ROUGH-IN-DIMENSIONS -------------------------------- 2-3
FOREWORD ------------------------------------------------- 3
GENERAL SAFETY INFORMATION --------------------5
Precautions ---------------------------------------------------5
Grounding Instructions ------------------------------------ 5
Chemical Vapor Corrosion ------------------------------- 5
Improper Combustion ------------------------------------- 5
Extended non-use Periods ------------------------------- 5
Insulation Blankets ----------------------------------------- 5
High Altitude Installation ---------------------------------- 6
FEATURES---------------------------------------------------- 6
High Limit Switch ------------------------------------------- 6
Electronic Ignition Control -------------------------------- 6
Exhaust Inducer (Blower Assy.) ------------------------- 7
Circulating Pump ------------------------------------------- 7
Dishwashing Machine Requirement ------------------ 7
INSTALLATION INSTRUCTIONS ------------------------ 7
Required Ability ---------------------------------------------- 7
Uncrating ------------------------------------------------------ 7
Locating The Heater --------------------------------------- 7-8
Levelling ------------------------------------------------------- 8
Clearances --------------------------------------------------- 8
Hard Water ----------------------------------------------------8
Air Requirements ------------------------------------------- 8-9
Venting --------------------------------------------------------- 9
Multiple Heater Manifold ---------------------------------- 9
Technical Data Venting ------------------------------------ 10-11
Water Line Connections ---------------------------------- 12
Water (Potable) Heating and Space Heating -------- 12
Thermometers (Not Supplied) -------------------------- 1 2
Relief Valve --------------------------------------------------- 1 2
INSTALLATION DIAGRAMS-TOP
INLET/OUTLET USAGE ----------------------------------- 1 3
General -------------------------------------------------------- 13
Code Restrictions ------------------------------------------ 13
INSTALLATION DIAGRAMS ------------------------------- 14-20
Heater Wiring ------------------------------------------------ 21
PagePage
Gas Piping ---------------------------------------------------- 2 2
Purging -------------------------------------------------------- 22
Gas Pressure Regulator ---------------------------------- 22-23
OPERATION -------------------------------------------------- 23
General -------------------------------------------------------- 23
Filling ----------------------------------------------------------- 23
SEQUENCE OF OPERATION ---------------------------- 24
Lighting and Operation ------------------------------------ 25
Water Temperature Control ------------------------------ 26
Checking Venting ------------------------------------------- 26
PREVENTIVE MAINTENANCE --------------------------- 26
Check The Ignitor Assembly ----------------------------- 26
Ignitor Assembly --------------------------------------------- 26-27
Main Burner --------------------------------------------------- 27
Gas Valves ---------------------------------------------------- 27
Checking The Input ----------------------------------------- 27-28
Venting System ---------------------------------------------- 28
Remote Storage Tank Temperature Control --------- 28
Relief Valve --------------------------------------------------- 28
Hot Water Odor ---------------------------------------------- 2 8
Anode Rod Inspection ------------------------------------- 28
Flushing ------------------------------------------------------- 2 8
Draining ------------------------------------------------------- 28
Recommended Procedure For Periodic
Removal of Lime Deposits From Tank Type
Commercial Water Heaters ------------------------------ 29
Tank Cleanout Procedures ------------------------------- 29
Ignition Module System ----------------------------------- 29-30
System Diagnostics ---------------------------------------- 30
SERVICE ------------------------------------------------------ 30
Electrical Servicing ----------------------------------------- 30
Sequence of Operation Flow Chart -------------------- 3 1
Operational Checklist -------------------------------------- 32
Limited Warranty -------------------------------------------- 33
NOTES --------------------------------------------------------- 34-35
FOREWORD
These designs comply with ANSI Z21.10.3 as an automatic
circulating or automatic storage tank type water heater.
Heaters having an input of 310,000, 366,000, 390,000 Btuh with
a recovery rating of 277.3 gph or more also comply with ANSI
Z21.10.3 as an automatic instantaneous type heater.
Detailed installation diagrams are found in this manual. These
diagrams will serve to provide the installer with a reference for
the materials and methods of piping necessary. It is highly
essential that all water, gas piping and wiring be installed as
shown on the diagrams.
Particular attention should be given to the installation of
thermometers at the locations indicated on the diagrams as
these are necessary for checking the proper functioning of the
heater.
The heater is designed to operate on natural gas only. If you
have obtained this heater for use on propane-STOP. Do not
install this water heater. Immediately call your supplier to correct
the situation.
These heaters may be installed on combustible floors.
In addition to these instructions, the equipment shall be installed
in accordance with those installation regulations in force in the
local area where the installation is to be made. These shall be
carefully followed in all cases. Authorities having jurisdiction
should be consulted before installations are made.
The installation must conform to these instructions and the local
code authority having jurisdiction. In the absence of local codes,
the installation must comply with the current editions of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the National
Electrical Code, NFPA 70, documents are available from the
National Fire Protection Association, 1 Batterymarch Park, Quincy,
MA 02269.
4
Page 5
GENERAL SAFETY
INFORMATION
OPERATION OF THESE FANS CAN PRODUCE A NEGATIVE
DRAFT IN THE AREA OF THE WATER HEATER PREVENTING
THE PRODUCTS OF COMBUSTION FROM EXHAUSTING
THROUGH THE CHIMNEY OR VENT PIPE.
PRECAUTIONS
DO NOT USE THIS APPLIANCE IF ANY PART HAS BEEN
UNDER WATER. Immediately call a qualified service technician
to inspect the appliance and to replace any part of the control
system and any gas control which has been under water.
IF THE UNIT IS EXPOSED TO THE FOLLOWING, DO NOT
OPERATE HEATER UNTIL ALL CORRECTIVE STEPS HAVE
BEEN MADE BY A QUALIFIED SERVICEMAN.
1. EXTERNAL FIRE.
2. DAMAGE.
3. FIRING WITHOUT WATER.
4. SOOTING
GROUNDING INSTRUCTIONS
This water heater must be grounded in accordance with the
National Electrical Code and/or local codes. These must be
followed in all cases.
The venting of the water heater should be inspected by a qualified
service technician at the time of installation and periodically
thereafter to ensure a down-draft condition does not exist.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION AND
VENTILATING AIR. ADEQUATE AIR FOR COMBUSTION AND
VENTILATION MUST BE PROVIDED FOR SAFE OPERATION.
EXTENDED NON-USE PERIODS
WARNING
HYDROGEN GAS CAN BE PRODUCED IN A HOT WATER
SYSTEM SERVED BY THIS HEATER THAT HAS NOT BEEN
USED FOR A LONG PERIOD OF TIME (GENERALLY TWO
WEEKS OR MORE). HYDROGEN GAS IS EXTREMELY
FLAMMABLE. To reduce the risk of injury under these conditions,
it is recommended that the hot water faucet be opened for several
minutes at the kitchen sink before using any electrical appliance
connected to the hot water system. If hydrogen is present, there
will probably be an unusual sound such as air escaping through
the pipe as the water begins to flow. THERE SHOULD BE NO
SMOKING OR OPEN FLAME NEAR THE FAUCET AT THE TIME
IT IS OPEN.
INSULATION BLANKETS
This water heater must be connected to a grounded metal,
permanent wiring system; or an equipment grounding conductor
must be run with the circuit conductors and connected to the
equipment grounding terminal or lead on the water heater, see
Figure 9.
CHEMICAL VAPOR CORROSION
WARNING
CORROSION OF THE FLUEWAYS AND VENT SYSTEM MAY
OCCUR IF AIR FOR COMBUSTION CONTAINS CERTAIN
CHEMICAL VAPORS. SUCH CORROSION MAY RESULT IN
FAILURE AND RISK OF ASPHYXIATION.
Spray can propellants, cleaning solvents, refrigerator and air
conditioning refrigerants, swimming pool chemicals, calcium and
sodium chloride (water softener salt), waxes, and process
chemicals and typical compounds which are potentially corrosive.
Do not store products of this sort near the heater. Also, air which
is brought in contact with a the heater should not contain any of
these chemicals. If necessary, uncontaminated air should be
obtained from remote or outside sources. The limited warranty is
voided when failure of water heater is due to a corrosive
atmosphere. (Refer to the limited warranty for complete terms
and conditions.
IMPROPER COMBUSTION
Insulation blankets available to the general public for external
use on gas water heaters are not approved for use on your
American water heater. The purpose of an insulation blanket is
to reduce the standby heat loss encountered with storage tank
water heaters. Your American water heater meets or exceeds
the ASHRAE/IES 90.1-2004 standards with respect to insulation
and standby loss requirement making an insulation blanket
unnecessary.
WARNING
Should you choose to apply an insulation blanket to this heater,
you should follow these instructions. Failure to follow these
instructions can result in fire, asphyxiation , serious personal injury
or death.
Do not apply insulation to the top of the water heater, as this
•
will interfere with safe operation of exhaust inducer.
• Do not cover gas valve on the temperature & pressure relief
valve.
• Do not cover the instruction manual. Keep it on the side of the
water heater or nearby for future reference.
Do not allow insulation to come within 2” (5cm) of the burner,
•
to prevent blockage of combustion air flow to the burners.
• Do not allow insulation to come within 9” (23cm) of the floor,
(within 2” (5cm) of bottom cover) to prevent blockage of
combustion air flow to the burners.
WARNING
ATTIC AND/OR EXHAUST FANS OPERATING ON THE
PREMISES WITH A WATER HEATER CAN RESULT IN CARBON
MONOXIDE POISONING AND DEATH.
