American Water Heater VGD625T 100, VG6250T 110 User Manual

RESIDENTIAL GAS WATER HEATERS
www.americanwaterheater.com
American Water Heater
Johnson City, TN 37605
Instruction Manual
POWER VENT/POWER DIRECT VENT GAS MODELS
WITH DIRECT SPARK IGNITION
MODELS VG6250T100/VGD6275T100 SERIES 130/131
For Your Safety •
Thank you for buying this energy efcient water heater. We appreciate your condence in our products.
KEEP THIS MANUAL IN THE POCKET ON HEATER FOR FUTURE REFERENCE
PRINTED 0114 326466-000
WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED.
1
AN ODORANT IS ADDED TO THE GAS USED
BY THIS WATER HEATER.
TABLE OF CONTENTS
SAFE INSTALLATION, USE AND SERVICE.................................3
APPROVALS .................................................................................3
GENERAL SAFETY INFORMATION .............................................4
Precautions ..............................................................................4
Grounding Instructions .............................................................4
Hydrogen Gas Flammable .......................................................4
INTRODUCTION ...........................................................................7
Abbreviations Used ..................................................................7
Qualications ............................................................................7
Preparing For The Installation ..................................................7
DIMENSIONS AND CAPACITY DATA ...........................................8
Rough In Dimensions: 50 Gallon Unit ......................................8
Rough In Dimensions: 75 Gallon Unit ......................................8
FEATURES AND COMPONENTS ..............................................10
Controls And Switches ...........................................................13
INSTALLATION CONSIDERATIONS ..........................................14
Locating The Water Heater ....................................................14
Insulation Blankets .................................................................15
Combustion Air And Ventilation ..............................................15
Unconned Space ..................................................................16
Conned Space ......................................................................16
Fresh Air Openings For Conned Spaces ..............................16
Outdoor Air Through Two Openings .......................................16
Outdoor Air Through One Opening.........................................16
Outdoor Air Through Two Horizontal Ducts ............................17
Air From Other Indoor Spaces ...............................................17
INSTALLATION REQUIREMENTS .............................................18
Chemical Vapor Corrosion......................................................18
Water Piping ...........................................................................18
Power Supply .........................................................................18
Mixing Valves..........................................................................19
Gas piping ..............................................................................19
Gas Supply Systems ..............................................................20
Gas Pressure Requirements ..................................................20
Supply Gas Regulator ............................................................20
Space Heating And Potable Water System ............................21
Closed Water Systems ...........................................................21
Thermal Expansion ................................................................21
Temperature-Pressure Relief Valve ........................................22
Condensate Piping .................................................................23
High Altitude Installations .......................................................23
Filling The Water Heater .........................................................23
INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH
OF MASSACHUSETTS ...............................................................24
VENTING INSTALLATION ..........................................................25
Vent Installation Considerations .............................................25
Polypropylene Installations .....................................................26
Vent Pipe Termination.............................................................27
Planning The Vent System .....................................................27
Installation Of Horizontal Through The Wall Vent System ......27
Direct Vent Terminal Installation .............................................28
Installation Sequence .............................................................28
Termination Clearances Sidewall Power Vent ........................29
Termination Clearances Sidewall Direct Vent .........................30
Vertical Vent Terminal Installation ...........................................31
Direct Vent Diagram ...............................................................32
Concentric Vent Installation ....................................................33
Low Prole Termination Installation ........................................36
LIGHTING AND OPERATION LABELS .......................................37
TEMPERATURE REGULATION .................................................38
CONTROL SYSTEM OPERATION .............................................39
Overview ................................................................................39
Control System Navigation .....................................................39
User Settings & Control System Menus .................................42
FOR YOUR INFORMATION ........................................................47
Start Up Conditions ................................................................47
Operational Conditions ...........................................................47
PERIODIC MAINTENANCE ........................................................48
Venting System Inspection .....................................................48
Anode Rod INSPECTION ......................................................48
Powered Anode Rod (optional models) ..................................49
Temperature-Pressure Relief Valve Test ................................49
Draining and ushing ..............................................................49
Service ...................................................................................50
LEAKAGE CHECKPOINTS .........................................................51
TROUBLESHOOTING ................................................................52
Installation Checklist ...............................................................52
Sequence Of Operation ..........................................................52
Sequence Of Operation Flow Chart .......................................53
Operational Problems .............................................................54
Fault And Alert Conditions ......................................................55
WIRING DIAGRAM .....................................................................58
2

