American Water Heater 505, 305 User Manual

Controller
In Use Indicator
Indicates that hot water is being supplied.
Priority Indicator
Indicates that this controller is setting the
Temperature Display
Indicates temperature setting or flashes error code.
Thermostat
Diagnostic Use of the Controller
1. To display error codes, press the ON/OFF button followed by the thermostat button to cycle through the error codes.
2. To display the water flow through the water heater, press the thermostat button (hold for 2 seconds) and then press the ON/OFF button while continuing to hold the thermostat button.
3. To display the outlet water temperature, press the thermostat button (hold for 2 seconds) and then press the ON/OFF button while continuing to hold the thermostat button.
water temperature.
Priority Button
When no water is being supplied, pressing this button allows this controller to set the water temperature.
ON/OFF Button
Ensure gas pressure check under Commissioning has been completed first! The regulator is electronically controlled and factory pre-set. Under normal circumstances it does not require adjustment during installation. Make adjustments only if the unit is not operating correctly and all other possible causes for incorrect operation have been eliminated.
1. Turn OFF the gas supply.
2. Turn OFF the 120 V power supply.
3. Remove the front panel from the appliance.
4. Check the gas type using the data plate on the side of the unit.
5. Attach the pressure gauge to the burner test point, located on
6. Turn ON the gas supply.
7. Turn ON the 120 V power supply.
8. If a controller is installed, turn the unit ON with the controller.
9. Set the unit to “Forced Low” combustion by setting No. 7 dip
10. Check the burner test point pressure.
11. Remove the rubber access plug and adjust the regulator screw
12. Set the unit to “Forced High” combustion by setting both No. 7
To Change the Temperature Scale (ºF / ºC)
Gas Pressure Setting
With the water heater turned off, press and hold the ON/OFF button until the display changes to the other temperature scale (about 5 seconds).
To Turn Off the Controller Sound (Mute)
To turn the sound off (mute), press and hold both the and thermostat buttons until a “beep” is heard (about 5 seconds).
13. Check the burner test point pressure.
14. Adjust the high pressure potentiometer (POT) on the PC board
15. Return the unit to normal operation by setting dip switches 7
16. Turn OFF the gas supply and 120 V power supply.
17. Remove the pressure gauge and install sealing screw.
18. Turn ON the gas supply and 120 V power supply.
19. Operate the unit and check for gas leaks at the test point.
20. Install the front panel.
Gas Pressure Setting
NOTE: For additional installation and commissioning information refer to the Operation and Installation Manual.
WARNING
This appliance must be installed, serviced and removed by a trained and qualified person. During pressure testing of the consumer piping, ensure gas valve is turned off before unit is shut off. Failure to do so may result in serious injury to yourself or damage to the unit.
APPLIANCE OPERATING PRESSURES
Gas Inlet Min./Max
NAT.G
5"W.C.
/10.5"W.C.
305
505
Water
Inlet Max.
Commissioning
With all gas appliances in operation at maximum gas rate, the flowing inlet pressure at the incoming test point on the water heater should read 5” W.C. - 10.5” W.C. on natural gas and 8” W.C. - 13.5 W.C. on propane gas. If the pressure is lower, the gas supply is inadequate and the unit will not operate to specification. Check the gas meter regulator and pipework for correct operation/sizing and correct as required.
Troubleshooting
Important Safety Notes
There are a number of (live) tests that are required when fault finding this product. Extreme care should be used at all times to avoid contact with energized components inside the water heater. Only trained and qualified service technicians should attempt to repair this product. Before checking for resistance readings, disconnect the power source to the unit and isolate the item from the circuit (unplug it).