• Do inspect the insulation blanket frequently to make sure it
does not sag, thereby obstructing combustion air flow.
• Do obtain new labels from American for placement on the
blanket directly over the existing labels.
5
Page 6
HIGH ALTITUDE INSTALLATIONS
WARNING
INSTALLATIONS ABOVE 2000 FEET (610 METERS) REQUIRE
REPLACEMENT OF THE BURNER ORIFICE IN ACCORDANCE
WITH THE NATIONAL FUEL GAS CODE (ANSI Z223.1). FAILURE
TO REPLACE THE ORIFICE WILL RESULT IN IMPROPER AND
INEFFICIENT OPERATION OF THE APPLIANCE RESULTING IN
THE PRODUCTION OF INCREASED LEVELS OF CARBON
MONOXIDE GAS IN EXCESS OF SAFE LIMITS WHICH COULD
RESULT IN SERIOUS PERSONAL INJURY OR DEATH.
You should contact your gas supplier for any specific changes
which may be required in your area.
As elevation above sea level is increased, there is less oxygen
per cubic foot of air. Therefore, the heater input rate should be
reduced at high altitudes for satisfactory operation with the reduced
oxygen supply. Failure to make this reduction would result in an
overfiring of the heater causing sooting, poor combustion and/or
unsatisfactory heater performance.
REQUIREMENTS
Ratings specified by manufacturers for most appliances apply for
elevations up to 2000 feet. For elevations above 2000 feet, ratings
must be reduced at the rate of 4% for each 1000 feet above sea
level. For example, if a heater is rated at 120,000 Btuh at sea level,
to rate the heater at 4000 feet, you subtract 4 (once for each thousand
feet) x.04 (4% input reduction) x 120,000 Btuh (original rating) from
the original rating. Therefore, to calculate the input rating at 4,000
feet: 4 x .04 x 120,000 =19,200 Btuh, 120,000 - 19,200 = 100,800
Btuh. At 6000 feet the correct input rating should be 91,200 Btuh.
The input reduction is primarily achieved by reducing the size of the
main burner orifices. To do this, the main burner orifices require
replacement with orifices sized for the particular installation
elevation. Correct orifice sizing and parts may be obtained from
American Water Heater Company. When ordering, be sure to state
the model number and the altitude of the location where the water
heater is being installed.
Upon completion of derating of the heater, adjustment to the gas
pressure regulator may be required. See CHECKING THE INPUT
section in this manual for inlet and manifold pressure requirements.
Note: The inlet tube may have 1, 3 or 7 cross tubes. - FIGURE 1
For proper function, the Eliminator must be oriented correctly.
There is a marked range on the pipe nipple that must be aligned
with the top of the inlet spud (check for label on the appliance)
to assure proper operation. Please check to confirm that the
marked range is in alignment with the top of the spud. A pipe
union is supplied with the Eliminator to help eliminate the
possibility of changing the orientation by accidentally
overtightening the inlet supply. Improper orientation of the
Eliminator may cause temperature buildup issues or spells of
colder than usual water temperatures.
HIGH LIMIT SWITCH
The digital thermostat (Fig. 2) contains the high limit (energy
cutoff) sensor. The high limit switch interrupts main burner gas
flow should the water temperature reach 203°F (95°C).
In the event of high limit switch operation, the appliance cannot
be restarted unless the water temperature is reduced to
approximately 120°F (49°C). The high limit reset button on the
front of the control then needs to be depressed.
Continued manual resetting of high limit control, preceded by
higher than usual water temperature is evidence of high limit
switch operation. The following is a possible reason for high
limit switch operation:
• A malfunction in the thermostatic controls would allow the
gas valve to remain open causing water temperature to exceed
the thermostat setting. The water temperature would continue
to rise until high limit switch operation.
Contact your dealer or service agent if continued high limit switch
operation occurs.
Also due to the input rating reduction required at high altitudes, the
output rating of the appliance is also reduced and should be
compensated for in the sizing of the equipment for application.
FEATURES
THE ELIMINATOR (SELF-CLEANING SYSTEM)
These units include The Eliminator (Self-Cleaning System) installed
in the front water inlet, see Figure 2. The Eliminator must be oriented
correctly for proper function. There is a marked range on the pipe
nipple portion of the Eliminator, that must be aligned with the top of
the inlet spud. A label above the jacket hole has an arrow that will
point to the marked portion of the pipe nipple if the orientation is
correct. If the arrow does not point within the marked range on the
pipe nipple, adjust the pipe nipple to correct. A pipe union is supplied
with the Eliminator to reduce the probability of misaligning the
Eliminator accidentally while tightening the connection to the inlet
water supply line. Improper orientation of the Eliminator can cause
poor performance of the heater and can significantly reduce outlet
water temperatures during heavy draws.
DIGITAL THERMOSTAT
FIGURE 2
ELECTRONIC IGNITION CONTROL
Each heater is equipped with a ignition module. The solid sate
ignition control (Fig. 3), ignites the main burner by utilizing a
silicone nitride ignitor. The silicone nitride ignitor shuts off during
the heating cycle and the main burner flame is sensed through
a remote flame sensor integral to the silicone nitride ignitor
assembly. The ignition control will try to ignite the main burner
three times before lockout. Then it waits one hour before trying
again to ignite the main burners. This is a continuous cycle.
6
Page 7
IGNITION CONTROL BOARD - FIGURE 3
EXHAUST INDUCER (BLOWER ASSY.)
All models are equipped with an exhaust inducer. The inducer
assists in drawing in fresh air to the unit for combustion and
then assists in dispensing the combustion by-products into the
venting leading outside.
The exhaust inducer is equipped with a gravity controlled damper to
reduce the amount of heat loss through the flue, improving efficiency.
EXHAUST INDUCER - FIGURE 4
CIRCULATING PUMP
A circulating pump is used when a system requires a circulating
loop or there is a storage tank used in conjunction with the
heater. Refer to the piping diagrams in this manual for electrical
hookup information and install in accordance with the current
version of the National Electrical Code ANSI/NFPA No. 70.
Only all bronze circulating pumps are used with commercial
water heaters.
Although circulating pumps are oiled and operated by the
manufacturer some circulating pumps must be oiled again
before operating. Please refer to manufacturer’s instructions.
DISHWASHING MACHINE REQUIREMENT
These appliances meet the National Sanitation Foundation
Standard for sanitary installations when used with the following
leg kit, Part No. 6570-7.
INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES
ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN
THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS
SUPPLY AND ELECTRICAL WORK ARE REQUIRED.
WARNING
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT
IN SERIOUS PERSONAL INJURY OR DEATH.
UNCRATING
The heater is shipped with the inducer already installed. The
wiring conduit runs from the thermostat to the inducer. Before
turning unit on, check to make sure the wiring conduit is securely
plugged into the inducer.
LOCATING THE HEATER
When installing the heater, consideration must be given to proper
location. Location selected should be as close to the stack or
chimney as practicable, with adequate air supply and as
centralized with the piping system as possible.
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH
AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER
AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR
ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED,
OPERATED OR REPAIRED. FLAMMABLE VAPORS ARE HEAVY
AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY
THE HEATER’S PILOT OR MAIN BURNER FLAMES CAUSING
FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT
OPERATION OF GAS APPLIANCES IN SUCH AREAS IF THEY
ARE INSTALLED 18” OR MORE ABOVE THE FLOOR. THIS MAY
REDUCE THE RISK IF LOCATION IN SUCH AN AREA
BE AVOIDED.
DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A
CARPETED FLOOR. A FIRE HAZARD MAY RESULT.
water heater must be placed on a metal or wood panel extending
beyond the full width and depth by at least 3 inches in any direction.
If the heater is installed in a carpeted alcove, the entire floor
shall be covered by the panel. Also, see the DRAINING
requirements in MAINTENANCE Section.
THE HEATER SHOULD BE LOCATED OR PROTECTED SO IT IS
NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.
CANNOT
Instead the
All dishwashing machines meeting the National Sanitation
Foundation requirements are designed to operate with water flow
pressures between 15 and 25 psi. Flow pressures above 25 psi, or
below 15 psi, will result in improperly sanitized dishes. Where
pressures are high, a water pressure reducing or flow regulating
control valve should be used in 180
and should be adjusted to deliver water between these limits.
The National Sanitation Foundation also recommends
circulation of 180
should be very gentle so that it does not cause any unnecessary
turbulence inside the water heater. The circulation should be
just enough to provide 180
dishwashing machine. Adjust flow by means of the plug cock in
the circulating line.
0
F water. Where this is done, the circulation
0
F line to the dishwashing machine,
0
F water at the point of take-off to the
INSTALLATION INSTRUCTIONS
REQUIRED ABILITY
WARNING
FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY
OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST
NEVER BE PLACED ON OR ADJACENT TO THE HEATER. OPEN
CONTAINERS OR FLAMMABLE MATERIAL SHOULD NOT BE
STORED OR USED IN THE SAME ROOM WITH THE HEATER.
THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT
WILL BE SUBJECT TO FREEZING.
LOCATE IT NEAR A FLOOR DRAIN. THE HEATER SHOULD BE
LOCATED IN AN AREA WHERE LEAKAGE FROM THE HEATER
OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE
ADJACENT AREA OR TO LOWER FLOORS OF THE
STRUCTURE.
WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE
METAL DRAIN PAN SHOULD BE INSTALLED UNDER THE
HEATER.
7
Such pans should be fabricated with sides at least 2"
Page 8
deep, with length and width at least 2" greater than the diameter
of the heater and must be piped to an adequate drain. The pan
must not restrict combustion air flow.
