AMETEK 1500 User Manual

INSTALLATION & SERVICE MANUAL
A
1500 Induction Control Relays
Principle of Operation
A B/W fl oatless liquid level control system consists of a relay of the proper type, a holder designed to support one or more electrodes or probes in the liquid container, and the corrosion resistant electrodes themselves. In as much as all B/W induction relays are quite similar differing only in contact arrangement, the following description of how a 1500-C Relay functions on a pump down control application will serve to explain the design, construction, and operating principles for the entire line.
As shown in diagrams below, the laminated core of the relay is
shaped. The primary coil is assembled to the upper bar of the core, and the secondary coil for the electrode is placed on the lower bar. An armature located below the legs of the connected to an insulated arm carrying the movable contacts. When the armature is raised, these contacts close or open the motor and electrode circuits, depending upon whether the contacts are normally open or closed. (Contacts shown normally open in this example).
core is
1500 Series
When a source of alternating current is connected to the primary coil at terminals 3 and 4, the primary coil sets up a magnetic ux which circulates through the shortest path following the lines of least resistance. As shown in Figure 1, this is through the lower bar of the laminated core on which the secondary coil is mounted. This magnetic fl ux induces a voltage in the secondary or electrode circuit coil. No current can fl ow in this coil, however, until the circuit is completed between the electrodes. Thus, the electrode circuit voltage being generated within the relay has no connection with the power line.
The B/W 1500 induction relay utilizes the liquid as an electrical conductor to complete the secondary circuit between the upper and lower electrodes. Thus, when the liquid contacts the upper electrode, the resulting fl ow of current in this circuit sets up a bucking action in the lower bar of the core. This action tends to divert lines of magnetic force to the core legs and sets up an attraction that pulls the armature in to contact with the legs, as shown in Figure 2. This armature movement closes the electrode and load contacts.
The lower contacts on 1500-C Relays (terminals 9 and 10) connect the secondary circuit to ground when liquid contacts the upper electrode and act as a holding circuit to maintain the relay in its closed position until the liquid falls below the lower electrode. This holding circuit provides control of the relay over any desired range in the liquid level, depending on the distance between the upper and lower electrodes.
The fl ow of current through the low energy secondary circuit is very small and varies with the voltage of the secondary coil. The secondary coil is selected to operate over the resistance of the liquid being controlled. Accordingly, since there is a wide range of secondary coils from which to choose, it is important that complete information regarding the nature of the liquid be furnished when ordering B/W induction relays.
1500C Relay Used for Pump Down Control
.C. LINE
FLUX
GROUND:
3
5
7
9
ARMATURE
A GOOD DEPENDABLE GROUND RETURN CONNECTION TO THE LIQUID IS REQUIRED
Figure 1 - Secondary coil circuit open; armature down. Figure 2 - Secondary coil circuit closed; armature up.
4
6
8
10
TO MOTOR STARTER
PUMP START ELECTRODE
PUMP STOP ELECTRODE
A.C. LINE
FLUX
GROUND:
3
5
7
9
ARMATURE
A GOOD DEPENDABLE GROUND RETURN CONNECTION TO THE LIQUID IS REQUIRED
10
4
6
8
TO MOTOR STARTER
PUMP START ELECTRODE
PUMP STOP ELECTRODE
1
Installation Instructions
Relay: Install relay in level upright position. Connect wires from AC supply to terminals #3 and #4 on relay. Make sure power is of same rated voltage and frequency as shown for connection to primary coil on relay data plate. Relays draw 9 volt amperes.
Electrodes: Install electrodes in tank or well by suspending them vertically from an electrode holder or some other suspending means. One electrode should be set at desired start level and one at desired stop level. For sewage or surface drainage sumps, make sure electrodes are hung far enough apart so that foreign matter fl oating on water cannot foul electrodes. Size 18 or larger Type TW or THW wire is recommended for connection to the relay.
Field Replaceable and Convertible Contacts
The Series 1500 Induction Relay provides circuit versatility by offering a contact kit that allows fi eld conversions from N.O. to N.C. or N.C. to N.O. contact arrangements. This option also allows you to add or replace contacts (up to 3 per relay) as required for expansion of your liquid level control needs.
CAUTION - Although the electrodes are connected to a low energy secondary coil output which has inherently low current, there may be up to 800 volts between the electrodes or from an electrode to ground. (See Secondary Coil Table.) Thus wiring and electrodes should be installed to protect personnel from accidental contact.
Ground: A system ground return circuit is required from the
indicated relay terminal to the liquid in order to complete the secondary circuit of relay. Conduit should not be used. Instead, connection should be made directly to uninsulated metal tank, or to metal pipe connected to tank below normal low liquid level. In wells, connect ground to pump or metallic water pipe. For concrete, wood, or insulated tanks, use an extra common electrode extending slightly below the longest operating electrode.
Secondary Coil: Because the secondary voltage on all B/ W relays is an induced voltage generated within the relay itself, the secondary coil should never be connected to any source of power. Voltage of the secondary coil installed on a given relay is determined by conductivity of liquid to be controlled.
Remove cover plate and armature
For a N.O. contact, install the moveable contact in the armature assembly facing toward the top of the relay. (away from the armature)
Contact Kit Part No. 15-000001
N.O. Contact N.C. Contact
For a N.O. contact, install the stationary contacts facing toward the bottom of the relay (toward the armature).
For a N.C. contact, install the moveable contact in the
N.O.
armature assembly facing toward the bottom of the
N.O.
relay. (toward the armature).
N.C.
For a N.C. contact, install the stationary contacts facing in toward the top of the relay (away from the armature).
Load Connections: B/W relays are two-wire control devices having load contacts rated at 1 hp., single-phase, 115 or 230 volts AC or standard duty pilot rating up to 600 volts AC. In operation, load contacts act as a switch to open or close a circuit. Connecting them to an external load does not introduce a source of alternating current into the circuit.
Accordingly, in making connections for direct operation of single-phase loads within rated capacity of relay, power connections must be made as shown in relay wiring diagram.
To operate higher rated single-phase loads or three­phase loads, a magnetic starter must be used. In making connections to motor starter, follow directions given on the starter wiring diagram for connecting two-wire control devices.
2
TOP CONTACT TERMINALS 1 & 2
MIDDLE CONTACT TERMINALS 5 & 6
BOTTOM CONTACT TERMINALS 9 & 10
CONTACT ARRANGEMENT CODE
A B C D E F G H J
1 N.O.
1 N.C.
2 N.O.
1 N.O.
1 N.C.
2 N.C.
3 N.O.
2 N.O.
1 N.C.
1 N.O.
2 N.C.
3 N.C.
1
3
LINE VOLTAGE
5
Clawson, Michigan 48017 U.S.A.
SECONDARY
7
1500-
9
R
B/W CONTROLS
50/60 Hz
VOLTS
2
4
6
R
8
10
Loading...
+ 4 hidden pages