(SV1, SV2, SV3 and POV) Gas valve and Modulating solenoids: (Set meter above 2K)
Wire color Voltage Resistance Connector # Pin #'s (Main) Pink - Black (SV1) Black - Yellow 11 ~ 13 VDC 36.8 ~ 44.8 ohms H6 5 - 6 (SV2) Black - Blue 11 ~ 13 VDC 36.8 ~ 44.8 ohms H7 4 - 6 (SV3) Black - Brown 11 ~ 13 VDC 36.8 ~ 44.8 ohms H8 3 - 6 (POV) Pink - Pink 2 ~ 15 VDC 67 ~ 81 ohms H3 9 - 10
(M) Water Flow Control Device Servo or Geared Motor:
Red - Blue 11 ~ 13 VDC 22 ~ 28 ohms F7 9 - 10 Grey - Brown 4 ~ 6 VDC N / A F7 5 - 7 Grey - Yellow N / A N / A F7 5 - 8
NOTE: The grey wire listed above turns to black at F connector on the PCB. (QS) Water Flow Sensor:
Black - Red 11 ~ 13 VDC 5.5 ~ 6.2 K ohms F2 1 - 3 Yellow - Black 4 ~ 7 VDC 1 ~ 1.4 Mega ohms F2 2 - 3
By-pass Flow Control (By-pass servo model ONLY):
Orange - White 2 ~ 6 VDC Yellow - White
(IG) Ignition System:
Grey - Grey 90 ~ 110 VAC N / A C1 1 - 2
(FM) Combustion Fan Motor:
Red - Black 6 ~ 45 VDC N / A E1 1 - 2 White - Black 5 ~ 10 VDC 9.2 ~ 9.4 K ohms E1 2 - 4 Yellow - Black 11 ~ 13 VDC 3.5 ~ 3.9 K ohms E1 2 - 3
Set your meter to the hertz scale. Reading across the white and black wires at terminals 2 and 4 you should read between 60 and 420 hertz.
Thermal Fuse / Overheat Switch:
Red - Red 11 ~ 13 VDC Below 1 ohms
Flame Rod:
Place one lead of your meter to the flame rod and the other to ground. With the unit running you should read between 5-150 VAC. Set your meter to the µ amp scale and series your meter in line with the flame rod. You should read 1 µ amp or greater for proper flame circuit. In the event of low flame circuit remove the flame rod and check for carbon or damage.
The original PC boards on the water heaters do not have the bank of 6 dip switches. Only spare PC boards have this bank.
Models 305 and 505 have a default maximum temperature of 120°F (49°C) and an option to increase the maximum temperature to 140°F (60°C). Temperature settings from 125-140°F (52-60°C) are available by setting dip switch 6 to ON in the SW1 bank of 8 dip switches.
Adjust switches 2 and 3 in the bank of 8 depending on your altitude according to the table below.
11 ~ 13 VDC 36.8 ~ 44.8 ohms H5 6 - 7
(Unit in operating mode)
Table 1
Forced Low
LPG NAT.G LPG NAT.G LPG
8"W.C.
/13.5"W.C.
15 ~ 35 ohms
G1 2 - 5 G1 3 - 5
F6 H1
2.9"W.C. 4.2"W.C.
.C.W"88.0.C.W"65.0ISP 051
3.3"W.C. 5.1"W.C.
Forced High
Heat Exchanger and Outgoing Water Temperature Thermistors:
Check all thermistors by inserting meter leads into each end of the thermistor plug. Set your meter to the 20 K scale and read resistance. Applying heat to the thermistor bulb should decrease the resistance. Applying ice to the thermistor bulb should increase the resistance. See below for examples of typical temperatures and resistance readings.
Outgoing Water Thermistor:
Heat Exchanger Temperature Thermistor:
Intake Air Thermistor (Indoor model ONLY)
Surge Protector:
With the power off you can check the continuity through the surge protector. Place a meter lead on the top pin #1 of the surge protector and pin #3 on the bottom of the surge protector. Check across the top pin #3 and bottom pin #1. If you read continuity
5 - 11GetihW - nworB
across these two points then the surge protector is good. If you do not get continuity then replace the surge protector.
