The Ameritron AL-1200 is a 1500 watt output linear amplifier
that operates from 160 through 15 meters. The Ameritron AL1200X is the export model and covers 160 throug h 10 meters.
The AL-1200 uses a single 3CX1200A7 tube in a class AB2
grounded grid circuit. CW, FM and RTTY efficiency is
improved by shifting the bias deeper into class B. The heavy
duty power supply and RF components, co mbined with a f orced
air system utilizing chimneys, provide long service life for
expensive components. The AL-1200 is shipped factory wired
for 240 volt, 50/60 Hz power mains.
PLEASE READ THIS MANUAL BEFORE OPERATING THIS EQUIPMENT!
116 Willow Rd.
Starkville
MS 39759
UNPACKING INSTRUCTIONS
y
p
1. Carefully remove t he amplifier, tra nsformer, and t ube from their shi pping carto ns.
Inspect each item for visible damage. If any damage occurred during shipment,
the transportation company immedi at e ly.
notif
2. Save all packi ng materials i n case you n eed to return your AL-1200(X) for factory
service. The cartons have been designed to give maximum protection for this
amplifier. Any units returned without proper packing may be damaged and
shipping claims cannot be made. C ontact the factor y bef ore retur ning an y units .
3. Remove the scr ews that hold the cover to the amplifier. Slide the cover back and
remove it from the amplifier. Remove the package that is in the area where the
transformer will be mounted. This package contains the chimney for the
3CX1200A7. There is also a small package that contains the fuse s, fuse caps and
the remainder of t he ch ass i s scr e ws .
4. Please read the GENERAL INFORMATION and SPECIFICATIONS sections
before attempting to install the transformer and tube. Go to the INSTALLATION section on page 4 to begin installin g t he tra nsf or me r and tube.
5. This amplifier must always be disconnected from the power mains before removing
the cover. S ee the precau tion on p age 10. Please rea d the e ntire manu al to become
familiar with the o
eration of t he AL -12 00(X) amplifier.
1. Inexpensive tubes: the AL-1200 uses a single rugged
p
p
pag
g
y
y
p
2. Fast warm-up time:the 3CX1200A7 requires only a
few seconds of warm-u
time.
3. SSB/CW switch: the bias voltage is switched to provide
the best linearity on SSB or the lowest dissipation on
CW operation.
6. Two Illuminated Panel Meters: the AL-1200 has two illuminated panel meters. . The Grid Current meter provides a continuous reading of grid current and indicates
proper operation of the amplifier. The other meter reads
Plate Voltage (HV), Plate Current (IP), Peak RF Watts
(PO) and ALC.
7. Operate/Standby Switch: filament and plate voltages are
maintained while allowing the amplifier to be bypassed
for "barefoot" operation.
4. ALC Indicator: the drive level is detected to provide a
control voltage for the exciter. ALC prevents overdriving of the linear and reduces distortion from excessive drive
ower.
5. Vernier Plate and Load Adjustments: both tuning con-
trols have vernier 6:1 reduction drives for smooth tuning.
-
Input
Circuit type: Pi-network, slug tuned coils
maximum VSWR at resonance: 1.2:1 minimum
2:1 VSWR bandwidth: 20% maximum drive
power permissible: 130 watts typical drive for
full power output: 100 watts
Output
circuit type: Pi-L, Pi
in
hour continuous carrier: 1500 watts (Below 18MHz) 30
second continuous carrier: 1800 watts plus
in
hour PEP two-tone test: 1800 watts
8.12 Volt Auxiliary Jack: 12 volts at 100 mA is provided
for accessories such as the ATR-15 Antenna tuner.
9. XMT Indicator LED: provides a front panel indication of
proper amplifier keying by the exciter during operation.
Caution: This amplifier must be disconnected from the
power mains before removing the cover. See the warning
e 10.
on
*
Metering: multimeter: plate current, plate voltage,
drive/ALC, power output (PEP watts). Grid: grid
current
ALC: ne
Efficienc
Efficienc
MARS/WARC: yes, bandswitch set to nearest amateur
Keying: requires relay closure or sinking to ground of
ative going, 0-20V, adjustable, phono jack
CW: 65% typical
SSB (envelope crest): 62% typical
band
ositive (+) 12 VDC at 100 mA, phono jack
Power Supply
circuit type: full wave bridge, capacitor input no
load voltage: 3600V
full load voltage. 3300V full load current: .8 amp
regulation: 10% or better transformer: 32 lbs.,
hypersil capacitors: 26 mfd total, computer grade
maximum draw at rated output: 13 amps at 240V
AC, 50/60 Hz
"
Weight: 77 lbs.
