Ames 980GS-16 User Manual

PUMP CONTROL VALVE
01/06
980 Series
Operation
The AMES Model 980-16 / 680-16 Pump Control Valve is designed to minimize the surges associated with the starting and stopping of pumps. The valve slowly opens and closes as required to control pumping related surges. The pump starts and stops against a closed valve.
Pump start up: When the pump is signaled to start, the 4-Way Solenoid is energized and directs uid and pressure into the power chamber (below the diaphragm), and relieves uid and pressure from the cover chamber (above the diaphragm). The uid and pressure relieved from the cover chamber is vented to atmosphere or available oor drain. The valve opens at an adjustable rate, gradually admitting pumping pressure into the distribution system. Rate of valve opening is controlled by the adjustable opening speed control, which restricts the speed at which uid and pressure evacuate the cover chamber. The valve
remains fully open during the pumping cycle.
Pump shutdown: When the pump is signaled to shut-off, the 4-Way Solenoid is de-energized, and directs
uid and pressure into the cover chamber (above the diaphragm), and relieves uid and pressure from the power chamber (below the diaphragm). The uid and pressure relieved from the power chamber is vented to atmosphere or available oor drain. The valve closes at an adjustable rate, gradually reducing pumping pressure. Rate of valve closure is controlled by the adjustable closing speed control, which restricts the speed at which uid and pressure evacuate the power chamber. When the valve reaches the closed position,
the limit switch is actuated, turning the pump off.
Model
680-16
980-16
Emergency Closure: The valve is equipped with a Mechanical Check Feature, which acts independent of
diaphragm position, and provides immediate closure when ow ceases.
Manual Operation: Engaging the Solenoid Manual operator simulates power to the solenoid, manually opening the main valve. Disengaging the Solenoid Manual operator returns the valve to the closed position.
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.amesrewater.com
PUMP CONTROL VALVE
01/06
980 Series
Installation Guidelines
• Prior to installation, ush line to remove debris.
• Install valve horizontally “in line” (cover facing UP), so ow arrow matches ow through the line. Avoid
installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than described.
• Install inlet and outlet isolation valves. NOTE: When using buttery valves, insure disc does not contact control valve. Damage or improper valve seating may occur.
• Provide adequate clearance for valve servicing and maintenance.
• Provide adequate drain for cover chamber and power chamber discharge. Consult “Valve Cover
Capacity” chart on appropriate main valve Engineering Bulletin.
• Install pressure gauges to monitor valve inlet and outlet pressure.
• Connect Solenoid and Limit Switch to appropriate pump control panel locations and power source in
compliance with local electrical codes.
Other AMES Pump Control Valves
980-16-19 / 680-16-19 Pump Control Valve with High Capacity Pilot System 981 / 681 Pump Control Valve with Pressure Reducing Feature 982 / 682 Pump Control Valve with Backpressure Feature 984 / 684 Pump Control Valve with Rate-of-Flow Feature 985 / 685 Deep Well Pump Control Valve 985-20 / 685-20 Deep Well Pump Control Valve with Pressure Relief Feature 986 / 686 Pump Control Valve
Model
680-16
980-16
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.amesrewater.com