AMETEK 1995B User Manual

Series 1995B
Gemco
Micro-Set Programmable Limit Switch
®
Installation & Programming Manual
1080 North Crooks Road Clawson, MI 48017-1097 Phone: (248) 435-0700 FAX: (248) 435-8120 Internet: www.ametekapt.com www.ametek.com
Preface
This manual is for the Installation and Maintenance of the Gemco Series 1995B Micro-Set Programmable Limit Switch.
Copyright 2000 by AMETEK
All Rights Reserved - Made in the U.S.A.
Version 0.1
AMETEK has checked the accuracy of this manual at the time it was printed. Any comments you may have for the improvement of this manual are welcomed.
AMETEK reserves the right to revise and redistribute the entire contents or selected pages of this manual. All rights to the contents of this manual are reserved by AMETEK.
iInstallation & Maintenance Manual
Contents
Chapter 1: Introduction/Description 1
1.1 Programmable Features ....................................................................................................... 1
1.2 General Information ............................................................................................................. 1
1.3 Controller Features and Functions ........................................................................................ 2
Chapter 2: Installation 3
2.1 Mechanical Installation ......................................................................................................... 3
2.2 Electrical Installation ............................................................................................................ 4
2.3 Wiring Instructions ............................................................................................................... 4
Chapter 3: Programming 5
3.1 Security Input ...................................................................................................................... 5
3.2 Initialization.......................................................................................................................... 5
3.3 Scale Factor ........................................................................................................................ 5
3.4 Number of Outputs.............................................................................................................. 5
3.5 Selecting Number of Outputs ............................................................................................... 6
3.6 Multiprogram (Available Only on P Option Units) .............................................................. 6
3.7 Setpoint Formula ................................................................................................................. 6
3.8 Setpoints ............................................................................................................................. 8
3.9 Clear an Existing Setpoint .................................................................................................. 10
3.10 Clear All Setpoints............................................................................................................ 10
3.11 Setpoint Availability ........................................................................................................... 10
3:12 Electronic Offset ............................................................................................................... 11
3.13 Motion Detector ............................................................................................................... 11
3.14 Power-Up in a Position or RPM ....................................................................................... 12
3.15 Decimal Point Programming .............................................................................................. 12
3.16 Enable/Disable Outputs..................................................................................................... 13
3.17 Linear Speed Offset (Available Only on Option P Units .................................................. 13
3.18 Programming 1995 PLS for Linear Speed ......................................................................... 15
3.19 Minimum Speed Disable ................................................................................................... 15
3.20 Time-Based Outputs (Available Only on Option P Units) ................................................ 16
3.21 Brake Monitor Operational Description ............................................................................ 17
Chapter 4: Expansion Modules 20
Chapter 5: Fault Check 21
5.1 PLS Output Status on Fault Conditions ............................................................................... 22
Installation & Maintenance Manualii
Chapter 6: Security Inputs 23
Chapter 7: Remote Circular Display 24
7.1 POS/RPM On Remote Circular Display ............................................................................. 24
Chapter 8: Troubleshooting 25
8.1 Preliminary Checks ............................................................................................................ 25
8.2 Transducer Excitation Voltages ........................................................................................... 25
8.3 Electrical Noise and Power Quality Consideration .............................................................. 26
8.4 Grounding ......................................................................................................................... 26
8.5 Incoming Power ................................................................................................................ 26
8.6 Low Level Inputs............................................................................................................... 26
Chapter 9: Specifications 28
9.1 1995 Micro-Set PLS Programmer ..................................................................................... 28
9.2 Mechanical Relay (Single Pole, Double Throw) .................................................................. 28
9.3 AC Solid-State (Single Pole, Normally Open) .................................................................... 28
9.4 DC Solid-State (Single Pole, Normally Open) .................................................................... 29
9.5 1995E Output Expansion Module ...................................................................................... 29
9.6 1995-1446 Remote Circular Display .................................................................................. 29
Chapter 10: Troubleshooting Guide 30
Chapter 11: Wiring Diagrams 33
iiiInstallation & Maintenance Manual
Chapter 1: Introduction/Description
Chapter 1: Introduction/Description
The 1995B Micro-Set is a fully self-contained, single-turn resolver-based programmable limit switch. It includes a three-digit LED display, five output relays, and one fault check relay, and it is fully pro­grammable for the following features:
1.1: Programmable Features
Scale Factor There is one scale factor only, permanently set to 360.
Electronic Offset Fully programmable offset to any number with the scale factor.
Motion Detector LS5 can be programmed for either limit switch or motion detect
output.
Expansion Outputs Programmable to accommodate up to 29 circuits.
See Section 1.2: General Information - Software Option P for more options.
1.2: General Information
The 1995B Micro-Set is a fully self-contained, microcomputer-based Programmable Limit Switch (PLS) with a convenient keypad for programming each independent output circuit to open or close at the desired settings. This system allows precise position control of rotary motion.
A 1995B consists of a resolver-based transducer, resolver-to-programmer cable assembly, and the programmer, which provides five limit switch outputs, one fault check output and one brake monitor output. The optional output expansion modules will add six additional limit switch outputs per module, and up to four expansion modules can be driven by the programmer, for a total of twenty-nine limit switch outputs.
The single-turn resolver transducer generates a ratiometric analog signal representing an absolute rotary position. This ratiometric signal is converted to a digital signal at the Micro-Set. A microprocessor calculates and/or converts these signals based on user-programmed data.
As the transducer passes through the preprogrammed dwell settings, the programmer outputs can energize solenoids, relays, or solid-state circuitry to control external circuits.
The 1995B PLS was designed for use in rotary and/or rotary-to-linear applications. It incorporates many features for safe, efficient operation.
The completely self-contained unit can operate up to 29 independent outputs (five standard) based on the rotary position of the resolver.
Installation and Maintenance Manual
1
Chapter 1: Introduction/Description
It offers an on line fault check which provides an automatic, in-process mechanism to verify that all major programmable limit switch functions are operating properly. The fault check output can be energized by activating the fault check enable input. The output is a mechanical relay with 1 N.O. and 1 N.C. contact, which remains energized during normal operation. A programmable motion detect output will energize a relay when the transducer speed meets or exceeds the customer-preprogrammed RPM value.
Also offered is an on-line brake monitor that checks the stopping time of the machine against a customer selected preset stopping time in milliseconds, and which can be used to check the stopping distance at any point in the stroke. A dedicated output remains energized when the stop time parameters are within tolerance. An excessive stop time will cause the relay to de-energize, which could be used to stop further machine operation.
SOFTWARE OPTION P ENHANCES THE SYSTEM BY OFFERING:
n Multiple Programs - Allow storage of job setups for future use. This saves time
spent reprogramming and lessens the chance of programming errors when tooling is changed.
n Speed-Induced Offsets - On many variable speed machines, the limit switch outputs
have to be adjusted when the speed increases or decreases. This option automatically adjusts specified circuits based on speed.
n Time-Based Outputs - Specified outputs can be programmed to turn on based on
position and turn off based on time (0.01 - 9.99 seconds).
