Ambirad VSX20UT, VSX25UT, VSX30UT, VSX35UT, VSX40UT User guide

...
Page 1
ASSEMBLY, INSTALLATION & SERVICING
ANUAL FOR AMBIRAD VISION
M
ANGE OF RADIANT TUBE HEATERS
R
®
VSX
INDEX Section
Introduction and Document Index Installation Requirements-------------------------------------------------1 Assembly Instructions------------------------------------------------------2
Commissioning Instructions----------------------------------------------3 Servicing Instructions------------------------------------------------------4 Spare Parts-------------------------------------------------------------------5 Fault Finding Guide --------------------------------------------------------6 Replacing Parts -------------------------------------------------------------7 User and Operating Instructions ----------------------------------------8
WARNINGS
AmbiRad equipment must be installed and maintained in accordance with the relevant provisions of the Gas Safety (Installations and Use) Regulations 1998 for gas fired products. Due account should also be taken of any obligations arising from the Health and Safety at Works Act 1974 or relevant codes of practice. In addition the installation must be carried out in accordance with the current IEE wiring regulations (BS 7671), BS 6896 (Industrial & Commercial) and any other relevant British Standards and Codes of Practice by a qualified installer. All external wiring MUST comply with the current IEE wiring regulations.
Page 2
2 3
Page 3
Introduction.
Welcome to the new range of high efficiency AmbiRad Vision radiant tube heaters. Local regulations may vary in the country of use and it is the installers responsibility to ensure that such regulations are satisfied.
All installation, assembly, commissioning and service procedures must be carried out by suitable qualified competent persons to the statutory regulations in the country of use.
When assembling, installing, commissioning and servicing is undertaken on radiant tube heaters specified in these instructions, due care
Document Index.
1 Installation Requirements
1.1 Health & Safety
1.2 Model Definitions
1.3 Heater Suspension
1.4 Wall Mounting
1.5 Clearance to Combustibles
1.6 Gas Connection & Supply Details
1.7 Electrical Connections
1.8 Ventilation Requirements
1.8.1 Unflued Radiant Heater Mechanical Ventilation Natural Ventilation
1.8.2 Flued Radiant Heater Mechanical Ventilation Natural Ventilation
1.9 Flue & Combustion Air Inlet
1.9.1 Important Information
1.9.2 Flue Installation
1.9.3 Condensation Considerations
1.9.4 Flue Connections
1.10 Technical Details
2 Assembly Instructions
2.1 Tools Required
2.2 Assembly Notes
2.2.1 Turbulators
2.2.2 Brackets
2.2.3 Tube Alignment Sections
2.2.4 Couplers
2.2.5 Reflectors
2.2.6 Burner/Heat Exchanger Assembly
2.3 Identification Check List
2.4 Prior to Assembly
2.5 Step by Step Installation
2.5.1 Tubes and Turbulators
2.5.2 Brackets, U Bolts and U Bend
2.5.3 Reflectors
2.5.4 End Caps
and attention is required to ensure that working at height regulations are adhered to at the mounting heights specified.
PLEASE READ this document prior to
installation to familiarise yourself with the components and tools you require at the various stages of assembly.
All Dimensions shown are in mm unless otherwise stated.
The manufacturer reserves the right to alter specifications without prior notice.
2.5.5 Canopies
2.5.6 Canopy End Caps
2.5.7 General
2.6 Detailed Assembly Drawings
3 Commissioning Instructions
3.1 Tools Required
3.2 Commissioning Chart for VSX Unitary Heaters
4 Servicing Instructions
4.1 Tools required
4.2 Burner Description
4.3 Burner Removal
4.4 Burner Gas Injector Servicing
4.5 Burner Head and Electrode Servicing
4.6 Combustion Fan Assembly
4.7 Radiant Tube Servicing
4.8 Heat Exchanger Servicing
4.9 Reflector Servicing
4.10 Inspection of Flue
4.11 Re-commissioning after Service
5 Spare Parts 6 Fault Finding Guide 7 Replacing Parts
7.1 Burner Controller Replacement
7.2 Air Pressure Switch Replacement
7.3 Gas Valve Replacement
8 User and Operating Instructions
8.3 To Start Heater
8.2 To Switch off Heater
8.3 Routine Maintenance Between Service Intervals
8.4 Frequency of Servicing
Page 4
3
1. Installation Requirements.
Isolate any electrical supply to the heater and controller before proceeding.
1.1 Health and Safety
AmbiRad heaters must be installed in accordance with the relevant provisions of the Gas Safety (Installations and Use) Regulations
1998. Due account should also be taken of any obligations arising from the Health and Safety at Works Act 1974 or relevant codes of practice. In addition the installation must be carried out in accordance with the current IEE wiring regulations (BS 7671), BS 6896 (Industrial & Commercial) and any other relevant British Standards and Codes of Practice by a qualified installer. Isolate all electrical supplies to the heater & controller before proceeding.
For your own safety we recommend the use of safety boots and leather faced gloves when handling sharp or heavy items. The use of protective eye wear is also recommended.
1.2 Model Definitions
VSXUT = Ambirad Vision High efficiency U
Tube heater with painted powered burner, deep profile stainless steel reflector and end caps, reflector canopy and end caps in Aluzink.
whole weight of the heater. In the event of suitable roof steelwork being unavailable, additional steelwork should be fitted to enable vertical hangers to be used for suspending the heaters.
These methods are illustrated in Figure 1.b. If there are any doubts as to the strength or suitability of roof steelwork to which heaters are to be suspended, please refer to a Consultant, Architect or owner of the building. The recommended mounting heights for AmbiRad heaters are given in the table above.
1.4 Wall Mounting
These radiant tube heaters can be wall mounted using the appropriate bracket (AmbiRad part no WMB-13-22-38).
When using the wall mounting brackets the heater must be inclined at an angle between 30° and 45°.
Burner MUST be mounted on the lower tube. It must also be installed to the right hand side of the heat exchanger.
