VIlI. Circulating Air and Filters ................................................ 18
IX. Sequence of Operation (Integrated Ignition Control) .... 21
X. Start-Up, Adjustments, and Checks ................................ 2 1
XI. Maintenance ....................................................................... 27
Affix this manual, Specification Sheet and Users
Information Manual adjacent to the furnace.
Amana Forced Air Central Furnace Design Complies With Requirements
Embodied in The American National Standard / National Standard of Canada
Shown Below.
ANSI Z21.47•CAN/CGA-2.3 Central Furnaces
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to
know the product better than the customer. This
includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize
yourself with this Instruction Manual. Pay special
attention to all safety warnings. Often during installation
or repair it is possible to place yourself in a position
which is more hazardous than when the unit is in
operation.
October 1997(1)
Fayetteville, TN 37334
Remember, it is your responsibility to install the product
safely and to know it well enough to be able to instruct
a customer in its safe use.
Safety is a matter of common sense...a matter of
thinking before acting. Most dealers have a list of
specific good safety practices...follow them.
The precautions listed in this Installation Manual should
not supersede existing practices but should be
considered as supplemental information.
Amana
10759818
Page 2
WARNING
If the information in these instructions is
not followed exactly, a fire or explosion
may result causing property damage,
personal injury or loss of life.
– Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
– What to do if you smell gas:
• Do not try to light any appliance.
• Do not touch any electrical switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor’s phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier,
call the fire department.
– Installation and service must be
performed by a qualified installer, service
agency or the gas supplier.
WARNING
Should overheating occur or the gas supply
fail to shut off, turn off the manual gas
control valve to the furnace before shutting
off the electrical supply.
To The Owner
It is important that you fill out the owner’s registration card
and mail it today. This will assist Amana in contacting you
should any service or warranty information change in the
future. When filling in the registration card, be sure to
include the Model, Manufacturing and Serial Numbers,
plus the installation date.
Your warranty certificate is also supplied with the unit.
Read the warranty carefully and note what is covered.
Keep the warranty certificate in a safe place, so you can
find it, if necessary.
If additional operating instructions are required, call the
dealer where the purchase was made.
To The Installer
Before installing this unit, please read this manual to
familiarize yourself on the specific items which must be
adhered to, such as maximum external static pressure to
unit, air temperature rise, minimum or maximum CFM,
motor speed connections, and venting. These furnaces
are designed for Category I venting only.
WARNING
To prevent possible death or personal injury
due to asphyxiation, Amana NonCondensing Gas Fired Warm Air Furnaces
must be Category I vented. Do not vent any
of these furnaces using Category III venting.
Keep this literature in a safe place for future
reference.
2
Page 3
I. Safety and Unit Location
WARNING
To prevent personal injury or death due to
improper installation, adjustment,
alteration, service, or, maintenance refer
to this manual or for additional assistance
or information consult a qualified installer,
service agency or the gas supplier.
WARNING
This product contains or produces a
chemical or chemicals which may cause
serious illness or death and which are
known to the State of California to cause
cancer, birth defects or other reproductive
harm.
WARNING
To prevent possible death, personal injury
or equipment damage due to fire, the
following points must be observed when
installing the unit.
WARNING
To prevent possible death, personal injury
or property damage due to electrical shock,
the furnace must be located to protect the
electrical components from water.
NOTE: This unit must not be used as a “construction
heater” during the finishing phases of construction on a
new structure. This type of use may result in premature
failure of the unit due to extremely low return air temperatures and exposure to corrosive or very dirty atmospheres.
WARNING
To prevent possible death, personal injury
or property damage, do not install this unit
in a mobile home, trailer or recreational
vehicle.
ADDITIONAL SAFETY CONSIDERATIONS
• This furnace is approved for Category I Venting only.
• When the furnace is heating, the temperature of the
return air entering the furnace must be between 55°F
and 100°F.
• Do not install the furnace where the combustion air is
exposed to the following substances: permanent wave
solutions, chlorinated waxes or cleaners, chlorine
based swimming pool chemicals, water softening
chemicals, deicing salts or chemicals, carbon tetrachloride, halogen type refrigerants, cleaning solutions
(such as perchloroethylene), printing inks, paint removers, varnishes, hydrochloric acid, cements and
glues, antistatic fabric softeners for clothes dryers,
and masonry acid washing materials. If the furnace is
installed near an area which will be frequently contaminated by these substances, the furnace should
be sealed from this area so that little contaminated air
can reach the furnace. The furnace must still have an
adequate supply of combustion air, either from a
nearby uncontaminated room or from outdoors. For
details, see “AIR REQUIREMENTS” Section III.
• Provisions must be made for venting combustion
products outdoors through a proper venting system.
The length of flue pipe could be a limiting factor in
locating the furnace.
• When installed horizontally, the furnace must be installed with the access doors vertical so that the
burners fire horizontally into the heat exchanger. The
unit cannot be installed with the access doors on top
or bottom. (See Specification Sheet)
• Allow clearances from the enclosure as shown on
Specification Sheet for fire protection, proper operation, and service access. These clearances must be
permanently maintained. The combustion and ventilating air openings in the front and top panels of the
furnace must never be obstructed.
• This furnace shall not be connected to a chimney flue
serving a separate appliance designed to burn solid
fuel.
• When the furnace is used in connection with a cooling
unit, the furnace must be upstream of, or in parallel
with, the cooling unit. For details see Section VIlI.
• On Counterflow Installations, the air conditioning coil
must be downstream from the heat exchanger of the
furnace.
•
Counterflow Installation over a noncombustible floor.
Before setting the furnace over the plenum opening,
insure the surface around the opening is smooth and
level. A tight seal should be made between the furnace
base and floor by using a silicone rubber caulking
compound or cement grout.
•
Counterflow Installation over a combustible floor.
installation over a combustible floor becomes necessary, use an accessory subbase as shown on the
Specification Sheet. Follow the instructions with the
subbase for proper installation. Do not install the
furnace directly on carpeting, tile, or other combustible
material other than wood flooring. (Note: The subbase
will not be required if an air conditioning coil is installed
between the supply air opening on the furnace and the
floor.)
• The furnace must be level. If the furnace is to be set on
a floor that may become wet or damp at times, the
furnace should be supported above the floor on a
concrete base sized approximately 1-1/2" larger than
the base of the furnace.
ADDITIONAL LOCATION CONSIDERATIONS
• The furnace should be as centralized as is practical
with respect to the air distribution system.
• Do not install the furnace directly on carpeting, tile, or
combustible material other than wood flooring.
• When suspending the furnace from rafters or joists,
use 3/8" threaded rod and 2” x 2” x 3/8” angle as shown
on the Specification Sheet. The length of the rod will
depend on the application and clearance necessary.
If
3
Page 4
• When installed in a residential garage, the furnace
must be positioned so the burners and ignition source
are located not less than 18 inches (457 mm) above the
floor and protected from physical damage by vehicles.
III. Air Requirements
COMBUSTION AND VENTILATION AIR
II. General Information
WARNING
Possible death, personal injury or property
damage due to fire, explosion, smoke, soot,
condensation, electrical shock or carbon
monoxide may result from improper
installation, repair, operation, or
maintenance on this product.
To ensure the furnace operates safely and efficiently, it
must be installed, operated and maintained in accordance
with these installation and operating instructions, all local
building codes and ordinances, or, in their absence, with
the latest edition of the National Fuel Gas Code, ANSI
Z223.1*, and/or CAN/CGA B149 Installation Codes.
The rated heating capacity of the furnace should be greater
than or equal to the total heat loss of the area to be heated.
The total heat loss should be calculated by an approved
method or in accordance with “ASHRAE. Guide” or “Manual
J-Load Calculations” published by the Air Conditioning
Contractors of America.