LEVELING
If the unit is not level, insert the bolts which were used in crating
into the legs to correct this condition.
CLEARANCES
These heaters are approved for installation on combustible
flooring (with Leg Kit 9003425205) in an alcove when the
minimum clearance from any combustion construction are
followed as indicated in figure 5 and Table 4.
In all installations the minimum combustible clearances from
vent piping shall be 6" (152mm). Vent piping passing through a
combustible wall or ceiling must be a continuous run (no joints)
and retain the 6" (152mm) clearance unless an approved
reducing thimble is used.
A service clearance of 24" (610mm) should be maintained from
serviceable parts, such as relief valves, flue baffles, thermostats,
cleanout openings or drain valves.
The units are approved for installation with side, rear and ceiling
clearances as indicated below:
Where hard water conditions exist, water softening or the threshold type
of water treatment is recommended. This will protect the dishwashers,
coffee urns, water heaters, water piping and other equipment.
See MAINTENANCE section for details of tank cleanout procedure.
AIR REQUIREMENTS
REFER TO THE CURRENT EDITION OF THE "NATIONAL FUEL
GAS CODE" ANSI Z223.1/NFPA 54.
KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE
MATERIALS, GASOLINE AND OTHER FLAMMABLES, VAPORS AND
LIQUIDS.
DO NOT OBSTRUCT THE FLOW OF COMBUSTION OR
VENTILATING AIR.
WARNING
FOR SAFE OPERATION PROVIDE ADEQUATE AIR FOR
COMBUSTION AND VENTILATION. AN INSUFFICIENT SUPPLY OF
AIR WILL CAUSE RECIRCULATION OF COMBUSTION PRODUCTS
RESULTING IN AIR CONTAMINATION THAT MAY BE HAZARDOUS
TO LIFE. SUCH A CONDITION OFTEN WILL RESULT IN A YELLOW,
LUMINOUS BURNER FLAME, CAUSING CARBONING OR SOOTING
OF THE COMBUSTION CHAMBER, BURNERS AND FLUE TUBES
AND CREATES A RISK OF ASPHYXIATION.
ILLUSTRATION OF MINIMUM COMBUSTIBLE CLEARANCES IN AN ALCOVE - FIGURE 5
8
Page 9
Where an exhaust fan is supplied in the same room with a
heater, sufficient openings for air must be provided in the
walls.
UNDERSIZED OPENINGS WILL CAUSE AIR TO BE
DRAWN INTO THE ROOM THROUGH THE CHIMNEY,
CAUSING POOR COMBUSTION. SOOTING MAY RESULT IN
SERIOUS DAMAGE TO THE HEATER AND RISK OF FIRE OR
EXPLOSION.
UNCONFINED SPACE
In buildings of conventional frame, brick, or stone construction,
unconfined spaces may provide adequate air for combustion,
ventilation and draft hood dilution.
If the unconfined space is within a building of tight construction
(buildings using the following construction: weather stripping,
heavy insulation, caulking, vapor barrier, etc.), air for combustion,
ventilation and draft hood dilution must be obtained from outdoors.
The installation instructions for confined spaces in tightly
constructed buildings must be followed to ensure adequate air
supply.
CONFINED SPACE
Heater must be protected from freezing downdrafts.
Remove all soot or other obstructions from the chimney that will
retard a free draft.
Type B venting is recommended with these heaters. For typical
venting application see TECHNICAL DATA VENTING on pages
10 and 11.
This water heater must be vented in compliance with all local
codes, the current edition of the National Fuel Gas Code (ANSIZ223.1) and with the Category I Venting Tables.
If any part of the vent system are exposed to ambient
temperatures below 40°F it must be insulated to prevent
condensation.
• Do not connect the heater to a common vent or chimney with
solid fuel burning equipment. This practice is prohibited by
many local building codes as is the practice of venting gas
fired equipment to the duct work of ventilation systems.
When drawing combustion and dilution air from inside a
conventionally constructed building to a confined space,
such a space shall be provided with two permanent
openings, ONE IN OR WITHIN 12 INCHES (30.5cm) OF
THE ENCLOSURE TOP AND ONE IN OR WITHIN 12 INCHES
(30.5cm) OF THE ENCLOSURE BOTTOM. Each opening
shall have a free area of at least one square inch per 1000
Btuh (2,225mm
the enclosure, but not less than 100 square inches (645
square cm).
If the confined space is within a building of tight construction,
air for combustion, ventilation, and drafthood dilution must be
obtained from outdoors. When directly communicating with
the outdoors or communicating with the outdoors through
vertical ducts, two permanent openings, located in the above
manner, shall be provided. Each opening shall have a free
area of not less than one square inch per 4000 Btuh
(8,900mm2/Kw)of the total input of all appliances in the
enclosure. If horizontal ducts are used, each opening shall
have a free area of not less than one square inch per 2000
Btuh (4,450mm2/Kw)of the total input of all appliances in the
enclosure.
2
/Kw) of the total input of all appliances in
VENTING
WARNING
THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST
BE FOLLOWED TO AVOID CHOKED COMBUSTION OR
RECIRCULATION OF FLUE GASES. SUCH CONDITIONS
CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.
FIGURE 6
• Where a separate vent connection is not available and the
vent pipe from the heater must be connected to a common
vent with an oil burning furnace, the vent pipe should enter
the smaller common vent or chimney at a point above the
large vent pipe.
MULTIPLE HEATER MANIFOLD
Figure 7 and tables on pages 10 and 11 should be used for
horizontally manifolding two or more heaters.
FIGURE 7
9
Page 10
TABLE 6. TECHNICAL DATA VENTING
TYPE B GAS VENT
Multiple Gas Fired Tank-Type Heaters
When venting multiple tank type heaters using Type B
vent pipe, follow the installation diagram (figure 4) and
tables below which give sizing and data based upon
NFPA 54/ANSI Z223. 1992.
(A)BCG3 Heatersin Thousands of Btu/hrManifold & Common Vent Diameter (Inches)
2732,00012101099988
798,000121210109988
31,098,00014141412121099
1,197,000141414121210109
41,464,000161614141412121 0
1,596,000161616141412121 0
11
Page 12
WATER LINE CONNECTIONS
SYSTEM CONNECTIONS
This manual provides detailed installation diagrams (see pages
14-20 of this manual) for typical methods of application for the
water heater(s).
The water heater may be installed by itself, or with a separate
storage tank, on both single and two-temperature systems. When
used with a separate storage tank, the circulation may be either
by gravity or by means of a circulating pump. When a circulating
pump is used it is important to note that the flow rate should be
slow so that there will be a minimum of turbulence inside the
heater.
If a water heater is installed in a closed water system, provisions
for the thermal expansion in the Hot Water System must be
provided. Contact the water supplier or local plumbing inspector
on how to control this situation.
WATER (POTABLE) HEATING AND SPACE
HEATING (See pages 14-20)
1. All piping components connected to this unit for space heating
applications shall be suitable for use with potable water.
2. Toxic chemicals, such as those used for boiler treatment, shall
NEVER be introduced into this system.
The system installation must conform to these instructions and to
the local code authority having jurisdiction. Good practice
requires that all heavy piping be supported.
THERMOMETERS (Not Supplied)
Thermometers should be obtained and field installed as shown in
the installation diagrams.
Thermometers are installed in the system as a means of detecting
the temperature of the outlet water supply.
RELIEF VALVE
This water heater is equipped with a combination temperaturepressure relief valve that complies with the standard for relief
valves for hot water supply system, ANSI Z21.22. FOR SAFE
OPERATION OF THE WATER HEATER, THE RELIEF VALVE(S)
MUST NOT BE REMOVED OR PLUGGED.
ASME ratings cover pressure relief capacities. CSA ratings cover
release rate with temperature actuation.
In addition to the appliance relief valve, each remote storage tank
which may be used in conjunction with this appliance shall also
be installed with a properly sized, rated and approved combination
temperature (ANSI) and pressure (ASME) relief valve(s).
3. This unit may NEVER be connected to any existing heating
system or component(s) previously used with a non-potable
water heating appliance.
4. When the system requires water for space heating at
temperatures higher than required for domestic water
purposes, a tempering valve must be installed. Please refer
to installation diagrams on pages 17 and 19 of this manual
for suggested piping arrangements.
CAUTION
A closed system will exist if a check valve (without bypass),
pressure reducing valve (without bypass), or a water meter (without
bypass) is installed in the cold water line between the water heater
and street main (or well).
Excessive pressure may develop in such closed systems,
causing premature tank failure or intermittent relief valve
operation.
a similar device may be required in the inlet supply line between
the appliance and the meter or valve to compensatefor the
thermal expansion of the water.
This is not a warranty failure. An expansion tank or
WARNING
THE PURPOSE OF RELIEF VALVE IS TO AVOID EXCESSIVE
PRESSURE OR TEMPERATURE INTO THE STEAM RANGE,
WHICH MAY CAUSE SCALDING AT FIXTURES, TANK
EXPLOSION, SYSTEM OR HEATER DAMAGE. NO VALVE IS
TO BE PLACED BETWEEN THE RELIEF VALVE AND TANK.
Your local code authority may have other specific relief valve
requirements.