1.3: Controller Features and Functions
The controller is housed in an all metal case that can be panel mounted. The controller consists of a keypad, a CPU Board, and a Power Supply I/O Board.
The following features are found on the 1995B Micro-Set.
n Display A (3) three-digit LED readout and a 10-place bar graph are provided.
The LED readout displays current angular position and/or RPM and programming details, while the bar graph shows fault check, program status, and limit status.
NOTE: The Bar graph will not display expansion board relay status.
n I/O Mechanical relays, AC solid-state, and DC solid-state relays are
available, and any combination can be specified. The example in the catalog shows three AC and three DC solid-state relays being speci­fied. There is a fixed price adder for any combination of relays other than all mechanical (6M). The fault check relay will always be a mechanical relay regardless of the type of output relays specified. See Chapter 9: Specifications.
2
Installation and Maintenance Manual
Chapter 2: Installation
Chapter 2: Installation
This section describes the installation and wiring of a standard 1995B Micro-Set PLS. Changes to these instructions should be made as necessary if special options and/or equipment are used.
The 1995B Micro-Set should be installed in an area free of water spray, corrosive gases, flying chips or other foreign matter. The operating temperature should be between 32 and 125 degrees Fahrenheit, with less than 95% relative humidity.
2.1: Mechanical Installation
Mounting the 1995 Micro-Set PLS
The 1995B Micro-Set PLS is designed to be panel mounted. The face of the 1995B can be affected by water and/or oil spray. Provisions should be made to protect the face of the unit from spraying or splashing.
Panel cutouts, mounting holes, and sizes for each component are shown on Pages 6 and 7 of the 1995B catalog section.
The controller should be mounted in the appropriate panel cutout and securely bolted into place using the four (4) 3/16" diameter mounting holes.
NOTE: In instances where the 1995B is being mounted directly on a mechanical stamping press, care
should be taken to isolate the controller from shock load and vibration.
It is always good design practice to mount the controller in the enclosure as far away from the motor starters and control relays as possible to minimize the effects of electromagnetic interference (EMI).
Interconnecting wiring also should be routed to minimize EMI coupling.
Mounting the Transducer
The proper mounting of the resolver transducer is critical to ensure the systems accuracy. There are two resolver transducers available.
(A) Standard foot mount resolver transducer. The foot mount resolver transducer should be
mounted in an area free of excessive shock and vibration (as is commonly seen by mounting plates that extend over the edge of the press). The resolver transducer should be connected in a 1:1 ratio with the crank. If a double-ended cam limit switch is available, it is preferable to mount off of the rear shaft
NOTE: The Micro-set programmable limits are not control reliable for the clutch/brake circuits.
Mechanical cam limits must be used for these circuits.
Installation and Maintenance Manual
3
Chapter 2: Installation
(B) Combination mechanical cam/resolver systems. Intended as bolt-in replacements to
existing switches. The cam/resolver combination unit should be coupled where the existing limit switch is located. Wire and adjust the mechanical cams in accordance with the original press manufacturers specifications and wire the resolver cable to the controller.
2.2: Electrical Installation
The Micro-Set is designed for use in an industrial environment and incorporates extensive transient suppression circuitry. However, the same general installation rules should be followed that are used on all microprocessor-based equipment. Incoming AC lines should be from a clean power source and lines carrying computer level signals should not be routed in the same conduit as high voltage, transient­producing circuits such as variable speed drives, welders or DC switching circuits.
The 1995B PLS is only used with a single-turn resolver. Wiring for this system is shown in Fig. 11-2, Chapter 11: Wiring Diagrams. This wiring diagram is applicable for all standard 1995 PLSs.
2.3: Wiring Instructions
Attach the pre-wired plug on the resolver transducer cable to the transducer and route the shielded cable through a separate grounded (earth ground) metal conduit to the panel. Connect the mating half terminal block to the 1995B PLS. Be sure the shield wire is connected to Pin 1 of the 16-place connector.
When extension to the factory supplied cable is necessary, a junction box should be used to connect the wire leads and the cable shields from one cable to the other. The cable shield should be grounded at the 1995 Micro-Set only.
AC line voltage - 115V AC + 10% 50-60 Hz - should be connected to the 1995B PLS at the AC power terminals on the 24-place connector.
4
Installation and Maintenance Manual
Chapter 3: Programming
Chapter 3: Programming
3.1: Security Input
The security input is often referred to as the Run/Program input. This input is located on the 16-place terminal strip and is discussed in Chapter 4: Expansion Modules. This input prevents unauthorized changes to the programmed functions. With the unit in the Program mode, all functions of the control­ler can be programmed. With the unit in the Run mode, all setpoints, motion detect and other opera­tional functions can be verified, but the programmed information cannot be changed.
3.2: Initialization
The following key commands should be entered on the keypad to clear all programmed data upon installation and PRIOR to programming. This sequence clears all programmed data. All operating parameters must be reprogrammed after using this initializa­tion function.
CIR#- 9- 9 5
--
ENT
3.3: Scale Factor
The 1995B is available only with a 360 degree scale factor, set permanently.
3.4: Number of Outputs
The 1995B comes programmed for five outputs, but it is expandable to 29 outputs. However, when using a Remote Circular Display, the maximum will be 23 outputs.
Installation and Maintenance Manual
5
Chapter 3: Programming
3.5: Selecting Number of Outputs
Selection of the number of outputs should be done after the system is initialized and , and before any other programming is done. See Chapter 4: Expansion Modules.
A) To program the number of outputs desired, the unit must be in the Program mode, then depress
. The unit will then show the number of circuits previ-
CIR#- 1- 7 7
ously stored. To change the number of outputs desired, enter the number of relays in multiples of six and depress .
--
ENT
ENT
1) Valid numbers for are and . Remember, if using a Remote Circular Display, the maximum number of
30 outputs is 23.
NOTE: If a number is entered that is not a multiple of six, the unit will store the next multiple of six.
CIR#- 1- 7 7
--
ENT
6 12 24 18
,,,,
3.6: Multiprogram (Available Only on P Option Units)
The Multiprogram feature allows the storage of multiple sets of output sequences that are preprogrammed based on the various requirements of different tooling. When dies or tooling are changed, the new program is simply called up on the keypad and all outputs are automatically set to the new output sequences. The number of available programs will vary based on the number of output limits and the number of setpoints programmed on each limit. A typical five-limit system with one ON and one OFF setpoint per output will be capable of storing twenty programs in memory
A setpoint is one CIR ON or CIR OFF entry. The following formula shows the relationship between the number of output relays, the number of programs, and the number of setpoints available per program.
3.7: Setpoint Formula
Setpoint/Programs = 1467 - 2
6
Number of Programs x A
Installation and Maintenance Manual
Chapter 3: Programming
Where: A = 5 for 5 outputs
= 6 for 11 outputs = 7 for 17 outputs = 8 for 23 outputs = 9 for 29 outputs
Setpoints are in whole numbers (drop decimal).