Table 1 Angle Mounting
1.3 Heater Suspension
See fig 1b. Attachment to the heater
support lugs should be made by a ‘speed link’, D shackle or in the case of drop rods, a closed formed hook. The hanging attachments to overhead steelwork etc. must be purpose made to good sound engineering practice or of a proprietary type fixing. They must be adequately fixed and designed to carry the
Figure 1.a. Angle Mounting using the Wall mounting bracket
Heater
Size
20 - 50
Required
angle
30-35°
45°
Chain
length 12 links 3 16 links 3
Eyebolt position
.
Model Recommended Mounting Height (m)
20
25 30 35
40 45 50
Horizontal
4.5 - 7.0m 3.5 - 5.0m
5.0 - 8.0m 4.0 - 5.0m
5.5 - 9.0m 4.0 - 6.0m
6.0 - 10.0m 4.5 - 6.5m
6.5 - 11.0m
7.0 - 12.0m
7.5 - 13.0m
5.0 - 7.0m
5.5 - 8.0m
6.0 - 9.0m
Inclined / wall
mounted
E
4
Page 5
Figure 1.b. Recommended Methods of Heater Suspension.
of inclination is 15°.
Where supports are inclined,
maximum recommended angle
15° max.
Vertical suspension chain ideal.
*
more than 45°.
be equal and not
* These angles to
Drop rod with formed hook.
note. hook or eyebolt must
be closed tight.
Shackle method of
attachment. Pin must
be tightened by pliers.
*
.
Vertical or inclined
support is recommended
angle of inclination greater
Where chain supports have an
than 15° an equal and opposite
suspension on this
plane is acceptable.
5
THE HEATER SHOULD SLOPE DOWNWARDS TOWARDS THE RETURN BEND
BY APPROX. 10mm FOR BOTH HORIZONTAL AND WALL MOUNTED INSTALLATIONS.
Typical Speedlink attachment.
Page 6
1.5 Clearance to Combustibles.
The minimum clearances to combustible materials are given in the tables below. These minimum distances MUST be adhered to at all times.
Figure 2 Diagram illustrating the clearance to combustibles
B
E
A
D
C
F
C C
VSXUT
Above Reflector
Above Burner / Heater Outlet
To the Sides
Below Tubes Horizontally from Heater Outlet
(UNFLUED) End Wall
A
B
C
D
E
F
D
20/25/30 35/40 45/50
100 100 100
500 500 500
1300 1300 1300
2300 2500 2500
1200 1200 1200
700 700 700
6
Page 7
1.6 Gas Connection and Supply
Before installation, check that the local
distribution conditions, nature of gas and pressure, and adjustment of the appliance are compatible.
A competent or qualified engineer is required to either install a new gas meter to the service pipe or to check that the existing meter is adequate to deal with the rate of gas supply required. Installation pipes should be fitted in accordance with BS 6896, so that the supply pressure, as stated in Table 2 will be achieved. It is the responsibility of the competent engineer to ensure that other relevant Standards and Codes of Practice are complied with in the country of installation. Pipes of smaller size than the heater inlet gas connection must not be used. The complete installation must be tested for soundness as described in the country of installation.
The gas union service cock MUST be fitted in the gas supply close to the heater, but not onto the burner itself.
Take care when making a gas connection
to the heater not to apply excessive turning force to the internal controls.
A flexible hose is installed to allow safe linear expansion of the heater without creating undue stress on the gas supply pipe work. It is therefore important that a tested and certified hose assembly made to ISO 10380, supplied with ½” BSP female cone seat adapters, is installed as per these instructions.
It is also important to ensure that expansion is taken up in the body of the flexible hose, and not on its attachment to the pipe work. Th e cone seat adapter supplied on one end of the flexible gas hose provides a `swivel` action, and must be fitted on the burner using a ½” BSP barrel nipple to provide ease of disconnection for future servicing. This assumes that the heater and fixed gas supply to the isolating valve have been installed.
The installation layout described below is
the only method recommended by the
institute of gas engineers, the hose manufacturer, and AmbiRad and must only be carried out by a qualified/competent gas engineer.
Figure 3. Correct Installation of Flexible Gas Connection
fig.a
Arrow denotes direction of expansion.
fig.d
Depending on the specific installation, the flexible gas hose may be routed to the gas cock at any of the following angles in relation to the burner: Vertical (fig.a) 45° angle (fig.b) 90° angle (fig.c) Any other position in between these angles is acceptable.
A clearance distance ‘x’ of min 200mm must be observed to allow side door
access .
fig.b
x
50 +/- 20mm
Care must be taken to observe the minimum pipe bend diameter (minimum 250mm, maximum 350mm) & pipe expansion distance (minimum 30mm, maximum 70mm) as shown in fig.e.
Maximum bend diameter for the 1000mm hose is 450mm.
The correct installation as shown will allow for approx 100mm of movement due to
expansion.
7
Burne
fig.c
300 +/- 50mm
x
fig.e
Page 8
fig.f
fig.g
The methods shown in fig.f and fig.g are unacceptable, due to undue stress on the hose & fittings.
Table 2 Gas Supply Pressures
Gas Category I2H Gas Type
Max Supply Pressure (mbar) Min Supply Pressure (mbar) Nominal Pressure (mbar) Gas Supply
Connection R½ ½in BSP Internal Thread
1.7 Electrical Connection
This appliance must be earthed. Supply 230V 50Hz single phase. Standard heater 116W. Current rating 0.55 amp max (inductive). Fuse: external 3 amp. All electrical work should be carried out to IEE
standards by a competent electrician. The electrical connection to the heater is made by
Natural Gas (G20)
25 17 20
Green & Yellow Earth; Blue Neutral; Brown Live
It is recommended the heater or group of heaters are controlled by thermostats, a time switch and if required manual control switches and a frost thermostat.
We recommend use of AmbiRad approved
controls. Please refer to control manual for
siting and installation details. Where alternative manufactures controls are used, please refer to their instructions for their siting and installation details.
means of a three pin plug-in power connector. Live, neutral and earth connections should be made via a flexible supply cable to the power connector and routed clear of the heater or tubes.
