American Water Heater HPE10260H045DV, HPE10280H045DV User Manual

Service Handbook
RESIDENTIAL HYBRID ELECTRIC HEAT PUMP WATER HEATER
FOR MODELS: HPE10260H045DV (60 GAL.) HPE10280H045DV (80 GAL.)
INSTALLATION CONSIDERATIONS -
PREVENTIVE MAINTENANCE -
SERVICE SHOULD ONLY BE PERFORMED BY A QUALIFIED SERVICE TECHNICIAN
PRINTED IN THE U.S.A. 0511 321549-000
Table of Contents
Introduction ............................................................................................................................................................ 3
Certifi cation and Approvals .................................................................................................................................... 3
Tools Required....................................................................................................................................................... 3
Terms, Defi nitions, and Formulas .......................................................................................................................... 4
Safety Precautions ................................................................................................................................................ 5
Installation Check List............................................................................................................................................ 6
Potential Issues ..................................................................................................................................................... 7
Dry Fire Protection / Powered Anode Operation ................................................................................................... 8
Water Piping System ............................................................................................................................................ 9
T&P Valve / Thermal Expansion .......................................................................................................................... 10
General Service / Preventive Maintenance ..........................................................................................................11
Operational Overview .......................................................................................................................................... 12
Operating Your Heat Pump.................................................................................................................................. 13
Control Board Overview ...................................................................................................................................... 14
Control Board Section “A”.................................................................................................................................... 15
Control Board Section “B”.................................................................................................................................... 16
Control Board Section “C” ................................................................................................................................... 17
Control Board Section “D” ................................................................................................................................... 18
Wiring Diagrams ............................................................................................................................................. 19-20
Accessing Maintenance Display .......................................................................................................................... 21
Element Test (Continuity Check) ......................................................................................................................... 22
Element Test (Ohm’s Check) ............................................................................................................................... 23
Heating Element Replacement ............................................................................................................................ 24
Energy Cutout (ECO) Troubleshooting ................................................................................................................ 25
Run Capacitor...................................................................................................................................................... 26
Powered Anode Replacement / Removing the Shroud ....................................................................................... 27
Component Check Flowcharts ....................................................................................................................... 28-31
Temperature Sensors .......................................................................................................................................... 32
Resistance vs. Temperature Charts .................................................................................................................... 33
R-134a Temperature Chart .................................................................................................................................. 34
Cleaning the Evaporator ...................................................................................................................................... 35
Common Service Problems ............................................................................................................................ 36-38
Fault Code Troubleshooting Guide ................................................................................................................. 39-44
Draining and Filling the Water Heater ................................................................................................................. 45
Condensate Pump ............................................................................................................................................... 46
Parts List.............................................................................................................................................................. 47
2
Service Handbook
Introduction:
Your safety, and the safety of others, is extremely important in the servicing of this water heater. Many safety-related messages and instructions have been provided in this handbook and on your water heater to warn you and others of potential hazards. Read, understand and obey all safety messages and instructions that appear throughout this handbook and in the Installation Instructions and Use & Care Guide that shipped with the water heater. It is very important that the meaning of each safety message is understood by you and others who service this water heater.
The information contained in this handbook is designed to answer commonly faced situations encountered in the operation of the residential electric heat pump product line and is not meant to be all-inclusive. If you are experiencing a problem not covered in this handbook, please contact the Technical Information Center listed on the back cover of this handbook for further assistance. Additional information is also available on the web site listed on the back cover of this handbook.
This handbook is intended for use by qualifi ed service technicians and reference should be made to the Installation Instructions and Use & Care Guide accompanying the product. This handbook contains supplemental information to the Installation Instructions and Use & Care Guide.
When servicing residential electric heat pump water heaters, it is essential that you return the unit to a safe condition before you leave the site. All original components must be re-installed and all safety measures must be implemented. In addition, the recommended water temperature setting is 120°F.