Example: 12 outputs relays with 10 programs:
S.P. = 1467 -2 = 24.45 - 2 = 22 Setpoints/Program 10 x 6
The following table shows the relationship between the number of outputs, the number of programs, and the number of setpoints per program. The table only shows a few of the many combinations that are possible. Before programming outputs, it is advisable to verify that enough setpoints are available, otherwise the number of programs may need to be reduced. A setpoint is one CIR ON or CIR OFF entry.
STUPTUO5STUPTUO11STUPTUO71STUPTUO32STUPTUO92
352/1242/1702/1181/1161/1
21/0252/993/534/497/2
9/6281/2142/843/525/3
6/6321/7181/0142/703/5
1/797/7241/3102/852/6
Number of program Resulting in number of setpoints per program.
äã
Programming 1995 PLS for Multiprogram
A) Specify the number of programs desired, unit must be in the Program mode. Depress
See above table
CIR#- 7- 7 0
-- CIR ON
ENT
-
- ENT-
# of Programs
.
for the capabilities of your unit.
B) Upon entering the above sequence, depressing the key will display the
CIR OFF
maximum amount of setpoints per program.
NOTE: A time-based output uses up three setpoints.
Installation and Maintenance Manual
7
Chapter 3: Programming
C) will display the total number of setpoints available for use in
D) To display the active program, depress .
NOTE: Program 0 is the first program. If 10 programs were previously selected using Code 770,
CIR# 7- 7- -2 ENT-
the currently selected active program.
CIR# - 7­ To change programs, with the unit in the Program mode, depress .
(0 thru Highest Program Number)
there will be programs 0-9.
-
ENT
7 1
-
ENT-
3.8: Setpoints
Programming New Setpoints
A) Unit must be in the Program mode.
B) Select a limit switch circuit for programming. Depress .
The circuit number selected cannot exceed the number of output relays specified earlier using CIR# 177. See Section 3.5: Selecting Number of Outputs.
CIR#
--(1 thru 30) -
ENT
-
C) Depress . The will set the selected relay turn-on
point.
D) Depress . . This will set the selected relay turnoff
point.
1) On units where time-based circuits have been selected, the will be the
E) Multiple ON and OFF setpoints can be programmed on each circuit. All decimal points will
flash when more than one setpoint exists on the selected circuit.
F) An LS (Limit Switch) may not have the same value for both the ON point and the OFF point.
If a value is entered that is already a setpoint for that LS, only the new one will be used. For example: If LS1 had an ON point at 100 and an OFF point of 100 was entered, the ON point at 100 would be deleted, and the OFF point would then take its place. Assuming that these were the only setpoints, the output would turn ON at 0 and OFF at 100.
The programmable limits are programmed based on dwell on and dwell off locations. The dwell on typically represents the location at which a selected limit turns on and the dwell off represents the location at which the limit turns off. The position locations for the dwell on and dwell off are based
CIR ON- (Desired Pos)
CIR OFF- (Desired Pos)
time interval that the relay will be active once the ON setpoint has been reached.
ENT
ENT
CIR OFF
8
Installation and Maintenance Manual
Chapter 3: Programming
on a scale factor corresponding to the 360-degree rotation of the resolver. Example: In the foregoing example, with a 360 scale factor, a dwell on of 0 and a dwell off of 100 would look like this:
0
The shaded area represents the area where the selected limit output relay is energized. Programmable limit switch outputs offer a unique function which normal rotating cam limits cannot, namely, the ability to turn a limit on or off more than once in a 360-degree cycle. Multiple dwells allow several dwell on and dwell off values to be programmed for a particular limit. Example: Dwell on settings of 20, 100, 200, and dwell off settings of 80, 180, 270 would look like the following:
100 359
0 20 80 100 180 200 270 359
Another feature of programmable limits is the ability of programming a dwell on or a dwell off only. If only a dwell on setting is programmed, the output will activate at the dwell on setting and remain on to 359 degrees. Example: Dwell on setting of 180 and dwell off not programmed will result in the following:
0 180
Conversely, if only a dwell off setting is programmed, the output will activate from 0 degrees to the dwell off setting. Example: Dwell on not programmed, dwell off set at 180 degrees will result in the following:
359
0 180 359
The programmable limits also have the ability to shift the dwells to turn on sooner. This can be done to compensate for mechanical lag in the devices they are controlling as the machine speed increases. (See Section 3.17: Linear Speed Offset for more details). Limits can also be programmed to turn off based on timed settings.
Installation and Maintenance Manual
9
Chapter 3: Programming
3.9: Clear an Existing Setpoint
A) Unit must be in the Program mode.
B) Depress .
C) Depress or key until setpoint to be cleared is on the display.
D) Depress the key. Upon depression of the key, the setpoint on
the display after Step C is deleted.
E) This keypad sequence must be completed once to clear an ON setpoint and a second time to
clear the OFF setpoint. See Section 3.8: Setpoints
CIR#
CIR ON
(Output to be Cleared) ENT
CIR OFF
--
CLR SETCLR SET
3.10: Clear All Setpoints
There are two methods of clearing all setpoints. This is accomplished as follows:
A) Unit must be in the Program mode.
B) To clear all of the setpoints in the active program, depress: .
The active program is the program currently selected using Code 771. See Section 3.7: Setpoint Formula.
CIR#- 9- 1
ENT
-OR-
C) To clear all the setpoints in all programs, depress: .
NOTE: CIR# 91 and CIR# 391 only clear out programmed setpoints. They do not clear out Linear
Speed ramps or change circuits that have been selected as Linear Speed or Time-Based; however, they will clear the setpoints programmed in these circuits.
CIR#- 3- 9- 1
--
ENT
3.11: Setpoint Availability
Every 1995 PLS has a limit on the number of setpoints that can be stored in memory. On units with the Multiprogram option, refer to Section 3.7: Setpoint Formula to calculate the maximum amount of setpoints available.
On units without Multiprogram, setpoint availability is dependent on the number of outputs enabled.
5 Outputs = 253 Setpoints Available 11 Outputs = 242 Setpoints Available
10
Installation and Maintenance Manual
Chapter 3: Programming
17 Outputs = 207 Setpoints Available 23 Outputs = 181 Setpoints Available 29 Outputs = 161 Setpoints Available
Refer to the Section 3.5: Selecting Number of Outputs.
3.12: Electronic Offset
The offset key is used to synchronize the digital display with the actual machine position. The Series 1995B PLS has full scale factor offset capabilities, and the offset is held in nonvolatile memory. How-
ever, to eliminate possible problems in the event that a replacement PLS is required, it is good practice to mechanically synchronize the resolver with the machine and then use the offset key to make final, fine­tune adjustments.
Programming the Electronic Offset
A) Unit must be in the Program mode.
B) Stop machine at a known location.
C) Depress . After this sequence is
completed, the display will change to the position entered. The display and outputs are now synchronized with the actual machine position.