The flexible supply cables should be of 0.5mm² and comply with BS 6500. The wires in the mains lead are coloured in accordance with the following code:
Figure 4.b Typical Wiring Connections
Figure 4.a Single Phase Wiring
Fused Spur
Fan plugs into burner
8
Page 9
Figure 5. Internal Burner Wiring Diagram.
C.
N.C.
N.O.
VACUUM SWITCH
VALVE
J.S.T.
BLUE
GREY
SOLENOID VALVE
2
1
BLUE
3
GRN/YLW
BLUE
N
GREEN/YELLOW
EMC FILTER
MAINS INPUT
BLUE
L
L
FAN
N
GREY
YELLOW
BLACK
WHITE
BURNER
ON
MAINS
LAMPS
WHITE
GREY
ON
BROWN
BROWN
MAIN J.S.T.
YELLOW
BLUE
BLUE
1
9
2
3
4
8
7
11
10 12
GRN/YEL
PINK
BLACK
FLAME SENSOR
IGNITER
9
Page 10
1.8 Ventilation Requirements
AmbiRad tube heaters can be operated as flued or unflued appliances in accordance with the relevant national requirements in the country of installation.
1.8.1 Unflued Radiant Heater
Radiant tube heaters can be operated as unflued appliances so that the concentration of Carbon Dioxide (CO will be inhaled does not exceed 0.28%. BS EN 13410 is a guide to achieving this requirement.
If the building air change rate exceeds 1.5 per hour or if the heat input is less than 5W/m³, no additional ventilation is required.
In addition to the ventilation requirements, consideration needs to be given to the possibility of condensation forming on cold surfaces.
It should be noted that the clearance distance around the burner increases when the unit is operated unflued (see section 1.5). It should be ensured that the combustion gases do not impinge on any combustible materials.
Mechanical Ventilation
Mechanical ventilation must be rated at minimum 10m³/h per kW input using appropriately sized fans and interlocked with heaters.
Natural Ventilation
BS EN 13410 should be used to size air vents to provide adequate ventilation, an example of this calculation is given below:
Site Details: 20°c Internal Operating Temperature 0°c Outside Air Temperature 5m between high and low level vents
Following the sizing procedure in BS EN 13410 gives an air exit velocity of 1.6m/s. This equates to a free area vent at both high level and low level of 17.36cm²/kW free area.
1.8.2 Flued Radiant Heater
In buildings having an air change rate of less than 0.5 per hour, additional mechanical or natural ventilation is required. For detailed information, please see BS6896 section
5.2.2.2.1
Mechanical Ventilation
Mechanical ventilation must be installed to
) at positions where the air
2
meet a minimum of 0.5 air changes per hour using appropriately sized fans and interlocked with the heaters.
Natural Ventilation
Low level ventilation openings with a free area of at least 2cm²/kW shall be provided. See section 5.2.2.2.2.1.
1.9 Flue and Combustion Air Inlet
- Options
Dependent on the type of burner fitted to your heater it is possible to have configurations of flue and combustion air inlet options to those shown overleaf:
1.9.1 Important Information
1.9.1.1 Option 1 and 2
A suitable flue system complying with EN1856-1 (type T250 N1 D Vm L11040 O50) should be used. Flue size 125mm diameter twin wall.
Flue systems can run either vertically or horizontally up to a maximum length of 9.5m (including up to 2 x 90° bends plus the terminal). The minimum flue length shall be 1m.
The flue system must be terminated in a vertical position and in accordance with the British Standard Code of Practice BS 5440: Part 1 - Installation and maintenance of flues and ventilation for gas appliances of rated input not exceeding 70kW net (1st, 2nd and 3rd family gases), and the flue system manufacturers instructions as supplied with the flue.
1.9.1.2 Option 3 A suitable flue system complying with EN1865-1 (type T200 P1 W V2 L50050 O00) should be used. Flue size 100mm diameter single wall.
The maximum flue length shall be 9.0m (including up to 2 x 90° bends plus the terminal). The minimum flue length shall be 1m.
• Option 1
For flued products of combustion and no ducted air please refer to Figure 6.a.
• Option 2
For ducted air and products of combustion to ventilated area please refer to Figure 6.b.
• Option 3
For flued products of combustion and ducted air via concentric pipe please refer to Figure
6.c.
10
Page 11
The flue system must be terminated vertically only and in accordance with the British Standard Code of Practice BS 5440: Part 1 ­Installation and maintenance of flues and ventilation for gas appliances of rated input not exceeding 70kW net (1st, 2nd and 3rd family gases), and the flue system manufacturers instructions as supplied with the flue.
1.9.2 Installation
Connection to an appliance which is not connected to the fuel supply may be carried out by a competent person. However, connection to an appliance that is connected to the fuel supply
be carried out by a registered installer.
must
If the flue passes through a wall, ceiling, or roof made from combustible material then it has to be sleeved so as to provide a minimum of a 50mm void between the exterior of the flue and the internal wall of the sleeve. A minimum of 50mm must be maintained as a clearance distance to all other combustible materials.
The manifold should be supported by chain, stainless steel flexible wire, or other flexible means from the roof structure to allow movement caused by thermal expansion.
The maximum distance between supports is
1.5m for horizontal runs. Wall bands are not load bearing and give lateral
support only. If used, wall bands should be fitted every 3m on vertical runs to ensure the system is rigidly held. The system should be braced immediately below passing through the roof line to ensure the flashing does not suffer lateral pressures.
The maximum height unsupported above the roof line is 1.5m. Where a joint is above the roofline it should be determined that in extreme wind conditions this joint would not be over exerted. If there is any doubt then a guy wire should be used. Beyond this guy wires should be installed every meter.
The POCED is capable of withstanding its own weight when installed in accordance with these instructions and the Regulations shown below.
The exhaust flue should be adequately supported from the building structure and installed in accordance with the British Standard Code of Practice BS 5440: Part 1 – Installation and maintenance of flues and ventilation for gas appliances of rated input not
exceeding 70kW net (1st, 2nd and 3rd family gases), and the flue system manufacturers instructions as supplied with the flue.