A DRAIN LINE MUST BE CONNECTED TO THE RELIEF VALVE
TO DIRECT DISCHARGE TO A SAFE LOCATION TO AVOID
SCALDING OR WATER DAMAGE. THIS LINE MUST NOT BE
REDUCED FROM THE SIZE OF THE VALVE OUTLET AND MUST
NOT CONTAIN VALVES, RESTRICTIONS NOR SHOULD IT BE
LOCATED IN FREEZING AREAS. DO NOT THREAD OR CAP
THE END OF THIS LINE. RESTRICTED OR BLOCKED
DISCHARGE WILL DEFEAT THE PURPOSE OF THE VALVE
AND IS UNSAFE. DISCHARGE LINE SHALL BE INSTALLED
TO ALLOW COMPLETE DRAINAGE OF BOTH THE VALVE AND
LINE.
See SERVICE INFORMATION section for procedure and
precautions.
12
Page 13
INSTALLATION DIAGRAMS-TOP INLET/OUTLET USAGE
GENERAL
The type, size and location of the relief valves must be in
accordance with local codes. The locations of the relief valves
shown in the installation diagrams are typical. The heater has a
factory installed high temperature limit switch and temperature
and pressure relief valve.
Cold water lines to heater should be installed as shown in order
to minimize gravity circulation of hot water to building cold water
lines.
A listed temperature and pressure relief valve of adequate capacity
is installed on the heater. The locations shown in the installation
diagrams on the following pages are typical.
The discharge opening of the temperature and pressure relief
valve, located in front of the heater must be piped to an open
drain and should not be subject to freezing temperatures.
Install in accordance with all local codes.
TUBE INLET INSTALLATION
Use of the top inlet water connection requires installation of an
inlet dip tube (refer to figure 8). The tube is supplied in the heater.
Follow caution labels if applying heat to this fitting. Do not allow
pipe dope to contact the plastic tube during installation.
CODE RESTRICTIONS
Use of the top inlet water connection is not permitted on
installations in the state of North Carolina, due to the material of
the tube (Polypropylene). Where such code restrictions exist,
use only lower inlet tank connection. This may also require a
heat trap - check local codes. The “Top Outlet” connection may
still be used on these applications. Plug or cap all unused
openings in the tank before filling with water.
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE
TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE
CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE
BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT
WATER SUPPLIED TO FIXTURES.
FIGURE 8
13
Page 14
VERTICAL STORAGE TANK AND FORCED CIRCULATION
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE
TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE
CONTROL WARNING ON PAGE 25. IF HIGHER PREHEAT
TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE
BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER
SUPPLIED TO FIXTURES.
HORIZONTAL STORAGE TANK AND FORCED CIRCULATION
14
Page 15
TWO TEMPERATURE - ONE HEATER HIGH TEMPERATURE STORAGE
WITH RECIRCULATION OF SANITIZING LOOP
NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C) WATER
CIRCULATION. INSTALL ON OR CLOSE TO DISHWASHING
MACHINE. TOGGLE SWITCH MUST BE CLOSED (ON) DURING
THE RINSE OPERATION AND OPEN (OFF) WHEN
DISHWASHER IS NOT OPERATING OR WHEN ON LONG
STANDBY.
NOTE 2:INSTALL LINE TEMPERATURE CONTROL IN AN
UNINSULATED TEE BEYOND THE DISHWASHING MACHINE
TAKEOFF IN THE SANITIZING LOOP. CONTROL SHOULD
BE SET AT 185°F (85°C).
NOTE 3:ADJUST PLUG COCK SO THE SANITIZING LOOP FLOW RATE
DOES NOT CAUSE UNNECESSARY TURBULENCE IN THE
TANK.
* TEMPERED WATER LOOP, IF USED, CONNECT TO
POINT “A”.
**PIPE RELIEF VALVE TO OPEN DRAIN.
INSTALL IN ACCORDANCE WITH LOCAL CODES.
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW
PREVENTER, CHECK VALVE OR WATER METER WITH
CHECK VALVE, PROVISIONS FOR THERMAL EXPANSION
OF WATER IN THE HOT WATER SYSTEM MUST BE
PROVIDED.
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE
TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL
WARNING ON PAGE 25. IF HIGHER PREHEAT TEMPERATURES ARE
NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTISCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
15
Page 16
INSTALLATION DIAGRAMS-SIDE INLET/OUTLET USAGE
A listed temperature and pressure relief valve of adequate
capacity is installed on the heater. The locations shown in the
installation diagrams on the following pages are typical.
The discharge opening of the temperature and pressure relief
valve must be piped to an open drain and should not be subject
to freezing conditions. DO NOT REDUCE, BLOCK OR PLUG
THE DISCHARGE OPENING OF THE VALVE.
TWO TEMPERATURE - TWO HEATERS, ONE PRE-HEATER/ONE - BOOSTER HEATER
WITH OR WITHOUT BUILDING RECIRCULATION
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE
TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL
WARNING ON PAGE 25. IF HIGHER PREHEAT TEMPERATURES ARE
NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTISCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
CIRCULATING RETURN LINE CONNECTION
-FROM FIXTURE LOOP, IF USED, CONNECT
TO PRE-HEATER INLET.
-FROM BOOSTED TEMPERATURE LOOP, IF
USED CONNECT TO BOOSTER INLET.
†AVAILABLE FROM A.O. SMITH.
*PIPE RELIEF VALVE TO OPEN DRAIN.
INSTALL IN ACCORDANCE WITH LOCAL CODES.
16
Page 17
ONE OR TWO TEMPERATURE - ONE HEATERS,HIGH TEMPERATURE
STORAGE WITH OR WITHOUT RECIRCULATION
HEATER WITH OR WITHOUT MIXING VALVE
HEATER WITH MIXING VALVE AND RECIRCULATED SANITIZING LOOP
* PIPE RELIEF VALVE TO OPEN DRAIN.
INSTALL IN ACCORDANCE WITH LOCAL
CODES.
CIRCULATING RETURN LINE CONNECTIONS.
- TEMPERED WATER LOOP, IF USED,
CONNECT TO POINT “R”.
- STORED TEMPERATURE WATER LOOP, IF
USED, CONNECT TO COLD WATER INLET.
NOTE 1: TOGGLE SWITCH CONTROLS 180°F (82°C)
WATER CIRCULATION. INSTALL ON OR CLOSE
TO DISHWASHING MACHINE. TOGGLE SWITCH
MUST BE CLOSED (ON) DURING THE RINSE
OPERATION AND OPEN (OFF) WHEN
DISHWASHER IS NOT OPERATING OR WHEN
ON LONG STANDBY.
DANGER
TEMPERATURE SETTING SHOULD NOT
EXCEED SAFE USE TEMPERATURE AT
FIXTURES. SEE WATER TEMPERATURE
CONTROL WARNING ON PAGE 25. IF HIGHER
PREHEAT TEMPERATURES ARE NECESSARY
TO OBTAIN ADEQUATE BOOSTER OUTPUT,
ADD AN ANTI-SCALD VALVE FOR HOT WATER
SUPPLIED TO FIXTURES.
NOTE 2: INSTALL LINE TEMPERATURE CONTROL
NOTE 3: ADJUST PLUG COCK SO THE SANITIZING
UNNECESSARY TURBULENCE IN THE TANK.
IN AN UNINSULATED TEE BEYOND THE
DISHWASHING MACHINE TAKEOFF IN
THE SANITIZING LOOP. CONTROL
SHOULD BE SET AT 185°F (85°C).
LOOP FLOW RATE DOES NOT CAUSE
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A BACKFLOW
PREVENTER, CHECK VALVE OR WATER METER WITH CHECK VALVE,
PROVISIONS FOR THERMAL EXPANSION OF WATER IN THE HOT WATER
SYSTEM MUST BE PROVIDED.
17
Page 18
TWO TEMPERATURE - TWO PRE-HEATERS WITH MIXING VALVE OR BOOSTER
HEATER WITH OR WITHOUT BUILING RECIRCULATION
TWO PRE-HEATERS WITH MIXING VALVE
DANGER
TEMPERATURE SETTING SHOULD NOT
EXCEED SAFE USE TEMPERATURE AT
FIXTURES. SEE WATER TEMPERATURE
CONTROL WARNING ON PAGE 25. IF HIGHER
PREHEAT TEMPERATURES ARE NECESSARY
TO OBTAIN ADEQUATE BOOSTER OUTPUT,
ADD AN ANTI-SCALD VALVE FOR HOT WATER
SUPPLIED TO FIXTURES.
TWO PRE-HEATERS WITH BOOSTER HEATER
18
Page 19
MEDIUM TEMPERATURE - ONE HEATER WITH AUXILIARY STORAGE TANK FORCED
CIRCULATION WITH OR WITHOUT BUILDING RECIRCULATION
VERTICAL STORAGE TANK
* PIPE RELIEF VALVE TO OPEN DRAIN.
**WHEN USING A T-140, -200,
-350 OR -400 STORAGE TANK, USE
LOWER 3/4” OPENING FOR TANK
TEMPERATURE CONTROL.
IF BUILDING CIRCULATING LOOP IS USED,
CONNECT TO AN OPENING NEAR THE
BOTTOM OF THE TANK.
HORIZONTAL STORAGE TANK
CAUTION: IF BUILDING COLD WATER SUPPLY HAS A
BACKFLOW PREVENTER, CHECK VALVE OR WATER
METER WITH CHECK VALVE, PROVISIONS FOR
THERMAL EXPANSION OF WATER IN THE HOT WATER
SYSTEM MUST BE PROVIDED.
*PIPE RELIEF VALVE TO OPEN DRAIN
INSTALL IN ACCORDANCE WITH LOCAL CODES.
DANGER
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE
USE TEMPERATURE AT FIXTURES. SEE WATER
TEMPERATURE CONTROL WARNING ON PAGE 25. IF
HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO
OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTISCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES.