OFFSET (Actual Machine Position) ENT
-
-
3.13: Motion Detector
A programmable Motion Detect output will energize a relay when the transducer speed exceeds the customers preprogrammed RPM value.
The motion detector is set by entering the following:
A) Unit must be in the Program mode.
B) The motion detect must first be enabled before you can store any values. To accomplish this,
depress . A one (1) will enable the motion
detect circuit, and LS5 will now be your motion detect output relay. If a zero (0) is entered, the motion detect feature is disabled and LS5 will function as a normal limit switch.
CIR#- 5- 5
-
ENT
-
(0 or 1)
-
ENT
C) To set the value at which the motion detect relay energizes, depress
CIR#- 1- 7 6
NOTE: A CIR #176 can only be entered if the motion detect option is enabled.
--
ENT
Installation and Maintenance Manual
-
(RPM Value)
-
ENT
.
11
Chapter 3: Programming
3.14: Power-Up in a Position or RPM
The 1995B can power up displaying either Position or RPM data.
The power-up mode is programmed by entering the following:
A) Unit must be in the Program mode.
B) Depress . If a zero (0) is entered,
positional data will be displayed upon power-up; if a one (1) is entered, the unit will power up displaying RPM.
CIR#- 1- 6 3
--
ENT
-
(0 or 1)
-
ENT
3.15: Decimal Point Programming
A continuous, nonfloating decimal point may be programmed on the display. If a scale factor is selected that needs a decimal point in order to properly display its resolution in engineering units, the following 50 series codes are used:
50 - No decimal point;
clears existing decimal point 123
51 - Tenths 12.3
52 - Hundreths 1.23
To program a decimal point, enter the following:
A) Unit must be in the Program mode.
B) Depress .
Example: CIR# 50 = 123
12
CIR#- 50or 51 52
CIR# 51 = 12.3 CIR# 52 = 1.23
or -
Installation and Maintenance Manual
ENT
Chapter 3: Programming
3.16: Enable/Disable Outputs
During setup, the outputs may be enabled or disabled. When outputs are selected to be disabled, the status LEDs and the relays will be OFF. The unit must be in the Program mode to disable the outputs; as soon as the unit is switched to the Run mode, the outputs will be enabled.
The enable/disable feature is programmed as follows:
A) Unit must be in the Program mode.
-
B) Depress
CIR# 380 Enables the Outputs. CIR# 381 Disables the Outputs.
NOTE: If you try to disable the outputs in the Run mode, the unit will display EEE.
CIR#
(380 or 381)
-
ENT
.
3.17: Linear Speed Offset (Available Only on Option P Units)
This feature allows limit switch outputs, one through five, to be programmed to automatically advance and retard as machine velocity varies. The number of circuits affected by speed offset, the amount of offset, and the RPM range over which the offset develops are all keypad programmable. The amount to offset per RPM change will be the same for all outputs selected for this type of operation. This feature is used to compensate for the mechanical lag in machine controls.
The 16-step linear speed offset feature allows up to 16 different offset steps to be selected and a different amount of positive or negative (advance or retard) offset to be programmed between each of the sixteen steps.
Access Codes 501 through 516 are used to select the successive steps that define a ramp between the various offset values. That is, Code 501 is used to access and program the ramp between 0 RPM and the RPM value assigned to the first step; Code 502 is used to access and program the ramp between the RPM value of the first step and the RPM value assigned to the second step; and so on.
After using the access code to call up a step for programming, the CIR ON key is depressed, followed by the total amount of offset (from zero offset) to be applied to the circuit at the specified RPM value. The CIR OFF key is depressed next, followed by the RPM value of that step. The programmed offset value will be the total amount of offset being applied to the circuits from their zero offset starting values. This allows the circuits to be advanced or retarded between any two steps. See Section 3.18: Programming 1995 PLS for Linear Speed.
Installation and Maintenance Manual
13
Chapter 3: Programming
The graph above shows an example of five steps of linear offset in which the output circuits remain the same in the first step, then are being advanced in the next two steps, retarded between the third and fourth, and remaining unchanged between the fourth and fifth. The first step (501) is programmed so that the outputs will not be affected until after 20 RPM. Then the second step (502) is programmed to linearly advance the selected outputs by 20 degrees between 20 and 60 RPM. Circuits originally programmed to turn on at 150 degrees and off at 350 degrees will be turning on at 130 degrees and off at 330 degrees while at 60 RPM. The third step (503) is programmed to advance these same outputs to a total of 50 degrees as RPM rises between 60 and 100 RPM. The example circuit mentioned above that was origi­nally programmed to turn on at 150 degrees and off at 350 degrees will now be turning on at 100 degrees and off at 300 degrees while at 100 RPM. The fourth step (504) is programmed to retard the circuits back to a total of 30 degrees as RPM continues to rise from 100 to 140 RPM. The example circuit, originally programmed to turn on at 150 degrees and off at 350 degrees is now turning on at 120 degrees and off at 320 degrees while running at 140 RPM. The fifth step (505) is programmed to maintain a fixed 30 degrees of total offset between 140 and 200 RPM.
NORMAL PLS DWELL
0 150 350 359
1ST COMPENSATION AT 20 RPM
0 150 350 359
2ND COMPENSATION AT 60 RPM
0 130 330 359
3RD COMPENSATION AT 100 RPM
0 100 300 359
4TH COMPENSATION AT 140 RPM
0 120 320 359
5TH COMPENSATION AT 200 RPM
0 120 320 359
The offset (advance or retard) is applied linearly between each step, and the offset follows the same curve as RPM decreases. Example: At 80 RPM, offset value would be 35°.
14
Installation and Maintenance Manual
Chapter 3: Programming
3.18: Programming 1995 PLS for Linear Speed
A) Unit must be in the Program mode.
B) Select the number of circuits that will be offset based on RPM. The affected circuits will always
start with CIR# 1 and will follow in ascending sequence to the number specified. Depress:
CIR#
NOTE: LS5 cannot be programmed for Linear Speed if it is set for Motion detect. See Section 3.13:
NOTE: On units built prior to November 1, 1990, the Linear Speed Offset had only a single ramp
-
Motion Detector
offset. CIR# - 81 - ENT - CIR ON = Offset Amount CIR# - 81 - ENT - CIR OFF = RPM Value Codes 501 - 516 will result in a programming error on this older software.
80
-
ENT
- -
(1 thru 5)
ENT
C) Starting with Circuit 501, program the amount of offset and RPM point for the first offset ramp.
Next use Circuit 502 to program both values for the second offset ramp. Continue with Circuit 503 and onward in ascending order until all desired ramps are programmed.
CIR#- 501 thru 516
1)
from the original output settings) -
2)
CIR#- 501 thru 516
above specified amount of offset occurs.)
NOTE: If CIR# 501 - CIR OFF is set to zero, all linear speeds will be disabled.
-
ENT
- CIR OFF-
ENT
-
CIR ON
ENT..
-
(Specify the total amount of offset
-
(Specify the RPM at which the
3.19: Minimum Speed Disable
The Minimum Speed Disable sets the minimum speed at which the Linear Speed will affect the outputs. Below the programmed speed, the Linear Speed outputs will not be enabled.
