Controller
In Use Indicator
Indicates that hot water
is being supplied.
Priority Indicator
Indicates that this
controller is setting the
Temperature Display
Indicates temperature
setting or flashes error
code.
Thermostat
water temperature.
Priority Button
When no water is
being supplied,
pressing this button
allows this controller to
set the water
temperature.
ON/OFF Button
Diagnostic Use of the Controller
1. To display error codes, press the ON/OFF button followed by
the thermostat button to cycle through the error codes.
2. To display the water flow through the water heater, press the
thermostat button (hold for 2 seconds) and then press the
ON/OFF button while continuing to hold the thermostat
button.
3. To display the outlet water temperature, press the thermostat
button (hold for 2 seconds) and then press the ON/OFF button
while continuing to hold the thermostat button.
To Change the Temperature Scale (ºF / ºC)
With the water heater turned off, press and hold the ON/OFF
button until the display changes to the other temperature scale
(about 5 seconds).
To Turn Off the Controller Sound (Mute)
To turn the sound off (mute), press and hold both the and
thermostat buttons until a “beep” is heard (about 5 seconds).
Gas Pressure Setting
NOTE: For additional installation and commissioning information refer
to the Operation and Installation Manual.
WARNING
This appliance must be installed, serviced and removed by a trained
and qualified person. During pressure testing of the consumer piping,
ensure gas valve is turned off before unit is shut off. Failure to do so
may result in serious injury to yourself or damage to the unit.
APPLIANCE OPERATING PRESSURES
Gas Inlet
Min./Max
NAT.G
5"W.C.
/10.5"W.C.
705(Indoor)
705(Indoor-ASME)
Water
Inlet Max.
Commissioning
With all gas appliances in operation at maximum gas rate, the
flowing inlet pressure at the incoming test point on the Rinnai
water heater should read 5" W.C. - 10.5" W.C. on natural gas
and 8" W.C. - 13.5" W.C. on propane gas. If the pressure is
lower, the gas supply is inadequate and the unit will not operate
to specification. Check the gas meter regulator and pipework for
correct operation/sizing and correct as required.
Table 1
Forced Low Forced High
LPG NAT.G LPG NAT.G LPG
8"W.C.
/13.5"W.C.
.C.W"7.3.C.W"0.3.C.W"38.0.C.W"76.0ISP 051
Troubleshooting
Important Safety Notes
There are a number of (live) tests that are required when fault
finding this product. Extreme care should be used at all times to
avoid contact with energized components inside the water heater.
Only trained and qualified service technicians should attempt to
repair this product. Before checking for resistance readings,
disconnect the power source to the unit and isolate the item from
the circuit (unplug it).
(SV1, SV2, SV3 and POV) Gas valve and Modulating solenoids: (Set meter above 2K)
Wire color Voltage Resistance Connector # Pin #'s
(Main) Pink - Black
(SV1) Black - Red 11 ~ 13 VDC 37 ~ 43 ohms H4 5 - 6
(SV2) Black - Orange 11 ~ 13 VDC 37 ~ 43 ohms H5 4 - 6
(SV3) Black - Yellow 11 ~ 13 VDC 37 ~ 43 ohms H6 3 - 6
(POV) Orange - Orange
(M) Water Flow Control Device Servo or Geared Motor:
Red - Blue 11 ~ 13 VDC 22 ~ 28 ohms F5 9 - 10
Grey - Brown 4 ~ 6 VDC N / A F5 5 - 7
Grey - Yellow N / A N / A F5 5 - 8
NOTE: The grey wire listed above turns to black at F connector on the PCB.
(QS) Water Flow Sensor:
Black - Red 11 ~ 13 VDC 5.5 ~ 6.2 K ohms F2 1 - 3
Yellow - Black 4 ~ 7 VDC 1 ~ 1.4 Mega ohms F2 2 - 3
By-pass Flow Control:
Orange - White 2 ~ 6 VDC
Yellow - White
(IG) Ignition System:
Grey - Grey 90 ~ 110 VAC N / A C1 1 - 2
(FM) Combustion Fan Motor:
Red - Black 6 ~ 45 VDC N / A E1 1 - 2
White - Black 5 ~ 10 VDC 9.2 ~ 9.4 K ohms E1 2 - 4
Yellow - Black 11 ~ 13 VDC 3.5 ~ 3.9 K ohms E1 2 - 3
Set your meter to the hertz scale. Reading across the white and black wires at terminals 2 and 4
you should read between 60 and 420 hertz.