Frequency Coverage: 1.8 through 21 MHz amateur bands
Third Order IMD at Rated Output: -34 dB at 1500
w
output
*
specifications ar e subj ect to c hang e wit hout notice or obli gatio n.
SAFETY INTERLOCK
y
p
p
quip
p
ply
(
GENERAL INFORMATION
PLATE SUPPLY
While the Amplifier's top cover is in place, the interlock switch
closes to allow AC line voltage to reach the power transformer.
When the top cover is removed, the interlock opens and
disconnects the l ine vo lt age . T his do e s no t d i scha rge t he b ank o f
power supply filter capacitors. Be sure to allow the filter
capacitors to discharge before you touch anything inside the
Amplifier. You can select the High Voltage function of the
Multimeter to check the high voltage potential. Never attempt to
defeat the safety interlock.
of this amplifier with the unit plugged into the power line.
WARNING- Never remove the cover
DRIVING POWER
This Amplifier is designed to operate at full ratings when it is
driven by an exciter that has approximately 100 watts of RF
output. You can use an exciter that has lower output power, but
the Amplifier's output will be less. If you use an exciter that
delivers more than 100 watts, carefully adjust the driving power
to avoid "over drive" a nd the crea tion of spur ious si gnals, whi ch
create needless interference to other operators. We highly
recommend that you use a monitor scope fo r continuous output
monitoring. The display on an oscilloscope is the best way of
determining the amplitude of the voice peaks which, if
excessive, can cause "flat topping" and splatter.
IMPORTANT: In no case should you advance the power output
control of your exciter beyond the point where the Amplifier's
Power Output indication ceases to increase. If you turn the
control past this point, nonlinear operation may occur.
The plate supply has a full wave bridge rectifier and a 1.8 KVA
CCS rated tape wound hypersil transformer. Filtering is
accomplished by a bank of high quality capacitors totaling 26
mfd (additional capacitance will not improve supply
performance). The Plate Supply will not be harmed by normal
continuous amateur operation at 1500 watt levels. Power is
applied thro ugh RLY2 when the 1 2V DC lo w voltage supp ly is
activated. A 10 ohm resistor limits the line current during the
filter capacitor charge time to lower the stress on components.
When the primary voltage approaches the full line value, RLY3
shorts the 10 ohm resistor and applies the full line voltage to the
plate transformer. The 10 ohm resistor acts as a fuse during
start-up if the high voltage supply has a short.
EXPORT MODIFICATIONS
A simple modification will allow operation on frequencies
above 15 meters. Instructions for this modification are available
by sending a written request for "Export Modification
Instructions" along with a copy of a valid amateur license.
There is no charge for this information. Export models are
shipped with this modification and have an "X" following the
serial number. Standard frequency coverages are indicated in
the chart following the tuning instructions on page 6.
TECHNICAL ASSISTANCE
Technical assistance is available during our normal business
hours on weekdays. The following information is required to
assist
ou with operational problems:
FILAMENT SUPPLY
The filament circuit of this amplifier satisfies all requirements
of the tube manufacturer related to tube performance and life.
Inrush current is controlled by the transformer internal
resistance and impedance, filament choke resistance and
filament wiring resistance. To insure maximum life of the tube
never replace any circuit components or wiring with substitute
parts.
The low voltage tap on the filament transformer primary provides the ability to operate the blower at slower speeds for
reduced noise. Normal amateur operation in CW and SSB will
not cause heat damage to components on any recommended tap.
It is always advisable to use the maximum speed (air flow) that
the level of noise permits to extend component life. Wiring
information for the blower is shown in the "Transformer
Connections" instructions.
The high voltage present on the plate choke and air variable
capacitors attracts dust and dirt out of the air stream. It is
particularly important that the high voltage areas at the bottom
of the plate choke and the insulators on the air variable
capacitors be dust free. These areas should be inspected every
few months if the amplifier is operated in a dusty environment.
Unplug the line cord, and wait about 90 seconds until the power
supply capacitors discharge. Remove the cover and connect a
jumper wire from ground to the anode connection of the tubes.