The Minimum Speed feature is programmed as follows:
A) Unit must be in the Program mode.
B) Depress . This sets the Minimum Speed at
which the Linear Speed will affect the outputs. Below the programmed speed, the Linear Speed outputs will not be enabled.
CIR#
-
85
-
ENT
-
(RPM Value)
Installation and Maintenance Manual
-
ENT
15
Chapter 3: Programming
3.20: Time-Based Outputs (Available Only on Option P Units)
In instances where it is desirable to have an output actuate based on crank position and turn off based on time, we offer time-based limits. Examples of areas where time-based limits are applicable include lubricators and air blow-off limits. Even if the press stopped in the limit dwell area, it would only stay energized for a specific time period, eliminating potential waste. Circuits one through five can be selected for this type of operation. Circuits cannot be programmed for Linear Speed Offset and
Time-Based outputs at the same time; thus the total combined number of Linear Speed Offset and Time-Based outputs cannot exceed five.
NOTE: CIR# 301 thru 305 only enable the circuit so that it can be programmed for a Time-Based
output. After Time-Based circuits are enabled, see Section 3.8: Setpoints.
The Time-Based feature is programmed as follows:
A) Unit must be in the Program mode.
B) Depress
CIR# 301 represents CIR# 1, CIR# 302 represents CIR# 2, etc. A zero (0) after CIR# 301­305 means that the circuit will function as a normal limit switch as outlined in Section 3.8: Setpoints; however, if a one (1) is entered in after CIR# 301-305, it means that the circuit is to be set up for a position ON and a timed OFF output.
C) This sequence only enables or disables LS1 thru LS5 for Time-Based operation. After an LS
is enabled as a Time-Based circuit, follow normal programming instructions. See Section 3.8: Setpoints, C and D.
NOTE: If LS5 is set as a motion detector, it cannot be set for Time-Based.
D) A Time-Based output may only have one CIR ON and one CIR OFF setpoint. This output
will turn on based upon the CIR ON position data and will turn OFF based upon the CIR OFF time data, which is displayed and programmed in 0.01 second increments. A Time-Based output uses three setpoints. See Section 3.7: Setpoint Formula.
E) Outputs 1 through 5 may incorporate Linear Speed Offset or may be Time-Based. How-
ever, no output can be both. In addition, LS5 may be selected to be a motion detect output. If two or three types of outputs are required, first select the number of Linear Speed circuits required (CIR 80) and then individually select the Time-Based outputs and Motion Detect output.
CIR#- (301 thru 305)
-
-
(0 or 1)
- ENT ENT .
16
Example: Outputs 1 & 2 Linear Speed
CIR = 80 - ENT - 2 - ENT
Outputs 3 & 4 Time-Based CIR = 303 - ENT - 1 - ENT CIR = 304 - ENT - 1 - ENT
Installation and Maintenance Manual
Output 5 Motion Detect CIR = 55 - ENT - 1 - ENT
Chapter 3: Programming
3.21: Brake Monitor Operational Description
The 1995B Brake Monitor PLS offers an on-line monitor which checks the stopping time of the press against a customer selected preset stopping time in milliseconds, and can be used to check the stopping distance at any point during the stroke.
With keypad commands, the digital readout will display the stopping time (CIR #174) or the stopping distance (degrees) (CIR# 175) of each cycle. If the time from deenergization of the press clutch voltage to stopping the ram exceeds a customers programmed value, the brake monitor output relay will de­energize which can be used to stop further press operation. This output can be reset by momentarily opening and then closing the fault check input. Please note that the brake monitor system operates independently of the fault check system but both use the fault check input to reset their individual faults. Opening the fault check input will de-energize the fault and brake monitor output relays allowing the user to verify that these outputs are operating properly and have not been hardwired.
NOTE: In efforts to make the brake monitor fail-safe , we have changed the brake monitor circuit so
that if you see motion without seeing the brake input, a break fault will occur.
WIRING
Wire the programmer per Fig 11-2 (Chapter 11: Wiring Diagrams). In this drawing, relay LS6 is the brake monitor relay. It is normally energized (N.O. contact is closed and N.C. contact is open) and de­energized on a fault condition. Operating in this manner a disconnected wire or disconnected relay will indicate a fault condition.
Relay LS5 is either a standard LS output or the motion detect output, as selected by the customer. If operating as a motion detect output, the relay will energize when the transducer speed is greater than the customer programmed RPM value.
The brake monitor calculates stopping time by monitoring the time span between the clutch disengage­ment and the presss coming to a complete stop. The system begins this timing sequence when it sees the isolated contact, wired between input terminals 14 and 15, open. This isolated contact can be the contact of an existing relay in your control circuit or it can be provided by the Gemcos optional Brake Monitor input Relay #SD0395100 as shown on the next page. The contact of the brake monitor input relay must be open when the clutch disengages, and all wiring between its isolated contact and terminals 14 and 15 of the 1995 programmer must be protected from induced electrical noise.
Installation and Maintenance Manual
17
Chapter 3: Programming
PROGRAMMING AND MONITORING
To monitor press stopping time, depress CIR# - 174 - ENT. Stopping time will be displayed in milli­seconds from 001 to 999. Three decimal points indicate a stopping time in milliseconds, a single decimal point, two places to the left, will indicate a stopping time in seconds to one hundredth of a second. If the customers preset stopping time is exceeded, the display and decimal(s) will flash. They will continue to flash until the brake monitor output has been reset.
To monitor press stopping angle, depress CIR# - 175 - ENT. Stopping distance will be displayed in degree increments. If the stopping time is exceeded while in the stopping angle mode, the display will flash. It will continue to flash until the brake monitor relay has been reset.
When operating in either of the above modes, the display will maintain the stopping data until initiation of the next timing cycle. At this point, the display will indicate dashes until new data is available. Depres­sion of the POS or RPM keys will return the display from this operating mode.
To program the maximum acceptable stopping time, depress CIR# - 173 - ENT. The time data can be programmed from 001 to 999 milliseconds. If the programmed stopping time is exceeded, the brake monitor output (LS6) will de-energize until the fault check input is opened and then closed again.
NOTE: If you are using the fault check option, the fault check relay will cycle OFF/ON when the
brake fault output is reset.
18
Installation and Maintenance Manual
Programming the Maximum Stopping Time
A) Unit must be in the Program mode.
Chapter 3: Programming
B) Depress
CIR#- 1- 7 3
--
ENT
-
Maximum Stopping Time
-
ENT
This sets the maximum allowable stopping time in .001 second intervals. If the time required to stop following the loss of the brake monitor contact exceeds the brake monitor stopping time, then the error output LS6 is de-energized.
Display of Stopping Time
A) Depress . The display will sample and hold the stopping
CIR#- 1- 7 4
--
ENT
time of each press stroke. The stopping time is displayed in milliseconds. A single decimal in the left-most position will indicate that a stopping time is in seconds. The display will flash when the brake monitor stopping time (CIR# 173) has been exceeded. The display will stop flashing when the error is reset with the fault check input. Exiting this mode is done only by pressing the RPM/POS key. No values may be entered.