All electrical work must be installed in accordance with the current
version of the National Electrical Code ANSI/NFPA No. 70, must
conform to all local code authority having jurisdiction. AN
ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF
ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION.
If any of the original wire as supplied with the appliance must be
replaced, use only type 105°C thermoplastic or equivalent.
2500C type F must be used for the flame sensor leads and the
spark ignition cable must be high voltage 250°C.
FIGURE 9 - SINGLE UNIT WIRING DIAGRAM
21
Page 22
GAS PIPING
Contact your local gas service company to ensure that adequate
gas service is available and to review applicable installation
codes for your area.
Size the main gas line in accordance with Table 7. The figures
shown are for straight lengths of pipe at 0.5 in. W.C. pressure
drop, which is considered normal for low pressure systems. Note:
Fittings such as elbows, tees and line regulators will add to the
pipe pressure drop. Also refer to the current edition of the National
Fuel Gas Code.
To prevent damage, care must be taken not to apply too much
torque when attaching gas supply pipe to gas valve inlet.
Apply joint compounds (pipe dope) sparingly and only to the
male threads of pipe joints. Do not apply compounds to the first
two threads. Use compounds resistant to the action of liquefied
petroleum gases.
BEFORE PLACING THE HEATER IN OPERATION, CHECK FOR
GAS LEAKAGE. Use soap and water solution or other material
acceptable for the purpose in locating the leaks. DO NOT USE
MATCHES, CANDLES, FLAME OR OTHER SOURCES OF
IGNITION FOR THIS PURPOSE.
WARNING
THE HEATER IS NOT INTENDED FOR OPERATION AT HIGHER
THAN 14.0" W.C.- NATURAL GAS, (1/2 POUND PER SQUARE
INCH GAGE) SUPPLY GAS PRESSURE. EXPOSURE TO
HIGHER SUPPLY PRESSURE MAY CAUSE DAMAGE TO THE
GAS VALVE WHICH COULD RESULT IN FIRE OR EXPLOSION.
IF OVERPRESSURE HAS OCCURRED SUCH AS THROUGH
IMPROPER TESTING OF GAS LINES OR EMERGENCY
MALFUNCTION OF THE SUPPLY SYSTEM, THE GAS VALVE
MUST BE CHECKED FOR SAFE OPERATION. MAKE SURE
THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS
AND THE SAFETY VENT VALVES ARE PROTECTED AGAINST
BLOCKAGE. THESE ARE PARTS OF THE GAS SUPPLY
SYSTEM, NOT THE HEATER. VENT BLOCKAGE MAY OCCUR
DURING ICE STORMS.
IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING
FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING
MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.
IF COPPER SUPPLY LINES ARE USED THEY MUST BE
INTERNALLY TINNED AND CERTIFIED FOR GAS SERVICE.
BEFORE ATTACHING THE GAS LINE, BE SURE THAT ALL GAS
PIPE IS CLEAN ON THE INSIDE.
TO TRAP ANY DIRT OR FOREIGN MATERIAL IN THE GAS
SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED SEDIMENT
TRAP OR DRIP LEG) MUST BE INCORPORATED IN THE PIPING
(SEE FIG. 10). THE DIRT LEG MUST BE READILY ACCESSIBLE
AND NOT SUBJECT TO FREEZING CONDITIONS. INSTALL IN
ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS
SUPPLIERS. REFER TO THE CURRENT EDITION OF THE
NATIONAL FUEL GAS CODE.
DISCONNECT THE HEATER AND ITS MANUAL GAS SHUTOFF
VALVE FROM THE GAS SUPPLY PIPING SYSTEM DURING ANY
SUPPLY PRESSURE TESTING EXCEEDING 1/2 PSIG. GAS
SUPPLY LINE MUST BE CAPPED WHEN DISCONNECTED
FROM THE HEATER FOR TEST PRESSURES OF 1/2 PSIG OR
LESS. THE APPLIANCE NEED NOT BE DISCONNECTED, BUT
MUST BE ISOLATED FROM THE SUPPLY PRESSURE TEST
BY CLOSING THE MANUAL GAS SHUTOFF VALVE.
GAS PIPING AND DIRT LEG INSTALLATION
FIGURE 10
PURGING
Gas line purging is required with new piping or systems in which
air has entered.
CAUTION
PURGING SHOULD BE PERFORMED BY PERSONS
EXPERIENCED IN THIS TYPE GAS SERVICE. TO AVOID RISK
OF FIRE OR EXPLOSION, PURGE DISCHARGE MUST NOT
ENTER CONFINED AREAS OR SPACES WHERE IGNITION CAN
OCCUR. THE AREA MUST BE WELL VENTILATED AND ALL
SOURCES OF IGNITION MUST BE INACTIVATED OR REMOVED.
GAS METER SIZE — NATURAL GASES ONLY
Be sure the gas meter has sufficient capacity to supply the full
rated gas input of the water heater as well as the requirements of
all other gas fired equipment supplied by the meter. If gas meter
is too small, ask the gas company to install a larger meter having
adequate capacity.
GAS PRESSURE REGULATOR
The gas pressure regulator is built into the gas valve and is
equipped to operate on the gas specified on model and rating
plate. The regulator is factory adjusted to deliver gas to burner at
22
Page 23
correct water column pressure allowing for a nominal pressure
drop through the controls.
AND PRESSURE RELIEF VALVE IS INSTALLED IN THE RELIEF
VALVE OPENING OF THE HEATER.
The minimum gas supply pressure for input adjustment must
not be less than 4.5" w.c. (1.12 kPa) for natural gas.
Do not subject the combination gas valve to inlet gas
pressures of more than 14.0" W.C. (3.48 kPa) - natural gas.
A service regulator is necessary if higher gas pressures are
encountered.
Gas pressure specified in Table 8, refer to flow pressure
taken at pressure tap of automatic gas valve while heater is
operating.
TABLE 8 - MANIFOLD GAS PRESSURE IN INCHES
OF WATER COLUMN (ALL MODELS*)
TYPE OF GAS
Natural
3.5 (0.87 kPa)
TABLE 9
APPROXIMATE TIME REQUIRED TO CONSUME
1 CU. FT. OF GAS AT FULL CAPACITY
TIME REQ’D
INPUTTYPEBTUHTO CONSUME
RATEOFPER 1CU. FT.
(BTUH)GASCU. FT.OF GAS
120,000NATURAL105031.5 SEC.
154,000NATURAL105024.5 SEC.
180,000NATURAL105021.1 SEC.
199,000NATURAL105019.0 SEC.
190,000NATURAL105020.1 SEC.
250,000NATURAL105015.1 SEC.
275,000NATURAL105013.75 SEC.
310,000NATURAL105012.4 SEC.
366,000NATURAL105010.4 SEC.
390,000NATURAL10509.5 SEC.
Figures shown are valid for 0-2000 ft. installations. See “HIGH
ALTITUDE INSTALLATIONS” for deration requirements over
2000 ft.
OPERATION
IMPORTANT
A qualified person must perform the initial firing of the heater. At
this time the user should not hesitate to ask the individual any
questions which they may have in regard to the operation and
maintenance of the unit.
An Operational Checklist is included at the rear of this manual.
By using this checklist the user may be able to make minor
operational adjustments and avoid unnecessary service calls.
However, the user should not attempt repairs which are not listed
under the USER column.
GENERAL
NEVER OPERATE THE HEATER WITHOUT FIRST BEING
CERTAIN IT IS FILLED WITH WATER AND A TEMPERATURE
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL
TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE
TO THE APPLIANCE.
CAUTION
Before proceeding with the operation of the unit make sure the
water heater and system are filled with water and all air is
expelled.
FILLING
1. Close the heater drain valve by turning handle clockwise.
2. Open a nearby hot water faucet to permit the air in the system
to escape.
3. Fully open the cold water inlet pipe valve allowing the heater
and piping to be filled.
4. Close the hot water faucet as water starts to flow.
5. The heater is ready to be operated.
WARNING
THE GAS VALVE MUST HAVE BEEN IN THE OFF POSITION FOR
AT LEAST 5 MINUTES. This waiting period is an important safety
step. Its purpose is to permit gas that may have accumulated in
the combustion chamber to clear. IF YOU DETECT GAS ODOR
AT THEEND OF THIS PERIOD DO NOT PROCEED WITH
LIGHTING. RECOGNIZE THAT GAS EVEN IF IT SEEMS WEAK,
MAY INDICATE PRESENCE OF ACCUMULATED GAS
SOMEPLACE IN THE AREA WITH RISK OF FIRE OR
EXPLOSION. SEE THE FRONT PAGE FOR STEPS TO BE TAKEN.
All gas and water lines leak tested and open.
Read SEQUENCE OF OPERATION section of this manual prior
to lighting and operating this appliance.
With above conditions satisfied, start the unit in accordance with
the instructions on the operating label attached to the heater. For
your convenience a copy of the instructions are shown of page
25. Each heater is equipped with an ignition control board. The
controller will try three times to light the main burner before going
into lockout. After the controller tries three times, it will wait one
hour before trying to light the unit again. This cycle will continue
until the main burners are ignited or the unit is shut down.
ADJUSTMENTS
ON INITIAL STARTUP SOME ADJUSTMENTS ARE
NECESSARY.
1. CHECK MANIFOLD AND INLET GAS PRESSURES.
2. CYCLE CHECK - CHECK AT LEAST ONE BURNER
OPERATION - WHEN THERMOSTAT IS SATISFIED, BURNER
WILL SHUT OFF AND INDUCER WILL STOP RUNNING. ON
CALL FOR HEAT - THE INDUCER WILL COME ON AND
CLOSE THE PRESSURE SWITCH AND THE IGNITION
SEQUENCE DESCRIBED ABOVE WILL BEGIN, SEE
“SEQUENCE OF OPERATION”.
