AMETEK 5200 Solid State Relay User Manual

INSTALLATION & SERVICE MANUAL
5200 Solid State Relays
Dual Voltage Contacts Contact Ratings
Arrangement Power Required
Operating Temp. Low Energy
Sensing Circuit
5200 Series
Basic Specifi cations
Either 115 or 230 volts AC at 50/60 hertz Silver Cadmium Oxide 10 amperes at 120 or 240 volts AC or 28 volts DC,
1/4 hp at 120 volts AC. and 1/3 hp at 240 volts AC Double pole, double throw load contacts plus single pole,
doublethrow holding circuit contacts 9 volt-ampere, 6 watt
-40°F to 180°F AC - 8 volts (less than 30 milliamperes) for 5200-L,
DC - 9.6 volts (less than 1 milliampere) for 5200-H
PRINCIPLE OF OPERATION
B/W 5200 Solid State Controls are offered in two basic types for use in a wide range of low and high sensitivity applications. Both are designed to operate on either 115 or 230 volts AC at 50/60 hertz. Both incorporate a low voltage sensing circuit. Both are also capable of performing control functions directly from electrodes suspended in a well or tank, the B/W Unifl oat level sensing system, or various pilot devices such as pressure, fl ow and limit switches, thermostats and pushbuttons, etc.
In addition, their operating characteristics are virtually unaffected by ambient temperatures ranging from -40°F to +180°F, or by variations from 80% to 110% of their rated voltage. Both controls are also furnished with a complete set of R1 fi xed sensitivity resistors or a variable resistance potentiometer to permit adjustment of operation based on the resistance of the liquid or material to be controlled. See tables below.
5200-LF1 Low Sensitivity Control
The basic components of this control are a transformer, a circuit board with voltage divider circuit, a silicon controlled rectifi er (SCR), and a load to provide isolated DPDT contacts. The sensing circuit voltage is 8.0 volts ac.
5200-HF2 High Sensitivity Control
This control is similar to the 5200-LF1, but with two basic differences: First, a rectifi er is used to convert the sensing circuit voltage from ac to 9.6 volts dc; second, a fi eld effect transistor (FET) is added to provide higher sensitivity. This permits positive operation on liquids with very high resistance.
Since the voltage divider circuit compares the liquid resistance to the R1 sensitivity resistor on both 5200-LF1 and 5200-HF2 controls it is important that the R1 resistor selected be rated higher than the resistance of the liquid or other sensing circuit.
Direct Operation
In direct operation, the load relay is energized when the level sensing circuit is completed. When operating from electrodes for pump down
operation, and liquid is below lower electrode, a high resistance is sensed across terminals 13 & 14, and a negative, or out-of-phase, signal is fed to the SCR.
When liquid rises to touch the upper electrode, a low resistance is sensed across terminals 13 & 14, and the signal to the SCR becomes positive, or in-phase, turning the SCR on, which, in turn, energizes the load relay to start the pump.
When load relay is energized, the holding circuit contact (4-7) closes to hold in the relay through the lower electrode and the liquid resistance until liquid level falls below the lower, or pump stop, electrode, at which time the SCR turns off and de-energizes the load relay to stop the pump.
Inverse Operation
In inverse operation, load relay is de-energized when the level sensing circuit is completed. In this mode of operation, function of load relay is reversed.
When operating from electrodes for pump up operation, and liquid is below lower electrode, a positive, or in-phase, signal turns the SCR on, energizing the load relay to start the pump.
When liquid rises to touch the upper electrode, a negative, or out-of-phase, signal turns the SCR off, de-energizing the load relay and stopping the pump. The holding circuit contact (1-7) closes, keeping the load relay de-energized until the liquid again falls below lower electrode.
5200-LF1 Low Sensitivity Control
R1 Sensitivity Resistor
270 ohms 15,000 feet All metallic circuits, B/W Controls Unifl oat 470 ohms 15,000 feet Strong electrolytes: Plating solutions. 1,000 ohms 15,000 feet Weak eletrolytes: Ammonium hydroxide, borax,
1,800 ohms 11,000 feet Most food processing applications: Beer wine, 3,900 ohms 5,000 feet Highly corrosive acid or caustic solutions where
10,000 ohms 2,000 feet Ordinary water with medium to high mineral
22,000 ohms 900 feet Sugar syrup solutions, most water with low
Maximum Lead Wire Lengths*
*Distance shown in the tables above are based upon the use of
two 18-gauge lead wires installed in 1/2” diameter conduit.
