-MYLCPB-U-IAIR Compact Board Mylar Bottom (NFPA) - IAIR A2P-MYLCPT-E-AGS Compact Board Mylar Top (ISO) - AGS A2P-MYLCPT-E-AIR Compact Board Mylar Top (ISO) - AIR A2P-MYLCPT-E-CO2 Compact Board Mylar Top (ISO) - CO2 A2P-MYLCPT-E-N2O Compact Board Mylar Top (ISO) - N2O A2P-MYLCPT-E-NIT Compact Board Mylar Top (ISO) - NIT A2P-MYLCPT-E-OXY Compact Board Mylar Top (ISO) - OXY A2P-MYLCPT-E-VAC Compact Board Mylar Top (ISO) - VAC A2P-MYLCPT-E-IAIR Compact Board Mylar Top (ISO) - IAIR A2P-MYLCPT-U-AIR Compact Board Mylar Top (NFPA) - AIR A2P-MYLCPT-U-OXY Compact Board Mylar Top (NFPA) - OXY A2P-MYLCPT-U-VAC Compact Board Mylar Top (NFPA) - VAC A2P-MYLCPT-U-WAG Compact Board Mylar Top (NFPA) - WAG A2P-MYLCPT-U-IAIR Compact Board Mylar Top (NFPA) - IAIR A2P-MYLCP-BLNK Compact Board Mylar - Blank A2P-MYLCP-COVER Compact Board Mylar - Cover
www.amico.com 31
Dimensions
AREA ALARM
Inch [mm]
3­5/16 [84]
NUMBER OF DISPLAY MODULES
Number of Display Modules A B Gang
1 MODULE
1 module 7 (178) 8 (203) 2
From 1 to 2 modules 11 (272) 12 (305) 3
FROM 1 TO 2 MODULES
From 1 to 3 modules 14 (356) 15 (381) 4
FROM 1 TO 3 MODULES
From 1 to 4 modules 17 (439) 18 (465) 5
FROM 1 TO 6 MODULES
From 1 to 6 modules 24 (610) 25 (635) 7
3­5/16 [84]
B
3-
5/16
[84]
A
A
11 [272]
14 [356] 15 [381]
24 [610]
B
8 [203] 7 [178]
12 [305]
25 [635]
3-
5/16
[84]
3-
5/16
[84]
5/8
[66]
2-
10
[254]
Local/Remote Sensor
CONNECTOR
Only supplied with Local Sensors 1/4”[6.4mm] (I.D.) Type “K” Copper Pipe
5/8
[16]
DISS
3/4
[19]
7-3/16
[182]
[102]
4
1-1/4
[32]
9
[229]
1.88 [48]
(approximate, can vary)
6.375[162]
7.50[191]
6.375 [162]
Brazing Filler Metal AWS Spec. BAg-7
Brazing Filler Metal AWS Spec.
1/2-14NPSM THD.
BAg-7
Brass 1[25] HEX
1/4[6] NPT
1/2 - 14 NPSM THD.
Brass 1 [25] HEX
NOTE: DISS demand check valves by 1/4” NPT, supplied with each re­mote sensor.
#22 Gauge twisted pair shielded cable 6”-8” [0.1m - 0.2 m] supplied
Wrench Flats
1
[25]
1/2” Conduit Connection
32 Amico Pipeline
1/2”-14 NPSM [13]
(see Thread Specs.)
MASTER ALARM
Inch [mm]
5/8
[16]
10
[254]
1-1/4
[32]
9
[229]
4
A
[102]
B
Number of Display Modules A B Gang
1 module 7 (178) 8 (203) 2
From 1 to 2 modules 11 (272) 12 (305) 3
From 1 to 3 modules 14 (356) 15 (381) 4
From 1 to 4 modules 17 (439) 18 (465) 5
From 1 to 6 modules 24 (610) 25 (635) 7
www.amico.com 33
COMPACT ALARM
Inch [mm]
1.65
1.65
1.65
1.65
1.65
1.65
1.65
[42]
[42]
[42]
[42]
[42]
[42]
Number of Display Modules A B Gang
1 module 7 (178) 8 (203) 2
From 1 to 2 modules 11 (272) 12 (305) 3
From 1 to 3 modules 14 (356) 15 (381) 4
From 1 to 4 modules 17 (439) 18 (465) 5
From 1 to 6 modules 24 (610) 25 (635) 7
1.65
[42]
[42]
1.65
1.65
1.7
[42]
[42]
1.5
[43]
[38]
Only supplied with Local Sensors 1/4”[6.4mm] (I.D.) Type “K” Copper Pipe
3/4
[19]
6.375[162]
7-3/16
[254]
5/8 [16]
10
[182]
1-1/4
[32]
[229]
7.50[191]
6.375 [162]
Brazing Filler
9
Metal AWS Spec. BAg-7
Brazing Filler Metal AWS Spec.