2. Date of
3. An accurate descri
Meter readings at all stages of the tuning proceedure are very
important along with a complete description of the other
e
ment used with our product.
Written assistance is also avaiable. Due to time delays in
rocessing mail, please allow at least three weeks for a writ
ten re
NOTE: This is a safety wire that must be installed when
beginning service work and removed when work is finished.
Use a soft bristle brush dipped in alcohol to clean areas mentioned previously. In the event that cleaning is required at
frequent intervals, place a low restriction air filter material over
the air inlet holes on the left front side of the cabinet near the
filter capacitors. Most hardware stores stock suitable materials
that are used as replacement filters for window air conditioners.
urchase and dealer
.
tion of the problem
AMERITRON 116
Willow Road
Starkville, MS 39759
Tel: (662) 323-8211
Fax:
662) 323-6551
METERING
OS
.
The AL-1200 has two illuminated meters. The Grid Current
meter provides a continuous indication of the 3CX1200A7 grid
current. This exclusive feature of Ameritron amplifiers indicates
proper amplifier operation better than any other parameter. Do
not exceed 300 mA on this meter during normal operation of
this amplifier. The other meter reads Plate Voltage (HV), Plate
Current (IP), Pe ak RF W a tts (P O) a nd ALC. These functio ns a re
selected with the Multimeter Switch.
Plate Voltage (HV): Read DC Plate Voltage on the 4000 volt
scale. This scale is 100 volts per division. Normal voltages are
6
3
00 volts no load, 3300 volts full load.
Peak RF Watts (PO): Read Peak RF Watts on the 2000 watt
scale. This scale has 50 watt divisions below 1000 watts and
INSTALLATION
TRANSFORMER INSTALLA TION
Remove the cover of the amplifier. Remove the package that is
in the plate transformer area. This is the fuse pack and chimney
for the AL-1200. Remove the top 7/16" nuts from the four
transformer mounting bolts inside of the amplifier. Carefully
remove the transformer from its shipping carton.
NOTE:This circuit uses an emitter follower to charge a
capacitor to the peak envelope voltage detected by the
ALC/Power Board. Accurate peak envelope power readings are
given when the amplifier is connected to a 50 ohm nonreactive
load. If the amplifier is used with a mismatched load, the power
meter will read higher or lower than normal by a ratio up to the
value of the SWR. Potentiometer R5 on the Meter Board (5001140-1) adjusts the calibration of the power meter.
ALC: Indicates a relative drive level (average, not PEP) that
can be estimated by dividing the Peak RF Watts scale by 10.
NOTE: There is a neutralization tab mounted on a ceramic
standoff near the 3CX1200A7. This tab increases the
amplifier's efficiency on 21 and 28 MHz. DO NOT CHANGE
THE P
ITION OF THIS TAB
Now slide the colored insulating boots back over the terminals.
Important: The leads must be in the positions indicated by the
color coded insulating boots(see Fig. 1) for 240V operation. For
220V operation, see page 5. Caution: Do not use the 220V
wiring unless the line voltage is always below 220 VAC. The
Standard USA voltage is 240 VAC, not 220
.
Place the transformer on the four
1
/4-20 mounting bolts. Use
care because the transformer is heavy. The side with the two
high voltage secondary RED leads must be adjacent to the center
panel(see Fig. 1). Now place a 7/16" nut on each bolt (see Fig.
2). Snug the nuts do wn manually. Do not ti ghten with a ratchet
wrench.
Remove the brass
1
/4" hex nuts and the top flat washer from the
two brass 6-32 screws on the rectifier board (see Fig. 1). Install
the RED lead ring terminals on the screws and replace the flat
washers and 1/4" hex nuts. Position the wires so that the black
insulated areas are at least
objects. Now tighten the
1
/4"
1
/4"
from each other and any metal
hex nuts.
For 240V Operation (factory wired):
The four primary leads have colored plastic insulating boots
over the quick disconnect terminals. Slide these back prior to
installing the leads. Install the color coded boots as follows:(see
Fig. 1)
BLUE (Brown wire) to the top relay terminal
YELLOW (Black/White) to the top terminal of terminal
CLEAR (Black wire) to the second terminal of terminal block
RED (Brn/Wht-240V)(Grn-220V) to the bottom terminal of
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.