*Obtain from: American National Standards Institute 1430
Broadway New York, NY 10018
TRANSPORTATION DAMAGE
Check the furnace for any shipping damage. If damage is
found, contact the company where the furnace was purchased.
While checking for transportation damage, remove all packaging material and dispose or recycle according to local
codes.
THERMOSTAT LOCATION
Locate the thermostat about 5 feet high on a vibration-free
inside wall, in an area having good air circulation
Do not install the thermostat where it may be affected by:
• drafts or dead spots behind door, in corners or under
cabinets.
• hot or cold air from ducts.
• radiant heat from sun or appliances.
• concealed pipes and chimneys.
• unheated (uncooled) areas behind the thermostat,
such as an outside wall.
Consult the instructions packaged with the thermostat for
mounting instructions.
WARNING
Possible death, personal injury or property
damage may occur if the furnace and other
fuel-burning appliances are not provided
with enough fresh air for proper combustion
and ventilation of flue gases. Most homes
require outside air to be supplied into the
furnace area.
Improved construction and additional insulation in buildings has reduced the heat loss, making these buildings
much tighter around doors and windows so air infiltration is
minimal. This creates a problem supplying combustion and
ventilation air for gas fired and other fuel burning appliances. Use of appliances pulling air out of the house
(clothes dryers, exhaust fans, fireplaces, etc.) increases
this problem causing appliances to starve for air.
This furnace must use indoor air for combustion. It cannot
be installed as a direct vent (i.e., sealed combustion)
furnace. The burner box is present only to help reduce
sound transmission from the burners to the occupied space.
AIR REQUIREMENTS
Most homes will require outside air supplied to the furnace
area by means of ventilation grilles or ducts connecting
directly to the outdoors or spaces open to the outdoors such
as attics or crawl spaces. The following information on air
for combustion and ventilation is reproduced from the
National Fuel Gas Code NFPA54/ANSI Z223.1 Section
5.3.
5.3.1 General:
(a) The provisions of 5.3 apply to gas utilization equipment
installed in buildings and which require air for combustion,
ventilation and dilution of flue gases from within the building. They do not apply to (1) direct vent equipment which is
constructed and installed so that all air combustion is
obtained from the outside atmosphere and all flue gases
are discharged to the outside atmosphere, or (2) enclosed
furnaces which incorporate an integral total enclosure and
use only outside air for combustion and dilution of flue
gases.
(b) Equipment shall be installed in a location in which the
facilities for ventilation permit satisfactory combustion of
gas, proper venting and the maintenance of ambient temperature at safe limits under normal conditions of use.
Equipment shall be located so as not to interfere with proper
circulation of air. When normal infiltration does not provide
the necessary air, outside air shall be introduced.
4
Page 5
(c) In addition to air needed for combustion, process air
shall be provided as required for: cooling of equipment or
material, controlling dew point, heating, drying, oxidation or
dilution, safety exhaust, odor control, and air for compressors.
(d) In addition to air needed for combustion, air shall be
supplied for ventilation, including all air required for comfort
and proper working conditions for personnel.
(e) While all forms of building construction cannot be
covered in detail, air for combustion, ventilation and dilution
of flue gases for gas utilization equipment vented by natural
draft normally may be obtained by application of one of the
methods covered in 5.3.3 and 5.3.4.
(f) Air requirements for the operation of exhaust fans,
kitchen ventilation systems, clothes dryers, and fireplaces
shall be considered in determining the adequacy of a space
to provide combustion air requirements.
5.3.2 Equipment Located in Unconfined Spaces: In
unconfined spaces (see definition below) in buildings,
infiltration may be adequate to provide air for combustion
ventilation and dilution of flue gases. However, in buildings
of tight construction (for example, weather stripping, heavily
insulated, caulked, vapor barrier, etc.), additional air may
need to be provided using the methods described in 5.3.3b or 5.3.4.
Space, Unconfined. For purposes of this Code, a space
whose volume is not less than 50 cubic feet per 1,000 BTU
per hour of the aggregate input rating of all appliances
installed in that space. Rooms communicating directly with
the space in which the appliances are installed through
openings not furnished with doors, are considered a part of
the unconfined space.
5.3.3 Equipment Located in Confined Spaces: (a)
from Inside the Building:
provided with two permanent openings communicating
directly with an additional room(s) of sufficient volume so
that the combined volume of all spaces meets the criteria
for an unconfined space. The total input of all gas utilization
equipment installed in the combined space shall be considered in making this determination. Each opening shall have
a minimum free area of 1 square inch per 1,000 BTU per
hour of the total input rating of all gas utilization equipment
in the confined space, but not less than 100 square inches.
One opening shall be within 12 inches of the top and one
within 12 inches of the bottom of the enclosure. (Figure 1 )
The confined space shall be
All Air
Figure 1
Equipment Located in Confined Spaces; All
Air from Inside Building. See 5.3.3-a
.
(b)
All Air from Outdoors:
provided with two permanent openings, one commencing
within 12 inches of the top and one commencing within 12
inches of the bottom of the enclosure. The openings shall
communicate directly, or by ducts, with the outdoors or
spaces (crawl or attic) that freely communicate with the
outdoors.
1. When directly communicating with the outdoors, each
opening shall have a minimum free area of 1 square
inch per 4,000 BTU per hour of total input rating of all
equipment in the enclosure (Figure 2).
The confined space shall be
Figure 2
Equipment Located in Confined Spaces; All
Air from Outdoors—Inlet Air from Ventilated
Crawl Space and Outlet Air to Ventilated
Attic. See 5.3.3-b
2. When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area
of 1 square inch per 4,000 BTU per hour of total input
rating of all equipment in the enclosure (See Figure 3).
5
Page 6
Figure 3
Equipment Located in Confined Spaces; All
Air from Outdoors Through Ventilated Attic.
See 5.3.3-b.
5.3.5 Louvers and Grilles:
In calculating free area in 5.3.3, consideration shall be
given to the blocking effect of louvers, grilles or screens
protecting openings. Screens used shall not be smaller
than 1/4 inch mesh. If the area through a design of louver
or grille is known, it should be used in calculating the size
of opening required to provide the free area specified. If the
design and free area is not known, it may be assumed that
wood louvers will have 20-25 percent free area and metal
louvers and grilles will have 60-75 percent free area.
Louvers and grilles shall be fixed in the open position or
interlocked with the equipment so that they are opened
automatically during equipment operation.
5.3.6 Special Conditions Created by Mechanical Exhausting or Fireplaces:
Operation of exhaust fans, ventilation systems, clothes
dryers, or fireplaces may create conditions requiring special attention to avoid unsatisfactory operation of installed
gas utilization equipment.
IV. Category I Venting (Vertical Venting)
3. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free
area of 1 square inch per 2,000 BTU per hour of total
input rating of all equipment in the enclosure. (Figure 4)
*If the appliance room is located against an outside wall and the air openings communicate
directly with the outdoors, each opening shall have a free area of not less than one square inch
per 4,000 BTU per hour of the total input rating of all appliances in the enclosure.
Figure 4
Equipment Located in Confined Spaces; All
Air from Outdoors. See 5.3.3-b.
4. When ducts are used, they shall be of the same crosssectional area as the free area of the openings to which
they connect. The minimum dimension of rectangular
air ducts shall not be less than 3 inches.
5.3.4 Specially Engineered Installations:
The requirements of 5.3.3 shall not necessarily govern
when special engineering, approved by the authority having jurisdiction, provides an adequate supply of air for
combustion, ventilation, and dilution of flue gases.