Display of Stopping Angle
A) Depress . The display will sample and hold the number
CIR#- 1- 7 3
--
ENT
of degrees traveled after initiation of the brake command. The stopping distance is the distance traveled since the loss of the contact. The display will flash when the brake monitor stopping time (CIR# 173) has been exceeded. The display will stop flashing when the error is reset with the fault check input. Exiting this mode is done only by pressing the RPM/POS key. No values may be entered.
Installation and Maintenance Manual
19
Chapter 4: Expansion Modules
Chapter 4: Expansion Modules
The 1995B PLS provides five outputs. A 1995E Expansion Module is required for each additional six outputs desired, up to a total of 29 outputs, or four expansion modules (units with Remote Circular Displays may use only up to 23 outputs total, or three expansion modules). The circuit location of each expansion module is defined by the location of a two-pin jumper on an eight-pin block in the upper left corner of the module. This jumper must be installed for the expansion module to operate. Two pairs of pins, located in the lower right corner of the expansion module, should be jumpered on only the last module in the wiring group. However, if a Remote Circular Display is being used, do not install these jumpers. Remove both jumpers from all intermediate expansion modules. See Chapter 11: Wiring Diagrams, Fig. 11-3 for additional expansion module wiring information. Each expansion module is provided with a full set of terminal strip designation decals. To avoid confusion, the appropriate decals should be installed along the output terminals, based on the location of the output selection jumper outlined below.
Fig. 4-1
See Section 3.5: Selecting Number of Outputs, for instructions on how to program unit for use with expansion modules.
20
Installation and Maintenance Manual
Chapter 5: Fault Check
Chapter 5: Fault Check
The Fault Check option provides an automatic in-process self-diagnostic mechanism to verify that all PLS functions are operating properly.
The Fault Check option will detect and disable system operation in the event of any of the following problems:
1. Disconnect or severed resolver cable.
2. Open or shorted resolver signals.
3. Resolver excitation failure.
4. Resolver-to-digital converter or associated electronic failure.
5. Microprocessor or 5 volt power supply failure.
Non-system-type faults, such as individual output failures, will not be sensed. It is recommended that the Fault Check output be used as an operate enable type signal. Loss of this output should immedi­ately stop the process which is being controlled.
The Fault Check input may be operated by an isolated contact, current sourcing, or current sinking device 5V DC at 10mA.
A normally closed, momentary open contact button can be wired per Fig 11-2, Chapter 11: Wiring Diagrams, to activate the Fault Check circuit, and it will provide a method of resetting the fault output after a fault condition has been sensed.
To reset the Fault Check output after the fault condition has been cleared, the fault reset input must be deactivated (open circuit) and then re-actuated. Cycling the fault reset input will cycle the fault check relay to verity that the Fault Check output is operating properly.
NOTE: If the Fault Check inputs are not wired, the display will still show when there is a fault and the
outputs will be disabled, but it will not lock on the fault. However, if the fault check inputs are wired as per Fig 11-2, Chapter 11: Wiring Diagrams, then upon seeing a fault, the fault check relay will drop out and all outputs will shut off until the fault is fixed and the fault check input is reset.
Installation and Maintenance Manual
21
Chapter 5: Fault Check
5.1: PLS Output Status on Fault Conditions
1) If a fault condition is detected, ALL limit switch outputs will turn off and the display will
show the following:
EE0 = Resolver Not Plugged in or Resolver Primary Open EE1 = Resolver Secondary S1-S3 Open or Shorted EE2 = Resolver Secondary S2-S4 Open or Shorted EE3 = Resolver Shorted - Primary Winding or Resolver Excitation Fault EE4 = Electronic Transducer Tracking Fault No Message Microprocessor or 5 Volt Power Supply Failure
The message will remain on the display and the outputs will be off until the problem is corrected and the fault reset button is pressed and released to reactivate the fault output and return the display and outputs to their normal operation.
2) If the fault condition is the result of a microprocessor failure or lockup, the state of the
limit switch output circuits cannot be predicted. However, the fault check output will turn off until the fault is cleared and the fault reset button is pressed and released. Removal and reapplication of power to the PLS system may clear a locked-up condition.
22
Installation and Maintenance Manual
Chapter 6: Security Inputs
Chapter 6: Security Inputs
The Run/Program security inputs may be operated by an isolated contact, current sourcing, or a current sinking device, 5V DC @ 10mA. See Fig 11-2, Chapter 11: Wiring Diagrams.
NOTE: The 1995 PLS cannot be programmed until the security input has been enabled by means of
connections from Pin 9 (+5V DC) to Pin 10 (Security +) input and from Pin 11 (Security -) input to Pin 14 (GND).
NOTE: If the Run/Security program is not needed (always in the Program mode) install jumper wires
form Pin 9 (+5V DC) to Pin 10 (Security +) and from Pin 11 (Security -) to Pin 14 (GND) on the 16-place resolver connector.
Installation and Maintenance Manual
23
Chapter 7: Remote Circular Display
Chapter 7: Remote Circular Display
The Remote Circular Display (1995-1446) is ideal for mechanical stamping presses and shears. Either position or RPM can be displayed on the large 3/4 LED digital display. A 360° bar graph will increment in 10° intervals showing the angle of the resolver.
The remote circular display gets its RS422 synchronous signal from the four-place terminal strip located on the back of the 1995 programmer. The display can be located up to 1,000 feet away from the programmer. See Fig 11-3, Chapter 11: Wiring Diagrams.
Installation and wiring of the remote circular display should be followed in the same manner as the
1995B described earlier in Chapter 2: Installation.
NOTE: When using a remote circular display, the maximum number of outputs is limited to 23 outputs
or three expansion boards.
7.1: POS/RPM On Remote Circular Display
The 3/4 LED display can display either position or RPM while the bar graph will always show angular position. To display RPM install a jumper wire from Pin 6 (RPM) to Pin 7 (GND) on the 11-place connector located on the bottom of the remote circular display.
24
Installation and Maintenance Manual
Chapter 8: Troubleshooting
Chapter 8: Troubleshooting
The following procedures are intended to aid in isolating system malfunctions to field replaceable modules. These modules include the 1995 programmer, output relays, remote circular display, trans­ducer, and all interconnecting cables. Once isolated, the defective module should be replaced and returned to the factory for repair.
NOTE: Field repair beyond this level is not recommended.
8.1: Preliminary Checks
Check all system wiring connections at the transducer and at the programmer. Amphenol-type connec­tors on the transducer and its cabling should be checked for tightness. A slight tug on all wire termina­tions should verify a good connection. Push-on cable connectors should be checked for proper con­nections. Verify that incoming AC voltage to the 1995 PLS is between 105V AC and 125V AC.