See reference BS 6896. Condensate drain pipes must be protected against the effects of freezing.
1.9.3 Condensation
When designing the flue system the prevention of the formation and entrapment of condensation must be a key consideration.
Horizontal flue should be fitted ensuring a slight gradient approx 5
Where condensation is unavoidable traps should be included to encourage the condensates to flow freely to a point from which they may be released, preferably into a gully. The condensate pipe from the flue to the disposal point must be made from corrosion resistant pipe of not less than 25mm internal diameter.
1.9.4 Method of Jointing Tube
1.9.4.1 Option 1
All pipe lengths and flue gas carrying components are joined together by a twist lock, bayonet system. The system should be installed with the visible male collar pointing upwards, this is reaffirmed by the directional arrow pointing upwards, indicating the directional flow of flue gases. Taping of the joints is unnecessary.
1.9.4.2 Option 3
The components are joined by pushing the male spigot and female socket together until the stop is reached. No sealant is required, but can be applied if the formation of condensation is anticipated.
To seal use an applicator gun and apply a 4mm diameter bead of high temperature silicon jointing compound externally round the end of the male spigot and internally round the end of the female socket.
Push the male spigot into the female socket using a slight rotating movement to spread the jointing compound uniformly until both fittings have fully engaged.
Note The silicon jointing compound remains workable after application for only 5 minutes
°
towards the terminal.
11
Page 12
Option 1 - Figure 6.a. Forced Burner with Heat Exchanger (Standard Flue)
For flued products of combustion and no ducted air
Products of combustion
J
G
L
K
G
E
Firing tube
Products of combustion
Maximum flue length = 9.5m @ Ø125mm Maximum no of bends = 2
All flues must terminate vertically. For further information on flue runs, please refer to section 1.9.1 BS 5440 pt.1
Air
Inlet
E Forced Burner F Heat Exchanger G 100mm (4ins) Clips x2 H 100mm (4ins) Flexible Flue
H G
F
Ducted air must be used in locations
where there is airborne dust or where
there is a polluted atmosphere e.g. Chlorinated Vapours.
Maximum length = 9m Minimum diameter = 100mm Maximum no of bends = 2
J 100mm (4ins) Flexible Flue to Fan K 127mm (5ins) to 100mm (4ins) Reducer L 127mm (5ins) Twin Wall Flue Pipe
Ventilation requirements are as detailed in section 1.8
12
Page 13
Option 2 - Figure 6.b. Forced Burner with Heat Exchanger (No External Flue)
For ducted air and products of combustion to ventilated area
J
E
Firing tube
G
Fresh
Air
M
Products of combustion to ventilated area
G
H
G
Products of
combustion
Ventilation requirements are as detailed in section 1.8
Ducted air must be used in locations
where there is airborne dust or where there is a polluted atmosphere e.g. Chlorinated Vapours.
Maximum length = 9m Minimum diameter = 100mm Maximum no of bends = 2
F
E Forced Burner F Heat Exchanger G 100mm (4ins) Clips x2 H 100mm (4ins) Flexible Flue J 100mm (4ins) Flexible Flue to Fan
M Shroud for unflued heater installation
13
Page 14
Option 3 - Figure 6.c. Forced Burner with Heat Exchanger (with Concentric Flue)
For flued products of combustion and ducted air via concentric pipe.
IMPORTANT NOTE
This option is a type B with ducted air and is not a room sealed balanced flue product.
flue system
23
Products of
combustion
Fresh
Air
Inlet
P
G
J
G
E
Firing
Tube
Products of
combustion
E Forced Burner
F Heat Exchanger G 100mm (4ins) Clips x2 H 100mm (4ins) Flexible Flue
J 100mm (4ins) Flexible Flue to Fan N Flue Extension optional
(0.25m/0.5m/1.0m)
P Concentric Flue Terminal
Fresh
Air
Products of combustion
N
H
G
F
Ventilation requirements are as detailed in section 1.8
Maximum flue length = 9.0m @ Ø125mm Maximum no of bends = 2
All flues must terminate vertically. For further information on flue runs, please refer to section 1.9.1 BS 5440 pt.1
Ducted air must be used in locations
where there is airborne dust or where there is a polluted atmosphere e.g. Chlorinated Vapours.
Maximum length = 9m Minimum diameter = 100mm Maximum no of bends = 2
14
Page 15
1.10 Table 3. Technical Details.
All heaters to run on Natural Gas (G20)
No of Injectors
Gas Connection
Flue Nominal Bore mm (in)
Unitary Fan Motor Details
Heater Model
VSX20UT VSX25UT VSX30UT VSX35UT VSX40UT VSX45UT VSX50UT
Heat Input kW Gas
Gross Nett
1
½ in BSP Internal thread
125 (5)
230 volt 1 phase 50Hz
Injector
Flowrate
(m³/hr)
20.0 18.0 1.9 10.0 1.7 450x4047x746 114 0.5 2501
25.0 22.5 2.4 9.4 1.9 450x4047x746 114 1.0 2507
32.0 28.8 3.1 13.0 2.0 450x4047x746 114 1.0 2507
36.0 32.4 3.4 12.3 2.3 450x5927x746 158 1.0 2507
40.0 36.0 3.8 12.8 2.4 450x5927x746 158 0.5 2560
44.0 39.6 4.2 11.6 2.9 450x5927x746 158 0.5 2560
49.5 44.6 4.7 12.8 2.5L 450x7692x746 205 0.5 2560
Pressure
(mbar)
Injector
Size
(mm)
Size
(h x l x w)
Weight
(Kg)
Fan
Rating
(A)
Fan
Type
Table 4. Flue details
Heater Model
VSX20UT VSX25UT VSX30UT VSX35UT VSX40UT VSX45UT VSX50UT
Mass Flow Rate of Flue
Gasses (kg/s)
0.0116
0.0132
0.0133
0.0166
0.0173
0.0196
0.0220
Flue Pressure (Pa)
Maximum Flue
Resistance
35 - 42 190 - 250
Flue Gas Temp (°C)
15
Page 16
2. Assembly Instructions.
PLEASE READ this section prior to
assembly to familiarise yourself with the components and tools you require at the various stages of assembly. Carefully open the packaging and check the contents against the parts and check list.
