1080 North Crooks Road
Clawson, MI 48017-1097
Phone: (248) 435-0700
FAX: (248) 435-8120
Internet: www.ametekapt.com www.ametek.com
Preface
This manual is for the Installation and Maintenance of the Gemco Series 1995L Micro-Set Programmable
Limit Switch.
Copyright 2000 by AMETEK
All Rights Reserved - Made in the U.S.A.
Version 0.1
AMETEK has checked the accuracy of this manual at the time it was printed. Any comments you may
have for the improvement of this manual are welcomed.
AMETEK reserves the right to revise and redistribute the entire contents or selected pages of this
manual. All rights to the contents of this manual are reserved by AMETEK.
iInstallation & Maintenance Manual
Contents
Chapter 1: Introduction/Description1
1.1 Programmable Features ....................................................................................................... 1
1.2 General Information ............................................................................................................. 1
1.3 Controller Features and Functions ........................................................................................ 2
The 1995L Micro-Set is a fully self-contained, 0 - 10 Volt input programmable limit switch. It includes
a three-digit LED display, six output relays, and one fault check relay, and it is fully programmable for
the following features:
1.1: Programmable Features
Scale FactorValid Scale Factor are 2 to 1,000.
Electronic OffsetFully programmable offset to any number with the scale factor.
Reset-to-PresetReset value is programmable to any number within the scale factor.
Motion DetectorLS6 can be programmed for either limit switch or motion detect
output.
Expansion OutputsProgrammable to accommodate up to 30 circuits.
See Section 1.2: General Information - Software Option P for more options.
1.2: General Information
The 1995L Micro-Set is a fully self-contained, microcomputer-based Programmable Limit Switch
(PLS) with a convenient keypad for programming each independent output circuit to open or close at
the desired settings. This system allows precise position control of linear motion.
A 1995L consists of an LTD (Linear Displacement Transducer) , LDT to programmer cable assembly,
and the programmer, which provides six limit switch outputs and one fault check output. The optional
output expansion modules will add six additional limit switch outputs per module, and up to four expansion modules can be driven by the programmer, for a total of thirty limit switch outputs.
The position input into this PLS is a 0 to 10 VDC analog signal usually provided by a Gemco LDT. The
0 to 10 volts is generated by the LDT over its active stroke. The PLS will read out position directly in
inches if the scale factor entered is the active stroke of the LDT (in inches).
The LDT generates a 0 to 10 Volt D.C. analog signal representing an absolute Linear position. This
Analog signal is converted to a digital signal at the Micro-Set. A microprocessor calculates and/or
converts these signals based on user-programmed data.
Installation and Maintenance Manual
1
Chapter 1: Introduction/Description
As the LDT passes through the preprogrammed dwell settings, the programmer outputs can energize
solenoids, relays, or solid-state circuitry to control external circuits.
The 1995L PLS was designed for use in linear applications. It incorporates many features for safe,
efficient operation.
The completely self-contained unit can operate up to 30 independent outputs (six standard) based on
the linear position of the LDT.
It offers an on line fault check which provides an automatic, in-process mechanism to verify that all
major programmable limit switch functions are operating properly. The fault check output can be
energized by activating the fault check enable input. The output is a mechanical relay with 1 N.O. and 1
N.C. contact, which remains energized during normal operation.
A programmable motion detect output will energize a relay when the LDT speed meets or
exceeds the customer-preprogrammed value.
SOFTWARE OPTION P ENHANCES THE SYSTEM BY OFFERING:
nMultiple Programs - Allow storage of job setups for future use. This saves time
spent reprogramming and lessens the chance of programming errors when tooling is
changed.
nReset-to-Preset-Allows an external input i.e. prox switch to reset the PLS to a
preprogrammed value.
1.3: Controller Features and Functions
The controller is housed in an all metal case that can be panel mounted. The controller consists of a
keypad, a CPU Board, and a Power Supply I/O Board.
The following features are found on the 1995L Micro-Set.
nDisplayA (3) three-digit LED readout and a 10-place bar graph will show
current Linear position, programming details and output status.
NOTE:The Bar graph will not display expansion board relay status.
nI/OMechanical relays, AC solid-state, and DC solid-state relays are
available, and any combination can be specified. The example in the
catalog shows three AC and three DC solid-state relays being specified. There is a fixed price adder for any combination of relays other
than all mechanical (6M). The fault check relay will always be a
mechanical relay regardless of the type of output relays specified.
See Chapter 8: Specifications.
2
Installation and Maintenance Manual
Chapter 2: Installation
Chapter 2: Installation
This section describes the installation and wiring of a standard 1995L Micro-Set PLS. Changes to
these instructions should be made as necessary if special options and/or equipment are used.
The 1995L Micro-Set should be installed in an area free of water spray, corrosive gases, flying chips
or other foreign matter. The operating temperature should be between 32 and 125 degrees Fahrenheit,
with less than 95% relative humidity.