Thermal Fuse / Overheat Switch:
Red - White 11 ~ 13 VDC Below 1 ohms
11 ~ 13 VDC 24 ~ 28 ohms H3 6 - 7
2 ~ 15 VDC 67 ~ 81 ohms H2 9 - 10
5 - 11GetihW - nworB
(Unit in operating mode)
15 ~ 35 ohms
G1 2 - 5
G1 3 - 5
5 - 41GdnuorG - etihW-deR
F6
H1
F6 - H12
Flame Rod:
Place one lead of your meter to the flame rod and the other to ground.
With the unit running you should read between 5-150 VAC. Set your
meter to the µ amp scale and series your meter in line with the flame
rod. You should read 1 µ amp or greater for proper flame circuit. In
the event of low flame circuit remove the flame rod and check for
carbon or damage.
Dip Switches Settings
Adjust switches 2 and 3 in the bank of 8 depending on
your altitude according to the table below.
The original PC boards on the water heaters do not
have the bank of 6 dip switches. Only spare PC
boards have this bank.
WARNING
High Altitude
DO NOT adjust the other dip switches unless specifically instructed
to do so. Incorrect Dip Switch Settings can cause the water heater
to operate in an unsafe condition and may damage the water heater
and void the warranty.
Gas Pressure Setting
Ensure gas pressure check under Commissioning has been
completed first! The regulator is electronically controlled and
factory pre-set. Under normal circumstances it does not require
adjustment during installation. Make adjustments only if the unit is
not operating correctly and all other possible causes for incorrect
operation have been eliminated.
1. Turn OFF the gas supply.
2. Turn OFF the 120 V power supply.
3. Remove the front panel from the appliance.
4. Check the gas type using the data plate on the side of the unit.
If using a spare PC board, check that the gas type switches are
in the correct position (dip switch 1 of SW2: ON for natural gas,
NG, and OFF for propane, LPG). See dip switch settings
section below. (ON is towards the right and OFF is towards the
left.)
5. Attach the pressure gauge to the burner test point, located on
the gas control (Fig. 2).
6. Turn ON the gas supply.
7. Turn ON the 120 V power supply.
8. If a controller is installed, turn the unit ON with the controller.
Select the maximum delivery temperature and open all
available hot water taps at full.
9. Set the unit to ‘Forced Low’ combustion by setting No. 7 dip
switch of the SW1 set to ON (Fig. 3).
10. Check the burner test point pressure.
11. Remove the rubber access plug and adjust the regulator screw
on the modulating valve (Fig. 4) as required in Table 1.
Replace the rubber access plug.
12. Set the unit to ‘Forced High’ combustion by setting both No. 7
and No. 8 dip switches of the SW1 set to ON (Fig. 5). Ensure
maximum water flow.
13. Check the burner test point pressure.
14. Adjust the high pressure potentiometer (POT) on the PC board
as required to the pressure shown in Table 1.
15. Return the unit to normal operation by setting dip switches 7
and 8 of the SW1 set back to OFF (Fig. 6). Close all water
taps.
16. Turn OFF the gas supply and 120 V power supply.
17. Remove the pressure gauge and install sealing screw.
18. Turn ON the gas supply and 120 V power supply.
19. Operate the unit and check for gas leaks at the test point.
20. Install the front panel.
High Pressure
Potentiometer
Burner
SW1
SW2
Spare Parts
Only
1
test point
Fig. 1 Fig. 2
Regulator adjustment
screw access plug
Fig. 3 Fig. 4
Fig. 5 Fig. 6
Heat Exchanger and Outgoing Water Temperature
Thermistors:
Check all thermistors by inserting meter leads into each end of the
thermistor plug. Set your meter to the 20 K scale and read
resistance. Applying heat to the thermistor bulb should decrease
the resistance. Applying ice to the thermistor bulb should increase
the resistance. See below for examples of typical temperatures and
resistance readings.
Example:
59°F = 11.4 ~ 14K
86°F = 6.4 ~ 7.8K
113°F = 3.6 ~ 4.5K
Outgoing Water Thermistor:
White - White N / A See example above F4 3 - 4
Heat Exchanger Temperature Thermistor:
Pink - White N / A See example above F3 3 - 11
Surge Protector:
Black - White 108 ~ 132 VAC N / A D2 1 - 3
Black - White 108 ~ 132 VAC N / A D1 1 - 3
140°F = 2.2 ~ 2.7K
221°F = 0.6 ~ 0.8K
With the power off you can check the continuity through the surge
protector. Place a meter lead on the top pin #1 of the surge
protector and pin #3 on the bottom of the surge protector. Check
across the top pin #3 and bottom pin #1. If you read continuity
across these two points then the surge protector is good. If you do
not get continuity then replace the surge protector.