The manufacturer reserves the right to alter specifications without prior notice.
2.1 Tools Required.
The following tools and equipment are advisable to complete the tasks laid out in this manual.
Trestles
4 & 5mm Allen keys
Leather Faced Gloves
Please ensure that all packaging is disposed of in a safe environmentally
friendly way.
For your own safety we recommend the
use of safety boots and leather faced gloves when handling sharp or heavy items. The use of protective eye wear is also recommended.
Suitable alternative tools may be used.
Pozidrive Screwdriver
Tape Measure
Spanner Set
2.2 Assembly Notes.
Please read these assembly notes in
conjunction with the correct assembly drawings (figs 7 to 10).
2.2.1 Turbulators
Ensure the correct length and quantity are
inserted into their respective correctly identified tube(s) as detailed in the assembly drawings.
2.2.2 Brackets
Tighten clamping ‘U’ bolt arrangement to
tubes ONLY WHERE STATED on the assembly drawings.
2.2.3 Tube alignment sections
For VSX50 Angle Mounted Installations ONLY. To allow for differential expansion of
the tubes, a tube alignment assembly is fitted to the first bracket on the fan side radiant tube. Position U bolt tube alignment sections over the tube and through bracket prior to clamping.
2.2.4 Reflectors.
All reflectors AND canopies must be positioned/attached to the brackets exactly
as detailed in the assembly drawings.
Remove the protective plastic coating.
16
Page 17
2.2.5 Couplers.
Locate and position tube couplers at the end
of the tubes. Ensure socket heads are facing outwards & the pre-fitted bolts in the couplers line up with the locating holes in the tubes.
Ensuring the bolts are not over tightened.
2.2.6 Burner and Heat Exchanger Assembly.
Slide the burner assembly onto the RIGHT HAND TUBE when viewed from above, ensuring
it is fully engaged.
Slide heat exchanger onto the LEFT HAND
TUBE when viewed from above, ensuring it is fully engaged. The hose connections should face vertically.
Secure both assemblies with grub screws.
2.3 Identification check list
COLOUR CODE
Burner
Heat Exchanger
U Bend
Inner Reflectors
Outer Canopy
VSX
20/25/30
1x
1x
1x 1x
2x 3x
2x 3x
VSX
35/40/45
1x
1x
VSX
50
1x
1x
1x
4x
4x
COLOUR CODE
Inner End Caps
Outer Canopy End Caps
Tubes
Turbulators
Couplers
VSX
20/25/30
2x 2x
2x
2x
2x
2x
VSX
35/40/45
2x
2x
3x
2x
VSX
50
2x
2x
4x
3x
4x
Brackets
No.5 Torque Screw
3x 4x
5x
13x 14x 15x
M8 U Bolt
M8 Full Nut
17
8x 6x
10x
16x 22x 28x
Page 18
COLOUR CODE
M6 Mudwasher
M6 Washer
M6 Full Nut
M6 x 35 Setpin
VSX
20/25/30
12x
4x
6x
4x
VSX
35/40/45
16x
6x
10x
6x
VSX
50
20x
8x
14x
8x
COLOUR CODE
M4 x 10 Pozi Setpin
M4 Full Nut
M4 Washer
M6 x 15 Setpin
VSX
20/25/30
7x
1x 2x
7x
2x
VSX
35/40/45
8x
8x
4x
2.4 Prior to assembly
• Ensure the area in which you are working is safe and clear of obstructions.
• Identify with the components in the check list and in which order they will be assembled.
• Arrange the trestles* in a straight line to allow for length of tubes.
• Remove all protective plastic from underside of Stainless Steel Reflectors / inside of End Caps.
* if saw horses cannot be located, ensure any alternative is sound and can carry the heater weight. Methodology: To cater for the expansion of the firing leg, all U bolts on the firing leg (except the one
closest to U bend) are to be loose as described below. All reflectors, tubes, brackets and canopies are bolted together.
VSX
50
9x
3x
9x
6x
2.5 Step by step installation.
2.5.1 Tubes and Turbulators
1
Locate and position tubes on trestles. After deciding which end will have the burner, mark out the position of the first bracket as shown in the assembly drawings section. Slide brackets over tubes as shown.
2x 2x 2x
2
VSX50 only: Locate & position the two shorter
tubes and affix to tubes using couplers. Keeping the tubes in line, tighten the couplers evenly until the tubes cannot be turned in the couplers.
0x 0x 2x
0x 0x 2x
18
Page 19
3
Locate and insert turbulator(s) into tube(s) ensuring the correct length and quantity are inserted into the correct tube. See assembly drawings section for location & length.
2x 3x 3x
CAUTION — SHARP EDGES!
2.5.2 Brackets, U Bolts and U bend.
Fit the M8 U bolts over the tubes into the holes
4
in the bracket & loosely secure with M8 nuts & washers, noting that all the brackets on the firing tube (right hand) except the bracket adjacent to the U bend should have nuts & washers on both sides of the bracket to allow bracket to be tightened whilst still allowing a 3mm gap for expansion between the tube & U bolt. Refer to sketch below..
3x 4x
this stage.
Working at the opposite ends of the tubes to the burner, locate & position two couplers so that the socket heads are facing outwards & the pre-fitted bolts in the couplers line up with the locating holes in the tubes. Do not fully tighten at
this stage.
2x 2x 5 2x
5x
DO NOT tighten any of the nuts at
L/H tube
R/H tube
6
Slide U bend into the open end of the couplers ensuring the pre-fitted bolts engage in the pre-cut holes in the U tube section. Tighten all four clamping bolts to provide a tight grip between tubes & U tube section.
1x 1x
1x
19
Page 20
2.5.3 Reflectors.
Remove protective film before starting.