5 - 41GdnuorG - etihW-deR
Remote Controls:
Frost Protection:
This unit has frost protection heaters mounted at different points to protect the water heater from freezing. The heaters located on the hot water outlet line should have a resistance reading of 180-207 ohms through each of these heaters. The heater located on the heat exchanger piping should have a resistance reading of 156-180 ohms and the one located in the water flow sensor valve should
F6 - H12
have a resistance reading 24-28 ohms.
Amp Fuses:
This unit has one inline (3) amp glass fuses. Remove the fuse and check continuity through it. If you have continuity through the fuse then it is good. Otherwise the fuse is blown and must be replaced.
WARNING
DO NOT adjust the other dip switches unless specifically instructed to do so. Incorrect Dip Switch Settings can cause the water heater to operate in an unsafe condition and may damage the water heater and void the warranty.
If using a spare PC board, check that the gas type switches are in the correct position (dip switch 1 of SW2: ON for natural gas, NG, and OFF for propane, LPG). See dip switch settings section below. (ON is towards the right and OFF is towards the left.)
the gas control (Fig. 2).
Select the maximum delivery temperature and open all available hot water taps at full.
switch of the SW1 set to ON (Fig. 3).
on the modulating valve (Fig. 4) as required in Table 1. Replace the rubber access plug.
and No. 8 dip switches of the SW1 set to ON (Fig. 5). Ensure maximum water flow.
as required to the pressure shown in Table 1.
and 8 of the SW1 set back to OFF (Fig. 6). Close all water taps.
BURNER TEST POINT
High Pressure Potentiometer
SW1
SW2
Spare Parts Only
1
Fig. 1 Fig. 2
Regulator adjustment screw access plug
Fig. 3 Fig. 4
Fig. 5 Fig. 6
Example:
White - White N / A See example above F5 3 - 4
Pink - White N / A See example above F4 3 - 11
Orange - White N / A See example above F3 3 - 12
Black - White 108 ~ 132 VAC N / A D2 1 - 3 Blue - Brown 108 ~ 132 VAC N / A D1 1 - 3
Te rminals B1 10 ~ 13 VDC 1.5 ~ 3.0 K ohms B 1 - 3
59°F = 11.4 ~ 14K 86°F = 6.4 ~ 7.8K 113°F = 3.6 ~ 4.5K
505
140°F = 2.2 ~ 2.7K 221°F = 0.6 ~ 0.8K
305
Error Codes
No burner operation during freeze protection mode
02
Service Call
Power interruption during Bath fill (Water will not flow when
03
power returns)
Turn off all hot water taps. Press ON/OFF twice.
Air Supply or Exhaust Blockage
10
Ensure approved venting materials are being used.
Check that nothing is blocking the flue inlet or exhaust.
Check all vent components for proper connections.
Ensure condensation collar was installed correctly.
Verify dip switches are set properly.
Check fan for blockage.
No Ignition
11
Check that the gas is turned on at the water heater, gas meter,
or cylinder.
Ensure gas type and pressure is correct.
Ensure gas line, meter, and/or regulator is sized properly.
Bleed all air from gas lines.
Verify dip switches are set properly.
Ensure appliance is properly grounded.
Disconnect EZConnect or MSA controls to isolate the problem.
Ensure igniter is operational.
Check igniter wiring harness for damage.
Check gas solenoid valves for open or short circuits.
Remove burner cover and ensure all burners are properly
seated.
Remove burner plate and inspect burner surface for
condensation or debris.
Flame Failure
12
Check that the gas is turned on at the water heater and gas
meter. Check for obstructions in the flue outlet.
Ensure gas line, meter, and/or regulator is sized properly.
Ensure gas type and pressure is correct.
Bleed all air from gas lines.
Ensure proper venting material was installed.
Ensure condensation collar was installed properly.
Verify dip switches are set properly.
Ensure appliance is properly grounded.
Disconnect keypad.
Disconnect EZConnect or MSA controls to isolate the problem.
Check power supply for loose connections.
Check power supply for proper voltage and voltage drops.
Ensure flame rod wire is connected.
Check flame rod for carbon build-up.