Application Recommondations
acetic acid fruit juices,milk buttermilk electrode current must be minimized to extend
electrode life: Hydrochloric acid, sulfuric acid, etc
content, sewage, water soluble oil and starch solutions.
mineral content. (Soft water-not distilled or deionized water. Use 5200-HF2 Control)
5200-HF2 High Sensitivity Control
R1 Sensitivity Resistor
10,000 ohms 50,000 feet Ordinary water with medium to highmineral
22,000 ohms 50,000 feet Water with low mineral content (soft - not
68,000 ohms 50,000 feet Steam condensate, corn syrup, strong alcohol 330,000 ohms 50,000 feet Alcohol solutions up to 70%
820,000 ohms 35,000 feet Deionized or distilled water, 95% glycerine, 90%
2.2 megohms 12,000 feet Glacial acetic acid, acetone, granular solids with
5.6 megohms 4,000 feet M.E.K. (Methyl ethyl ketone)
12.0 megohms 2,000 feet Anhydrous ammonia NOTE: DI water, glycols, alcohols and granular solids may require the 2.2, 5.6
or 12.0 megohms R1 resistor depending upon their purity or moisture content.
Maximum Lead Wire Lengths*
Application Recommondations
content, sewage, water soluble oil and starch solutions, long distance applications
distilled or demineralized), sugar syrup solutions, long distance applications.
solutions up to 50%
hydrogen peroxide, 95% ethyl alcohol, granular solids with high moisture content
some moisture content
INSTALLATION INSTRUCTIONS
These instructions relate primarily to the B/W electrode system of liquid level sensing. Call 1-800-635-0289 to request the B/W Catalog (Z66) for complete specifi cations, wiring and electrode equipment, etc.
ELECTRODE LEAD WIRES
Shielded cable is not required. Generally the size of the wire used is passed upon the physical strength required to meet given installation condition. Size 14 to 18 gauge wire is generally strong enough for private buried or overhead wiring, although size 26 gauge wire is adequate for positive relay operation. In some long distance applications, communication cable or telephone circuits may be used. In all cases, however, control circuit wires must have good insulation, and splices or connections must be watertight and insulated from ground.
Special Note - In order to prevent feed-back which can cause faulty operation, electrode lead wires should not be run in the same conduit with power or load carrying circuits.
ELECTRODE LEAD WIRE LENGTH 5200-LF1 Low Sensitivity Control
These controls operate with 8 volts ac on the sensing circuit, and in general, the maximum lead length is determined by the capacitance of the lead wires and the value of the R1 sensitivity resistor. Refer to Table on page 1 for suggested maximum lead lengths.
5200-HF2 High Sensitivity Controls
These controls operate with 9.6 volts dc on the sensing circuit, and in general, the maximum lead length is determined by the resistance of the lead wires. These controls will operate reliably with electrode lead lengths of several miles, but it is important to select the correct R1 sensitivity resistor to assure positive operation over these extreme distances. Refer to Table on page 1 for suggested maximum lead lengths. If your application involves greater distances than those shown, please contact factory.
GROUND CONNECTIONS
In all installations using electrodes, a good external ground connection and a dependable return circuit to the liquid are required. In most instances, grounding to a metal pipe leading to the tank is suitable, but electrical conduit should not be used for this purpose.
If a good ground connection to the liquid is not available, an additional ground or common electrode is required. When used, the ground or common electrode should extend slightly below the longest operating electrode. In addition, it is also desirable to ground the control chassis directly to the ground terminal or through a mounting screw.