1/2-14NPSM THD.
BAg-7
Brass 1[25] HEX
Local/Remote Sensor
1.88 [48]
[102]
1/4[6] NPT
4
1/2 - 14 NPSM THD.
Brass 1 [25] HEX
Note: DISS Demand check valves by 1/4” NPT, supplied with each remote sensor.
#22 Gauge twisted pair shielded cable 6”-8” [0.1m - 0.2 m] supplied
DISS
CONNECTOR
(approximate, can vary)
Wrench Flats
1
[25]
1/2” Conduit Connection
34 Amico Pipeline
1/2”-14 NPSM [13]
(see Thread Specs.)
COMPACT MASTER COMBINATION ALARM
1.65
1.65
1.65
1.65
1.65
1.65
1.65
1.65
1.65
1.65
[42]
[42]
[42]
[42]
[42]
[42]
[42]
[42]
[42]
1.65
[42]
[42]
[254]
Inch [mm]
3/4
Only supplied with Local Sensors 1/4”[6.4mm] (I.D.) Type “K” Copper Pipe
7-3/16
5/8 [16]
10
[182]
[102]
4
[19]
1-1/4
[32]
[229]
6.375[162]
7.50[191]
6.375 [162]
Brazing Filler
9
Metal AWS Spec. BAg-7
Brazing Filler Metal AWS Spec.
1/2-14NPSM THD.
BAg-7
Brass 1[25] HEX
1/4[6] NPT
1/2 - 14 NPSM THD.
Brass 1 [25] HEX
Number of Display Modules A B Gang
1 module 7 (178) 8 (203) 2
From 1 to 2 modules 11 (272) 12 (305) 3
From 1 to 3 modules 14 (356) 15 (381) 4
From 1 to 4 modules 17 (439) 18 (465) 5
From 1 to 6 modules 24 (610) 25 (635) 7
Local/Remote Sensor
DISS
CONNECTOR
1/2”-14 NPSM [13]
(see Thread Specs.)
1.88 [48]
(approximate, can vary)
Wrench Flats
1
[25]
1/2” Conduit Connection
Note: DISS Demand check valves by 1/4” NPT, supplied with each remote sensor.
#22 Gauge twisted pair shielded cable 6”-8” [0.1m - 0.2 m] supplied
www.amico.com 35
2 in 1 ALARM
Inch [mm]
3-5/6
3-5/6
3-5/6
[84]
[84]
A
B
Number of Display Modules A B Gang
1 module 7 (178) 8 (203) 2
From 1 to 2 modules 11 (272) 12 (305) 3
From 1 to 3 modules 14 (356) 15 (381) 4
From 1 to 4 modules 17 (439) 18 (465) 5
From 1 to 6 modules 24 (610) 25 (635) 7
[84]
3-5/6
[84]
3-5/6
[84]
Only supplied with
2-5/8
Local Sensors
[66]
1/4” [6.4mm] (I.D.) Type “K” Copper Pipe
5/8
[16]
10
[254]
Local/Remote Sensor
DISS
CONNECTOR
7-3/16
[182]
[102]
3/4
[19]
1-1/4
[32]
9
[229]
4
(approximate, can vary)
1.88 [48]
6.375[162]
7.50[191]
Brazing Filler Metal AWS Spec. BAg-7
1/2-14NPSM THD.
Brass 1[25] HEX
1/4[6] NPT
Note: DISS Demand check valves by 1/4” NPT, supplied with each remote sensor.
#22 Gauge twisted pair shielded cable 6”-8” [0.1m - 0.2 m] supplied
Wrench Flats
1
[25]
1/2” Conduit Connection
36 Amico Pipeline
1/2”-14 NPSM [13]
(see Thread Specs.)
NEMA 4 ALARM
Inch [mm]
10.50 [267]
Top View
8.50
[216]
Top View
Side View
6.125 [156]
Side View
14.55 [370]
12.55 [319]
8.625 [219]
www.amico.com 37
Appendix A
Wiring Diagram Auto-Switching Power Supply
Toggle Switch
AC Supply 115 to 220 VAC
G
N
L
L - Live N - Neutral G - Ground
Fuse (1 AMPw)
Ground
38 Amico Pipeline
DC Power Cable: Connect to Annunciator Module
are fail
newer.
Versions
Appendix B
Wiring Diagram Annunciator
NOTE:
NC COM NO GND +12V
NOTE:
Relays on the annunciator safe for Version 3.1 or
Relays are not fail safe for
3.0 or older.
Relays on the annunciator are fail safe for version 3.1 or newer.
Relays are not fail safe for version 3.0 or older.
www.amico.com 39
Appendix C
Wiring Diagram Automatic Voice/Pager Dialing System
Annunciator Module
NOTE:
Relays on the annunciator are fail safe for version 3.1 or newer.