Certifications and Approvals:
Code Compliance - All models meet or exceed federal minimum energy standards effective January 20, 2004,
according to latest editions of the National Appliance Energy Conservation Act (NAECA). They also comply with the latest editions of the B.O.C.A. National Codes, C.E.C., U.B.C., S.B.C.C., C.A.B.O. and the H.U.D. standards. All models U.L. listed according to safety specifications outlined in Underwriters Laboratories, Inc. Standards for Safety (UL 174 and UL 1995)
Tools for servicing residential electric heat pump water heater models:
• Container (to measure flow rate)
• Continuity checker or electrical multimeter (with alligator leads)
• Funnel (for chlorination or scale-removal treatments)
• Hose (to drain tank)
• Needle nose pliers
• Pipe wrench
• Screw drivers (flat tip and Phillips)
• Nut Drivers - 5/16” & 9/32”
• Socket wrench:
1-1/16 inch socket– 6 point deep well (for anode removal)
1-1/2 inch socket (for element removal)
Appropriate extensions
• Thermometer
• Water pressure gauge
• Flashlight
• Drill
• Amp meter-clamp type
Figure 1
Digital multimeter shown.
Supplies for servicing residential electric heat pump water heater models:
• Chlorine Bleach (for chlorination procedure, as well as algae/scale removal from condensate drain pan)
• Cotton swabs (to check for minor leaks)
• Teflon
• All Purpose ABS/PVC Cement
• Un-Lime or Mag Erad (for removal of scale)
®
tape or approved thread sealant
3
Terms, Defi nitions and Formulas
First Hour Rating (FHR) is a volume of hot water delivered by a water heater during a 1-hour, Department
Of Energy mandate test procedure. The FHR is given in gallons or liters.
Energy Factor (EF) is an indicator of the combined thermal effi ciency and standby effi ciency of a water heater. The higher the Energy Factor, the more effi cient the water heater will be.
Recovery rate is the amount of water, expressed in gallons per hour (GPH),heated to a given temperature rise. Residential water heaters are typically rated at approximately 90°F temperature rise. IE: A standard electric water heater with one 4.5 kW (kilowatt) electric heating element can produce 20 GPH at an approximate 90°F rise.
Temperature rise is the increase in the temperature from its coldest “inlet” water temperature to the desired hot “outlet” setting.
Standby ef ciency relates to the ability of the product to retain the stored heat (Btu) while the heating source is not on. Insulation and other services are used to increase this effi ciency.
Water (for all practical purposes) cannot be compressed.
Water expands when it is heated. The volume and pressure of water increases when it is heated in a closed
system. IE: Water heated from 90°F to 140°F in a 40 gallon water heater will expand by approximately one­half gallon.
Minerals and gases will separate from water as temperature increases.
Amperage (Amps) (1 phase) = Watts divided by Volts (Ohm’s Law)
KW Required = (GPH X 8.25 X Temp. Rise X 1.0) divided by (3413)
Ohms = Volts divided by Amperes (Ohm’s Law)
One killowatt is equal to 1000 watts
One kilowatt is equal to 3,413 BTU
Recovery Rate =(KW X 3413) divided by (Temp. Rise X 8.25)
Rise (°F) = (KW X 3413) divided by (GPH X 8.25)
Supply electrical fusing and wiring or breakers should be sized at least 125% of expected heater
amperage, per NEC and local codes.
Water weighs 8.25 pounds per gallon at 120°F
% of Hot water = (Mixed temp. - Cold) divided by (Hot temp. - Cold). This formula gives the number of
gallons drawn from the water heater for each gallon delivered at a shower head or faucet. If the shower head ow rate (gallons per minute) is known, the draw effi ciency and gallon capacity of the water heater may be used to calculate the length of the showering period in minutes.
Watt Density = the density of the wattage output of the element compared to the surface area of the element (i.e. “High Watt Density Element” will have the most wattage per square inch of element surface.
4
Safety Precautions
Explosion Hazard
 7HPSHUDWXUHSUHVVXUHUHOLHI
YDOYHPXVWFRPSO\ZLWK$16, =&6$DQG$60( FRGH
 3URSHUO\VL]HGWHPSHUDWXUH
SUHVVXUHUHOLHIYDOYHPXVWEH LQVWDOOHGLQRSHQLQJSURYLGHG
 &DQUHVXOWLQRYHUKHDWLQJ
DQGH[FHVVLYHWDQNSUHVVXUH
 &DQFDXVHVHULRXVLQMXU\RU
GHDWK
WARNING
Excessive Weight Hazard
Use two or more people to move and install water heater.
Failure to do so can result in back or other injury.