Disconnect and re-connect all wiring harnesses on unit and PC
board.
Check all components for electrical short.
Check gas solenoid valves for open or short circuits.
Remove burner plate and inspect burner surface for
condensation or debris.
Thermal Fuse
14
Check gas type of unit and ensure it matches gas type being
used.
Check for restrictions in air flow around unit and vent terminal.
Check for low water flow in a circulating system causing short-
cycling.
Ensure dip switches are set to the proper position.
Check for foreign materials in combustion chamber and/or
exhaust piping.
Check heat exchanger for cracks and/or separations.
Check heat exchanger surface for hot spots which indicate
blockage due to scale build up. Refer to instructions in manual for flushing heat exchanger.
Measure resistance of safety circuit.
Ensure high fire and low fire manifold pressure is correct.
Check for improper conversion of product.
Wiring Diagram
G
3
4
FM
P P
Y
F
R R
H
SV0
SV1
SV2
SV3
BR
6
1
O Y R W
5
O
13
BL BR
P
R
Y
W Y
BK
R
R R
1
H
5
P
BK
H
6
Y
BK
H
7
BL BK
H
8
BR BK
(CN12)
GND
BY-PASS SERVO MODEL ONLY
BY-PASS FLOW CONTROL DEVICE
FREEZE PROTECTION OPTION
WATER FLOW SENSOR
QS
INDOOR MODEL ONLY
AIR TEMPERATURE THERMISTOR
HEAT EXCHANGER THERMISTOR
OUTGOING WATER THERMISTOR
F
7
WATER FLOW CONTROL DEVICE
F
2
RR Y
Y
BK
BK
R BL BR
Y GY
THERMAL FUSES
H
2
MODULATING SOLENOID VALVE
FLAME ROD
MAIN SOLENOID VALVE
SOLENOID VALVE 1
SOLENOID VALVE 2
SOLENOID VALVE 3
G R
F
1
F
3
W
W
W
O
F
4
W
W
W
P
F
5
W
W
W
W
GY
R
BL
Y
BR
E
1
COMBUSTION FAN
OVERHEAT SWITCH
H
POV
H
BRROYW
G
1
(CN7)
F
YBKR
G
1
(CN5)
WW
E
41
YBKR
W
SURGE PROTECTOR
BL BR
D
1
G/Y
Over Temperature Warning
16
Check for restrictions in air flow around unit and vent terminal.
Check for low water flow in a circulating system causing short-
cycling.
Check for foreign materials in combustion chamber and/or
exhaust piping.
Check for clogged heat exchanger.
Outgoing Water Temperature Sensor Fault
32
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build up.
Replace sensor.
Heat Exchanger Outgoing Temperature Sensor Fault
33
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build up.
Replace sensor.
Combustion Air Temperature Sensor Fault
34
Check for restrictions in air flow around unit and vent terminal.
Check sensor wiring for damage.
Measure resistance of sensor.
Clean sensor of scale build up.
Ensure fan blade is tight on motor shaft and is in good
condition.
Replace sensor.
Modulating Solenoid Valve Signal Abnormal
52
Check modulating gas solenoid valve wiring harness for loose
or damage terminals.
Measure resistance of valve coil.
Combustion Fan Failure
61
Ensure fan will turn freely.
Check wiring harness to motor for damaged and/or loose
connections.
Measure resistance of motor winding.
Water Flow Servo Faulty (does not stop flow properly)
65
If blank screen is present on remote control then the flow control has shorted out. Unplug flow control. If remote lights up and unit starts operating then replace flow control assembly.
SV0, SV1, SV2, and SV3 Solenoid Valve Circuit Fault
71
Check wiring harness to all solenoids for damage and/or loose
connections.
Measure resistance of each solenoid valve coil.
Flame Sensing Device Fault
72
Ensure flame rod is touching flame when unit fires.
Check all wiring to flame rod for damage.
Remove flame rod and check for carbon build-up; clean with
sand paper.