WARNING
To prevent possible death or personal injury
due to asphyxiation, Amana NonCondensing Gas Fired Warm Air Furnaces
must be Category I vented. Do not vent any
of these furnaces using Category III venting.
Category I Venting is venting at a non-positive pressure. A
furnace vented as Category I is considered a fan-assisted
appliance and does not have to be “gas tight.” NOTE:
Single stage gas furnaces with induced draft blowers draw
products of combustion through a heat exchanger allowing
in some instances common venting with natural draft appliances (i.e. water heaters).
All installations must be vented in accordance with National
Fuel Gas Code, NFPA 54/ANSI Z223.1 - latest edition. In
Canada, the furnaces must be vented in accordance with
the National Standard of Canada, CAN/CGA B149.1 and .2
- latest editions and amendments.
NOTE: The vertical height of the Category I venting system
must be at least as great as the horizontal length of the
venting system.
WARNING
To prevent possible death or personal injury
due to asphyxiation, common venting with
other manufacturer’s induced draft
appliances is not allowed.
Common venting with specific Amana Category I 80%
furnaces is allowed with the addition of a common vent kit
(CVK) for each appliance. Contact the local installing dealer,
distributor or Amana directly for more information.
6
Page 7
The minimum vent diameter for the Category I venting
system is as shown below:
MINIMUM VENT DIAMETER
MODELGUI*GCI*
453 Inch4 Inch
704 Inch4 Inch
904 Inch4 Inch
1155 Inch5 Inch
1405 Inch5 Inch
Under some conditions, larger vents than those shown
above may be required or allowed.
When an existing furnace is removed from a venting system
serving other appliances
large to properly vent the remaining attached appliances.
The following steps shall be followed with each appliance
remaining connected to the common venting system placed
in operation, while the other appliances remaining connected to the common venting system are not in operation.
(a) Seal any unused openings in the common venting
system.
(b) Visually inspect the venting system for proper size and
horizontal pitch as required in the National Fuel Gas
Code, ANSI Z223.1, or the CAN/CGA B149 Installation
Codes and these instructions. Determine there is no
blockage or restriction, leakage, corrosion or other
deficiencies which could cause an unsafe condition.
(c) Where practical, close all building doors, windows, and
all doors between the space where the appliances
remain connected to the common venting system are
located and other spaces of the building. Turn on all gas
appliances not connected to the common venting system and operate on high speed all exhaust fans (range
hoods and bathroom), except summer exhaust fans.
Close fireplace dampers.
(d) Following the lighting instructions, place the furnace
being inspected in operation. Adjust thermostat so
appliance will operate continuously.
(e) Test for spillage at the draft hood relief opening after 5
minutes of main burner operation. Use the flame of a
match or candle, or smoke from a cigarette, cigar, or
pipe.
(f) After it has been determined that each appliance re-
maining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and
any other gas-burning appliance to their previous conditions of use.
(g) If improper venting is observed during any of the above
tests, the common venting system must be corrected in
accordance with the latest edition of the National Fuel
Gas Code, ANSI Z223.1.
When resizing any portion of the common venting system,
use the appropriate table in Appendix G in the latest edition
of the National Fuel Gas Code, ANSI Z223.1.
Upflow or Horizontal units
draft blower discharging from the top of the furnace. (“Top”
is as viewed for an upflow installation.) The induced draft
blower can be rotated 90 degrees counterclockwise for
Category I venting, with the airflow horizontal left to right
(Figure 5). For horizontal installations, a 4-inch single wall
pipe can be used to extend the induced draft blower outlet
, the venting system may be too
are shipped with the induced
1/2” beyond the furnace cabinet. Vent the furnace in
accordance with the National Fuel Gas Code, NFPA54/
ANSI Z223.1 - latest edition. In Canada, vent the furnace
in accordance with the National Standard of Canada, CAN/
CGA B149 - latest editions and amendments.
Figure 5
Upflow Rotated Induced Draft Blower
Counterflow units
blower discharging from the top of the furnace. (“Top” as
viewed for an counterflow installation.) The induced draft
blower can be rotated 90 degrees counterclockwise for
Category I venting, with the airflow horizontal right to left
(Figure 6). For horizontal installations, a 3-inch B-vent pipe
can be used to extend the induced draft blower outlet 1/2”
beyond the furnace cabinet. Vent the furnace in accordance with the National Fuel Gas Code, NFPA54/ANSI
Z223.1 - latest edition. In Canada, vent the furnace in
accordance with the National Standard of Canada, CAN/
CGA B149 - latest editions and amendments.
Supply
Air
are shipped with the induced draft
Vent
Return
Air
Figure 6
Counterflow Rotated Induced Draft Blower
To rotate the induced draft blower counterclockwise proceed as follows:
1. Disconnect electrical power from furnace.
WARNING
To prevent death or personal injury due to
electrical shock, disconnect electrical
power.
2. Remove the round cutout from the side of the furnace.
Note: The assembly, starting from the outside, is
3. Remove and save the four screws which hold the
rotation plate on the partition panel. Note that one of the
screws which hold the induced draft blower on the
rotation plate needs to be removed.
4. Turn the rotation plate 90 degrees counterclockwise.
The inner gasket must turn with the rotation plate.
5. Reinstall the rotation plate on the partition panel, using
the four screws removed in step 3.Tighten screws to
provide an airtight seal.
6. Make sure all wires are at least one inch from flue pipe.
Relocate junction box to right side of cabinet if necessary. Refer to Section Vl for instructions.
V. Masonry Chimneys
WARNING
Possibility of property damage, personal
injury, or death - Damaging condensation
can occur inside masonry chimneys when
a single fan assisted Category I appliance
(80% AFUE furnace) is vented without
adequate dilution air. Do not connect an
80% furnace to a masonry chimney unless
the furnace is common vented with a draft
hood equipped appliance, or the chimney
is lined with a metal liner or Type B metal
vent. All installations using Masonry
chimneys must be sized in accordance with
the appropriate Venting Tables.
If an 80% furnace is common vented with a
draft hood equipped appliance, the potential
for condensation damage may still exist
with extremely cold conditions, long vent
connectors, exterior chimneys, or any
combination of these conditions. The risk
of condensation damage is best avoided by
using the masonry chimney as a pathway
for properly sized metal liner or Type B
metal vent.
Crown
Clay Tile Size Generally
12" x 12" (24" Len
th)
Wash
Roof Line
Clay Tile Size: 8" x 8" x12"
(Each x 24" Len
th)
WARNING
To prevent death or serious illness to
building occupants due to flue products
leaking into the building, proper installation
of gaskets and screws is essential for
providing a gas tight seal between the
partition panel and the induced draft blower.
Attic Floor
1/2" to 1" Air Space
Second Floor
Throat
Clean Out
Damper
Breech
F.A.F. Vent
Connector
Fan Assisted
Forced Air
Furnace
First Floor
Natural Draft
Water Heater
Figure 8
Typical Multiple Flue Clay Tile Chimney
8
Water Heater
Vent Connector
Basement Floor
Page 9
CHECKLIST SUMMARY
This checklist serves as a summary of the items to be
checked before venting an Air Command 80 furnace into a
masonry chimney. In addition, we recommend that a qualified serviceman use this checklist to perform a yearly
inspection of the furnace venting system.
This checklist is only a summary. For detailed information
on each of the procedures mentioned, see the paragraph
referenced with each item.
This inspection is based upon a draft topical report, “Masonry Chimney Inspection and Relining”, issued by the Gas
Research Institute. While not yet finalized, we believe this
report represents the best information on this subject which
is currently available.
CHECK 1 - PROPER CHIMNEY TERMINATION.