5
Installation Checklist
Water Heater Location
Centrally located with the water piping system.
• The fl ooring beneath the water heater must be able to support the weight of the water heater when lled with water (see Table 1).
TABLE 1: Weight of water heater, full of water
Capacity Weight (lbs)
60 Gallon 760
80 Gallon 967
Located indoors (such as a basement or garage) and in a vertical position. Protected from freezing temperatures.
Provisions made to protect the area from water damage. Metal drain pan installed and piped to an adequate drain.
Sufficient room to service the water heater.
Sufficient air for the heat pump to function. The approximate minimum air requirement is 750 cubic feet of space. For example: this would be a room approximately 10’X9 1/2’ in size with an 8’ ceiling. NOTE: For optimal effi ciency, the following minimum clearances should be maintained: 3 ft. on the air inlet side, 6 ft. on the air outlet side and 2 ft. front and back.
• Unrestricted airfl ow, the unit cannot be placed into any type of closet or small enclosure.
The site location must be free from any corrosive elements in the atmosphere such as sulfur, fl uorine, and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresheners, paint and varnish removers, and many other commercial and household products. In addition, excessive dust and lint may affect the operation of the unit and require more frequent cleaning, see “Cleaning/Replacing the Air Filter” section (p.11).
Ambient air temperature must be between 45°F and 109°F (inclusive) in order for the heat pump to work properly. If the ambient air temperature falls outside these upper and lower limits the electrical elements will activate to meet hot water demand.
Water System Piping
Temperature and pressure relief valve properly installed with a discharge pipe run to an adequate drain and protected from freezing.
All piping properly installed and free of leaks.
Heater completely filled with water, see “Water Piping System” section (p.9).
Closed system pressure buildup precautions
installed, see “Closed System/Thermal Expansion” section (p.10).
Mixing valve (when applicable) installed per manufacturer’s instructions see “Water Piping System” (p.9).
Condensate Drain Line Installation
Must be located with access to an adequate drain or condensate pump.
Condensate drain lines installed and piped to an adequate drain or condensate pump.
Electrical Connections
The water heater requires nominal 240 VAC for proper operation.
Wiring size and connections comply with all applicable codes or in the absence of local or state codes follow NFPA-70, the National Electrical Code-current edition.
Water heater and electrical supply are properly grounded.
Wiring enclosed in approved conduit (if required by local codes).
Dedicated circuit with proper overload fuse or circuit breaker protection installed.
Post Installation Review
To maintain optimal operation check, remove and clean the air filter see “Cleaning/Replacing the Air Filter” section (p.11).
Understand the importance of routine inspection/ maintenance of the condensate drain pan and lines, see “Inspection/Cleaning of the Condensate Drain Pan & Condensate Drain Lines” (p.46). This is to help prevent any possible drain line blockage resulting in the condensate drain pan overflowing. IMPORTANT: Water coming from the plastic shroud is an indicator that both condensation drain lines may be blocked. Immediate action is required.
Understand how to use the User Interface Module to set the various modes and functions, see “Adjusting the User Interface Module/Operating Modes” (p.12-13).
Understand the various Operating Modes and which mode may be best based on season, ambient temperature, and usage see “Operating Mode Description” (p.12-13). NOTE: It may be necessary to temporaily change modes if, for example, filling a spa or hot tub.
The Installation Instructions and Use & Care Guide should be kept with the water heater for reference.
6
Potential Installation Issues
Symptom Cause Solution
Temperature set to 60 ºF and not adjustable
Electric mode selected but the heat pump is running
Vacation mode is on Turn off Vacation mode by pressing
the Vacation button
Upon initial start up, the heat pump will run until the tank temperature reaches the set point; this is done so that the heat pump operation can be verified. The water heater will operate according to the selected mode after this first run.
No action is necessary.
If after heat pump operation has been verified and element heating is desired, lower the set point temperature to 95ºF. The heat pump will shut off when the tank temperature is 95º F. Set the temperature to the desired set point. The elements will now be used for heating in Hybrid and Electric modes.