8.2: Transducer Excitation Voltages
AC voltage across terminals 2 (RH) and 3 (RL) of the 16-place terminal strip (labeled Red and BK/R) should be from 1.6 to 1.9V RMS. This is the output voltage being supplied to the resolver rotor. If this voltage is not present, disconnect the resolver wires at the 1995 programmer and recheck the voltage. If this voltage is still not present, the resolver excitation circuitry in the 1995 programmer has failed and should be replaced. If this voltage appears, a shorted condition in the resolver or its cable should be checked.
The return signals from the resolver stator windings are wired to the 1995 programmers 16-place terminal strip at terminals 4 and 5 (labeled White and BK/W), and terminals 6 and 7 (labeled Green and BK/G). To verity the presence of these AC return signals, put a voltmeter across terminals 4 and 5 and rotate the resolver. A voltage reading that rises and falls (0-2.3V RMS) between these terminals as the resolver is rotated indicates a good resolver return signal. Repeat this same procedure with your meter across terminals 6 and 7. No voltage or a voltage that does not vary as the resolver rotates indicates an open or shorted condition in the resolver windings or the resolver cable.
To check for an open or shorted condition inside of the resolver, disconnect the Amphenol-style con­nector from the transducer and make the following checks at the resolver: Measure the resistance across Pins A & B (rotor); it should measure approximately 19-50 ohms. Then measure across Pins C & D (stator); it should measure approximately 50-120 ohms. The resistance across E & F should be the same as C & D.
NOTE: Due to the many different types of resolvers that we have used over the years, these
resistance readings are only approximate and are intended for locating opens or shorts in the resolver wires or windings.
Installation and Maintenance Manual
25
Chapter 8: Troubleshooting
8.3: Electrical Noise and Power Quality Consideration
The 1995 PLS is designed for use in an industrial environment and incorporates extensive transient suppression circuitry. However, the same general installation rules should be followed that apply to all microprocessor-based equipment.
Problems that can be attributed to extreme electrical noise or poor power quality include loss of/or changes in program memory, loss of initialization, keypad or microprocessor lockup, sporadic outputs, and damage to resolver drive circuits and auxiliary input circuits.
8.4: Grounding
Circuit board level noise suppression circuits, ground planes, and cable shields all depend on a good earth ground for proper operation. Our field experience has shown that the quality of the service ground at many machines is marginal.
8.5: Incoming Power
Solenoids, welders, large motors, and variable-speed drives are all devices that generate excessive electrical noise throughout the power grid in a typical industrial environment. Isolation transformers or constant voltage type power supplies should be used to isolate microprocessor-based circuitry. The power on the output side of these isolation devices should be fed to the programmable limit switch and other microprocessor-based devices only. The loads being driven by the programmable limit switch output relays must not get their power from the output side of the isolation device. Using the output side of an isolation device to power loads other than the programmable limit switch totally defeats the purpose of the isolation device.
NOTE: When using an output relay for driving inductive loads such as solenoids, a noise suppression
device must be installed across the coil of the load. Use an MOV or RC noise suppressor for AC loads, or a commutating diode for DC loads.
8.6: Low Level Inputs
Low level inputs to the 1995B PLS include the resolver cable and other special purpose contacts such as fault check, brake monitor and security inputs.
The resolver should be wired to the 1995 PLS using an uninterrupted run of cable consisting of four twisted pairs with shields. Whenever possible, this cable should be run in a conduit by itself. If it must run in a conduit with other wiring, this wiring should not include power wires above 110V AC or wires driving noise producing loads.
26
Installation and Maintenance Manual
Chapter 8: Troubleshooting
If the resolver cable must be run through a terminal strip, it must be mounted in a small enclosure with no other wiring. The shields of the incoming and outgoing cable must be tied together and isolated from ground.
Special purpose contact inputs all operate by connecting the input pin on the 1995 PLS to a power or GND terminal (depending on method wired per Fig. 11-2; Chapter 11: Wiring Diagrams) on the 1995 PLS through a remote contact or solid-state switch. These computer level signals must be protected from induced electrical noise.
The contact used to activate the input should not be located outside the enclosure in which the 1995 PLS is mounted. Any wiring between the 1995 PLS input terminals and this contact located within the enclosure should be routed away from any power handling relays, contactors, or other noise generating devices.
If the input is to be activated by a remote device, the contact of the remote device should be used to energize a relay within the enclosure. The contacts of this relay are wired to the 1995 PLS input terminals.
Installation and Maintenance Manual
27
Chapter 9: Specifications
Chapter 9: Specifications
9.1: 1995 Micro-Set PLS Programmer
Resolution -12 Bit (4096) Scale Factor -360 Scan Time -Standard 335 µseconds Temperature -32°F to 125°F (Operating) Range -0°F to 150°F (Storage) Operating Voltage -110/120V AC 50/60 Hz 300 mA
INPUTS
Transducer -Resolver accurate to ±3 arc minutes provides resolution of 1
part in 4096, 2800 RPM maximum speed.
Logic -Fault check and security 5V DC at 10mA. May be operated
by isolated contact, current sourcing or current sinking device.