1 K
SILENCE TEST
5 U
2 U
NO NC COM GND +12V
4 U
M R O
3
N
U
O IS
DC Power cable from Power Supply
1 U
NOTE:
Relays on the annunciator are fail safe for Version 3.1 or newer.
1
J
Relays are not fail safe for Versions
3.0 or older.
Relays are not fail safe for version 3.0 or older.
40 Amico Pipeline
Appendix D
Wiring Diagram Area Display Module - Local Sensor
OXYGEN
# 22 Gauge twisted pair shielded cable
6”-8” [0.1m-0.2m] supplied
www.amico.com 41
2,500 750
Appendix E
Wiring Diagram Area Display Module - Remote Sensor
NOTE:
For multiple sensors, a multi-conductor twisted pair, shielded cable should be used.
42 Amico Pipeline
Appendix F
Wiring Diagram 2 in 1 Display Module
OXYGEN
Dry contacts for remote monitoring of
High and Low alarms
2 in 1
Module
Sensor
Module
Black Red
NO NC COM NO NCCOM
- +
# 22 Gauge twisted pair shielded cable
6”-8” [0.1m-0.2m] supplied
Source Equipment
C NC
C NC
C NC
C
-----
HC2HC3HC4HC5HC
+++++
1
NC C
NC
Dry contacts only, no voltage
Note: Jumper any unused points
www.amico.com 43
Appendix G
2,500 750
Wiring Diagram Compact Module
NOTE:
Version 3: Jumper any unused points on
the Master module
Version 4: Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
44 Amico Pipeline
Appendix H
2,500 750
Wiring Diagram Area Module to Master Module
NOTE:
Version 3: Jumper any unused points on
the Master module
Version 4: Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
www.amico.com 45
Appendix I
2,500 750
Wiring Diagram 2 in 1 Module to Master Module
NOTE:
Version 3: Jumper any unused points on
the Master module
Version 4: Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
46 Amico Pipeline
Appendix J
Wiring Diagram Abnormal Condition
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
Source
Equipment
NOTE:
Version 3: Jumper any unused points on
the Master module
Version 4: Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
SW-2
www.amico.com 47
Appendix K
Wiring Diagram Area Slave
Alarm #1
SLAVE
SENSOR LOW ALARM
- + - +
NO NC COM
HIGH ALARM NO NC COM
OXYGEN MEDICAL AIR MEDVAC
SLAVE
SENSOR LOW ALARM
- + - +
U12 U11
HIGH ALARM
NO NC COM
NO NC COM
U2
K1 K2
U4
UP
S1
DOWN
S2 S3
ON 1 2 3 4 5
U1
U3
6 7 8
U3
R41
R42
R19
SLAVE
SENSOR LOW ALARM
HIGH ALARM
NO NC COM
NO NC COM
- + - +
U2
K1 K2
U4
UP
S1
DOWN
S2
S3
ON 1 2 3 4 5
U1
U12 U11
R43
U3
6 7 8
U3
R41
R42
R19
SLAVE
- + - +
U12 U11
R43
SENSOR LOW ALARM
NO NC COM
U2
HIGH ALARM NO NC COM
K1 K2
U4
UP
S1
DOWN
S2
S3
ON 1 2 3 4 5
U1
U3
6 7 8
U3
R43
R41
R42
R19
Alarm #2
SLAVE
SENSOR LOW ALARM
- + - +
NO NC COM
Note: Set the gas specific dip switch on each area slave panel
HIGH ALARM NO NC COM
U10
SLAVE
- + - +
U12 U11
U10
U6U7U8
PAL1
PAL2
SENSOR LOW ALARM
NO NC COM
U2
U4
U1
U6U7U8
PAL1
PAL2
U9
U9
HIGH ALARM NO NC COM
U3
U6U7U8
U10
PAL1
PAL2
SLAVE
U12 U11
- + - +
SENSOR LOW ALARM
NO NC COM
U2
U9
U13
HIGH ALARM NO NC COM
K1 K2
U4
UP
S1
DOWN
S2 S3
ON 1 2 3 4 5
U1
U3
6 7 8
U3
R43
R41
R42
R19
U13
K1 K2
UP
S1
DOWN
S2 S3
ON 1 2 3 4 5 6 7 8
U3
R43
R41
R42
R19
U6U7U8
U10
PAL1
PAL2
U13
U9
U13
U10
U10
U12 U11
SLAVE
- + - +
U6U7U8
PAL1
PAL2
SENSOR LOW ALARM
NO NC COM
U2
U4
U1
U6U7U8
PAL1
PAL2
U9
U13
HIGH ALARM NO NC COM
K1 K2
UP
S1
DOWN
S2 S3
ON 1 2 3 4 5
U3
6 7 8
U3
R43
R41
R42
R19
U9
U13
NOTE: “The slave alarm does not work with A2P-POWER-CONV, both Alarm must be attached the A2P-POWER-V2
48 Amico Pipeline
Appendix L
Wiring Diagram Master/NEMA 4 Module
Source
Equipment
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
NOTE:
Version 3: Jumper any unused points on
the Master module
Version 4: Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
Note: Turn OFF dip-switches for any unused points (Location SW-2)
Dry Contacts only
No Voltage
SW-2
www.amico.com 49
Appendix M
Wiring Diagram Pressure Switch Connection to a Master Alarm
Master
Module
l a n g i S m r a l A w o L
Source
Equipment
C
NO
e l p r u P
Blue
Red
Vacuum
Green
(for Ground)
wiring code
Ground - Green Common - Purple Normally Closed -Red Normally Open -Blue
Nitrogen
Switch for High Alarm
NO
C
C NO NCC NO NC
Switch for Low Alarm
n w o r B
e g n a r O
C
NC
l a n g i S m r a l A h g i H
wiring code
Circuit #1 for Low Circuit #2 for High Common - Purple Common - Brown Normally Closed - Blue Normally Closed - Orange Normally Open - Red Normally Open - Yellow
e l p r u P
l a n g i S m r a l A w o L
d e R
Six Leads 18” Long (Approx.)