A masonry chimney used as a vent for gas fired equipment
must extend at least three feet above the highest point
where it passes through the roof. It must extend at least two
feet higher than any portion of a building within a horizontal
distance of 10 feet. In addition, the chimney must terminate
at least 3 feet above any forced air inlet located within 10
feet. The chimney must extend at least five feet above the
highest connected equipment draft hood outlet or flue
collar.
If the chimney does not meet these termination requirements, but all other requirements in the checklist can be
met, it may be possible for a mason to extend the chimney.
If this will not be practical, see Fix 1, page 12.
Proper Chimney
Termination?
(Check 1)
Yes
Chimney channel
free of solid and
liquid fuel
appliances?
(Check 2)
Yes
Crown in good
condition?
(Check 3)
Yes
Cleanout free of
debris?
(Check 4)
Yes
Line, terminate with
No
No
No
No
listed vent cap
(Fix 1)
Change venting
arrangements
(Fix 2)
Rebuild crown
(Fix 3)
and /or Reline
(Fix 4)
Reline
(Fix 4)
2' Min.
Ridge
10' or Less
2' Min.
Wall or
Parapet
Chimney
10' or Less
2' Min.
Chimney
3' Min.
3' Min.
Liner in good
condition?
(Check 5)
Yes
Dilution air
available?
(Check 6)
Yes
Complete the
installation.
(Check 7)
No
No
Reline
(Fix 4)
Reline
(Fix 4)
Figure 9
Termination 10 Feet Or Less From Ridge,
Wall or Parapet
9
Page 10
g
More than 10'
g
3' Min.
ht
10"
2' Min.
Chimney
Chimney
ht above any
Hei
roof surface within
10 feet horizontally.
3' Min.
Wall or
Parapet
Ridge
: No Hei
NOTE
above parapet
required when distance
from walls or parapet is
more than 10 feet.
More than 10'
Figure 10
Termination More Than 10 Feet From Ridge,
Wall or Parapet
CHECK 2 - ANY SOLID OR LIQUID FUEL
APPLIANCES VENTED INTO THIS CHIMNEY
CHANNEL
Solid fuel appliances include fireplaces, wood stoves, coal
furnaces, and incinerators.
Liquid fuel appliances include oil furnaces, oil-fired boilers
and oil-fired water heaters.
Appliances which burn propane (sometimes referred to as
LP (liquefied petroleum)) gas are considered gas-fired
appliances.
CHECK 3 - CHIMNEY CROWN CONDITION.
Damage from condensate usually shows up first in the
crown. If any of the following trouble signs are present, the
condition of the crown is not satisfactory:
a) Crown leaning
b) Bricks missing
c) Mortar missing
d) Tile liner cracked
e) No tile liner
f) Salt staining at mortar pints. (White stains, and mortar
becomes sandy and/or erodes.)
For problems a, b, or c, see Fix 3. If problems d, e, or f are
present, see Fix 4. IMPORTANT: It may be necessary to
follow both Fix 3 and Fix 4.
CHECK 4 - DEBRIS IN CLEANOUT
A cleanout (dropleg) must be present such that the upper
edge of the cleanout cover is at least 12 inches below the
lower edge of the lowest chimney inlet opening.
A chimney without a cleanout could become partially blocked
by debris. If no cleanout is present, the chimney must be
refined (Fix 4).
Remove the cleanout cover, and examine the cleanout for
debris. If significant amounts of any of the following are
found:
• Fuel oil residue
• Bricks
• Mortar or sand
• Pieces of the tile liner
• Rusted pieces of the metallic liner
reline the chimney (Fix 4).
CHECK 5 - LINER CONDITION.
If a metal liner is present, it must be checked. It cannot be
assumed that all existing metal liners are correctly installed
and in good condition.
Remove the lowest existing vent connector, and examine
the inside of the elbow or tee at the base of the liner. A small
amount of soot may be considered acceptable, provided
the installer vacuums it away. If rusted pieces of the liner
have collected here, the metal liner must be removed and
replaced (Fix 4).
Next, gently tap the inside of the liner with a phillips
screwdriver. If the screwdriver perforates the liner, or if the
tapping does not sound like metal hitting metal, the liner
must be removed and replaced (Fix 4).
Remember that all appliances must be vented inside the
liner. Venting one appliance inside the liner and another
appliance outside the liner is not acceptable.
Next, use a flashlight and small mirror to sight up the liner.
B vent must be supported so as to not come into direct
contact with the chimney walls or tile liner. If it is not, it can
probably be rehung so as to be acceptable. A thimble or fire
stop may be helpful here.
Flexible liners should be hung straight or nearly straight. If
it is spiraled in the chimney and in good condition, it should
be rehung. To do this, break the top seal; pull up and cut off
the excess liner length, and refit the top seal. Use caution
when doing this, as the cut edges of flexible liners may be
sharp.
The surfaces of the liner must be physically sound. If gaps
or holes are present, the metal liner must be removed and
replaced (Fix 4).
Finally, confirm that the metallic liner is the correct size for
the appliances to be installed. Use the GAMA tables and
rules.
If a metal liner is not present, a clay tile liner must be
present, or the chimney must be lined (Fix 4).
10
Page 11
Use a flashlight and small mirror at the cleanout or vent
connector to inspect the clay tile liner. If any of the following
problems are present:
• Tile sections misaligned
• Tile sections missing
• Gaps between tile sections
• Signs of condensate drainage at the cleanout or vent
connectors
• Mortar protruding from between tile sections
• Use of sewer pipe or drainage pipe rather than an
approved fire clay tile
reline the chimney (Fix 4).
Next, measure the size of the liner. It may be possible to do
this from the cleanout. The liner must be at least as large as
the minimum size established by the tables in National Fuel
Gas Code, NFPA 54/ANSI Z223.1 - latest edition and in the
National Standard of Canada, CAN/CGA B149.1 and .2 latest editions and amendments. If the liner is too small or
too large, then the chimney must be relined (Fix 4).
CHECK 6 - DILUTION AIR.
If gas-fired appliances are to be vented into a clay tile liner,
a source of dilution air is required.
Dilution air cannot be obtained through:
• Induced draft appliances
• Natural draft appliances with vent dampers
Sufficient dilution air can ordinarily be obtained through the
draft hood of a natural draft appliance only if the appliance’s
vent connector does not include a vent damper.
If dilution air will not be available, the chimney must be
relined (Fix 4).
CHECK 7 - COMPLETE THE INSTALLATION.
If Checks 1 through 6 have been satisfactory, and the liner
is an acceptable size as determined by the tables in
National Fuel Gas Code, NFPA 54/ANSI Z223.1 - latest
edition and in the National Standard of Canada, CAN/CGA
B149.1 and CAN/CGA B149.2 - latest editions and amendments, then the clay tile liner can probably be used as a vent
for the gas appliances. However, the installer must keep in
mind the following factors which may render the tile liner
unsuitable for use as a vent:
• Extremely cold weather
• Long vent connectors
• Masonry chimneys with no air gap between the liner
and the bricks. (In practice, this can be difficult to
detect.)
• Exterior chimneys (The tables in National Fuel Gas
Code, NFPA 54/ANSI Z223.1 - latest edition and in the
National Standard of Canada, CAN/CGA B149.1 and
CAN/CGA B149.2 - latest editions and amendments
assume interior chimneys.)
If, in the judgment of the local gas utility, installer, and/or
local codes; one or more of the above factors is likely to
present a problem, the chimney must be relined (Fix 4).
FIX 1 - LINER TERMINATION.
Any cap or roof assembly used with a liner must be
approved by the liner manufacturer for such use. The liner
and cap/roof assembly must then terminate above the roof
in accordance with the manufacturer’s instructions.
In some cases, a shorter extension above the roof may be
possible with a liner than would be required with a masonry
chimney.