Reflectors are supplied pre-punched and are universal throughout the VSX series.
7
Starting at the burner end, slide the reflectors through the brackets until they are all roughly in position along the heater, referring to the assembly diagram showing overlaps. Measure the distance between the end of the burner end tubes & the centre of the end bracket, This should be 6” (150mm), slide bracket along tubes to adjust, then tighten U bolts on the end bracket.
2x 3x
3x
CAUTION — SHARP EDGES!
8
Slide end reflector so that the innermost slotted holes line up with 1st bracket fixing holes, then fix in place using M6 x 35mm pins, washers & nuts.
2x 2x
9
slotted hole in 1st reflector, & bolt together using M6 x 35mm pins, washers & nuts. Bolt 1st & 2nd reflectors together using end elongated holes in each. Refer to notes ‘W’, ‘X’, ‘Y’ and Z in fig.12 for further details.
2x
Slide 2nd bracket to line up with innermost
4x 4x 4x
10
Repeat this procedure referring to the assembly diagram for quantities used on specific models, but noting that the final bracket is not bolted to the reflector. (See photo)
At this stage all the U bolts should be fully tightened.
20
Page 21
Locate M4 pins, washers & nuts into holes in
11
overlapping reflectors as shown.
1x 2x 1x 2x 1x 2x
3x 3x 3x
2.5.4 End Caps
12
Using M4 setpins & washers fix the blank end cap beneath the reflector profile at the U bend end with the flanges facing outwards.
3x 3x 3x 3x
2x 2x
13
end cap beneath the reflector profile at the burner end with the flanges facing outwards.
3x 3x
2x
Using M4 setpins & washers fix the 'cut out'
3x 3x 3x 3x
3x 3x
2.5.5 Canopies
14
Remove protective film before starting.
Slide the outer canopies over the reflectors from the U bend end ensuring correct location in re­flector profile. Line up burner end canopy flush with burner end reflector. Overlap canopies as shown in the assembly diagram.
2x 3x
4x
CAUTION — SHARP EDGES!
15
Adjust canopies so that the holes on top align with each other as detailed in the assembly instructions. Locate and fix one No.5 torque screw on every canopy overlap.
1x 2x
3x
21
Page 22
2.5.6 Canopy End Caps
16
Locate 6 off No.5 torque screws. Position the blank canopy end cap with the end cap flanges facing inwards, beneath the canopy profile at the U bend end & fix with screws. Repeat procedure for 'cut-out' canopy end cap, again ensuring the flange faces inwards.
2x 2x
12x 12x
2x
12x
CAUTION — SHARP EDGES!
2.5.7 General
17
The heater assembly is now complete and can now be installed. We would recommend that the burner and heat exchanger be assembled once the heater has bee n installed in the roof space.
1x 1x
1x
1x 1x
1x
2.6 Detailed Assembly Drawings
The following pages show the technical dimensional details of the VSX heaters.
Please note the heater type, length and
22
reference number from the delivery/advice note before identifying the correct model drawing.
Refer to figure 12 for details of ‘W’, ‘X’, ‘Y’ and
‘Z’ fastening and locations.
Page 23
Figure 7. VSX 20/25/30
Y
150
Z
3400mm TUBE
4047mm REFERENCE
Y
50mm O/LAP
W
Z
X
50 mm O/LAP
1365mm 1650mm
976mm TURBULATOR
2600mm(20); 3400mm(25/30) TURBULATOR
Z
Y
COUPLER
38mm
23
Page 24
Figure 8. VSX 35/40/45
Y
Z
150
2600mm TURBULATOR
5200mm TUBE
5927mm REFERENCE
Y
Y
W
Z
X
50mm O/LAP
1880mm 1650mm
50mm O/LAP
Z
W
X
50mm O/LAP
50mm O/LAP
1365mm
976mm TURBULATOR
2600mm TURBULATOR
Z
138mm
Y
24
COUPLER
Page 25
Figure 9. VSX 50
Y
Y
Z
50mm O/LAP
W
Z
X
50mm O/LAP
150
3400mm TURBULATOR
5200mm TUBE
7590mm REFERENCE
Y
Y
Z
W
50mm O/LAP
50mm O/LAP
X
1880mm 1880mm 1650mm
COUPLER
Z
W
50mm O/LAP
50mm O/LAP
X
1740mm TUBE
1200mm
976mm TURBULATOR
3400mm TURBULATOR
Z
25
COUPLER
293mm
Page 26
Figure 10. VSX Heater Breakdown (3 module shown)
26
Page 27
3. Commissioning Instructions.
These appliances should be commissioned by a qualified engineer.
3.1 Tools Required.
The following tools and equipment are advisable
Leather Faced Gloves
12mm Spanner
Check installation has
been carried out to these
instructions.
Reconnect gas hose. Open isolating valve.
Check soundness.
Open control housing and check that all components
are securely fastened.
Pozidrive Screwdriver
4mm Allen Key
Ensure gas and electricity
supplies are isolated.
Replace burner on tube
and secure.
Check thermostat is set to
maximum and is calling
for heat.
to complete the tasks laid out in this manual.
Suitable alternative tools may be used.
Small Flat Head Screwdriver
Manometer
Wrench with Extension
Large Adjustable Spanners or 22, 26 & 27mm Spanners for fitting of Gas Flex.
Disconnect gas hose from
burner
Remove burner from tube
and inspect burner head.
(See servicing instructions)
Switch on electrical supply.
The red neon should now
be illuminated. If restarting
heater a delay of 15s
should be allowed.
13mm Socket
A successful ignition is indicated by the amber
light illuminating and
remaining illuminated.
Has the
burner lit?
Check operation on
flame failure.
Check gas pressure.
Close control housing
The heater should now
run through its start up
sequence and ignite.
NO
YES
Check gas
pressure.
Check operation of air pressure switch
Leave the instructions
with a responsible
person.
Turn off power and check
that all components are
securely fastened.
Figure 11. VSX Gas Valve adjustment
Injector pressure test point.