SAFE INSTALLATION, USE AND SERVICE

The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others.
Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning of each safety message is understood by you and others who install, use, or service this water heater.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates an imminently
DANGER
WARNING
CAUTION
hazardous situation which, if not avoided, will result in injury or death.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in injury or death.
CAUTION indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury.
CAUTION used without the safety alert
CAUTION
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message, and how to avoid the risk of injury.
The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of potential exposure to such substances.
This product contains a chemical known to the State of California to cause cancer, birth defects, or other reproductive harm. This water heater can cause low level exposure to some of the substances listed in the Act.
symbol indicates a potentially hazardous situation which, if not avoided, could result in property damage.

APPROVALS

3
CAUTION

GENERAL SAFETY INFORMATION

PRECAUTIONS

DO NOT USE THIS WATER HEATER IF ANY PART HAS BEEN
UNDER WATER. Immediately call a qualied service agency to inspect the water heater and to make a determination on what steps should be taken next.
If the unit is exposed to the following, do not operate heater until all corrective steps have been made by a qualied service agency.
1. External re.
2. Damage.
3. Firing without water.

GROUNDING INSTRUCTIONS

This water heater must be grounded in accordance with the National Electrical Code and/or local codes. These must be followed in all cases. Failure to ground this water heater properly may also cause erratic control system operation.
This water heater must be connected to a grounded permanent wiring system; or an equipment grounding conductor must be run with the circuit conductors and connected to the equipment grounding terminal or lead on the water heater.

HYDROGEN GAS FLAMMABLE

Explosion Hazard
Flammable hydrogen gases may be present.
Keep all ignition sources away from faucet when turning on hot water.
Hydrogen gas can be produced in a hot water system served by this water heater that has not been used for a long period of time (generally two weeks or more). Hydrogen gas is extremely ammable. To reduce the risk of injury under these conditions, it is recommended that a hot water faucet served by this water heater be opened for several minutes before using any electrical appliance connected to the hot water system. If hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to ow. THERE SHOULD BE NO SMOKING
OR OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN.
Verify the power to the water heater is turned off before performing any service procedures.
Read and understand this instruction manual and the safety messages herein before installing, operating or servicing this water heater.
Failure to follow these instructions and safety messages could result in death or serious injury.
This manual must remain with the water heater.
Water temperature over 125°F (52°C) can cause severe burns instantly resulting in severe injury or death.
Children, the elderly and the physically or mentally disabled are at highest risk for scald injury.
Feel water before bathing or showering.
Temperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures.
Improper installation, use and service may result
in property damage.
Do not operate water heater if flood damaged.
Inspect anode rods regularly, replace if damaged.
Install in location with drainage.
Fill tank with water before operation.
Properly sized thermal expansion tanks are required on all
closed water systems.
Refer to this manual for installation and service.
Explosion Hazard
Overheated water can cause water tank explosion.
Properly sized temperature and pressure relief valve must be installed in the opening provided.
4
GENERAL SAFETY INFORMATION
5
Fire or Explosion Hazard
Read instruction manual before
installing, using or servicing
water heater.
Avoid all ignition sources if you smell gas.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Use only the gas shown on the water heater rating plate.
Keep ignition sources away from faucets after extended periods of non-use.
Maintain required clearances to combustibles.
Do not expose water heater controls to excessive gas pressure.
Do not obstruct water heater air intake with insulating blanket.
Gas and carbon monoxide detectors are available.
Install water heater in accordance with the instruction manual.
Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual.
Breathing Hazard - Carbon Monoxide Gas
Property Damage Hazard
All water heaters eventually leak.
Do not install without adequate drainage.
CAUTION
GENERAL SAFETY INFORMATION
Fire Hazard
For continued protection against risk of fire:
Do not install water heater on carpeted floor.
Do not operate water heater if flood damaged.
Fire and Explosion Hazard
Use joint compound or Teflon tape compatible with propane gas.
Leak test before placing the water heater in operation.
Disconnect gas piping and main gas shutoff valve before leak testing.
Install sediment trap in accordance with NFPA 54.
Electrical Shock Hazard
Turn off power to the water heater
before performing any service.
Label all wires prior to disconnecting
when performing service. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
Failure to follow these instructions can
result in personal injury or death.
Fire and Explosion Hazard
Do not use water heater with any gas other than the gas shown on the rating plate.
Excessive gas pressure to gas valve can cause serious injury or death.
Turn off gas lines during installation. Contact a qualified installer or service
agency for installation and service.
6