For further information on relining, see Fix 4.
FIX 2 -CHANGE VENTING ARRANGEMENTS
If the masonry chimney has more than one channel, it may
be possible to vent the gas appliances into one channel and
vent the solid or liquid fuel appliance(s) into another
channel(s). Do not vent an Air Command 80 inside of a
metal liner with other appliances vented outside the liner.
Alternatively, the homeowner may agree to discontinue use
of the fireplace (solid fuel appliance). If so, the tile liner must
be cleaned to remove creosote buildup. The fireplace
opening must then be permanently sealed.
If oil-fired appliance(s) are being replaced by gas-fired
appliance(s), the tile liner must first be cleaned to remove
the fuel oil residue.
If none of the above options is practical, the Air Command
80 may need to be vented vertically with a B Vent.
Under some conditions an Air Command 90 or 95 could be
installed rather than an Air Command 80. The Air Command 90 or 95 can be vented horizontally or vertically
through PVC pipe.
FIX 3 - REBUILD THE CROWN.
If the chimney crown is damaged, a qualified mason must
repair it in accordance with nationally recognized building
codes or standards. One such standard which may be
referenced is the Standard for Chimneys, Fireplaces, Vents,
and Solid Fuel Burning Appliances, ANSI/NFPA 211.
FIX 4 - RELINING.
Relining options include B vent and flexible liners.
If the chimney has diagonal offsets, B vent probably cannot
be used.
If B vent is to be used, it must be supported adequately.
Supports (such as fire stops or thimbles) must be used to
prevent the B vent from coming into direct contact with the
tile liner or chimney walls. Direct contact would result in
higher heat loss, with an increased possibility of poor
venting system performance.
It is not acceptable to vent one appliance inside the B vent
and other appliances outside. The excess space between
the B vent and the chimney walls must be covered at the top
of the chimney by a weatherproof, corrosion resistant
flashing.
The B vent should then be topped with a listed vent cap. The
listed vent cap will, when installed per the manufacturer’s
instructions, prevent problems due to rain, birds, or wind
effects.
11
Page 12
A B-vent installed as described in this section is considered
to be an enclosed vent system, and the sizing tables in
National Fuel Gas Code, NFPA 54/ANSI Z223.1 - latest
edition and in the National Standard of Canada, CAN/CGA
B149.1 and CAN/CGA B149.2 - latest editions and amendments may be used.
If a flexible liner is to be used, it must be made of the proper
materials:
• For most residential applications, an aluminum liner
should be acceptable.
• If the combustion air supplied to the furnace will be
contaminated with compounds containing chlorine or
fluorine, a liner of AL294C stainless steel should be
used. Common sources of chlorine and fluorine compounds include indoor swimming pools and chlorine
bleaches, paint strippers, adhesives, paints, varnishes,
sealers, waxes (which are not yet dried) and solvents
used during construction and remodeling. Various
commercial and industrial processes may also be
sources of chlorine/fluorine compounds.
• Heavier gauge 300 and 400 series stainless steel
liners were developed for use with oil or solid fuel
appliances. They are not suitable for use with gas-fired
appliances. Flexible liners specifically intended and
tested for gas applications are listed in the UL “Gas and
Oil Equipment Directory”. (UL Standard 1777).
For sizing of flexible liners, see Note 22 and the tables in
the National Fuel Gas Code, NFPA 54/ANSI Z223.1 latest edition and in the National Standard of Canada,
CAN/CGA B149.1 and CAN/CGA B149.2 - latest editions
and amendments.
To install the liner, read and follow the liner manufacturer’s
instructions and your local codes. Excess liner length
should be pulled out of the chimney and cut off. Use caution
when doing this, as the cut edges of flexible liners may be
sharp. Do not spiral excess liner inside of the chimney.
Support the liner as recommended by the liner manufacturer.
Some manufacturers of flexible liners offer an insulation
sleeve designed to be added to the liner before it is installed
in the chimney. (Poured insulation, either vermiculite or
other materials, is no longer recommended.) Insulation will
need to be added to the flexible liner if:
• It is required by the liner manufacturer’s instructions.
• The previous liner was properly sized and installed,
and suffered from condensation damage.
• It is required by your local building codes.
Even if none of those three conditions exist which require
additional liner insulation, the installer may wish to consider it if:
• The local climate is very cold
• The chimney is very tall
• The vent connectors used are very long or have a large
number of elbows
• Local experience indicates that flexible liners installed
without insulation are likely to have condensation
problems.
Insulation must be selected and installed in accordance
with the liner manufacturer’s instructions.
Finally, cap the chimney and terminate the liner in accordance with the liner manufacturer’s instructions.
VI. Gas Piping
The rating plate is stamped with the model number, type of
gas and gas input rating. Make sure the furnace is equipped
to operate on the type of gas available.
Inlet gas pressure must not exceed the maximum value
shown in table above.
NOTE: Adjusting the minimum supply pressure below the
limits in the above table could lead to unreliable ignition.
Gas input to the burners must not exceed the rated input
shown on the rating plate. Overfiring of the furnace could
result in premature heat exchanger failure. Gas pressures
in excess of 14 inches water column could result in permanent damage to the gas valve.
IMPORTANT NOTE: The furnace will naturally derate itself
with altitude. Do not attempt to increase the firing rate by
changing orifices or increasing the manifold pressure. This
can cause poor combustion and equipment failure.
At all altitudes, the manifold pressure must be within 0.3
inches WC of that listed on the “Specification Sheet” for the
fuel used. At all altitudes and with either fuel, the air
temperature rise must be within the range listed on the
furnace nameplate.
GAS PIPING
IMPORTANT NOTE: To avoid possible unsatisfactory op-
eration or equipment damage due to underfiring of equipment, do not undersize the natural/propane gas piping from
the meter/tank to the furnace. Include all appliances which
may be operated simultaneously when sizing a trunk line.
The gas pipe supplying the furnace must be properly sized
based on gas flow required, specific gravity of the gas and
length of the run. The gas line installation must comply with
local codes, or in the absence of local codes, with the latest
edition of the National Fuel Gas Code ANSI Z223.1.
(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on
0.60 Specific Gravity Gas)
BTUH Furnace Input
CFH =
Heati ng Value of Gas (BTU/Cubic Foot)
In Cubic Feet of Gas Per Hour (CFH)
12
Page 13
NATURAL GAS CONNECTION
Refer to Figure 11 for the general layout at the furnace. The
following rules apply:
1. Use black iron or steel pipe and fittings for the building
piping.
2. Use pipe joint compound on male threads only. Pipe
joint compound must be resistant to the action of the
fuel used.
3. Use ground joint unions.
4. Install a drip leg to trap dirt and moisture before it can
enter the gas valve. The drip leg must be a minimum of
three inches long.
5. Use two pipe wrenches when making connection to the
gas valve to keep it from turning.
gas valve on the manifold must be the same as shipped
from the factory.
6. Within six feet of the unit, install a manual cutoff valve
between the meter and the unit. If a union is installed,
the union must be downstream of the manual shutoff
valve, between the shutoff valve and the furnace.
7. Tighten all joints securely.
8. The furnace must be connected to the building piping
by one of the following:
The orientation of the
• Rigid metallic pipe and fittings.
• Semirigid metallic tubing and metallic fittings. Alumi-
num alloy tubing must not be used in exterior locations.
• Listed gas appliance connectors, used in accor-
dance with the terms of their listing, must be completely in the same room as the furnace.
• The connectors or semirigid tubing must be pro-
tected against physical and thermal damage when
installed. Aluminum-alloy tubing and connectors must
be coated to protect against external corrosion when
in contact with masonry, plaster or insulation or are
subject to repeated wettings by such liquids as water
(except rain water), detergents or sewage.