Check inside burner chamber for any foreign material blocking
flame at flame rod.
Measure micro amp output of sensor circuit with flame present.
Replace flame rod.
Scale Build-up in Heat Exchanger (when checking
LC
maintenance code history “00” is substituted for “LC”)
Flush heat exchanger. Refer to instructions in manual.
Replace heat exchanger.
No Code (Nothing happens when water flow is activated.)
Clean inlet water supply filter.
On new installations ensure hot and cold water lines are not
reversed.
Check for bleed over. Isolate unit from building by turning off
hot water line to building. Isolate the circulating system if present. Open your pressure relief valve; if unit fires, there is bleed over in your plumbing.
Ensure you have at least the minimum flow rate required to fire
unit.
Ensure turbine spins freely.
Measure the resistance of the water flow control sensor.
Remote control does not light up but you have 12 VDC at the
terminals for controls.
COLOR CODING
W :White BK:Black BR:Brown R :Red BL:Blue Y :Yellow P :Pink
O :Orange G :Green GY:Gray
D
5
A
3
(CN9)
H
(CN2)
12 1
P
YP
G/Y
GND
BLBKP
D
BK
3
1
W
R
1
3
for 2-Unit Connection (Optional)
MAX
MIN
BKRW
Dip SW1
O
1
F F
Dip SW2
O F F
B
YBR
(CN1)
C
D
(CN3)
BL BR
2
FUSE (3A)
BKW
MODULATING VALVE CURRENT ADJUSTING
1 2 3 4 5 6 7
Gas pressure
8
1
Gas type
2 3
Spare Parts Only
4 5 6
B
BK BK
C
W W
1
1
GY GY
IGNITER
(W) (W)
AC120VAC120V
HOT
HOT NEUTRAL
NEUTRAL
GROUND
1
3
(CN4)
GY GY
1
3
REMOTE CONTROLLER
SPARK ELECTRODE
IG
GND
D
3
FROST SENSING SWITCH
BLBL
ANTI-FROST HEATER
D
BLBL
4
ANTI-FROST HEATER
SW No.
2
3
High Altitude
Off
Off
Level 0
0-2000ft
(0-610m)
Off
On
NOTES
Level 1
2001-5200ft
(610-1585m)
On
Off
(1585-2347m)
Level 2
5201-7700ft
On
7701-10200ft
On
(2347-3109m)
Level 3
070 00012 39526 5
505
Outdoor
305
U287-1185 (02)
EXPLODED VIEW - CABINET
EXPLODED VIEW - INTERNALS
801
802
011
012
017
006
015
007
005
008
004
001
013
807
014
806
003
016
002
002
808
808
708
707
118
116
119
117
114
138
135
137
103
717
718
716
710
709
711
143
810
132
REMOTE CONTROLLER
EXPLODED VIEW - INTERNALS
818
101
401
100
413
113
812
803
110
125
EXPLODED VIEW - ELECTRICAL
725
706
729
721
703
805
409
702
730
814
810
804
701
822
408
410
816
411
805
700
404
815
403
814
727
813
405
821
817
101
402
813
400
820
102
820
807
819
713
712
726
724
723
722
Number 001 002 003 004 005 006 007 008 011 012 013 014 015 016 017 100 101 102 103 103 110 110 113 114 116 117 118 119 125 132 135 137 138
Description Main Body (W) Wall Mounting Bracket (W) Rubber Bushing Connection Reinforcement Panel Heat Protection Plate Front Panel Front Panel Packing Front Panel Packing Side Screw Cover Screw Cover Lid Cable Access Assy Rubber Bushing Rain Hood Packing Screw Cover Assy Gas Control Assembly Test Port Set Screw Gas Connection (3/4" NPT) Burner Unit Assy (LPG) Burner Unit Assy (NG) Manifold Assembly (LPG) Manifold Assembly (W-NG) Pressure Point Sealing Screw Combustion Chamber Sightglass Plate Electrode Flame Rod Electrode Packing Electrode Holder Fan Assembly Combustion Chamber Fan Bracket Flue Outlet Flue Outlet Gasket Seal Packing
