Ames 972GS-20 User Manual

ON-OFF FLOAT VALVE with PRESSURE SUSTAINING FEATURE
01/06
970 Series
Operation
pressure during tank lling operations.
The On-Off Float Pilot directs upstream pressure into and out of the cover chamber of the 3-way Accelerator Pilot. When the cover of the Accelerator Pilot is pressurized, the main valve cover chamber is vented downstream, causing the valve to open. When the cover of the Accelerator Pilot is de-pressurized, the main valve cover chamber is connected to upstream pressure, causing the valve to close drip tight. Valve opening and closing speeds are separately adjustable. When water level reaches the adjustable high-level setpoint, the Float Pilot de-pressurizes the cover chamber of the 3-Way Accelerator, closing the valve drip tight. The valve remains closed as water level decreases. When water level reaches the adjustable low­level setpoint, the Float Pilot pressurizes the cover chamber of the 3-Way Accelerator, opening the valve.
High and low levels are separately adjustable by positioning stop collars on the oat rod(s) at desired
opening and closing setpoints.
Model
672-20
972-20
The normally closed sustaining pilot remains open when upstream pressure is above the adjustable setpoint, and modulates toward a closed position if upstream pressure falls below the setpoint. As the sustaining pilot
closes, uid is directed into the main valve cover chamber, allowing the valve to modulate toward a closed position, raising upstream pressure. Normal on-off oat control operation resumes when upstream pressure
is above the sustaining pilot setpoint.
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.amesrewater.com
ON-OFF FLOAT VALVE with PRESSURE SUSTAINING FEATURE
01/06
970 Series
Installation Guidelines
• Prior to installation, ush line to remove debris.
• Install valve horizontally “in line” (cover facing UP), so ow arrow matches ow through the line. Avoid
installing valves 6” and larger vertically. Consult factory prior to ordering if installation is other than described.
• Install inlet and outlet isolation valves. NOTE: When using buttery valves, insure disc does not contact control valve. Damage or improper valve seating may occur.
• Provide adequate clearance for valve servicing and maintenance.
• Install pressure gauge to monitor valve inlet pressure. If On-Off Float Pilot is remotely mounted it should
be eld connected with 3/8” minimum copper tubing in accordance with factory piping schematic.
• Float Pilot, Rods, and Ball should be mounted in a eld installed “stilling well” for protection against
surface turbulence and interference.
• Additional 12” Float Rods available. Consult Factory.
Other AMES Float Control Valves
972 / 672 On-Off Float Control Valve (4” & smaller) 972-19 / 672-19 On-Off Float Control Valve (6” & larger)
979 / 679 Modulating Float Control Valve
979-15 / 679-15 Modulating Float Control Valve with Solenoid (On-Off) Feature
979-20 / 679-20 Modulating Float Control Valve with Pressure Sustaining Feature
Model
672-20
972-20
8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.amesrewater.com