UPFLOW INSTALLATIONS
When the gas piping enters through the right side of the
furnace
(starting from the gas valve):
, the installer must supply the following fittings
• 90 degree elbow
• Close nipple
• 90 degree elbow
• Straight pipe to reach the exterior of the furnace (Figures 12 & 13).
Figure 12
Gas Inlet Through Furnace Right Side
A ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases, the
installer may also need to supply a transition piece from 1/
2" to another pipe size.
Figure 11
General Furnace Layout
Figure 13
Gas Inlet Through Furnace Bottom Side
(Upflow)
13
Page 14
When the gas piping enters through the left side of the
furnace, the installer must supply the following fittings
(starting from the gas valve):
• Straight pipe to reach the exterior of the furnace (Fig-
ures 14 & 15).
• A ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases,
the installer may also need to supply a transition piece
from 1/2 inch to another pipe size.
Figure 14
Gas Inlet Through Furnace Left Side
(Upflow)
Figure 15
Gas Inlet Through Furnace Top Side
(Upflow)
COUNTERFLOW INSTALLATIONS
When the gas piping enters through the left side of the
furnace, the installer must supply a straight pipe to reach
the exterior of the furnace (Figure 17).
Figure 17
Gas Inlet Through Left Side
(Counterflow)
A ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases, the
installer may also need to supply a transition piece from
1/2" to another pipe size.
When the gas piping enters through the right side of the
furnace, the installer must supply the following fittings
(starting at the gas valve):
• 90 degree elbow.
• Close nipple.
• 90 degree elbow.
• Straight pipe to reach exterior of furnace (Figure 18).
A ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases, the
installer may also need to supply a transition piece from
1/2 inch to another pipe size.
The gas piping connections shown in Figures 13 and 14 are
for a furnace equipped for a right hand discharge. Adaptation for left hand discharge should be self explanatory.
Figure 16
Horizontal Furnace
(Right Hand Discharge)
Figure 18
Gas Inlet Through Right Side
(Counterflow)
“Left side” and “right side” above are as viewed for a
counterflow installation. Adaptation for horizontal airflow
should be self explanatory.
14
Page 15
CHECKING GAS PIPING
CAUTION
To prevent personal injury or property
damage due to fire, the following
instructions must be performed regarding
gas connections, pressure testing, location
of shutoff valve and installation of gas
piping.
Before placing in operation, leak test the unit and gas
connections. To avoid the possibility of explosion or fire,
never use a match or open flame to test for leaks. Never
exceed specified pressures for testing. Higher pressure
may damage the gas valve and cause overfiring, resulting
in heat exchanger failure.
This unit and shutoff valve must be disconnected from the
gas supply piping system before supply piping system
pressure testing with test pressures in excess of 1/2 psig
(3.48 kPa).
This unit must be isolated from the gas supply system by
closing its manual shutoff valve before pressure testing of
gas supply piping system with test pressures equal to or
less than 1/2 psig (3.48 kPa).
For satisfactory operation, propane gas pressure must be
10 inch WC at the furnace manifold with all gas appliances
in operation. Maintaining proper gas pressure depends on
three main factors:
1. Vaporization rate, depending on temperature of the
liquid, and “wetted surface” area of the container or
containers.
2. Proper pressure regulation. (Two-stage regulation is
recommended for both cost and efficiency).
3. Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe
size will depend on length of pipe run and total load of
all appliances.
Complete information regarding tank sizing for vaporization, recommended regulator settings, and pipe sizing is
available from most regulator manufacturers and propane
gas suppliers.
Since propane gas will quickly dissolve white lead or most
standard commercial compounds, special pipe dope must
be used. Shellac base compounds resistant to the actions
of liquefied petroleum gases such as Gasolac, Stalactic,
Clyde’s or John Crane are satisfactory.
Refer to Figure 19 for typical propane gas installations.
TANKS AND PIPING - PROPANE GAS UNITS
WARNING
To prevent death, personal injury or property
damage due to fire or explosion caused by
a propane gas leak, install a gas detecting
warning device. Since rust can reduce the
level of odorant in propane gas, a gas
detecting warning device is the only reliable
way to detect a propane gas leak. Contact a
local propane gas supplier about installing
a gas detecting warning device.
WARNING
All metal inserts, screens or turbulators
must be removed from the heat exchanger
tubes when using propane gas. Failure to
comply could cause serious personal injury
or death. Failure to comply with this
requirement will also void warranty
coverage.
All propane gas equipment must conform to the safety
standards of the National Board of Fire Underwriters (See
NBFU Manual 58).
Figure 19
Propane Gas Installation (Typ.)
PROPANE GAS PIPING CHARTS
Sizin g Between First and Sec ond Stage Regulator
Maximum Propane Capac ities listed ar e bas ed o n 2 psi g pressure d r op a t 10 psi g se tting.
Capacities in 1,000 BTU/hour.
Pipe orNominal Pipe Size
TubingTubing Siz e, O. D. Type LSchedule 40
To convert to capacities at 15 psig settings - multi ply by 1.130
To convert to capacitie s at 5 psi g setti ngs - multiply by 0. 8 79
15
Page 16
Siz ing Between Single or S econd St a ge Regu lator and Appl iance*
Maxim um P ropane Capac ities Listed are Based on 1/2" W.C. pres s ure drop at 11" W . C. s etting .
Capacit i es in 1, 0 00 BTU/hour.
To prevent death, serious personal injury
or property damage due to fire or explosion
caused by a propane gas leak, install a gas
detecting warning device.
WARNING
If the propane gas furnace is installed in a
basement, an excavated area or a confined
space, a warning device is required due to:
• Propane gas is heavier than air and any
leaking gas can settle in any low areas
or confined spaces.
• Propane gas odorant may fade, making
the gas undetectable except with a
warning device.
If the presence of gas is suspected, follow
the instructions on Page 2 of this manual.
VIl. Electrical Wiring
WARNING
To prevent death or personal injury due to
electric shock, disconnect electrical power
before changing any electrical wiring.
Power supply to the furnace must be NEC Class 1, and
must comply with all applicable codes. The furnace must be
electrically grounded in accordance with the local codes or,
in their absence, with the latest edition of the National
Electrical Code, ANSI NFPA No. 70 and/or the CSA C22. 1
Electrical Code. A fused disconnect must be provided and
sized in accordance with the unit maximum overcurrent
protection.
Figure 20
Typical Field Wiring
(24 VAC Control Circuit)
A 40 VA transformer and an integrated electronic control
are built into the furnace to allow use with most cooling
equipment.
CAUTION
To avoid the risk of electrical shock, wiring
to the unit must be properly polarized and
grounded.
To provide more reliable sensing of flame, the
must run to the electrical panel.
Line voltage wiring
must enter into the junction box pro-
vided with the furnace.
As shipped, the junction box is attached to the left side of
the furnace (as viewed for an upflow installation). If this is
suitable for your installation, no changes are necessary.
If the line voltage wiring is to enter through the right side of
the furnace (as viewed for an upflow installation), relocate
the junction box as shown in Figure 21.
ground wire
CAUTION
When servicing controls, label all wires
before disconnecting. Wiring errors can
cause improper and dangerous operation.
After servicing is completed, always verify
proper operation.
The unit wiring harness is an integral part of the furnace.
Field alteration to comply with electrical codes should not
be required.
Junction
Box
Figure 21
Junction Box (Left Side)
16
Page 17
WARNING
To prevent death or personal injury due to
electric shock, disconnect electrical power.
Low Voltage
Terminals
Heating Fan
Off Adjustments
1. Remove both doors from the furnace.
2. Remove and save the screws holding the junction box
to the left side of the furnace.