INTRODUCTION

Thank You for purchasing this water heater. Properly installed and maintained, it should give you years of trouble free service.

ABBREVIATIONS USED

Abbreviations found in this Instruction Manual include :
• ANSI - American National Standards Institute
• ASME - American Society of Mechanical Engineers
• AHRI - Air-Conditioning, Heating and Refrigeration Institute
• NEC - National Electrical Code
• NFPA - National Fire Protection Association
• CSA - Canadian Standards Association

QUALIFICATIONS

QUALIFIED INSTALLER OR SERVICE AGENCY
Installation and service of this water heater requires ability equivalent to that of a Qualied Agency (as dened by ANSI below) in the eld involved. Installation skills such as plumbing, air supply, venting, gas supply and electrical supply are required in addition to electrical testing skills when performing service.
ANSI Z223.1 2006 Sec. 3.3.83: “Qualied Agency” - “Any individual, rm, corporation or company that either in person or through a representative is engaged in and is responsible for (a) the installation, testing or replacement of gas piping or (b) the connection, installation, testing, repair or servicing of appliances and equipment; that is experienced in such work; that is familiar with all precautions required; and that has complied with all the requirements of the authority having jurisdiction.”
If you are not qualied (as dened by ANSI above) and licensed or certied as required by the authority having jurisdiction to perform a given task do not attempt to perform any of the procedures described in this manual. If you do not understand the instructions given in this manual do not attempt to perform any procedures outlined in this manual.

PREPARING FOR THE INSTALLATION

1. Read the entire manual before attempting to install or operate the water heater. Pay close attention to the General Safety Information on Page 4 thru Page 6. If you don’t follow the safety rules, the water heater may not operate safely. It could cause property damage, injury and/or death.
This manual contains instructions for the installation, operation, and maintenance of the water heater. It also contains warnings throughout the manual that you must read and be aware of. All warnings and all instructions are essential to the proper operation of the water heater and your safety. Detailed installation diagrams are also found in this manual. These diagrams will serve to provide the installer with a reference. It is essential that all venting, water piping, gas piping and wiring be installed as shown.
See the Installation Checklist and Troubleshooting on Page 51. By using this checklist the user may be able to make minor operational adjustments and avoid unnecessary service calls. However, service and diagnostic procedures should only be performed by a Qualied Service Agency.
NOTE: Costs to correct installation errors are not covered under the limited warranty.
2. Be sure to turn off power when working on or near the electrical system of the water heater. Never touch electrical components with wet hands or when standing in water.
3. The installation must conform to all instructions contained in this manual and the local code authority having jurisdiction. These shall be carefully followed in all cases. Authorities having jurisdiction should be consulted before installation begins if there are any questions regarding compliance with local, state or national codes.
In the absence of local codes, the installation must comply with the current editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the National Electrical Code, NFPA 70. All documents are available from the Canadian Standards Association, 8501 East Pleasant Valley Road, Cleveland, OH
44131. NFPA documents are also available from the National Fire Protection Association, 1 Batterymarch Park, Quincy, MA
02269.
4. If after reading this manual you have any questions or do not understand any portion of the instructions, call the toll free number on the back cover of this manual for technical assistance. In order to expedite your request, please have the full Model, Serial and Series number of the water heater you are working with available for the technician. This information is located on the water heater’s rating plate.
5. Carefully plan the placement of the water heater. Examine the location to ensure that it complies with the requirements in Locating The Water Heater on Page 14 and the Rough In Dimensions on Page 8.
.
6. For installation in California this water heater must be braced or anchored to avoid falling or moving during an earthquake. See instructions for correct installation procedures. Instructions may be obtained from California Ofce of the State Architect, 1102 Q Street, Suite 5100, Sacramento, CA 95811.
7. Massachusetts Code requires this water heater to be installed in accordance with Massachusetts 248-CMR 2.00: State Plumbing Code and 248-CMR 5. See Commonwealth of Massachusetts
on Page 24.
Particular attention should be given to the installation of thermometers at the locations indicated in the piping diagrams as these are necessary for checking the operation of the water
heater.
The principal components of the water heater are identied in Features And Components on Page10 & Page 11 in this manual. Use this reference to locate and identify various components on the water heater.
7