OUTPUTS -Plug-in relays listed below
9.2: Mechanical Relay (Single Pole, Double Throw)
Contact Relay -10 Amp Isolated Contact Pick-Up -2 ms Drop-Out -15 ms
9.3: AC Solid-State (Single Pole, Normally Open)
Maximum Load -1 Amp Load Voltage Range -70 - 250V AC Zero Voltage Switching Leading Current -3 mA at 120V AC Voltage Drop w/Output On -3.0V RMS or Less Inputs -N.O. and Common Operate & Reset Time -1/2 cycle of line voltage max. +1ms or less
28
Installation and Maintenance Manual
9.4: DC Solid-State (Single Pole, Normally Open)
Maximum Load -2 Amp DC Load Voltage Range -5 to 60V DC Leakage Current -2 mA Maximum On State Voltage Drop -1.5V Maximum Surge Current -5A (1 Sec. Maximum) Min. Operational Current -50 mA Operate Time -0.5ms Maximum Reset Time -2 ms Maximum
9.5: 1995E Output Expansion Module
Operating Voltage -110/120V AC 50/60 Hz 100 mA Temperature Range -32°F to 125°F (Operating)
0°F to 150°F (Storage)
Outputs -Same as Programmer
Chapter 9: Specifications
9.6: 1995-1446 Remote Circular Display
Operating Voltage -110/120V AC 50/60 Hz 150 mA Temperature Range -32°F to 125°F (Operating)
0°F to 150°F (Storage)
Installation and Maintenance Manual
29
Chapter 10: Troubleshooting Guide
Chapter 10: Troubleshooting Guide
MOTPMYS SESUACELBISSOP
EEE:swohSyalpsiD sitinuroecneuqesgnimmargorptcerrocnI
.noitamrofni
retpahCweiveR.edommargorpehtniton
margorP/nuRrofstupnIytiruceS:6
0EE:swohSyalpsiD 1EE 2EE 3EE 4EE
PPP:swohSyalpsiD.noitazilaitinifossoL
weiveR.esionlacirtceleronoitautculf
.noitazilaitinI
,etarepotonseodyalertuptuolaudividninA
reporpsetacidnidapyeknothgilsutatstub
.noitarepo
.atadsselgninaemsyalpsiddapyeK noitarbivrokcohshgihanidetnuommetsyS
lacirtceletnettimretnignisuacaera
.snoitcennoc
ytilauQrewoPdnaesioNlacirtcelE
.noitaredisnoC
sretpahCweiveR.tluafadetcetedsahtinU
.gnitoohselbuorT:8dnakcehCtluaF:5
rewoperevesasetacidninoitazilaitinifossoL
:2.3noitceSdnagnitoohselbuorT:8retpahC
noDELsutatsyalerfI.eruliafyalertuptuO
nrutt'nseodyalerehttub,setarepodapyek
.yalerecalpeR.deliafevahyamyaler,no
esionlacirtcelehgihanignitarepometsyS
snoitcurtsninoitallatsniweiveR.tnemnorivne
:6.8noitceSniselbacfognituorgninrecnoc
larenegweiverosladnastupnIleveLwoL
:3.8noitceSnisnoitaredisnocesionlacirtcele
30
sinottubtesffonehwEEEsyalpsidtinU
.desserped
.snoitcurtsnierawtfoS
Installation and Maintenance Manual
ro,edommargorpehtnitonsitinurehtiE
sseccalaicepsahtiwdeppiuqesitinuruoy
naclennosrepdezirohtuaylnoerehwedoc
latnemelppuSotrefeR.metsystesffo
MOTPMYS SESUACELBISSOP
Chapter 10: Troubleshooting Guide
astibihxetubylreporpsetarepometsyS
.stuptuollafossolyratnemommodnar
ehtotrewopllafossolyratnemommodnaR
atrohssarofrewopfossolA.metsys
ehtesuaclliwsdnocesillim05sanoitarud
sirewopnehW.nwodtuhsotmetsys
larevesekatnacmetsyseht,deilppaer
emitsihtgniruD.flestiezilaitinierotsdnoces
sihT.delbasiderastuptuolla,doirep
desuacebdluocrewopfossoltnettimretni
yalerdab,noitcennocpirtslanimretdabayb
rotomegralyrevafonoitacilppa,tcatnoc
tnalpgnimocnifossolyratnemomro,daol
.rewop
noitazinorhcnysesolstuptuodnayalpsidehT
.noitisopenihcamhtiw
ehtniegappilsybdesuacyllarenegsi
noitazinorhcnysfossolgnirrucer,laudargA
yfireV.revloserehtotsgnilpuoclacinahcem
,sgnilpuocfoytirgetnilacinahcemeht
nierataht,htrofosdna,sniahc,stekcorps
.tfahstupnis'revloserehtotniartevirdeht
lanretni,llamsasesuylbmessarevloserehT
ottfahstupnistitcennocotgnilpuocelbixelf
ehtedisnidetnuomsisiht;revlosereht
dnarevloserehtelbmessasiD.ylbmessa
.swercsgnilpuocehtfossenthgitehtkcehc
agnimmargorpnehwstnioplamicedgnihsalF
.tiucric
elpitlumsetacidnistnioplamicedgnihsalF
llaeesoT.tiucricdetcelesehtnostnioptes
"NORIC"ehtgnisserpedeunitnoc,sgnittes
evahstnioptesllalitnuyek"FFORIC"ro
.stniopteS:8.3noitceSeeS.deyalpsidneeb
demmargorpebtonnac5SL tcetednoitomarofputesylbaborpsi5SL
rotceteDnoitoM:31.3noitceSeeS.tiucric
.sliatedrof
.gnitarepotonerastuptuodeepSraeniL tonsahMPRelbanedeepsmuminimehT
muminiM:91.3noitceSeeS.dehcaerneeb
.sliatedrofelbasiDdeepS
.tesffotonlliwstuptuodeepSraeniL ,205,105#RICniderotssitahwweiveR
,ffotiucricehtniderotssi0afI.cte,305
noitceSeeS.deraelceratahtretfaspetslla
hcihwweiveR.tesffOdeepSraeniL:71.3
.deepSraeniLrofdelbaneerastiucric
Installation and Maintenance Manual
31
Chapter 10: Troubleshooting Guide
tluaFrotinoMekarB sahemitgnippotselbawollamumixamehT
MOTPMYS SESUACELBISSOP
weiveR.)371#RIC(dedeecxeneeb
lanoitarepOrotinoMekarB:12.3noitceS
.noitpircseD
ehtdnaspirttuptuotluafekarbehtfI
tonsahemitgnippotselbawollamumixam
teS-orciMehtrehtie,dedeecxeneeb
tuohtiwtnemevomfoMPR5detceted
tupniekarbehtro,tupniekarbehtgnisnes
.deliafsah)0015930DS(eludomyaler
rotinoMekarB:12.3noitceSotrefeR
.noitpircseDlanoitarepO
.delbanetonyalerkcehctluaF delbaneebylnolliwyalerkcehctluafehT
.giFrepderiwsitupnikcehctluafehtnehw
afI.)smargaiDgniriW:11retpahC(2-11
eht,deriwtupniehttuohtiwdetcetedsitluaf
lladnaegassemtluafehtwohslliwyalpsid
sitluafehtlitnudelbasideblliwstuptuo
.dexif
.giFrepderiwsitupnikcehctluafehtfI
adna)smargaiDgniriW:11retpahC(2-11
nawohslliwyalpsideht,detcetedsitluaf
eblliwstuptuollA.EGASSEMRORRE
lliwyalerKOkcehctluafehtdnadelbasid
ehtlitnutuodeppordniamerdnatuopord
situpnikcehctluafehtdnadexifsitluaf
rofkcehCtluaF:5retpahCeeS.teser
.sliated
rorretluafayalpsidyliratnemomlliwtinU
.egassem
.)smargaiDgniriW:11retpahC(
.noitceridgnorwehtnignitnuocsitinU neerG-kcalBesrever,elbacrevloserehtnO
.)smargaiDgniriW
,tluafyratnemomagnitcetedsimetsysehT tluafehtesuacebtinokcoltonlliwtub ,2-11.giFrepderiwtonsitupnikcehc
:11retpahC(,2-11.giFotrefeR.riaperiw
32
Installation and Maintenance Manual
Chapter 11: Wiring Diagrams
Chapter 11: Wiring Diagrams
Fig 11-1 Wiring Diagram
Drawing E0177100
Installation and Maintenance Manual
33
Chapter 11: Wiring Diagrams
34
Fig 11-2 Wiring Diagram
Drawing E0198203
Installation and Maintenance Manual
Chapter 11: Wiring Diagrams
Fig 11-3 Wiring Diagram
Drawing E0204400
Installation and Maintenance Manual
35
1080 N. Crooks Road l Clawson, MI 48017
800-635-0289 l 248-435-0700 l Fax 248-435-8120
www.ametekapt.com l www.ametek.com
898
01/03.Z83
5C
Loading...