23
Page 24
SEQUENCE OF OPERATION
The following information will describe the Sequence of Operation
for this appliance.
1. Switch power on to unit.
2. Thermostat calls for heat.
3. Ignition Control Board performs diagnostic check on system
components.
4. On completion of diagnostics check, the Ignition Control Board
sends signal to Exhaust Inducer.
5. Exhaust Inducer begins drawing air through appliance closing
the Prover Switch.
6. On completion of Prover Switch engagement, the Ignition
Control Board begins the ignition cycle.
7. The Ignition Control Board provides power to the Silicon Nitride
Ignitor.
8. The Silicon Nitride Ignitor heats up for approximately 17 to 20
seconds.
9. At the end of Silicon Nitride Ignitor’s warm-up, the Ignition
Control Board opens the Gas Valve.
10.From the time the Gas Valve opens, the Ignition Control Board
waits 3 seconds and then shuts off power to the Silicon Nitride
Ignitor.
11.From the time the Silicon Nitride Ignitor’s power is shut off,
the Ignition Control Board waits 3 more seconds to monitor
the Flame Sensor.
12.If the Flame Sensor does not detect a strong enough flame,
the Ignition Control Board shuts off the Gas Valve and allows
the Exhaust Inducer to purge the unit for 20 seconds. At that
time, the Ignition Control Board restarts with step 7. It will try
and ignite the main burners 2 more times. If the unit does not
light, the Ignition Control Board will wait one hour and then
restart at step 3. This cycle will continue until the unit lights or
the power is shutoff to the unit.
13.If the Flame Sensor detects a strong flame, the Ignition Control
Board will allow the unit to operate until the thermostat is
satisfied.
14.Once the unit is satisfied, the Ignition Control Board will shut
off the Gas Valve and the unit will be in standby mode until
another call for heat is initiated by the thermostat.
See the flow chart on page 31 for more information.
24
Page 25
LIGHTING AND OPERATION INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
A.This appliance does not have a pilot. It is equipped with
an ignition device which automatically lights the burner.
Do not try to light the burner by hand.
B.BEFORE OPERATING smell all around the appliance
area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle
on the floor.
“WHAT TO DO IF YOU SMELL GAS”
•Do not try to light any appliance.
•Do not touch any electric switch; do not use any telephone
in your building.
•Immediately call your gas supplier from a neighbor’s
telephone. Follow the gas supplier’s instructions.
IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION
MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
OPERATING INSTRUCTIONS
1.STOP! Read the safety information above on this
2.Set thermostat to lowest setting.
3.Turn off all electric power to the appliance.
4.This appliance is equipped with an ignition device which
5.Push in gas control knob slightly and turn clockwise
label.
automatically lights the burner. Do not try to light the
burner by hand.
to “OFF”.
•If you cannot reach your gas supplier, call the fire
department.
C.Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or
turn by hand, don’t try to repair it, call a qualified service
technician. Force or attempted repair may result in fire
or explosion.
D.Do not use this appliance if any part has been under
water. Immediately call a qualified service technician
to inspect the appliance and to replace any part of the
control system and any gas control which has been
under water.
9.Set thermostat to desired setting.
10. If the appliance will not operate, follow the instructions
“To Turn Off Gas To Appliance” and call your service
technician or gas supplier.
6.Wait five (5) minutes to clear out any gas. If you
then smell gas, STOP! Follow “B” in the
safety information above on this label. If you
don’t smell gas, go on to the next step.
7.Turn gas control knob counterclockwise to “ON”.
8.Turn on all electric power to the appliance.
FOR YOUR SAFETY READ BEFORE OPERATING
1.Set the thermostat to lowest setting.
2.Turn off all electric power to appliance if service is to be performed.
3.Push in gas control knob slightly and turn clockwise to “OFF”. Do not force.
25
Page 26
WATER TEMPERATURE CONTROL
DANGER
THIS WATER HEATER IS EQUIPPED WITH AN ADJUSTABLE
THERMOSTAT TO CONTROL WATER TEMPERATURE. HOT
WATER TEMPERATURES REQUIRED FOR AUTOMATIC
DISHWASHER AND LAUNDRY USE CAN CAUSE SCALD BURNS
RESULTING IN SERIOUS PERSONAL INJURY AND/OR DEATH.
THE TEMPERATURE AT WHICH INJURY OCCURS VARIES WITH
THE PERSON'S AGE AND TIME OF EXPOSURE. THE SLOWER
RESPONSE TIME OF CHILDREN, AGED OR DISABLED
PERSONS INCREASES THE HAZARDS TO THEM. NEVER
ALLOW SMALL CHILDREN TO USE A HOT WATER TAP, OR TO
DRAW THEIR OWN BATH WATER. NEVER LEAVE A CHILD OR
DISABLED PERSON UNATTENDED IN A BATHTUB OR SHOWER.
THE WATER HEATER SHOULD BE LOCATED IN AN AREA
WHERE THE GENERAL PUBLIC DOES NOT HAVE ACCESS
TO SET TEMPERATURES.
SETTING THE WATER HEATER TEMPERATURE AT 120°F
(49°C) WILL REDUCE THE RISK OF SCALDS.
provinces require settings at specific lower temperatures.
Below you will find listed the approximate time-to-burn relationship
for normal adult skin. Short repeated heating cycles caused by
small hot water uses can cause temperatures at the point of use
to exceed the thermostat setting by up to 20F°. If you experience
this type of use, you should consider using lower temperature
settings to reduce scald hazards.
TABLE 10
TemperatureTime to Produce 2nd & 3rd
SettingDegree Burns on Adult
180°F (82°C)Nearly instantaneous
170°F (77°C)Nearly instantaneous
160°F (71°C)About 1/2 second
150°F (66°C)About 1-1/2 seconds
140°F (60°C)Less than 5 seconds
130°F (54°C)About 30 seconds
120°F (49°C)More than 5 minutes
Valves for reducing point-of-use temperature by mixing cold and
hot water are available. Also available are inexpensive devices
that attach to faucets to limit hot water temperatures. Contact a
licensed plumber or the local plumbing authority.
The water temperature is controlled by a thermostat, fig. 2, which
has two sensing elements. One sensor is located near the top of
the tank and the other is near the center. The thermostat is set in
the lowest position before the heater leaves the factory.
Some states or
Skin
suggested the dial be placed on the lowest setting which
produces an acceptable hot water supply. This will always
give the most energy efficient operation. The temperature
control has a 4F° fixed differential.
CHECKING VENTING
The following steps should be followed with each appliance
connected to the venting system placed in operation, while any
other appliances connected to the venting system are not in
operation.
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal
pitch, as required in the National Fuel Gas Code, ANSI Z223.1
and these instructions. Determine that there is no blockage
or restriction, leakage, corrosion and other deficiencies which
could cause an unsafe condition.
3. So far as is practical, close all building doors and windows
and all doors between the space in which the water heater(s)
connected to the venting system are located and other
spaces of the building. Turn on all appliances not connected
to the venting system. Turn on all exhaust fans, such as
range hoods and bathroom exhausts, so they operate at
maximum speed. Close fireplace dampers.
4. Follow the lighting instruction. Place the water heater being
inspected in operation. Adjust thermostat so appliance
operates continuously.
5. Test for spillage at the burner level after 5 minutes of main
burner operation.
6. After it has been determined that each BCG3 connected to the
venting system properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace dampers and
any other gas burning appliance to their previous conditions
of use.
7. If improper venting is observed during any of the above tests,
the venting system must be corrected.
WARNING
FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR
CONTAMINATION AND UNSAFE CONDITIONS.
• If the back draft cannot be corrected by the normal method or
if a suitable draft cannot be obtained, a blower type flue gas
exhauster must be employed to assure proper venting and
correct combustion.
PREVENTIVE MAINTENANCE
CHECK THE IGNITOR ASSEMBLY
At least once a year, check the ignitor assembly, Fig. 11, and the
main burner, Fig. 12, for proper operation. Refer to the following
ignitor assembly and main burner sections.
IGNITOR ASSEMBLY
The thermostat temperature dial, fig. 2, is accessible by
removing the control cover. The dial is adjustable and may be
set for 120
1200F (49°C) is the recommended starting point. It is
0
(49°C) to 1800F (82°C) water temperature, but
For access to ignitor assembly, unfasten two screws to burner
cover and remove. Locate the burner with the ignitor assembly
and remove screw holding burner to manifold. Slide burner out
to access ignitor assembly.
26
Page 27
Servicing of the ignitor assembly includes keeping the ignitor
free of lint, scale or any other foreign debris.
FIGURE 13
CHECKING THE INPUT
FIGURE 11, IGNITOR
MAIN BURNER
The main burner, fig.12, should display the following
characteristics:
• Cause rapid ignition and carry across entire burner.
• Give reasonably quiet operation during ignition, burning, and
extinction.
• Cause no excessive lifting of flame from burner ports.
FIGURE 12
If the preceding burner characteristics are not evident, check for
accumulation of lint, scale or other foreign debris that restricts or
blocks the air openings to the burner or heater.
NOTE:
1. Remove main burners from unit.
2. Check that burner venturi and ports are free of foreign debris.
3. Clean burners with bristle brush and/or vacuum cleaner - DO
NOT distort burner ports or pilot location.
4. Reinstall burners in unit. Make sure front and rear of burners
are installed correctly in burner support brackets.