DIMENSIONS AND CAPACITY DATA

ROUGH IN DIMENSIONS: 50 GALLON UNIT

Figure 1: DIMENSIONS FOR 50 GALLON UNIT

ROUGH IN DIMENSIONS: 75 GALLON UNIT

Figure 1A: DIMENSIONS FOR 75 GALLON UNIT
Table 1 – ROUGH-IN-DIMENSIONS
Units A B C D E F G H I
50G
75G
Top Inlet and Outlet: 50G - 3/4” NPT; 75G - 1” NPT Side Inlet and Outlet: 3/4” NPT Gas Inlet: 1/2” NPT
Inches 66.75 49.25 22.00 15.75 3.00 8.00 8.00 62.00 65.00
cm 169.5 125.09 55.88 40.00 7.62 20.32 20.32 157.48 165.1
Inches 64.71 45.64 27.75 16.00 3.71 8.00 7.93 57.36 58.98
cm 164.4 115.9 70.5 40.6 9.4 20.3 20.1 145.7 149.8
8
DIMENSIONS AND CAPACITY DATA
Table 2 – CAPACITY, GAS AND ELECTRICAL CHARACTERISTICS
Approximate Capacity Manifold Pressure Electrical Characteristics
U.S. Gals. Liters Gas Type “WC kPA Volts/Hz Amperes
50 189 Nat./LP 0 0 120/60 <5
75 284 Nat/LP 0 0 120/60 <5
All models - Maximum Supply Pressure: 14 inches W.C. (3.48kPa) Minimum Supply Pressure for Natural Gas: 3.50” (.87kPa) Minimum Supply Pressure for Propane Gas: 8.00” (1.99kPa) Minimum pressure must be maintained under both load and no load (dynamic and static) conditions.
Table 3 – RECOVERY CAPACITIES
Input Recovery Capacities
Rating
(Btu/hr)
100,000 29.3
Recovery capacity based on 96% thermal efciency.
Rating
(kW)
Temp.
Rise
F 30 40 50 60 70 80 90 100 110 120 130 140
C 17 22 28 33 39 44 50 56 61 67 72 78
GPH 387 291 233 194 166 145 129 116 106 97 90 83
LPH 1465 1102 882 734 628 549 488 439 401 367 341 314
9
**29