Power is applied to the unit, but there is no display on the User Interface Module (UIM)
“Low Water Level Alarm” message displayed on the UIM
“Heat Pump Fault” message displayed on the UIM
Efficiency mode selected but elements come on instead of heat pump
The unit is in Standby; the power button on the UIM is RED
The tank is not completely filled with water
There are 12 potential causes for this fault
Ambient air or water temperature outside the heat pump safe operating envelope
Press the power button; it should turn green and the display should light up. If the power button does not turn green, remove the protective film over the face of the UIM and re-try the power button.
If the unit does not power up, cycle power to the unit and re-try using a thumb.
Purge air from the tank using the procedure outlined in the “Dry Fire Element Protection” section (p.8).
If the tank is properly filled, the unit should operate normally.
Refer to the Trouble Shooting section for corrective actions (p.39-44)
Heat pump safety lock out occurs if :
ambient air temperature is below 45º F or above 109º F;
tank temperature is below 59º F
7
Dry Fire Element Protection
Dry Fire is a term used to describe a heating element that is on and not fully submerged in water. This will result in permanent damage to the element. The dry fi re element protection algorithm is installed on this heat pump water heater and prevents damage to the heating elements in the event that power is applied to the water heater without suffi cient water in the tank to cover the elements. This routine takes approximately four (4) minutes. If it is determined that the element is not fully submersed in water, an error will be displayed on the user interface: LOW WATER LEVEL ALARM. The water heater will not operate while this fault is active and it must be
Powered Anode Operation
cleared before the water heater will operate. In order to clear the error, shut off power to the water heater, and purge all air from the water heater tank. This is done by opening all hot water taps in the building. Run the water until there is no air coming out with the water. Shut off all hot water taps. Apply power to the water heater. After four (4) minutes, dry fi re detection should be complete, the error should be cleared and the water heater should operate normally. If the LOW WATER LEVEL ALARM repeats, purge air from tank again by following the method outlined above.
Checking the Powered Anode for Proper Operation:
When dissimilar metals are in contact with water, a galvanic cell will likely result and corrosion of the metal components will occur. If left unchecked, corrosion will weaken the wall of a water heater tank which will eventually leak. Passive anodes are typically used to counteract this corrosion and extend tank life. Passive anodes erode over time and become less effective until they stop working all together, another type of protective device is a powered anode.
A powered anode is an active device that counteracts galvanic corrosion in the water heater tank. Unlike a standard depleting anode, a powered anode does not lose effectiveness over time. The powered anode circuit is made up of an electronic control, a titanium anode rod, and the water heater tank. The electronic control monitors conditions in the tank and produces a voltage that will prevent galvanic corrosion from occurring. The titanium anode rod consists of two functional parts: A steel body which threads into the tank providing mechanical and electrical connection to the tank and a titanium rod that is electrically insulated
from the body. The voltage produced by the powered anode circuit is delivered to the titanium anode rod by a red wire connected to the tab that connects to the anode rod. Current fl ows from the titanium anode rod, through the water and to the grounded tank wall. The powered anode circuitry will maintain the minimum voltage required to protect the tank steel.
Fault detection is built into the powered anode software. If a fault is detected, an error message will be displayed on the User Interface Module (UIM): “Powered Anode Fault”. By checking the fault code history, see “Accessing the Maintenance Display” (p.21), a specifi c fault code can be read to aid in isolating the cause. Refer to the “Fault Code Troubleshooting Guide” (p39-44) for the list of powered anode fault messages, what the messages indicate, possible causes, and corrective actions. IMPORTANT: The anode protecting the tank requires power to the unit to operate. Do not shut off power to the unit for an extended period of time. If power must be turned off, drain the tank completely to minimize corrosion.
8
Water Piping System
Piping, fi ttings, and valves should be installed according to the installation drawing (Figure 2). If the indoor installation area is subject to freezing temperatures, the water piping must be properly insulated.
Water supply pressure should be 50-60 PSIG (.35 MPa) and not exceed the maximum 80 PSIG (.55 MPa). If the supply line pressure exceeds 80 PSIG (.55 MPa), a pressure reducing valve (PRV) with a bypass should be installed in the cold water supply line. This should be placed on the supply to the entire house in order to maintain equal hot and cold water pressures.
IMPORTANT:
Heat must not be applied to the water fittings on
the heater as they may contain nonmetallic parts. If solder connections are used, solder the pipe to the adapter before attaching the adapter to the hot and cold water fittings.