3. Disconnect the hose from the pressure switch. Leave
the other end attached to the induced draft blower.
4. Remove five wires entering junction box from split
grommet in blower deck.
5. Swap locations of the two bushings in the junction box.
6. Rotate the junction box 180 degrees so the access
panel continues to face forward. The open snap bushing should now be at the bottom.
7. Insert five wires into the split grommet on the right side
of the blower deck.
8. Insert the five wires through the open bushing in the
bottom of the junction box.
9. Attach the junction box to the right side of the furnace,
using the screws removed in step 2.
10. Reconnect the hose to the pressure switch.
11. Check the location of the pressure hose and all wiring.
Confirm that it will not be damaged by heat from the
burners or by the rotation of the fan. Also confirm that
wiring location will not interfere with filter removal or
other maintenance.
After the junction box is in the desired location, use washers
to connect field-supplied conduit to the junction box in
accordance with NEC and local codes. Connect hot, neutral, and ground wires as shown in the furnace wiring
diagram. The wires and ground screw are located in the
furnace junction box.
Low voltage wiring may enter through the right or left side
of the furnace (as viewed for an upflow installation - top or
bottom for a horizontal installation). See Specification Sheet
for hole locations. Run the thermostat wires through either
grommet in the blower deck (Figure 21).
Low voltage wires may be connected to the terminal strip as
shown in Figure 22.
IMPORTANT NOTE: To avoid possible equipment malfunction, route the low voltage wires to avoid interference
with filter removal or other maintenance.
12
ON
OFF
Style A
OR
B1
B2
B3
Style B
B4
Pins (4)
Jumper
Figure 22
Integrated Ignition Control
(Viewed in an Upflow Installation)
AIR CIRCULATION BLOWER FAN TIMING
All items in this section refer to the air circulation blower fan,
not to the induced draft blower. The timing sequence for the
induced draft blower is not adjustable.
When a call for cooling occurs, the circulation fan will come
on. It will remain on for 45 seconds after the call for cooling
ends. This fan timing is not adjustable.
During normal heating operation, the circulation fan will
come on 37 seconds after the gas valve opens. This timing
is not adjustable.
As shipped, the circulation fan will remain on for 90 seconds
after the gas valve closes. If desired, this timing may be
adjusted. The adjustment pins or switches are near the low
voltage terminal strip (Figure 23).
Style B
B2
B1
B4
B2
B1
B4
B2
B1
B4
B2
B1
B4
B3
B3
B3
B3
60
Second
Delay
90
Second
Delay
120
Second
Delay
180
Second
Delay
Style A
12
ON
12
ON
12
ON
12
ON
OFF
OFF
OFF
OFF
17
Switches viewed in an upflow installation.
Figure 23
Heating Fan Off Adjustments
Page 18
HEAT ANTICIPATOR SETTING
Adjust the heat anticipator in the room to obtain the proper
number of heating cycles per hour. The heat anticipator is
a wire-wound adjustable heater that prevents the room
temperature from “overshooting” the room thermostat setting. The heat anticipator must be set at 0.7 amps. The heat
anticipator is part of the thermostat. If the thermostat fails
for any reason, replace the thermostat.
LINE VOLTAGE CONNECTION FOR OPTIONAL
HUMIDIFIER AND ELECTRONIC AIR CLEANER
The control module is equipped with line voltage accessory
terminals used for controlling the power to an optional fieldsupplied humidifier and/or electronic air cleaner.
Accessory Load Specification
Air Cleaner: 1.0 Amp max. at 120 VAC
Humidifier: 1.0 Amp max. at 120 VAC
Accessory Installation:
Follow the electronic air cleaner and humidifier manufacturers’ instructions for mounting and electrically grounding
these accessories. Check that the power supply to the
furnace has been disconnected. Wire the accessories to
the control module as shown below. All connections to the
control module are to be made through 1/4 inch female
terminals.
If it is necessary to supply additional line voltage wiring to
the interior of the furnace, the wiring must comply with all
local codes. This wiring must have a minimum temperature
rating of 105°C and must be routed away from the burner
compartment. All line voltage wire splices must be made
inside the furnace junction box.
Control Module
Hot 120 VAC
Cool
Heat
Park
Optional
Accessories
Park
Transformer
Line
{
EAC
Hum
Air
Cleaner
Humidifier
Neutral
120 VAC
Line
Cir
Transformer
EAC
Hum
Figure 24
Line Voltage Connection for Accessories
Accessory Operation: The furnace control module ener-
gizes the humidifier whenever the induced draft blower is
energized (when an air cleaner is installed on the system,
the humidifier is not energized until the air cleaner is
energized). The control module energizes the air cleaner
whenever the air circulation blower is energized.
VIlI. Circulating Air and Filters
DUCTWORK - AIR FLOW
Duct systems and register sizes must be properly designed
for the CFM and external static pressure rating of the
furnace. Ductwork should be designed in accordance with
the recommended methods of “Air Conditioning Contractors of America” Manual D.
A duct system must be installed in accordance with Standards of the National Board of Fire Underwriters for the
Installation of Air Conditioning, Warm Air Heating and
Ventilating Systems. Pamphlets No. 90A and 90B.
A closed return duct system must be used, with the return
duct connected to the furnace. Supply and return connections to the furnace may be made with flexible joints to
reduce noise transmission. To prevent the blower from
interfering with combustion air or draft when a central return
is used, a connecting duct must be installed between the
unit and the utility room wall. A room, closet, or alcove must
not be used as a return air chamber.
When the furnace is used in connection with a cooling unit,
the furnace should be installed in parallel with or on the
upstream side of the cooling unit to avoid condensation in
the heating element. With a parallel flow arrangement, the
dampers or other means used to control the flow of air must
be adequate to prevent chilled air from entering the furnace
and, if manually operated, must be equipped with means to
prevent operation of either unit unless the damper is in the
full heat or cool position.
When the furnace is installed without a cooling coil, it is
recommended that a removable access panel be provided
in the outlet air duct. This opening shall be accessible when
the furnace is installed and shall be of such a size that the
heat exchanger can be viewed for visual light inspection or
such that a sampling probe can be inserted into the airstream. The access panel must be made to prevent air
leaks when the furnace is in operation.
When the furnace is heating, the temperature of the return
air entering the furnace must be between 55°F and 100°F.
When a furnace is installed so that supply ducts carry air
circulated by furnace to areas outside the space containing
the furnace, the return air shall also be handled by a duct
sealed to the furnace casing and terminating outside the
space containing the furnace.
Filters - Read This Section Before Installing The Return
Air Ductwork
Filters must be used with this furnace. Discuss filter maintenance with the building owner. Filters do not ship with this
furnace, but must be provided by the installer. Filter(s) must
comply with UL900 or CAN/ULCS111 standards. If the
furnace is installed without filters, the warranty will be
voided.
The following chart shows recommended minimum filter
sizes for each furnace model. Larger sizes are also acceptable.
18
Page 19
Min imum Recommended Filter Sizes
Qty. - Nominal Size, Inches (Sq. In. Surfac e Area)
Size_Air FlowDisposablePermanent
045_301 - 20 X 25 (500)1 - 15 X 20 (300)
070_301 - 20 X 25 (500)1 - 15 X 20 (300)
070_402 - 14 X 25 (350)1 - 16 X 25 (400)
090_301 - 24 X 24 (576)1 - 16 X 25 (400)
090_502 - 18 X 25 (450)1 - 20 X 25 (500)
115_402 - 14 X 25 (350)1 - 18 X 25 (450)
115_502 - 18 X 25 (450)1 - 20 X 25 (500)
140_502 - 18 X 25 (450)1 - 20 X 25 (500)
Figure 25
Upflow/Horizontal Furnaces
Guide dimples locate the side and bottom return cutout
locations. Use a straight edge to scribe lines connecting the
dimples. Cut out the opening on these lines. An undersized
opening will cause reduced airflow. For bottom return
connection, remove the bottom of the cabinet before setting
the furnace on the raised platform or return air duct.