5. Check flame inserts. Make sure there is no bending or cracking
and that they are free from lint, scale or any foreign material.
Also check for good flow of combustion and ventilating air to the
unit. Maintain a clear area around the heater at all times.
GAS VALVES
Figure 13 shows the type of combination manual gas control valve
and regulator used on these heaters.
If the gas valve becomes defective, repairs should not be
attempted. A new valve should be installed in place of the defective
one.
For appliance installation locations with elevations above 2000
feet, refer to HIGH ALTITUDE INSTALLATIONS section of this
manual for input reduction procedure.
1. Attach a pressure gauge or a manometer to the manifold
pressure tap on the gas valve and refer to Table 3, for correct
manifold pressure.
2. Use this formula to “clock” the meter. Be sure that other gas
consuming appliances are not operating during this interval.
3600 X H = Btuh
T
T = Time in seconds to burn one cubic foot of gas.
H = Btu’s per cubic foot of gas.
Btuh = Actual heater input.
Example: (Using BTN-250 heater)
T = 15.1 seconds
H = 1050 Btu
Btuh = ?
36.8 X 1050 = 250,000 Btuh (Compare with the 100T2506NOX model and rating.)
Should it be necessary to adjust the gas pressure to the burners
to obtain the full input rate, the steps below should be followed:
3. Remove the regulator adjustment sealing cap, fig. 13, and
adjust the pressure by turning the adjusting screw with a
screwdriver.
Clockwise to increase gas pressure and input rate.
Counterclockwise to decrease gas pressure and input
rate.
4. “Clock” the meter as in step 2 above.
5. Repeat steps 3 and 4 until the specified input rate is achieved.
6. Turn the gas control knob to PILOT. Remove the pressure
gauge and replace the sealing cap and the allen wrench set
screw in the pressure tap opening.
WARNING
UNDER NO CIRCUMSTANCES SHOULD THE GAS INPUT
EXCEED THE INPUT SHOWN ON THE HEATER MODEL AND
RATING PLATE. OVERFIRING COULD RESULT IN DAMAGE OR
SOOTING OF THE HEATER.
27
Page 28
When the heater is operating at full capacity, or full gas input, it
should consume 1 cu. ft. of gas in time indicated on Table 9.
VENTING SYSTEM
Examine the venting system every six months for obstructions
and/or deterioration of the vent piping.
Remove all soot or other obstructions from chimney which will
retard free draft.
problem persists, chlorination of the heater and replacement of
the factory installed magnesium anodes with aluminum anodes
may correct the condition.
Occasionally water softener companies recommend removal of
heater anodes for odor reasons.
CAUTION
Unauthorized removal of the anode(s) will void the warranty. For
further information contact your dealer.
REMOTE STORAGE TANK
TEMPERATURE CONTROL
The water temperature in the remote storage tank (if used) is
controlled by the storage tank temperature control. The sensing
element is mounted in the hot water storage tank, see page 13.
A change in water temperature in the storage tank lower than the
tank temperature control setting will cause the sensor to activate
the circulating pump. The pump then circulates the water through
the heater where the thermostat senses the drop in water
temperature and activates main burner operation of the appliance.
If the storage tank temperature control is out of calibration, replace
with new control.
WARNING
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL
TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE
TO THE APPLIANCE.
RELIEF VALVE
At least once a year, the temperature and pressure relief valve
should be checked to ensure that it is in operating condition. Lift
the lever at the top of the valve several times until the valve seats
properly and operates freely.
If the appliance installation includes other relief valves, such as
in “remote” storage tanks etc., check their relief valve operation
with the same frequency.
ANODE ROD INSPECTION
The heater tank is equipped with anode rods to provide corrosion
control. At least once a year the anode rods should be checked
to determine if replacement is necessary. Initially the anode
rods are approximately 7/8" in diameter with a 1/8" diameter
steel core wire running down the center of the anode material.
THE ANODES SHOULD BE REPLACED when the 1/8" diameter
core wire is visible as this means that the anode material has
been expended in the control of corrosion.
For models with top inlet and outlet, it is recommended that,
before removing the inner cover for cleaning, inspection or
removal of inner parts, you obtain two new nipple collars, part
no. 74060. The nipple collars on the heater will usually be
damaged when removed. New pipe collars will insure that the
seal is such as to prevent leakage of flue products when properly
installed.
NOTE:Anode rod inspection may need to be made more
frequently in areas subject to acid rain that obtains their water
supply from surface water as the low pH will accelerate anode
consumption.
CAUTION:Close cold water inlet valve serving heater and open
nearby hot water faucet to relieve the pressure in the heater before
attempting to remove anode(s) for inspection.
FLUSHING
1. Turn off the heater electrical disconnect switch.
WARNING
THE WATER PASSING OUT OF THE VALVE DURING THIS
CHECKING OPERATION MAY BE EXTREMELY HOT. AVOID
CONTACT AND DISCHARGE SAFELY TO PREVENT WATER
DAMAGE.
If the temperature and pressure relief valve on the heater
discharges periodically or continuously, a problem exists. This
may be due to unusually high water temperatures or pressures
in the system, or to a faulty relief valve. Contact your dealer or a
qualified service technician to find the cause of the problem and
to correct it. This may also be due to thermal expansion in a
closed water supply system. Contact the water supplier or local
plumbing inspector on how to correct this situation.
PLUG THE TEMPERATURE AND PRESSURE RELIEF VALVE.
DO NOT
WARNING
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL
TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE
TO THE APPLIANCE.
HOT WATER ODOR
On occasion, hot water may develop a strong odor. If this occurs
drain the heater completely, flush thoroughly, and refill. If the
2. Open the drain valve and allow water to flow until it runs clean.
3. Close the drain valve when finished flushing.
4. Turn on the heater electrical disconnect switch.
DRAINING
The heater must be drained if it is to be shut down and exposed
to freezing temperatures. Maintenance and service procedures
may also require draining the heater.
1. Turn off the heater electrical disconnect switch.
2. Close the cold water inlet valve to heater.
3. Open a nearby hot water faucet to vent the system.
4. Open the heater drain valve.
5. If the heater is being drained for an extended shutdown, it is
suggested the drain valve be left open during this period.
• Follow FILLING instructions when restoring hot water
service.
28
Page 29
RECOMMENDED PROCEDURE FOR
PERIODIC REMOVAL OF LIME DEPOSITS
FROM TANK TYPE COMMERCIAL WATER
HEATERS
The amount of calcium carbonate (lime) released from water is in
direct proportion to water temperature and usage, see chart. The
higher the water temperature or water usage, the more lime
deposits are dropped out of the water. This is the lime scale
which forms in pipes, heaters and on cooking utensils.
Lime accumulation not only reduces the life of the equipment but
also reduces efficiency of the heater and increases fuel
consumption.
1. Once a month the heater should be flushed. Open the drain
valve and allow two gallons of water to drain from the heater.
Inlet water valve should remain open to maintain pressure in tank.
2. A cleanout opening is provided for periodic cleaning of the
tank. Gas must be shut off and heater drained before opening
cleanout.
To clean heater through cleanout opening, proceed as follows:
1. Drain heater.
2. Remove outer cover plate from lower side of heater jacket.
3. Remove six (6) hex head screws securing tank cleanout plate
and remove plate.
The usage of water softening equipment greatly reduces the
hardness of the water. However, this equipment does not always
remove all of the hardness (lime). For this reason it is
recommended that a regular schedule for deliming be
maintained.
The time between cleaning will vary from weeks to months
depending upon water conditions and usage.
4. Remove lime, scale, or sediment using care not to damage
the glass lining.
5. Inspect cleanout plate gasket.
6. Install cleanout plate. Be sure to draw plate up tight by
tightening screws securely.
7. Replace outer jacket cover plate.
In some water areas the sediment might not be removed by this
method and may result in the water heater making rumbling or
boiling noises.
FIGURE 14
Hydrochloric base acids are not recommended for use on glass
lined tanks.
CAUTION
Observe handling instructions on label of product being used.
TANK CLEANOUT PROCEDURE
The following practices will ensure longer life and enable the unit
to operate at its designed efficiency:
FIGURE 15
IGNITION MODULE SYSTEM
Before calling your service agent, the following checklist should
be examined to eliminate obvious problems from those requiring
replacement or servicing.
— Check that “main manual gas shutoff valve” is fully open and
that gas service has not been interrupted.
— Check that after following the appliance OPERATING
INSTRUCTIONS, the “Top Knob” of the appliance gas valve is
in “ON” position.
— Check electrical supply to the appliance for possible blown
(or tripped) fusing or power interruption.
— Is the water temperature in tank below the thermostat dial
setting on the appliance thermostat (calling for heat)?
29
Page 30
— It is possible that the high limit (E.C.O.) has functioned to
shut off the appliance. See FEATURES — Water Temperature
Control for reset procedure. Contact your serviceman if limit
continues to function to shut off appliance.
Use this diagnostic system in conjunction with the
“OPERATIONAL CHECKLIST” and the “SEQUENCE OF
OPERATION” to troubleshoot the appliance.
SYSTEM DIAGNOSTICS
Your water heater is equipped with an ignition module that
incorporates a diagnostic system to assist in troubleshooting
the appliance. The indicator codes on the ignition module are
as follows:
1 flashSystem lockout (retries or cycles exceeded)
2 flashesPressure switch stuck close
3 flashesPressure switch stuck open
4 flashesOpen on high temperature limit switch (eco)
6 flashes115 volt AC power reversed (check polarity)
7 flashesLow flame sense signal (make sure flame
sensor is in burner flame)
8 flashesCheck ignitor
TABLE 11.
continuous flash -> continuous flame sensed > 5 seconds
without gas valve
continuous on -> internal control failure - replace ignition control
module.