Always use a good grade of joint compound and be certain that all fittings are tight.
IMPORTANT: DO NOT over apply joint compound.
Piping Installation
1. Install the water piping and fittings as shown (Figure 2). Connect the cold water supply (3/4” NPT) to the fitting marked “Cold”. Connect the hot water supply (3/4” NPT) to the fitting marked “Hot”.
2. The installation of unions in both the hot and cold water supply lines are recommended for ease of removing the water heater for service or replacement.
3. Some local codes may require, and the manufacturer of this water heater recommends, installing a mixing valve or an anti-scald device in the domestic hot water line as shown (Figure 2), or at the point of use. These valves reduce the point-of-use temperature of the hot water by mixing cold and hot water and are readily available. Contact a licensed plumber or the local plumbing authority for more information.
4. Some local codes may require, and the manufacturer of this water heater recommends, installing a pressure reducing valve (PRV) in the cold water inlet line where it enters the residence as shown (Figure 2).
5. If installing the water heater in a closed water system, install an expansion tank in the cold water line as specified under “Closed System/Thermal Expansion” (p.10).
6. Install a shut off valve in the cold water inlet line. It should be located close to the water heater and be easily accessible. Know the location of this valve and how to shut off the water to the heater.
7. Install a discharge line from the temperature and pressure relief valve in the opening marked “T & P RELIEF VALVE”. See Figure 3 and the “Temperature and Pressure Relief Valve” (p.10)
8. After piping has been properly connected to the water heater, open the nearest hot water faucet. Then open the cold water shut off valve and allow the tank to completely fill with water. To purge the lines of any excess air and sediment, keep the hot water faucet open for three (3) minutes after a constant flow of water is obtained. Close the faucet and check all connections for leaks.
Figure 2
Massachusetts: Install a vacuum relief in cold water line per section 19 MGL 142.
Vacuum Relief Valve
Temperature and Pressure Relief Valve
Hot
(Outlet)
Discharge Pipe (Do Not Cap or Plug)
Metal Drain Pan 2 1/2” Depth Maximum and 2 Inches wider than the water heater.
Drain Line 3/4” ID Minimum
* If an adequate drain is not available for the condensate drain lines then a condensate pump should be used. DO NOT discharge the condensate drain lines into the metal drain pan.
Cold
(Inlet)
Drain
Union
Shut-off Valve (Hot)
Untempered Water Outlet
Mixing Valve - Follow the Mixing Valve’s Manufacturer’s Installation Instructions. (Set to 120° F)
Tempered Water to Fixtures
Condensate Drain Lines*
Cold Water Outlet
In a closed system, use a thermal expansion tank. See “Closed System/ Thermal Expansion” section.
Shut-off Valve (Cold)
6” Maximum Air Gap
Union
Pressure Reducing Valve (PRV) should be installed where the water supply enters the residence.
Cold Water Inlet Valve
Cold Water Inlet
9
Figure 3 Temperature and Pressure Relief Valve Installation
Temperature and Pressure Relief Valve
Discharge Pipe (Do Not Plug or Cap)
Drain Pan 2 1/2” (63.5mm) Depth Maximum and 2” (51mm) wider than the water heater.
Temperature and Pressure Relief Valve
tubing so that any discharge from the valve exits only within 6 in. (152mm) above drain, or at any distance below, the structural fl oor, and does not contact any live electrical part.
Explosion Hazard
 7HPSHUDWXUHSUHVVXUHUHOLHI
YDOYHPXVWFRPSO\ZLWK$16, =&6$DQG$60( FRGH
 3URSHUO\VL]HGWHPSHUDWXUH
SUHVVXUHUHOLHIYDOYHPXVWEH LQVWDOOHGLQRSHQLQJSURYLGHG
 &DQUHVXOWLQRYHUKHDWLQJ
DQGH[FHVVLYHWDQNSUHVVXUH
 &DQFDXVHVHULRXVLQMXU\RU
GHDWK
The discharge opening must not be blocked or reduced in size under any circumstance.
IMPORTANT: Only a new temperature and pressure relief valve should be used with your water heater. Do not use an old or existing valve as it may be damaged or not adequate
for the working pressure of the new water heater. Do not place any valve between the relief valve and the tank.
The Temperature & Pressure Relief Valve:
Shall not be in contact with any electrical part.