Fixed Resistor Sensitivity
5200-LF1 Sensitivity Control 5200-HF2 High Sensitivity Control
Part Number Nominal Resistance Part Number Nominal Resistance
04-154900 270 ohms 04-149400 10,000 ohms 04-155000 470 ohms 04-138400 22,000 ohms 04-138300 1,000 ohms 04-138500 68,000 ohms 04-155100 1,800 ohms 04-138600 330,000 ohms 04-155200 3,900 ohms 04-138800 .007 to 1.0 megohms 04-149400 10,000 ohms 04-138900 820,000 ohms 04-138400 22,000 ohms 04-139000 2.2 megohms
04-139100 5.6 megohms
SERVICE INSTRUCTIONS
B/W Solid state controls are designed and built to require a minimum of service in the fi eld. Each one is tested at the factory to insure positive operation, and should not be altered or tampered with prior to installation. If a control does not operate properly after it has been installed with the proper sensitivity resistor added, the following information will be helpful in determining the probable cause.
Direct Operation
In direct operation, the load relay is energized when the liquid reaches the upper electrode or Unifl oat reed switch level, and electrode current is fl owing. Be sure sensitivity resistor has been installed between terminals 14 and 15, and a good ground connected to terminal 13.
!#,INE
6OR6
OR(Z
'ROUNDRETURNTOTANK
ORELECTRODEIFREQUIRED
3ENSITIVITY
2ESISTOR
6
6



3%2)%3
2%,!9
2



4!.+
,OAD
#ONTACTS
%,%#42/$% (/,$%2
05-034!243
05-034/03
#HASSIS'ROUND 4HROUGH-OUNTING3CREW
4/05-0 34!24%2
6!2)!",% 2%3)34!.#% 0/4%.4)/-%4%2 /04)/.!,!4 %842!#/34
If PVC well casings or drop pipes are used to contain the electrodes, a ground or common electrode is required.
R1 SENSITIVITY RESISTORS
Both the high sensitivity and the low sensitivity controls are shipped from the factory with a complete set of fi xed resistors or with a variable resistance potentiometer. Variable resistance potentiometers are furnished in three different ranges according to the table which follows.
Sensitivity Ranges
Relay Type R1 Resistor Direct Operation Inverse Operation
5200-LF1 5200-LV1
5200-LV2 5200-HF2
5200-HV3 5200-HV4 5200-HV5
Fixed R1 Resistor
Variable Variable Fixed R1
Resistor Variable Variable Variable
Up to 16,000 ohms Up to 26,000 ohms 100 to 700 ohms 200 to 1,200 ohms
600 to 15,000 ohms 1,000 to 24,000 ohms Up to 11.6 megohms Up to 12.0 megohms
2,000 to 100,000 ohms 2,000 to 100,000 ohms .007 to 1.0 megohms .007 to 1.0 megohms .047 to 5.0 megohms .047 to 5.0 megohms
To determine which fi xed sensitivity resistor to install, please refer to the table which follows. When operating from electrodes, select a resistor having a sensitivity value greater than the specifi c resistance of the material to be controlled. Any of the resistors can be used when operating from switch contacts, but the smallest value is recommended. Fixed resistance R1 resistors should be installed as shown on the wiring diagram furnished with the control.
2
PUMP DOWN
A - Load Relay Will Not Pull In
1. Power Failure or No Voltage at AC Line Terminals
Voltage at power in-put terminals should be 115 volts ac between terminals 10 & 11 or 230 volts ac between terminals 10 & 12.
2. Defective Control
To check control, disconnect electrode and load connections from control terminals. Apply line voltage to the appropriate terminals (10-11) or (10-12), and touch terminals 13 and 14 with an insulated jumper wire. Load relay should pull in when the jumper is connected, and drop out when the jumper is removed. Failure to do so indicates a defective control.
3. Poor Ground Connection
Controls will not function unless a good dependable ground connection is made to terminal 13. If a load relay does not pull in when liquid contacts the upper electrode, check ground connection to be sure it complies with installation instructions.
4. Broken Wires
A broken or loose wire from the control to the upper electrode or the ground (common electrode) will prevent load relay from pulling in. Broken wires can be checked by shorting the upper electrode to ground, or to the common electrode if used, at the electrode holder. If relay fails to pull in, one or both of the electrode leads is open. The individual leads can be checked by running temporary wires from the control to the electrode holder outside of conduit. If the load relay now pulls in, when shorting electrodes as noted above, the break is between the control and electrode holder. If load relay pulls in when the leads are shorted with a jumper at holder, but not at electrode tips, the break is in the electrode suspension wire.
Loading...
+ 2 hidden pages