Remote Controls:
Te rminals B1 10 ~ 13 VDC 1.5 ~ 3.0 K ohms B 1 - 3
Frost Protection:
This unit has frost protection heaters mounted at different points to
protect the water heater from freezing. The heaters located on the
hot water outlet line should have a resistance reading of 180-207
ohms through each of these heaters. The heater located on the
heat exchanger piping should have a resistance reading of 156-180
ohms and the one located in the water flow sensor valve should
have a resistance reading 24-28 ohms.
Amp Fuses:
This unit has one inline (3) amp glass fuses. Remove the fuse and
check continuity through it. If you have continuity through the fuse
then it is good. Otherwise the fuse is blown and must be replaced.
705(Indoor)
705(Indoor-ASME)
NAT.GLPG
ON
1
O
2
F
3
F
4
5
6
7
8
ON
11
O
2
F
3
F
4
5
6
ON
1
O
2
F
3
F
4
5
6
7
8
ON
O
2
F
3
F
4
5
6
Error Codes
No burner operation during freeze protection mode
02
• Service Call
Power interruption during Bath fill (Water will not flow when
03
power returns)
• Turn off all hot water taps. Press ON/OFF twice.
Air Supply or Exhaust Blockage
10
• Ensure approved venting materials are being used.
• Check that nothing is blocking the flue inlet or exhaust.
• Check all vent components for proper connections.
• Ensure vent length is within limits.
• Ensure condensation collar was installed correctly.
• Verify dip switches are set properly.
• Check fan for blockage.
No Ignition
11
• Check that the gas is turned on at the water heater, gas meter,
or cylinder.
• Ensure gas type and pressure is correct.
• Ensure gas line, meter, and/or regulator is sized properly.
• Bleed all air from gas lines.
• Verify dip switches are set properly.
• Ensure appliance is properly grounded.
• Disconnect multi-unit connections to isolate the problem.
• Ensure igniter is operational.
• Check igniter wiring harness for damage.
• Check gas solenoid valves for open or short circuits.
• Remove burner cover and ensure all burners are properly
seated.
• Remove burner plate and inspect burner surface for
condensation or debris.
Flame Failure
12
• Check that the gas is turned on at the water heater and gas
meter. Check for obstructions in the flue outlet.
• Ensure gas line, meter, and/or regulator is sized properly.
• Ensure gas type and pressure is correct.
• Bleed all air from gas lines.
• Ensure proper venting material was installed.
• Ensure condensation collar was installed properly.
• Ensure vent length is within limits.
• Verify dip switches are set properly.
• Ensure appliance is properly grounded.
• Disconnect keypad.
• Disconnect multi-unit connections to isolate the problem.
• Check power supply for loose connections.
• Check power supply for proper voltage and voltage drops.
• Ensure flame rod wire is connected.
• Check flame rod for carbon build-up.
• Disconnect and re-connect all wiring harnesses on unit and PC
board.
• Check all components for electrical short.
• Check gas solenoid valves for open or short circuits.
• Remove burner plate and inspect burner surface for
condensation or debris.
Thermal Fuse
14
• Check gas type of unit and ensure it matches gas type being
used.
• Check for restrictions in air flow around unit and vent terminal.
• Check for low water flow in a circulating system causing short-
cycling.
• Ensure dip switches are set to the proper position.
• Check for foreign materials in combustion chamber and/or
exhaust piping.
• Check heat exchanger for cracks and/or separations.
• Check heat exchanger surface for hot spots which indicate
blockage due to scale build up. Refer to instructions in manual
for flushing heat exchanger.
• Measure resistance of safety circuit.
• Ensure high fire and low fire manifold pressure is correct.
• Check for improper conversion of product.
Wiring Diagram
BL:Blue
BK:Black
BR:Brown
R :Red
1
2
38765
4
F
F
O
Dip SW1
1
BKRW
3
A
(CN9)
F
YBKR
G
1
F
Y
RR
BK
2
F
Y
BK
QS
WATER FLOW
SENSOR
Y :Yellow
P :Pink
O :Orange
GY:Gray
G :Green
Gas pressure
Spare Parts Only
Gas type
4
123
F
O
Dip SW2
(CN5)
1
WWP
Y
BL BR
R
13
W
W
P
3
4
F
F
W
W
W
HEAT EXCHANGER
WATER THERMISTOR
OUTGOING WATER
2-Unit Connection
(Optional)
1
A
G
BRROYW
Y
ORW
BR
1
G
BY-PASS FLOW
CONTROL DEVICE
W :White
COLOR CODING
MODULATING VALVE
CURRENT ADJUSTING
MIN
MAX
(CN7)
1
5
G
R
FREEZE PROTECTION
(OPTIONAL)
Over Temperature Warning
16
• Check for restrictions in air flow around unit and vent terminal.