NO C
3/4” NPT Conduit Connection
Circuit No. 1 Calibrated Dial
Circuit No. 2 Calibrated Dial
9/32” x 5/8” Mounting Hole (Typ.)
1/4” NPT Gas Service Connection
not required
e u l B
2 - 1/2”
3 - 1/2”
w o l l e Y
Green
(for Ground)
(OXY, AIR, N2O, CO2)
Circuit No. 1 Circuit No. 2
Blue
Purple
Red
C
NO
Gas
Brown
Orange
NC
C
Yellow
NOTE: There are 2 NIT switches, one for high alarm and one for low alarm.
50 Amico Pipeline
Appendix N
Wiring Diagram Computer Interface Module
Computer Interface Module
Source
Equipment
Dry contacts for interface with: Building Management System. Contacts are Common and NC, open on Alarm.
Ratings: 24VDC 0.1A
Master Module
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
NOTE:
Version 3: Jumper any unused points on
the Master module
Version 4: Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
SW-2
www.amico.com 51
Appendix O
Wiring Diagram Master to Slave Module
"Master 1" "Master 2"
+
-
0 1 H C
+
-
9 H C
+
-
8 H C
+
-
7 H C
+
6 H C
-
+
-
5 H C
+
4 H C
-
+
3 H C
-
+
2 H C
-
+
-
1 H C
+
-
0 1 H C
+
-
9 H C
+
-
8 H C
+
-
7 H C
+
-
6 H C
+
-
5 H C
+
-
4 H C
+
-
3 H C
+
-
2 H C
+
-
1 H C
NOTE:
Version 3: Jumper any unused points on
the Master module
Version 4: Jumper any unused points on the Master module.
Turn OFF dip-switches for any unused points (Location SW-2)
52 Amico Pipeline
Source Equipment (typical)
C NC
Appendix P
Technical Specication
Supply Voltage: 115 to 220 VAC - 50 to 60 Hz
Current Draw: 1 Amp.Max.
Fuse (1/4 * 1-1/4): Fast Blow 1 Amp.
Cable requirement:
Area Display Module to Remote Sensor:
Distance: Maximum 2,500 feet [750 m]
Cable: Belden # 8451 or equivalent.
#22 gauge shielded, twisted pair. (For multiple sensors a multi-conductor twisted pair, shielded cable should be used).
Signal: 30 VDC - 1.0 Amps.
60 VDC - 0.3 Amps. 125 VAC - 0.5 Amps.
Master Module to Source equipment:
Distance: Maximum 10,000 feet [3,000 m]
Cable: Minimum #22 gauge wire (does not have to be shielded, twisted pair).
Signal: 5 VDC, < 5 µA.
Computer Interface Board:
Output: Dry Contacts NC, open on Alarm.
Rating: 30 VDC - 1.0 Amps.
60 VDC - 0.3 Amps. 125 VAC - 0.5 Amps.
www.amico.com 53
Notes
54 Amico Pipeline
Notes
www.amico.com 55
www.amico.com
Amico Pipeline | www.amico.com
85 Fulton Way, Richmond Hill
Ontario, L
Toll Free Tel: 1.877.264.2697 Toll Free Fax: 1.866.440.4986 Tel: 905.764.0800
Fax: 905.764.0862 Email: info@amico.com
4B 2N4, Canada
C US LISTED
APE-OPER-MAINT-ALM-V5.8 04.23.2014
Loading...