Adjustment screw under cap to set injector pressure
Gas inlet test point
27
Page 28
4. Servicing Instructions.
These appliances should be serviced annually by a competent person to ensure safe and efficient operation. In exceptional dusty or polluted conditions more frequent servicing may be required. The manufacturer offers a maintenance service. Details available on request
4.1 Tools Required.
The following tools and equipment are advisable to complete the tasks laid out in this manual.
Leather Faced Gloves
12mm Spanner
Pozidrive Screwdriver
4mm Allen Key
4.2 Burner Description.
Figure 12. Burner breakdown
I
A
Small Flat Head Screwdriver
Manometer
Suitable alternative tools may be used.
Large Adjustable Spanners or 22, 26 & 27mm Spanners for Fitting of Gas Flex.
Wrench with 13mm Socket
M
B
Soft Brush
N
O
G
F
A Ignition Controller B Gas Valve C Burner On Amber Neon D Power On Red Neon E Injector F Burner Tube G Ignitor Assembly
K
L
K
K
E
H Jet Carrier
I Combustion Fan
J Pressure Switch K Gaskets L Burner Orifice Plate
M Fan Orifice Plate
N Mains Input Filter
O Fan Connector
C
n.b. burner insulation
omitted for clarity
D
J
28
Page 29
4.3 Burner Removal
Step 1 Isolate power and gas supplies.
Step 2 Unplug the power connectors.
Step 3 Detach the gas supply as shown below, taking care to support the burner connection.
Step 6 Slacken the set screw on the burner support casting to enable the burner to be removed from the radiant tube.
Step 7 Remove the burner and position
the burner in a safe area to prevent the burner or components attached to the burner from falling to the ground.
Step 4 If ducted air is connected, slacken hose clip and remove the flexible hose from the burner.
Step 5 slacken the jubilee clip attaching the pre-heated air hose to the heat exchanger and remove the flexible hose from the burner.
4.4 Burner Gas Injector Servicing
Step 1.a Remove the burner support casting and gasket.
Step 1.b The burner head assembly can be disconnected by separating the connectors of the ignition lead assembly and removing the pressure switch silicon tube.
29
Page 30
Step 2 The gas injector can be inspected and replaced if contaminated or blocked.
When replacing the gas injector ensure approved thread sealant is used.
replaced ensuring the 5 holes on the outer ring are aligned alongside the probes.
Step 3 The condition of the igniter assembly can be checked for deterioration. However, we advise replacement at each service to ensure continued reliability. Detach the electrode assembly from the burner head by removing the two screws and separating the igniter lead connectors.
Step 3 Reconnect ignition leads and silicone tube to test nipple. Refit gasket and support casting.
4.5 Burner Head and Electrode Servicing
Step 1 Check the pepper pot burner head for contamination. If necessary this can be removed. See below. This can be cleaned together with the Inside of the burner head.
Step 2 The pepper pot burner head can be
10.0°
Ø3”
3/8”
7/64” ±1/64”
Step 4 Refit the electrode assembly and ensure the connections are secure to prevent arcing of the spark electrode.
Step 5 Check the positions and spark gap as shown below.
Step 6 The burner assembly is ready to refit after servicing the combustion fan and the radiant tube assembly.
25/64”
1 7/64”
±5/64”
2 13/64” ±13/64”
25/64”
30
Page 31
4.6 Combustion Fan Assembly
Step 1 Slacken jubilee clip and remove the flexible hose from the fan.
Step 2 Remove fan screws and unplug from burner box.
Step 7 Ensure the impeller rotates freely. Step 8 Refit components.
4.7 Radiant Tube Servicing
Step 1 Brush any dust from the exterior of the tubes.
Step 2 Inspect the fan and burner tubes visually. If the tubes appear clean, skip to servicing the reflector.
Step 3 Remove the U bend.
Step 3 The combustion fan can now be detached.
Step 4 Remove the fan orifice plate spigot and spinning.
Step 5 Inspect the impeller and remove any dust with a soft brush.
Step 6 Remove any dust from fan scroll and from around the motor.
Step 4 Withdraw the turbulators from the appliance. Carefully noting their condition and position. Replace turbulators if necessary.
31
Page 32
Step 5 The turbulators should be cleaned with a soft brush.
Step 3 If required the interior of the tubes can then be cleaned using an industrial vacuum cleaner or by using long poles and a scraper.
Step 4 Refit components.
4.8 Heat exchanger Servicing
Step 1 Remove the flue connections
4.9 Reflector Servicing
The condition of the reflectors should be noted. If necessary the reflectors can be cleaned with a mild detergent. This can significantly improve the efficiency of the appliance.
4.10 Sweeping of Flue
Inspect the fresh air inlet duct and vent to ensure they are free from any blockage or obstruction. The air inlet terminal and vent terminal should be inspected to ensure they are not liable to obstruction.
4.11 Recommissioning After Service
After servicing of the heater has been undertaken, it will be necessary to re-commission the heater as detailed in Section 3 of these instructions.
Step 2 Slacken casing support screws and remove heat exchanger from the radiant tube.
Step 3 Remove any dust and dirt from the heat exchanger & refit.
32
Page 33
5. Spare Parts.
Required Spares
In order to aid troubleshooting and servicing we recommend that the components shown in this section should be stocked.
Item
Ignition Controller
Nat Gas Valve Twin sol reg 220/240
Part No. Description
2015S
201857
200988 Pepperpot Head
Note Any spare part components that are
not approved by AmbiRad could invalidate the approval of the appliance and validity of the warranty.
Item
Amber Neon (Burner On)
Red Neon (Mains On)
Part No. Description
201676 Pressure Switch:
2175
2180
Extruded Burner Head
Injector
Jet Carrier (all except *)
Jet Carrier * VSX50 ONLY
201284 Ignitor Assembly
200358
See section 1.10
200420
201630
Combustion Fan
Cables: Spark Electrode
(black)
Rectification lead
(purple)
Earth lead
(green/yellow)
See Section 1.10
201488 Gasket Set
900225-2 900225-3 900225-1
201321 Ducted Air Hose
Flame Plate (20/25 ONLY)
Turbulators Burner tube Fan tube 25/30/50 Fan tube others
201358
6618T 200015T 6619T
7541 Hose Clamp
33
Page 34
6. Fault Finding Guide.
Ensure gas & electricity
supplies are enabled.
