Series 5400
OTHER FEATURES AND ADVANTAGES
• UL Recognized Component File No. E61377
• CUL File No. LR 33434
• Choice of direct or inverse operation to provide fail-
safe control. In direct operation, load relay is
energized when the low voltage ac sensing circuit
is completed. In inverse operation, load relay is
de-energized when the low voltage ac sensing
circuit is completed.
• LED indicates when relay is energized.
• Relays will operate reliably when mounted in any
position required to meet a complete range of
application design requirements.
• Relays will operate over ambient temperature
range from –10° + 131°F (-23° to 55 °C).
• User adjustable sensing resistance.
• Rugged octal plug-in housing.
• Heavy-duty internal construction.
B/W Controls
Series 5400
Liquid Level Controls
Single Probe (Direct Operation)
Cat. No.: 5400-A-L1
Voltage: 120 VAC
Sensitivity range: 1 K to 250K ohms
®
E67365
2.90
3.45
MAX.
Clawson, MI 48017 U.S.A.
2.40
1.75
Series 5400 Relay Dimensions
B/W Controls
Plug In Style Liquid Level Control Relay
COMPACT PLUG IN STYLE RELAY
B/W Series 5400 Relays were developed especially for us e as safe, reliable,
economical original equipment components in many different types of
commercial and industrial products.
Designed to operate from electrodes or probes contacting conductive liquids,
they are ideally suited to level control applications in such products as
vending, dispensing, ice-making machines, water softeners, dishwashers,
and coffee makers, plus many type of operating equipment in the food, drug,
dairy, brewing, distilling and chemical processing industries.
In addition, Series 5400 Relays have a low energy sensing circuit with a lockin holding feature that permits operation over a range of levels, or from
momentary contact pilot devices such as float, actuators, etc. Thus they are
equally suitable for use as original equipme nt components in many products
and systems that require monitoring and control of such process variab le as
temperature, pressure, humidity, flow, voltage and current, etc.
BASIC SPECIFICATIONS
Voltage: 120 volts ac, 50/60 hertz
240 volts ac, 50/60 hertz
24 volts ac, 50/60 hertz
(special order)
Power Required: 1.2 volt-amperes max.
Load Contacts: Single pole, double throw.
Silver Cadmium Oxide
Contact Ratings:
at 120 volts ac; 6 amps at 240
volts ac or 28 volts dc. Min. load
100 mA at 5 VDC.
Sensing Voltage: 18 VAC RMS max.
Sensing Current: 2.0 mA RMS max.
Sensitivity: Adjustable 1K to 250K ohms
Mounting: 8 pin octal base socket
Time Delay: 5 seconds +/- 10%, other delay
NOTE: All line voltage circuits are isolated from the low
voltage ac sensing circuit to assure optimum safety in service.
DISCONNECT POWER BEFORE SERVICING
1.575
.315
2.362
1.299
.984
Ø.165
7.00
5400- STRAP
10 amps resistive load or 1/3 hp
+/- 10%. Factory set at 100k
OHMS +/- 10%.
(sold separately)
times available on 5400-A and
5400-B series only.
.866
54
6
7812
.709
3
5400-RS
.45
.065±.015
.33
TYPICAL APPLICATIONS
Diagrams at right illustrate basic details of typical
application in which Series 5400 Relays are used as
original equipment components to provide fail-safe
control by de-energizing the load in event of po wer
of relay failure.
In Diagram 1, Type 5400-C Relay is used in direct
operation to provide automatic pump down control
for dehumidifiers, sumps or any other product
requiring control of a liquid at a given high-level set
point.
In Diagram 2, Type 5400-D Relay is used in inverse
operation to provide pump-up control for
carbonators, humidifiers, purification stills, etc.
where liquid must be kept above a low level set
point.
In Diagram 3, Type 5400-A Relay is used in direct
operation to provide high-level alarm.
In Diagram 4, Type 5400-B Relay is used in inverse
operation to provide low-level alarm.
ACCESSORIES
The 5400 relays require a standard 8 pin octal base
for mounting. In addition a hold down strap is also
available to secure the 5400 the relay to the octal
base in vibration environments.
INSTALLATION NOTES
Because Series 5400 Relays feature a low voltage,
low current sensing circuit, inexpensive small
gauge lead wires may be used bet ween relays and
electrodes, sensors, or pilot switching devices.
Shielded cable is not required, and lead wires do
not have to be isolated from other wiring. Also, in
many level control applications, a common
electrode is not required so long as a good,
dependable metallic ground return from the relay to
the liquid is provided. The length of the control
wires, between the electrodes and the Series 5400,
are dependent on two factors, the control wire
configuration and the sensitivity setting, see
reference chart to the right.
Ordering Information
SINGLE LEVEL DUAL LEVEL
110 Volts A.C. 5400-A-L1 5400-B-L1 5400-C-L1 5400-D-L1
220 Volts A.C. 5400-A-L2 5400-B-L2 5400-C-L2 5400-D-L2
Direct Operation
(High Level Alarm)
Inverse Operation
(Low Level Alarm)
DIAGRAM 1:
PUMP DOWN CONTROL
5400-C DIRECT OPERATION
LOAD
LINE
LINE
LINE
VOLTAGE
LINE
VOLTAGE
{
LOAD
{
{
{
VOLTAGE
DIAGRAM 2:
PUMP UP CONTROL
5400-D INVERSE OPERATION
VOLTAGE
DIAGRAM 3:
HIGH LEVEL ALARM
5400-A DIRECT OPERATION
DIAGRAM 4:
LOW LEVEL ALARM
5400-B INVERSE OPERATION
Telephone Pair
Minimum
(1.0K ohms
Sensitivity)
In excess of
50,000 feet
5400-C RELAY
3
2
5400-D RELAY
3
2
5400-A RELAY
N.C.
N.O.
3
COM.
2
5400-B RELAY
N.C.
N.O.
3
COM.
2
B/W TYPE
4
5
1
B/W TYPE
54
1
B/W TYPE
54
1
B/W TYPE
5
4
1
6
7
8
6
7
8
6
7
8
6
7
8
LOW LEVEL
Two #14
in open air
In excess of
50,000 feet
Maximum
(250k ohms
700 feet 530 feet 265 feet 35 feet
Sensitivity)
Direct Operation
(Pump Down)
1080 North Crooks Road • Clawson, MI 48017 USA
800-635-0289 • 248-435-0700 • Fax 248-435-8120
www.ametekapt.com
COM
LOW PROBE
HIGH PROBE
COM
LOW PROBE
HIGH PROBE
COM
PROBE
COM
PROBE
Inverse Operation
START DRAIN
STOP DRAIN
GROUND RETURN TO TANK
OR COMMON ELECTRODE
STOP FILL
START FILL
GROUND RETURN TO TANK
OR COMMON ELECTRODE
HIGH LEVEL
GROUND RETURN TO TANK
OR COMMON ELECTRODE
GROUND RETURN TO TANK
OR COMMON ELECTRODE
Two #14
in ½” conduit
In excess of
50,000 feet
(Pump Up)
5400.B2R
11/02 • Z118
ELECTRODE
HOLDER
SOLENOID VALVE
OR PUMP
ELECTRODE
ELECTRODE
HOLDERHOLDER
SOLENOID VALVE
OR PUMP
ELECTRODE
HOLDER
ELECTRODE
HOLDER
Two #14
in lead sheath
8,000 feet