Shall be connected to an adequate discharge line.
Shall not be rated higher than the working pres­sure shown on the data plate of the water heater.
The Discharge Line:
Shall not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line.
Shall not be capped, blocked, plugged or contain any valve between the relief valve and the end of the discharge line.
Shall terminate a maximum of 6 in. (152mm) above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the build­ing.
Shall be of material listed for hot water distribution.
Shall be installed to allow complete drainage of both the valve and discharge line.
6” (152mm) Drain Line 3/4” (19mm) ID Minimum
Drain
Maximum
Air Gap
For protection against excessive pressures and temperatures, a temperature and pressure relief valve must be installed in the opening marked “T & P RELIEF VALVE” (Figure 3).
To reduce the risk of excessive pressures and temperatures in this water heater, install temperature and pressure relief protective equipment required by local codes, but no less than a combination temperature and pressure relief valve certifi ed by a nationally recognized testing laboratory that maintains periodic inspection of the production of listed equipment or materials, as meeting the requirements for Relief Valves and Automatic Shutoff Devices for Hot Water
Supply Systems, ANSI Z21.22 - latest edition. This valve must
be marked with the maximum set pressure not to exceed the marked maximum working pressure of the water heater. Install the valve into an opening provided and marked for this purpose in the water heater, and orient it or provide
Closed System/Thermal Expansion
As water is heated, it expands (thermal expansion). In a closed system, the volume of water will grow. As the volume of water grows, there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent temperature-pressure relief valve operation: water discharge from the valve due to excessive pressure build up. The temperature pressure relief is not intended for the constant relief of thermal expansion. This condition is not covered under the limited warranty.
A properly-sized thermal expansion tank should be installed on all closed systems to control the harmful effects of thermal expansion. Contact a plumbing service agency or your retail supplier reguarding the installation of a thermal expansion tank.
10
General Service information
Volts times Amps = Watts
Watts divided by Volts = Amps
• Replacement Elements:
Use replacement elements that are rated at the same wattage, voltage and shape indicated on the heater model and rating plate. Installing an element with a higher voltage rating or wattage output may create a safety hazard. (It could overload the heater wiring, the supply wiring, or the fusing.) Installing an element with a lower wattage or voltage rating will reduce performance.
Also, select replacement elements with the most surface area (low watt density) available for your water heater. By spreading the heat of the element over a greater area, the lime (calcium) buildup rate should be reduced.
Elements constructed of Incoloy are much more durable than zinc-coated copper elements.
• Element Cycling:
Most two-element water heaters are non­simultaneous. In other words, only one element operates at a time.
If the upper element fails, the customer will lose hot water. (Power switches to the lower element only after the water at the top of the tank is heated.) If the lower element or thermostat fails, the customer should still have hot water in the top 1/3 of the tank.
Also, with two-element water heaters, the lower element and thermostat will cycle more frequently than the upper element and thermostat. For this reason, the lower element will normally accumulate lime faster and fail more often than the upper element. This increased cycling also causes lower thermostats to fail more often than upper thermostats.
Routine Preventive Maintenance
At least monthly, a visual inspection should be made of the following:
Air Filter (Remove and inspect, clean if needed, and reinstall).
Condensate drain pan and condensate lines.
The lower metal drain pan for standing water which may indicate a clogged condensate drain pan, condensate lines, or plumbing leak.
Leaking or damaged water piping.
Presence of corrosive materials in the installation area.
Presence of combustible materials near the water heater.
After servicing this water heater, check to make sure it is working properly, see “Operational Overview/Initial Start Up” (p.12)
IMPORTANT: If you lack the necessary skills required to properly perform this visual inspection, you should not proceed, but get help from a qualified person.
Cleaning/Replacing the Air Filter
Air Filter Cleaning/Replacement
IMPORTANT: Before attempting to clean or replace the air lter, press the power button to place the water heater
in Standby Mode and turn-off power to the water heater at the circuit breaker/fuse box.
1. Locate the screw securing the filter panel to the heat pump shroud and remove it.
2. Remove (slide) the filter from the unit.
3. If you are replacing the filter, skip to step 4. To clean the filter, use a vacuum with a hose attachment to remove any dust or debris.
