NNoottee:: “Graphics in this document are for representation
only. Actual model may differ in appearance.”
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
October 2014
SSAAFFEETTYY WWAARRNNIINNGG
11-BC37D1-1D-EN
SAFETY SECTION — OUTDOOR
IImmppoorrttaanntt — This document contains a wiring diagram
and service information. This is customer property and
is to remain with this unit. Please return to service
information pack upon completion of work.
WAITTWO(2)MINUTESafterdisconnectingpowerpriortotouchingelectricalcomponents as they may holdadangerouschargeof400VDC,thenverifyDCVoltageislessthan42VDCatinvertertestpointslabeled+VDC and -VDC beforeservicingboard.
400 VOLTS
WARNING
+VDC
and
-VDC
CAUTION - HOTSURFACE
Scan to see an
overview video
about the IVSC
Board
SSAAFFEETTYY SSEECCTTIIOONN —— OOUUTTDDOOOORR
Approved Combinations for Variable Speed Units
•AZONE 850 Comfort Control, or AZONE 950 with Software Version
3.0 or Higher
•TAM8C or later models
•Platinum SV Furnace
•Platinum ZV Furnace
•Approved System Accessories
Note: See AHRI directory for approved indoor and outdoor model
combinations. Only Trane coils and air handlers are approved
for use with variable speed outdoor units.
Note: It is recommended that these precautions be taken for
units being installed in areas where snow accumulation and
prolonged below-freezing temperatures occur.
•Units should be elevated 3–12 inches above the pad or
rooftop, depending on local weather. This additional height
will allow drainage of snow and ice melted during defrost cycle
prior to its refreezing. Ensure that drain holes in unit base pan
are not obstructed, preventing drainage of defrost water.
•If possible, avoid locations that are likely to accumulate snow
drifts. If not possible, a snow drift barrier should be installed
around the unit to prevent a build-up of snow on the sides of
the unit.
Coastal Considerations
If installed within one mile of salt water, including seacoasts and inland waterways, models without factory supplied Seacoast Salt Shields
require the addition of BAYSEAC001 (Seacoast Kit) at installation time.
11-BC37D1-1D-EN
7
Unit Preparation
1. Check for damage and report promptly to the carrier
any damage found to the unit.
2. To remove the unit from the pallet, remove tabs by
cutting with a sharp tool.
Setting Up the Unit
Table 7. Pad Installation
When installing the unit on a support pad, such as a concrete slab,
consider the following:
•The pad should be at least 1” larger than the unit on all sides.
•The pad must be separate from any structure.
•The pad must be level.
•The pad should be high enough above grade to allow for drainage.
•The pad location must comply with National, State, and Local
codes.
8
11-BC37D1-1D-EN
Refrigerant Line Considerations
LineLength
Liquid Line
VaporLine
Insulation
Table 8. Required Refrigerant Line Length
Determine required line length and lift. You will need this to determine
the subcooling charging corrections later in the installation process.
Total Line Length = ___________________________Ft.
Total Vertical Change (lift) = ____________________Ft.
Table 9. Refrigerant Line Insulation
Important: The Vapor Line must always be insulated. DO NOT allow
the Liquid Line and Vapor Line to come in direct (metal to
metal) contact.
Note: The gas line must always be insulated. Insulating the liquid line
through attic spaces may benefit system performance by
minimizing heat gain in the liquid line.
11-BC37D1-1D-EN
9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.