FEATURES AND COMPONENTS

50 GALLON UNIT
20
23
22
21
**14
21
30
32
18
16
1
12
**15
25
11
ACCESS PANEL
5
17
13
26, 27
24
33
19
18
35
Caution:
This access panel covers a 2” NPT plug that was required during the manufacturing of this water heater. This 2” NPT ange is not a cleanout tting, removing the 2” NPT plug and using this tting as a cleanout could void your warranty.
31
9
34 (SEE ACCESS
3
2
4
PANEL CAUTION)
VACUUM RELIEF
VALV E
28
*INSTALL PER
LOCAL CODES
* CAUTION HARNESS HAS 120 VAC. IN OPERATION. ** See Planning the Vent System, Installation of Vent System and Condensate Piping for more information.
Figure 1B: 50 GALLON UNIT
10
**29
FEATURES AND COMPONENTS (CONT.)
75 GALLON UNIT
21
13
18
**14
21
20
23
22
**15
5
12
11
17
1
18
16
25
24
3
2
26, 27
31
4
33
19
9
35
32
30
34
VACUUM RELIEF
VALV E
28
*INSTALL PER
LOCAL CODES
* CAUTION HARNESS HAS 120 VAC. IN OPERATION. ** See Planning the Vent System, Installation of Vent System and Condensate Piping for more information.
Figure 1C: 75 GALLON UNIT
11
FEATURES AND COMPONENTS (CONT.)
1: Control Assembly 2: Blocked Intake Switch 3: Blocked Outlet Switch 4: Blower Prover Switch 5: Blower Assembly 6: Burner Assembly 7: Flame Sensor 8: Igniter Assembly 9: Junction Box 10: Gas Control Valve Assembly 11: Display Board 12: Top Plastic Enclosure 13: Display Enclosure ** 14: Exhaust Elbow Assembly ** 15: Condensate Tubing 16: Off/On Switch 17: Display Label 18: Hot Water Outlet 19: Gas Supply 20: Main Manual Gas Shutoff Valve 21: Union 22: Inlet Water Shutoff Valve 23: Cold Water Inlet
24: Inlet Dip Tube
25: T/P Relief Valve
26: Rating Plate
27: Labels
28: Drain Valve
** 29: Vent Terminal
30: Drain Pan
31: Anode Rod
32: Insulation
33: Temperature Probe
34: Access Door
35: Spark Module
12

CONTROLS AND SWITCHES

This model is provided with three pressure switches. These switches are essential to the safe and proper operation of the unit. All switches are wired in series. The controller is set up to shut the unit down whenever there is a failure of any of the switches. It is important to understand the purpose of each switch.
BLOCKED EXHAUST SWITCH
The Blocked Exhaust Switch is set up to shut the unit off when a build­up of positive pressure in the exhaust vent pipe occurs. This switch is a positive pressure switch that requires an increase in pressure to
change the electrical contacts from normally closed to open. When this switch prevents the unit from igniting, most likely the exhaust is blocked by some means. Check to see if the condensate is allowed to ow freely from the exhaust elbow and for obstructions in the exhaust venting and exhaust vent terminal. Also verify that the vent length does not exceed the maximum allowed as shown in the Vent Section of this manual.
Blocked Exhaust Switch
Blocked
Intake
Switch
Blower
Prover
Switch
50 GALLON UNIT
Blocked
Intake
Switch
Blower
Prover
Switch
BLOCKED INTAKE SWITCH
The Blocked Intake Switch is set up to shut the unit off when a build-up of negative pressure in the intake air pipe occurs. This switch is a negative pressure switch that requires an increase in negative pressure to change the electrical contacts from normally closed to open. The switch is connected to the pressure tap on the PVC pipe connected to the inlet of the blower. When this switch prevents the unit from igniting, most likely the intake is blocked. Verify that the screen on the intake air connection (conventional vent), the intake air pipe and termination (direct vent installations) are free of obstructions that may prevent air from entering the unit. Insure the screen on intake air connection has been removed on direct vent installations, see “Figure 13: AIR INTAKE SCREEN”. Also verify the intake air pipe length does not exceed the maximum allowed as shown in the Vent Section of this manual.
WATER HEATING ENABLE/DISABLE (ON/OFF) SWITCH
The Water Heating Enable/Disable (On/Off) Switch is a single-pole, single-throw rocker switch. This switch provides 24V power to the gas control valve.
SPARK IGNITER
The Spark Igniter is a device that ignites the main burner by spark. When high voltage is applied to the igniter, spark is generated to ignite the main burner.
75 GALLON UNIT
Figure: 2
BLOWER PROVER SWITCH
The Blower Prover Switch is provided on the heater to verify that the fan is operating. It is a positive pressure switch whose electrical contacts are normally open. When the fan increases the pressure in the burner, the pressure switch will allow the electrical contacts to close. The pressure switch is connected to the blower pressure tap by a piece of tygon tubing. This tubing must be connected in order for the switch to change the electrical contacts. The controller requires that the electrical contacts on this air ow switch be open before it will allow the blower to come on.
13
CAUTION