4. Place the new or cleaned filter into the filter panel and secure the filter to the shroud with the screw loosened earlier. Use the slots for guides when inserting the filter into the water heater and replace the screws.
5. Restore power to the water heater and press the power button to turn the water heater on. NOTE: The water heater will conduct a system diagnostic prior to operation.
11
Operational Overview
Heat Pump Water Heater Operation:
Heat pump water heaters remove heat from surrounding air and use that heat to heat water. By doing so, heat pump water heaters can operate much more effi ciently and at signifi cantly lower costs compared to standard electric water heaters.
This heat pump water heater has four (4) operating modes for maximum fl exibility in meeting hot water needs under a variety of conditions. Available modes are: Effi ciency, Hybrid, Electric and Vacation.
Operating Mode Descriptions:
Ef ciency Mode provides the highest effi ciency and lowest cost operation by using only the heat pump to heat water. Recovery time and effi ciency will vary with ambient temperature and relative humidity. Effi ciency will be greatest when both are high and recovery time will be shortest. At lower temperatures and relative humidity levels, effi ciency will be lower and recovery will take longer. Heat pump operation is allowed from 45°F to 109°F ambient temperature. At ambient temperatures lower that 45°F and greater than 109°F the heat pump will not operate. Similarly, if the water temperature in the tank is less than 59°F, the heat pump will not operate. The unit will operate in electric mode until ambient and water temperatures return to the safe operating range of the heat pump.
Hybrid mode provides the best combination of energy effi ciency and hot water delivery. The heat pump will be used to heat water after moderate hot water use. When a large quantity of hot water is used, the upper electric heating element will heat water in order to speed up recovery. Once the upper portion of the tank reaches set point, the element will shut off and the heat pump will heat water until the average tank temperature reaches set point. Hybrid mode provides the highest fi rst hour hot water delivery with excellent economy.
Electric mode allows operation like a standard electric water heater, using the upper and lower heating elements to heat water. The heat pump is not used in this mode. The key advantage of using this mode is that it eliminates the cool air exhausted from the heat pump. During cold weather months, this may be desirable. Hot water delivery and operating costs are comparable to a standard electric water heater with similar tank capacity.
Vacation mode should be used when hot water will not be needed for a period of time greater than three (3) days. In vacation mode electric elements are used to heat water and set point is a non-adjustable 60°F. Minimal electricity will be used and maintaining 60°F minimizes the risk of the water heater freezing in cold weather.
User Interface Module Overview:
The User Interface Module (UIM) is used to control the heat pump water heater. It displays useful information about the operating status of the water heater, the selected mode of operation and the set point temperature. Fault information will be displayed should a malfunction occur with one of the components or sub-systems. The UIM also is used to set the water heater to the desired set point temperature, mode of operation, temperature units (°F or °C) and to check the operating condition of the heat pump through the maintenance display, see “Accessing the Maintenance Display”(p. 21).
Initial Start Up:
When powered up for the fi rst time (or when power is re-applied after a power outage or service work is performed), the control will run the dry fi re check to establish that the tank is completely fi lled with water, see “Dry Fire Element Protection” (p.8). The UIM will display “Dry Fire” during this operation, which will take about four (4) minutes. After eight (8) minutes have elapsed, the fan should come on; after an aditional thirty (30) seconds, the heat pump compressor should turn on. Note that during the initial start up, the heat pump will come on regardless of operation mode selected. This is intended to allow for evaluation of the heat pump to ensure that it is operating properly. The heat pump will heat water until the set point temperature is reached in the tank; it will then shut off. After this initial start up is complete, the water heater will operate per operational mode setting, ambient air and tank water tamperatures, and set point temperature.
12
Operating Your Heat Pump Water Heater
Turning the Unit On:
The power button is located at the bottom of the UIM, below the display. There are two (2) conditions for the power button indicated by color: RED-the unit is in STANDBY and power is applied to the unit; GREEN-the unit is ON. Press the power button to turn the unit on if needed.
NOTE: All buttons on the User Interface are touch sensitive and require only a light touch.
Adjusting Set Point Temperature:
The water temperature can be adjusted from 95°F to 150°F. Use the Up and Down Buttons on the UIM to set the desired temperature.
IMPORTANT: Before attempting to adjust the thermostat, read the information on water temperature adjustment above. If the instructions are not clear, contact a qualifi ed person.