Par ts Number 701022-005 701022-007 701022-008 701022-009 701022-010 701022-012 701022-013 701022-014 701022-017 701022-018 701022-019 701022-021 701022-022 701022-023 701022-024 701022-025 701022-026 701022-027 701022-028 701022-029 701022-031 701022-033 701022-034 701022-035 701022-036 701022-037 701022-038 701022-039 701022-044 701022-047 701022-049 701022-052 701022-054
412
Quantity
505
1 2 1 1 1 1 1 2 2 4 1 1 1 1 2 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
305
1 2 1 1 1 1 1 2 2 4 1 1 1 1 2 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Number 143 143 400 401 401 402 403 404 404 405 408 409 410 411 412 413 700 700 701 701 702 703 706 707 708 709 710 711 712 713 715 716 717
PA RTS LIST
Description Heat Exchanger Assembly Heat Exchanger Assembly Water Inlet (3/4" NPT) Water Flow Servo & Sensor Assembly Water Flow Servo & Sensor Assembly Rectifier By-pass Servo Assembly Stop Bracket Stop Bracket Plug Band Hot Water Outlet (3/4" NPT) Stop Bracket Plug Band (small) Drain Valve Water Filter Assy Cover PCB PCB Surge Protector Surge Protector with terminal (optional) PCB cover - side PCB cover - front Ignitor High Tension Cord Electrode Sleeve Thermistor - Heat Exchanger Thermistor Clip Large Temperature Fuse Clip Frost Sensing Switch Anti Frost Heater (120V) Valve Heater (120V) Assembly Antifrost Heater Clip B Antifrost Heater Clip A
Par ts Number 701022-061 701022-062 701022-070 701022-071 701022-072 701022-073 701022-074 701022-075 701022-076 701022-077 701022-078 701022-079 701022-080 701022-081 701022-082 701022-083 701022-281 701022-280 701022-086 701022-087 701022-089 701022-090 701022-091 701022-092 701022-093 701022-094 701022-095 701022-096 701022-097 701022-099 701022-100 701022-102 701022-103
Quantity
505
1
­1 1
­1 1 2
­1 1 1 1 1 1 1 1
­1 1 1 1 1 1 1 1 1 5 1 1 1 2 1
305
­1 1
­1 1
-
­1 1 1 1 1 1 1 1
­1 1 1 1 1 1 1 1 1 1 5 1 1 1 2 1
715
Number 718 721 722 723 724 724 725 726 727 729 730 801 802 803 804 805 806 807 808 810 812 813 814 815 816 817 818 819 820 821 822 888 889
Description Antifrost Heater Clip C Fuse Harness (W) Power Harness Solenoid Valve Harness Sensor Harness Sensor Harness Thermal Fuse Harness Assy Ignitor Harness Flow Sensor Remote Controller Harness Thermistor Screw Resin Washer O-ring Thermistor Stop Screw Screw Screw Resin Washer Screw O-ring O-ring O-ring O-ring O-ring O-ring O-ring Packing Screw Screw Screw Screw Manual Tech Sheet
Quantity Par ts Number 701022-105 701022-109 701022-110 701022-111 701022-114 701022-115 701022-116 701022-117 701022-118 701022-119 701022-120 701022-122 701022-123 701022-124 701022-125 701022-126 701022-127 701022-128 701022-129 701022-130 701022-132 701022-133 701022-134 701022-135 701022-136 701022-137 701022-138 701022-139 701022-140 701022-141 701022-142 315898-000 315896-000
505
1 1 1 1 1
­1 1 1 1 1 4 4 3 1 3 2 2 4 2 1 2 2 2 1 1 2 2 4 2 3 1 1
305
1 1 1 1
­1 1 1 1 1 1 4 4 3 1 2 2 2 4 2 1 1 2 1 1 1 2 2 4 2 3 1 1
Loading...