• Check for low water flow in a circulating system causing short-
• Check for foreign materials in combustion chamber and/or
• Check for clogged heat exchanger.
Outgoing Water Temperature Sensor Fault
32
• Check sensor wiring for damage.
• Measure resistance of sensor.
• Clean sensor of scale build up.
• Replace sensor.
Heat Exchanger Outgoing Temperature Sensor Fault
33
• Check sensor wiring for damage.
• Measure resistance of sensor.
• Clean sensor of scale build up.
• Replace sensor.
Combustion Air Temperature Sensor Fault
34
• Check for restrictions in air flow around unit and vent terminal.
• Check sensor wiring for damage.
• Measure resistance of sensor.
• Clean sensor of scale build up.
• Ensure fan blade is tight on motor shaft and is in good
• Replace sensor.
Modulating Solenoid Valve Signal Abnormal
52
• Check modulating gas solenoid valve wiring harness for loose
• Measure resistance of valve coil.
Combustion Fan Failure
61
• Ensure fan will turn freely.
• Check wiring harness to motor for damaged and/or loose
• Measure resistance of motor winding.
Water Flow Servo Faulty (does not stop flow properly)
65
If blank screen is present on remote control then the flow control
has shorted out. Unplug flow control. If remote lights up and unit
starts operating then replace flow control assembly.
SV0, SV1, SV2, and SV3 Solenoid Valve Circuit Fault
71
• Check wiring harness to all solenoids for damage and/or loose
• Measure resistance of each solenoid valve coil.
Flame Sensing Device Fault
72
• Ensure flame rod is touching flame when unit fires.
• Check all wiring to flame rod for damage.
• Remove flame rod and check for carbon build-up; clean with
• Check inside burner chamber for any foreign material blocking
• Measure micro amp output of sensor circuit with flame present.
• Replace flame rod.
Scale Build-up in Heat Exchanger (when checking
LC
maintenance code history “00” is substituted for “LC”)
• Flush heat exchanger. Refer to instructions in manual.
• Replace heat exchanger.
No Code (Nothing happens when water flow is activated.)
• Clean inlet water supply filter.
• On new installations ensure hot and cold water lines are not
• Check for bleed over. Isolate unit from building by turning off
• Ensure you have at least the minimum flow rate required to fire
• Ensure turbine spins freely.
• Measure the resistance of the water flow control sensor.
• Remote control does not light up but you have 12 VDC at the
FROST SENSING
SWITCH
W
W
BL BL
3
D
REMOTE CONTROLLER
1
B
BK
BK
5
6
3
B
H
(CN2)
12 1
41
Y
BLRBR
GY
R
BL
BRYGY
R
Y
(CN12)
WATER FLOW
1
(CN1)
YY
OBKO
RP
O
W
BK
W
RBKY
W
FM
1
E
COMBUSTION FAN
CONTROL DEVICE
F
E
W
W
5
F
WATER THERMISTOR
cycling.
exhaust piping.
condition.
or damage terminals.
connections.
connections.
sand paper.
flame at flame rod.
reversed.
hot water line to building. Isolate the circulating system if
present. Open your pressure relief valve; if unit fires, there is
bleed over in your plumbing.
unit.
terminals for controls.
ANTI-FROST
HEATER
W
W
W
W
W
W
5
4
D
SPARK
C
6
D
D
W
W
W
W
W
W
W
ELECTRODE
FUSE
GND
IG
GY
GY
IGNITER
1
C
GY
GY
1
(CN4)
O
O
2
H
W
1
H
W
MODULATING
RR
OVERHEAT
SWITCH
POV
SOLENOID VALVE
R
6
F
R
THERMAL FUSES
GROUND
AC120VAC120V
NEUTRAL
NEUTRAL
HOT
HOT
(3A)
BK
W
2
D
1
WBK
1
D
(CN3)
P
BK
3
H
SV0
MAIN SOLENOID VALVE
1
D
SURGE
PROTECTOR
G/Y
WBK
1
BK
W
3
G/Y
Y
FLAME ROD
O
R
BK
4
5
H
H
SV1
SV2
SOLENOID VALVE 1
(CENTER)
SOLENOID VALVE 2
GND
GND
7
H
Y
BK
BK
6
H
SV3
(LEFT)
SOLENOID VALVE 3
(RIGHT)
SW
No.
2
3
High Altitude
Off
Off
Level 0
0-2000 ft
(0-610 m)
Off
On
NOTES
Level 1
2001-5200 ft
(610-1585 m)
On
5201-7700 ft
Off
(1585-2347 m)
Level 2
On
7701-10200 ft
On
(2347-3109 m)
Level 3
705 Indoor
070 00012 36676 0
U273-1373(01)