INSTALLATION CONSIDERATIONS

LOCATING THE WATER HEATER

Carefully choose a location for the new water heater. The placement is a very important consideration for the safety of the occupants in the building and for the most economical use of the water heater.
Property Damage Hazard
All water heaters eventually leak.
Do not install without adequate drainage.
Whether replacing an existing water heater or installing the water heater in a new location observe the following critical points:
1. The water heater must be located indoors.
2. The water heater must not be located in an area where it will be subject to freezing temperatures.
3. Locate the water heater so it is protected and not subject to physical damage by a moving vehicle.
4. Locate the water heater on a level surface.
5. Locate the water heater near a floor drain. The water heater should be located in an area where leakage of the tank or connections will not result in damage to the area adjacent to the water heater or to lower floors of the structure. When such locations cannot be avoided, it is recommended that a metal drain pan, piped to adequate drain, be installed under the water heater. Drain pan should be fabricated with sides at least 2” deep with diameter at least 2” greater than diameter of heater. Pan must not restrict combustion air flow.
6. Locate the water heater close to the point of major hot water usage.
7. Locate the water heater close to a 120 VAC power supply. See Power Supply on Page 18 for requirements.
8. Locate the water heater where an adequate supply of fresh air for combustion and ventilation can be obtained. See Combustion Air and Ventilation on Page 15.
9. Locate the water heater where the vent and intake air piping, when installed, will remain within the maximum equivalent lengths allowed. See Venting on Page 25.
10. Do not locate the water heater where noise (such as the Combustion Blower) during normal operation will be objectionable in adjacent areas.
11. Do not locate the water heater where the subsequent installation of the vent (exhaust) or intake air terminations would be objectionable due to noise at the termination(s). This includes locations close to or across from windows and doors. See Venting starting on Page 25.
Do not locate water heater areas where flammable liquids (vapors) are likely to be present or stored (garages, storage and utility areas, etc.): Flammable liquids (such as gasoline, solvents, propane (LP or butane, etc.) and other substances (such as adhesives, etc.) emit flammable vapors which can be ignited by a gas water heater’s ignition device or main burner. The resulting flashback and fire can cause death or serious
burns to anyone in the area.
Also, the water heater must be located and/or protected so it is not subject to physical damage by a moving vehicle.
This water heater must not be installed directly on carpeting. Carpeting must be protected by metal or wood panel beneath the water heater extending beyond the full width and depth of the water heater by at least 3” (7.6 cm) in any direction, or if the water heater is installed in an alcove or closet, the entire oor must be covered by the panel. Failure to heed this warning may result in a re hazard.
14
Minimum clearances between the water heater and combustible construction are 0 inch at the sides and rear, 5.5” (14.0 cm) from the front and 18” (45.7 cm) from the top. (Standard clearance.) If clearances stated on the heater differ from standard clearances, install water heater according to clearances stated on the heater.
Adequate clearance 30” (76 cm) for servicing this water heater should be considered before installation, such as changing the anode rods, control system components and gas control valve.
A minimum clearance of 5.5” (14.0 cm) must be allowed for access to replaceable and/or serviceable parts such as the thermostats, drain valve, condensate drain, temperature-pressure relief valve, clean out opening, and the vent connection (exhaust elbow).
When installing the heater, consideration must be given to proper location. Location selected should be as close to the wall as practicable and as centralized with the water piping system as possible.
Do not apply insulation to the top of the water heater, as this will interfere with safe operation of the blower assembly.
Do not cover the control system LCD on top of the water heater.
Do not cover the outer door, thermostat or temperature & pressure relief valve.
Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.
Do obtain new warning and instruction labels from the manufacturer for placement on the blanket directly over the existing labels.
Do inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air ow.