2.1: Mechanical Installation
Mounting the 1995 Micro-Set PLS
The 1995L Micro-Set PLS is designed to be panel mounted. The face of the 1995L can be affected
by water and/or oil spray. Provisions should be made to protect the face of the unit from spraying or
splashing.
Panel cutouts, mounting holes, and sizes for each component are shown on Pages 6 and 7 of the 1995L
catalog section.
The controller should be mounted in the appropriate panel cutout and securely bolted into place using
the four (4) 3/16" diameter mounting holes.
NOTE:In instances where the 1995L is being mounted directly on a mechanical stamping press, care
should be taken to isolate the controller from shock load and vibration.
It is always good design practice to mount the controller in the enclosure as far away from the motor
starters and control relays as possible to minimize the effects of electromagnetic interference (EMI).
Interconnecting wiring also should be routed to minimize EMI coupling.
Mounting the Transducer
The transducer should be mounted securely to the machine in such a manner so as to minimize shock
and vibration. The transducer should be coupled to the moving machine. Coupling methods should
minimize backlash and be in accordance with the system accuracy required.
Installation and Maintenance Manual
3
Chapter 2: Installation
2.2: Electrical Installation
The Micro-Set is designed for use in an industrial environment and incorporates extensive transient
suppression circuitry. However, the same general installation rules should be followed that are used on
all microprocessor-based equipment. Incoming AC lines should be from a clean power source and
lines carrying computer level signals should not be routed in the same conduit as high voltage, transientproducing circuits such as variable speed drives, welders or DC switching circuits.
The 1995L PLS is designed to be used with a Gemco 0 to 10 Volt Analog LDT. Wiring for this system
is shown in Fig. 10-1, Fig. 10-2 and Fig. 10-3; Chapter 10: Wiring Diagrams. This wiring diagram is
applicable for all standard 1995 PLSs.
2.3: Wiring Instructions
Attach the pre-wired plug on the LDT cable to the LDT and route the shielded cable through a separate
grounded (earth ground) metal conduit to the panel and connect the mating half terminal block to the
1995L PLS. Be sure the shield wire is connected to Pin 1 of the 16-place connector.
When extension to the factory supplied cable is necessary, a junction box should be used to connect the
wire leads and the cable shields from one cable to the other. The cable shield should be grounded at the
1995 Micro-Set only.
AC line voltage - 115V AC 60Hz - should be connected to the 1995L PLS at the AC power
terminals on the 24-place connector.
4
Installation and Maintenance Manual
Chapter 3: Programming
Chapter 3: Programming
3.1: Security Input
The security input is often referred to as the Run/Program input. This input is located on the 16-place
terminal strip and is discussed in Chapter 6: Security Inputs. This input prevents unauthorized changes
to the programmed functions. With the unit in the Program mode, all functions of the controller can be
programmed. With the unit in the Run mode, all setpoints, reset-to-preset, motion detect and other
operational functions can be verified, but the programmed information cannot be changed.
3.2: Initialization
The following key commands should be entered on the
keypad to clear all programmed data upon installation and PRIOR to programming. This sequence
clears all programmed data. All operating parameters must be reprogrammed after using this initialization function.
CIR#- 9- 9 5
--
ENT
3.3: Scale Factor
NOTE:Programming of the desired scale factor or the number of outputs will delete all programmed
data held in memory. Therefore, these should be the first steps in your setup procedure.
The 1995L Valid Scale Factors are 2 to 1,000.
To program the scale factor, the following procedures must be followed:
1) Unit must be in the Program mode.
2) Depress- Desired Scale Factor -
CIR#- 1- 8 0
--
ENT
ENT
NOTE:Display will read from 0 to 1 less than Scale Factor.
Installation and Maintenance Manual
5
Chapter 3: Programming
3.4: Number of Outputs
The 1995L comes programmed for six outputs, but it is expandable to 30 outputs.
3.5: Selecting Number of Outputs
Selection of the number of outputs should be done after the desired scale factor is entered, and before
any other programming is done. See Chapter 4: Expansion Modules.
A)To program the number of outputs desired, the unit must be in the Program mode, then depress
. The unit will then show the number of circuits previ-
CIR#- 1- 7 7
ously stored.To change the number of outputs desired, enter the number of relays in multiples
of six and depress .
--
ENT
ENT
1)Valid numbers for are and
.
30
NOTE:If a number is entered that is not a multiple of six, the unit will store the next multiple of six.
CIR#- 1- 7 7
--
ENT
6 12 24 18
,,,,
3.6: Multiprogram (Available Only on P Option Units)
The Multiprogram feature allows the storage of multiple sets of output sequences that are
preprogrammed based on the various requirements of different tooling. When dies or tooling are
changed, the new program is simply called up on the keypad and all outputs are automatically set to the
new output sequences. The number of available programs will vary based on the number of output
limits and the number of setpoints programmed on each limit. A typical six-limit system with one ON
and one OFF setpoint per output will be capable of storing twenty programs in memory
A setpoint is one CIR ON or CIR OFF entry. The following formula shows the relationship
between the number of output relays, the number of programs, and the number of setpoints available
per program.
6
Installation and Maintenance Manual
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.