SERVICE
The installer may be able to observe and correct certain
problems which may arise when the unit is put into operation.
HOWEVER, it is recommended that only qualified
servicemen, using appropriate test equipment, be allowed
to service the heater.
As preliminary step, check wiring against diagram, check for
grounded, broken or loose wires. Check all wire ends to be sure
that they are making good contact.
ELECTRICAL SERVICING
CAUTION
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN
SERVICING CONTROLS. WIRING ERRORS CAN CAUSE
IMPROPER AND DANGEROUS OPERATION.
VERIFY PROPER OPERATION AFTER SERVICING.
30
Page 31
SEQUENCE OF OPERATION FLOW CHART
Description of this flow chart can be found in the “SEQUENCE OF OPERATION” section.
Ignition
Switch power on
to unit.
Thermostat calls
for heat.
Control Board
opens Gas
Valve.
Ignition Control
Board shuts off
Silicon Nitride
Ignitor after
3 seconds
Ignition Control
Board performs
diagnostic check on
components
Ignition Control
Board sends power
to Exhaust Inducer
Exhaust Inducer
engages Prover
Switch
Ignition Control
Board provides
power to Silcon
Nitride Ignitor
Ignition Control
Board waits 3 more
seconds to
monitor Flame
Sensor.
Did Main
Burner Light?
YES
Ignition Control
Board monitors
units until T’Stat
is satisfied.
NO
Ignition Control
Board shuts off Gas
Valve and allows the
Exhaust Inducer to
purge appliance for
20 seconds.
Silicon Nitride
Ignitor
warms up for
20 seconds
31
Page 32
OPERATIONAL CHECKLIST
This checklist in conjunction with “TROUBLESHOOTING” and the “SEQUENCE OF OPERATION” should be used as an on-the-job
troubleshooting guide to identify the cause of incorrect system operation and suggest a remedy for its correction. Because improper
piping and wiring can result in unsatisfactory system performance, it is suggested that the installation be examined before using the
checklist. Be sure to refer to the correct piping and wiring diagram for the type of system that is installed.
The system should be filled with water, purged of air, valves properly set and utilities connected and ready to operate.
REMEDY
COMPLAINT CAUSE USER SERVICEMAN
*Water not hot enough.Thermostat set too low.Set thermostat dial to a higher
Thermostat out of calibration. Call service agentRecalibrate thermostat. If thermostat cannot
*Insufficient hot waterThermostat set too low.Set thermostat dial to a higher
*See WATER TEMPERATUREtemperature.
CONTROL WARNING (on
Page 5).Thermostat out of calibration. Call service agent.Recalibrate thermostat. If thermostat cannot
Main manual gas shutoffOpen main manual gas shutoff
valve partially closed.valve to fullest extent.
Heater too small for demand. Space usage to give heater time
Thermostat differential isCall service agent.Replace dual bulb controller if differential is
too wide.greater than 4°F.
Heater recovery is slower.Call service agent.Check gas input. If incorrect, adjust gas
Drafthood not installed orCall service agent.Install drafthood or baffles as furnished
one or more flue baffles.with unit.
Water temperature too hot.Thermostat set too high.Set thermostat to a lower setting.
Heater makes sounds: sizzling. Condensation on outside
of tank, normal.
Rumbling.Sediment accumulation onDrain a quantity of water throughDelime heater.
bottom of tank.drain valve. If rumbling persists,
temperature.
be recalibrated, replace.
be recalibrated, replace.
to restore water temperature.
pressure or replace main burner orifice.
call a service agent.
Ticking or metallic sounds.Expansion and contraction-
Pounding.Air chambers in piping haveDrain piping system and refill.
Combustion noises.Too much primary air.Adjust shutters.
Water leaks.Drain valve not closedIf drain valve cannot be closed
Gas odors.Heater is overfired.Shut off gas supply to heaterCheck for sooted flue passage.
normal.
become waterlogged.Heater must be off while this is
being done.
Overfired heater; IncorrectCall service agent.Check and correct as necessary.
burners or orifice for type
of gas used.
tightly.tightly, replace.
If leakage source cannotShut off gas supply to heaterRepair or in case of suspected tank leakage,
be corrected or identified,and close cold water inlet valvebe certain to confirm before replacing heater.
call serviceman.to heater.
and call a service agent.
Check for obstructed vent line.
Check backdraft or lack of draft.
Possible gas leaks.Shut off gas supply to heater and
call gas company at once.
32
Page 33
Limited Warranty
American Water Heater, the warrantor, extends the following LIMITED WARRANTY to the owner of this water heater.
1. THE TANK
If the glass-lined tank in this water heater shall prove upon examination by the warrantor to have leaked due to natural corrosion from potable
water therein, during the first THREE years after initial installation, the warrantor will supply a complete new American Water Heater of equivalent
size and current model. Some government agencies are requiring energy efficient standards for water heaters. In the event regulations prohibit
sale of a model of equivalent size and construction, American Water Heater will provide a model which complies with the regulations of your area,
in which case the consumer will be charged the difference in price between the like replacement and the energy efficient model required. The
warranty on the replacement water heater will be limited to the unexpired term of the original warranty.
2.ALL OTHER PARTS
If within ONE year after initial installation of this water heater, any part or portion shall prove upon examination by the warrantor to be defective in
material or workmanship, the warrantor will repair or replace such part or portion at its option.
3. CONDITIONS AND EXCEPTIONS
This warranty shall apply only when the water heater is installed in accordance with local plumbing and building codes, ordinances and regula-
tions, the printed instructions provided with it and good industry practices. In addition, a temperature and pressure relief valve, certified by
A.G.A./CGA and approved by the American Society of Mechanical Engineers, must have been installed.
a. This warranty shall apply only when the heater is:
(1) used at temperatures not exceeding the maximum calibrated setting of its thermostat;
(2) used at water pressure not exceeding the working pressure shown on the heater;
(3) filled with potable water, free to circulate at all times and with the tank free of damaging water sediment or scale deposits;
(4) used in a non-corrosive and non-contaminated atmosphere;
(5) used with factory approved anode(s) installed;
(6) in its original installation location;
(7) in the United States, its territories or possessions, and Canada;
(8) sized in accordance with proper sizing techniques for commercial and/or residential water heaters;
(9) bearing a rating plate which has not been altered, defaced or removed, except as required by the warrantor;
(10) used in an open system or in a closed system with properly sized and installed thermal expansion tank;
(11) operated with properly installed dirt leg;
(12) fired with the fuel for which it was factory built;
(13) fired at the factory rated input;
(14) operated with the inner and outer combustion chamber doors in place.
b. Any accident to the water heater, any misuse, abuse (including freezing) or alteration of it, any operation of it in a modified form, any use
of insulation blankets, or any attempt to repair tank leaks will void this warranty.
c. This warranty is void if a device acting as a backflow prevention device (check valves etc.) is installed in the cold water supply the heater
is connected to, unless an effective method of controlling thermal expansion is also installed at the heater(s) and operational at all times.
The relief valve installed on the heater is not an acceptable method.
4.SERVICE AND REPAIR EXPENSES
Under the limited warranty the warrantor will provide only a replacement water heater or part thereof. The owner is responsible for all other costs.
Such costs may include but are not limited to:
a. Labor charges for service removal, repair or reinstallation of the water heater or any component part;
b. Shipping, delivery, handling, and administrative charges for forwarding the new heater or replacement part from the nearest distributor and
returning the claimed defective heater or part to such distributor.
c.All cost necessary or incidental for any material and/or permits required for installation of the replacement heater or part.
5. LIMITATIONS ON IMPLIED WARRANTIES
Implied warranties, including the warranty of merchantability imposed on the sale of this heater under state law are limited to one (1) year
duration for the heater or any of its parts. Some states do not allow limitation on how long an implied warranty lasts, so the above limitation may
not apply to you.
6.CLAIM PROCEDURE
Any claim under the warranty should be initiated with the dealer who sold the heater, or with any other dealer handling the warrantor’s products.
If this is not practicable, the owner should contact:
a. The warrantor will only honor replacement with identical or similar water heater or parts thereof which are manufactured or distributed by
the warrantor.
b. Dealer replacements are made subject to in-warranty validation by warrantor.
7. DISCLAIMERS
NO OTHER EXPRESS WARRANTY HAS BEEN OR WILL BE MADE IN BEHALF OF THE WARRANTOR WITH RESPECT TO THE MERCHANTABILITY
OF THE HEATER OR THE INSTALLATION, OPERATION, REPAIR OR REPLACEMENT OF THE HEATER. THE WARRANTOR SHALL NOT BE
RESPONSIBLE FOR WATER DAMAGE, LOSS OF USE OF THE UNIT, INCONVENIENCE, LOSS OR DAMAGE TO PERSONAL PROPERTY OR
OTHER CONSEQUENTIAL DAMAGE. THE WARRANTOR SHALL NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR
DAMAGE TO ANY PERSONS OR PROPERTY, WHETHER DIRECT OR INDIRECT, AND WHETHER ARISING IN CONTRACT OR IN TORT.
a. Some states do not allow the exclusion or limitation of the incidental or consequential damage, so the above limitations or
exclusions may not apply to you.
b. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Fill in the following for your own reference. Keep it. Registration is not a condition of warranty. The model and serial number are found on the heater’s
rating plate.
Model No. ___________________________ Serial No. _______________________________________ Date Installed ___________________
Dealer’s Name _______________________________________________________________________________________________________