IMPORTANT: Filling a spa or hot tub from this water heater may result in extended recovery/re-heat time. Switching (temporarily) to Hybrid Mode or Electric Mode will decrease the recovery/re-heat time. Be sure to switch back to the desired operational mode when nished. The factory temperature set point is 120°F. Notify homeowner if the set point is increased above 120° at any time for any reason. Return the set point to
a safe level upon completion of service work.
Vacation Mode - The set point changes to 60°F
VACATION
which is the temperature that will be maintained. This mode is recommended for periods of three (3) days or more in which the water heater will be idle. Vacation Mode minimizes energy consumption and minimizes the risk of freezing during cold weather. NOTE: To activate Vacation Mode touch the Vacation Mode button. To deactivate Vacation Mode, touch the Vacation Mode button again.
Other Controls
Lock - Holding this button for more than 3
seconds switches the lock mode on or off. When the User Interface Module is locked a symbol and “Lock” text will be visible on the display and there will be no access to mode change or set point change.
°F/°C
°F/°C - The button switches the display to
show the set temperature in Fahrenheit or Celsius.
Selecting Operating Mode:
The operating mode can be changed by touching the desired mode icon on the User Interface Module (Figure 4).
NOTE: While vacation mode is on, the other modes cannot be selected and set point temperature can not be changed. Turn off vacation mode by pressing the vacation mode button. Desired mode and set point can now be selected.
Effi ciency Mode - Is the most energy effi cient
EFFICIENCY
HYBRID
Electric Mode - The water heater functions as
ELECTRIC
mode. This mode uses the heat pump to heat water in the tank. The elements are not used unless the ambient operating temperature is below 45°F or above 109°F.
Hybrid Mode - Combines high energy effi ciency
with reduced recovery time. This mode uses the heat pump as the primary heating source. The heating element will heat water if demand exceeds a predetermined level so that the set point temperature can be recovered more quickly.
a conventional electric unit, relying totally on the elements to heat the water in the tank. This mode may be useful in winter to eliminate the output of cold air from the unit.
Figure 4 User Interface Module (UIM)
Operational Mode Buttons
HEAT PUMP
HYBRID
ELEMENT
°F/°C
LOCK
EFFICIENCY
Element Functioning Icon
Heat Pump Functioning Icon
Temperature Up (Increase) Button
Fahrenheit/Celsius Temperature Display Button
Power Button: On - Green Standby - Red
ELECTRIC
VACATION
F
EFFICIENCY
LCD Display Panel Lock Button
Water Temperature Set Point
Water Heater Mode/Status Indicator
Water Heater Efficiency Status Icon
LCD Control Panel Lock Icon
Temperature Down (Decrease) Button
13
Control Board Overview
Figure 5
B
A
D
C
Heat Pump Water Heater Control Board Overview:
The Control Board on the Heat Pump Water Heater monitors the complete heating system and reports any errors through the User Interface Module (UIM). Based on the inputs from the sensors and/or the manual inputs from the UIM, the Control Board determines which heating mode the unit should be in to reach the user set-point.
Above, the Control Board is broken down into four (4) sections. The specifi cs of each section are explained in greater detail in the following pages.
14
Section “A” of Control Board
Figure 6
CN201
CN207
FUS202FUS201
Section “A”
CN 201 Line Power:
Pin 1 - Control board power wire L1 (240VAC)
CN202 CN206
Pin 2 - Control board power wire L2 (240VAC)
Pin 3 - Not used
Pin 4 - Control board power wire ground
CN 202 ECO Bottom:
Pin 1 - Connect to lower heating element
Pin 2 - Connect to L1 behind ECO switch
CN 206 Compressor:
Pin 1 - Compressor power L1
Pin 2 - Unused
Pin 3 - Unused
Pin 4 - Compressor power L2
CN 207 Fan Low/high:
Pin 1 - Fan power L1
Pin 2 - Unused
Pin 3 - Fan power
FUS 201:
Fuse 201 (3 Amp, 250V, slow blow) fuses the L1 power leg coming to the Control Board
FUS 202:
Fuse 202 (3 Amp, 250V, slow blow) fuses the L2 power leg coming to the Control Board
15
Loading...
+ 33 hidden pages