YES
Does the RED
neon
illuminate?
YES
Does the
combustion fan
run?
YES
NO
NO
YES
Is there power
on the burner?
NO
Check:
1. Wiring harness & plugs
2. Vacuum switch operation
3. Replace fan
NO
Check:
1. Burner controller
2. Red neon faulty
Check:
1. Operation of any thermostat
2. Any external fuses
3. Correct voltage is selected
Check:
1. Vacuum switch tubes
2. Emitter tubes, air inlet & flue for obstructions
3. Operation of vacuum switch
4. Replace combustion fan
Does the
amber light
illuminate after
10s purge?
YES
Does the
amber light
illuminate for 10s
then go out?
NO
If the heater still fails to
operate normally,
please contact
the AmbiRad
service department.
NO
YES
Does the
vacuum switch
`pull in`?
Is the burner
sparking?
YES
Does the gas
valve open?
YES
YES
NO
NO
Check:
1. Burner controller
2. Wiring harness
3. Amber neon faulty
Check:
1. Integrity of spark leads
2. Integrity of electrode assembly & spark gap
3. Burner controller
Check:
1. Burner controller
2. Replace gas valve
Check:
1. Burner inlet pressure
2. Burner nozzle pressure
3. Check live & neutral polarity
4. Check presence of good earth
34
Page 35
7. Replacing Parts.
Turn of gas any electrical supplies to the heater before starting repair work.
7.1 Burner Controller Replacement
Step 1 Slacken screw in burner lid and open the right hand burner access door.
Step 2 Undo 2 screws from controller bracket and remove. Disconnect burner controller from the wiring harness.
Step 6 Refit HT leads and refit burner controller to wiring harness.
Step 7 Test product and close access doors.
7.2 Air Pressure Switch Replacement
Step 1 Disconnect the two silicone impulse tubes and three wiring connections making note of replacement positions.
Step 3 Disconnect the HT Lead from burner controller.
Step 4 Remove the four screws attaching the controller to the bracket and remove.
Step 2 Remove the two screws as shown below.
Step 3 The air pressure switch can now be removed.
Step 4 Fit the new air pressure switch ensuring the impulse tubes are connected as shown opposite.
Step 5 Test product and close access doors.
Step 5 Fit new burner controller
35
Page 36
7.3 Gas Valve Replacement
Step 1 Remove the burner assembly as described in the section 4.3 Servicing.
Step 2 Open the left hand access door and detach the impulse hoses from the air pressure switch.
Step 3 Remove the 4 screws holding the burner head onto the burner assembly and carefully pull burner head assembly from housing.
Step 5 From within the combustion chamber, remove the two screws holding the front of the gas valve.
Step 6 Turning the housing over, remove the four screws holding the rear burner plate in position.
Step 4 The burner head can now be detached by disconnecting the impulse tube and the burner head wiring (ignition and rectification leads).
Step 7 Open the two side doors and remove the rear plate assembly.
Step 8 Whilst the valve is still attached to the plate, the jet carrier, gas inlet, and wiring harness can now be detached from the gas valve.
36
Page 37
Step 9 The two screws retaining the gas valve can then be removed.
Step 10 The gas valve can now be replaced. Step 11 Refit all components in reverse order. Step 12 Ensure step screw is in the correct
position as indicated in the diagram below.
Step 13 Set gas pressures to data badge or as per section 1.11 and ensure reliable burner performance.
Step 14 Test product and close access doors.
Step Screw Adjustment
37
Page 38
Notes
38
Page 39
Notes
39
Page 40
8. User & Operating Instructions.
8.1 To Start the Heater
1. Ensure gas supply is turned on.
2. Electrical supply to the controls is on.
3. Ensure that the controls are correctly set i.e.;
• Clock is correctly set.
• Heater program is correctly set.
• Required room temp is correctly set
4. Once the heating controller ‘calls for heat’ power will be supplied to the heater(s). The red neon will then illuminate.
5. After a pre-purge period of 10 seconds the burner will ignite and the amber neon will then illuminate.
6. If lockout occurs press the lockout reset button (if available), or switch off electrical supply and restart after 15 seconds.
7. If lockout occurs three times consecutively switch off and isolate the gas and electricity supplies. Contact the AmbiRad Service department.
8.2. To Switch Off Heater
1. Switch off electrical supply to the heater. The burner will stop and the fan will shut off.
2. If the heater is to be switched off for periods in excess of one week it is highly recommended that both the gas and the electrical supplies are turned off.
8.3. Routine Maintenance between Service Intervals
After ensuring that the heater is cold and mains electric isolated, cleaning of the reflectors with a soft cloth and a mild detergent (non solvent based cleaners only) in water can be undertaken.
Additional removal of dust from the radiant tubes, burner and heat exchanger can be undertaken.
8.4 Frequency of Servicing
The manufacturer recommends that to ensure continued efficient and safe operation of the appliance, the heater is serviced annually by a competent person e.g. every year in normal working conditions but in exceptional dusty or polluted conditions more frequent servicing may be required.
The manufacturer offers a maintenance service. Details are available on request.
For Service requirements, please contact AmbiRad.
For further technical and service support visit our Support Information Database at www.s-i-d.co.uk
AmbiRad Limited Fens Pool Avenue Brierley Hill West Midlands DY5 1QA United Kingdom.
Telephone 01384 489700 Facsimile 01384 489707 Email [email protected] Website www.ambirad.co.uk Technical Support www.s-i-d.co.uk
AmbiRad is a registered trademark of AmbiRad Limite d. Because of continuous product innovation, AmbiRad reserve the right to change product specification without due notice
40
Document reference number GB/VS/190/0112
Loading...