COMBUSTION AIR AND VENTILATION

A gas water heater cannot operate properly without the correct amount of air for combustion. Do not install in a conned area such as a closet, unless you provide air as shown in the Facts to Consider About Location section. Never obstruct the ow of ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amount of combustion air can result in a re or explosion and cause death, serious bodily injury, or property damage.
Figure 3: CLEARANCES

INSULATION BLANKETS

Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. Your water heater meets or exceeds the Energy Policy Act standards with respect to insulation and standby loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you should follow these instructions (For identication of components mentioned below, see “Figure 1B: 50 GALLON UNIT” & “Figure 1C: 75 GALLON UNIT”. Failure to follow these instructions can restrict the air ow required for proper combustion, potentially resulting in re, asphyxiation, serious personal injury or death.
Figure 4: COMBUSTION AIR AND VENTILATION
If this water heater will be used in beauty shops, barber shops, cleaning establishments, or self-service laundries with dry cleaning equipment, it is imperative that the water heater(s) be installed direct vent so that all air for combustion and ventilation is taken from outdoors.
Propellants of aerosol sprays and volatile compounds, (cleaners, chlorine based chemicals, refrigerants, etc.) in addition to being highly ammable in many cases, will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heater. The results can be hazardous, and also cause product failure.
15

UNCONFINED SPACE

An Unconned Space is one whose volume IS NOT LESS THAN 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all appliances installed in the space. Rooms communicating directly with the space, in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconned space.

FRESH AIR OPENINGS FOR CONFINED SPACES

The following instructions shall be used to calculate the size, number and placement of openings providing fresh air for combustion, ventilation and dilution in conned spaces. The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into conned spaces only. DO NOT refer to these illustrations for the purpose of vent installation. See Venting Installation on Page 25 for complete venting installation instructions.
Makeup air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers and replaces shall also be considered in determining the adequacy of a space to provide combustion, ventilation and dilution air.
UNUSUALLY TIGHT CONSTRUCTION
In unconned spaces in buildings, inltration may be adequate to provide air for combustion, ventilation and dilution of ue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.) additional air must be provided using the methods described in the Conned Space section that follows.

CONFINED SPACE

A Conned Space is one whose volume IS LESS THAN 50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input rating of all appliances installed in the space.
Openings must be installed to provide fresh air for combustion, ventilation and dilution in conned spaces. The required size for the openings is dependent on the method used to provide fresh air to the conned space AND the total Btu/hr input rating of all appliances installed in the space.
DIRECT VENT APPLIANCES
Appliances installed in a Direct Vent conguration that derive all air for combustion from the outdoor atmosphere through sealed intake air piping are not factored in the total appliance input Btu/hr calculations used to determine the size of openings providing fresh air into conned spaces.
EXHAUST FANS

OUTDOOR AIR THROUGH TWO OPENINGS

Figure: 5
The conned space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The openings shall communicate directly with the outdoors. See Figure 5.
Each opening shall have a minimum free area of 1 square inch per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm2).
Where exhaust fans are installed, additional air shall be provided to replace the exhausted air. When an exhaust fan is installed in the same space with a water heater, sufcient openings to provide fresh air must be provided that accommodate the requirements for all appliances in the room and the exhaust fan. Undersized openings will cause air to be drawn into the room through the water heater’s vent system causing poor combustion. Sooting, serious damage to the water heater and the risk of re or explosion may result. It can also create a risk of asphyxiation.
LOUVERS AND GRILLES
The free areas of the fresh air openings in the instructions that follow do not take in to account the presence of louvers, grilles or screens in the openings. The required size of openings for combustion, ventilation and dilution air shall be based on the net free area of each opening. Where the free area through a design of louver or grille or screen is known, it shall be used in calculating the size of opening required to provide the free area specied. Where the louver and grille design and free area are not known, it shall be assumed that wood louvers will have 25% free area and metal louvers and grilles will have 75% free area. Non motorized louvers and grilles shall be xed in the
open position.

OUTDOOR AIR THROUGH ONE OPENING

Figure: 6
16
Alternatively a single permanent opening, commencing within 12 inches (300 mm) of the top of the enclosure, shall be provided. See Figure 6. The water heater shall have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (150 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors and shall have a minimum free area of the following:
1. 1 square inch per 3000 Btu/hr (733 mm2 per kW) of the total input rating of all appliances located in the enclosure, and
2. Not less than the sum of the areas of all vent connectors in the space.

OUTDOOR AIR THROUGH TWO HORIZONTAL DUCTS

AIR FROM OTHER INDOOR SPACES

Figure: 8
The conned space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 8.
Figure: 7
The conned space shall be provided with two permanent horizontal ducts, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. The horizontal ducts shall communicate directly with the outdoors. See Figure 7.
Each duct opening shall have a minimum free area of 1 square inch per 2,000 Btu/hr (1100 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure.
When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches.
Each opening shall communicate directly with an additional room(s) of sufcient volume so that the combined volume of all spaces meets the criteria for an Unconned Space.
Each opening shall have a minimum free area of 1 square inch per 1,000 Btu/hr (2200 mm2 per kW) of the aggregate input rating of all appliances installed in the enclosure. Each opening shall not be less than 100 square inches (645 cm2).
17

INSTALLATION REQUIREMENTS

CHEMICAL VAPOR CORROSION

Corrosion of the ueways and vent system may occur if air for combustion contains certain chemical vapors. Such corrosion may result in failure and risk of asphyxiation.
Spray can propellants, cleaning solvents, refrigerator and air conditioning refrigerants, swimming pool chemicals, calcium and sodium chloride (water softener salt), waxes, and process chemicals are typical compounds which are potentially corrosive.
Do not store products of this sort near the heater. Also, air which is brought in contact with the heater should not contain any of these chemicals. If necessary, uncontaminated air should be obtained from remote or outside sources. The limited warranty is voided when failure of water heater is due to a corrosive atmosphere. (See limited warranty for complete terms and conditions).

WATER PIPING

HOTTER WATER CAN SCALD: Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, cleaning and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the physically or developmentally disabled. If anyone using hot water ts into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satises your hot water needs, a means such as a mixing valve should be used at the hot water taps used by these people or at the water heater. Valves for reducing point of use temperature by mixing cold and hot water are also available:
This water heater shall not be connected to any heating systems or component(s) used with a non-potable water heating appliance.
All piping components connected to this unit for space heating applications shall be suitable for use with potable water.
Toxic chemicals, such as those used for boiler treatment shall not be introduced into this system.
When the system requires water for space heating at temperatures higher than required for domestic water purposes, a mixing valve must be installed.
These water heaters cannot be used in space heating applications only.

POWER SUPPLY

The water heaters covered in this manual require a 120 VAC, 1Ø (single phase), 60Hz, 15 amp power supply and must also be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70.
POWER FLUCTUATIONS AND ELECTRICAL NOISE
The water heater’s control system requires a source of stable clean electricity for proper operation. Connecting the water heater to a branch circuit that is subject to fluctuations in voltage level or electrical line noise such as EMI (electro magnetic interference) or RFI (radio frequency interference) may cause erratic control system operation and malfunction.
A high quality power supply filter/suppressor must be installed if the above conditions exist. Call the technical support phone number listed on the back cover of this manual for more information.
NOTE: Malfunctions caused by the power supply and the costs to install power supply filters are not covered under the limited warranty.
DEDICATED POWER WIRING AND BREAKERS
Dedicated power supply wires, ground wiring and dedicated circuit breakers often prevent electrical line noise and should be considered when installing the water heater.
Consult a Qualied Installer or Service Agency. Follow manufacturer’s instructions for installation of the valves. Before changing the factory setting on the thermostat, read the Temperature Regulation section in this manual.
18
Loading...
+ 42 hidden pages