HORIZONTAL INSTALLATIONS
Filter(s) must be installed external to the furnace casing.
Using a central return with filters installed in the duct behind
the return air grille allows filters to be replaced by just
removing the grille. This prevents having to go into the attic
or crawl space when a filter has to be changed.
Refer to the preceding chart on Recommended Minimum
Filter Sizes. (Figure 25)
UPFLOW INSTALLATIONS
This furnace contains rails for installing 16 x 25 x 1 filters on
each side of the interior furnace cabinet. A retainer is also
included for bottom return. Refer to the chart below for filter
sizes when using bottom return.
Bottom Return Air Filters
SizeFilter Size, InchesType
045, 07014 X 25 X 1P
9016 X 25 X 1P
115, 14020 X 25 X 1P
Figure 26
Bottom Return
Filter Sizes
The illustration below shows how the filter is retained over
the bottom return air opening.
COUNTERFLOW INSTALLATIONS
A filter rack is shipped with the furnace. To use this rack,
proceed as follows:
Figure 28
Furnace Mounted Filter Rack
1. Center the filter rack over the plenum flange and push
down firmly (Figure 28). Since the return air plenum will
need to be attached later, do not screw the filter rack
down.
2. Install the return air plenum on the furnace. For proper
filter performance, the sides of the plenum must be at
least as tall as dimension “A” shown in Figures 29 and
30.
Return Air
Figure 27
Filter Retainer
One inch throwaway filters should be sized for a face
velocity of 300 feet per minute or less (14 x 25 x 1
throwaway = 730 CFM max.; 16 x 25 x 1 throwaway = 830
CFM max.; 18 x 25 x 1 throwaway = 940 CFM max.; 20 x
25 x 1 throwaway = 1040 CFM max.) All other filters should
be sized according to their manufacturer’s instructions.
For air delivery of less than 1800 CFM; use one side return
or bottom return.
For air delivery of 1800 CFM or higher; use two side returns,
or one side return plus bottom return.
Optional
Access
Door
"A"
Min
Figure 29
Return Air Plenum Installation
NOTE: For easier filter inspection and replacement, the
installer may wish to provide a removable panel in the front
of the return air plenum.
19
Page 20
Heating
Timing Chart for Integrated Ignition Control Normal Heating Operation
Air Circulation Blower
Induced Draft Blower
Gas Valve
Ignitor
Pressure Switch
Combustion Blower
Thermostat
On
Off
Open
Closed
On
Off
Closed
Open
On
Off
On
Off
Seconds* 0 17 21 24 54 0 5 60, 90, 120,
or 15 or 180
* Timings may vary ±2 secon ds.
Integrated Ignition Control
Diagnostic Signal Chart
Refer to Abnormal
Light Signa l
Operation Number
Continuous Li ght1 Internal Cont rol F ail ure
1 Fl as h2 Sy st em Lock out
2 Fl as hes3 Pres sure Switc h S tuc k Clos ed
3 Flashes4 Pressure Switch Stuck Open
4 Fl as hes5 Open Limit Cont rol
5 Fl as hes6 Open Rollout Cont rol
Continuous F l ashing7 Flame Sens ed No Call F or Heat
Timing Chart for Normal Cooling Operation
Indoor Fan
Outdoor Fan
And
Compresso r
On
Off
On
Off
Thermostat
On
Off
Seconds 0 45
20
Page 21
CAUTION
Size_Air
Dimens ion "A",
Inches
Minimum R ecommended
Filter Sizes, Inches
Flow
Throwaway
Perm.
Fiberglass
Throwaway
Permanent
To prevent personal injury, use only blunt
pointed screws to attach the plenum to the
furnace and filter rack. Screws should not
be placed where they could interfere with
filter replacement.
3. With the air flow direction arrow pointing toward the
furnace, insert the filters from the left side of the blower.
Starting with the right filter, push the filter into the
plenum so the bottom of the filter fits into the filter rack
and the upper edge rests against the side of the
plenum. Repeat with the left filter (Figure 29).
OTHER FILTER OPTIONS
External filter grilles can be used instead of the filter rack.
IX. Sequence of Operation (Integrated
Ignition Control)
Refer to Timing Charts for sequencing.
NORMAL HEATING SEQUENCE
1. Thermostat calls for heat.
2. The induced draft blower is energized.
3. The ignitor is energized and is allowed to preheat for 17
seconds.
4. The gas valve is energized delivering gas to the burners
and starting combustion.
5. The control checks for a signal from the flame sensor
within seven seconds after the gas valve is energized.
Gas will only continue to flow if a signal is present.
6. The control waits 30 seconds and turns on the air
circulation blower to the speed that was selected for
heating operation.
7. The thermostat is satisfied and opens.
8. The control de-energizes the gas valve.
9. After a 15 second delay while flue products are purged
from the furnace heat exchanger, the induced draft
blower motor is de-energized.
10. The air circulation blower has an adjustable delay-off
timing of 60, 90, 120 or 180 seconds (starting from the
time the gas valve closes). This allows more heat from
the furnace to be transferred to the conditioned space.
After this time has elapsed, the blower will be deenergized.
NORMAL COOLING SEQUENCE - INTEGRATED
IGNITION CONTROL
With the room thermostat in the FAN-AUTO position, the
indoor air circulation blower and outdoor condensing unit
will be energized when a call for cooling occurs. When the
call for cooling ends, the outdoor condensing unit will be deenergized. The indoor air circulation blower will continue to
run for 45 seconds.
OTHER ITEMS
Constant Fan. During normal operation, the air circu-
lation blower will continually run at “Cooling” speed as
long as power is present at terminal G. If a call for heat
occurs, the blower will run at heating speed throughout
the heating cycle.
If a trip on high/auxiliary/rollout limit occurs, the air
circulation blower will run at “Heating” speed. Even if
power is present at terminal G, the blower will run at
heating speed until the limit closes.
X. Start-Up, Adjustments, and Checks
GENERAL OPERATION
This furnace is equipped with an electronic ignition device
to light the burners and an induced draft blower to exhaust
combustion products.
An interlock switch prevents furnace operation if the blower
door is not in place. Keep the blower access doors in place
except for inspection and maintenance.
This furnace is also equipped with a self-diagnosing electronic control module. In the event a furnace component is
not operating properly, the control module LED will flash
on and off in a factory-programmed sequence, depending
on the problem encountered. This light can be viewed
through the observation window in the blower access door.
Refer to the
of the lighting codes and Section X,
Integrated Ignition Control
sible problem.
On new installations, or if a functional part such as the gas
valve, pressure switch, or limit control has been replaced,
verify that the furnace is operating properly after servicing.
Check furnace operation as outlined in the following instructions. If any sparking, odors, or unusual noises are
encountered, shut off electrical power and recheck for
wiring errors, or obstructions in or near the blower motors.
Various shipping materials must be removed before the
blower motor is operated.
Diagnostic Signal Chart
for an explanation of the pos-
for further explanation
Abnormal Operation -
21
Page 22
ROLLOUT PROTECTION DEVICE
If the flames from the burners are not properly drawn into
the heat exchanger, a protection device will open causing
the gas valve to close. In GUI(-) furnaces installed horizontal right-to-left airflow, the device must be relocated.
Supply
Air
Return
Air
Figure 31
Right To Left Installation
Return
Air
Supply
Air
Figure 32
Left To Right Installation
If relocation is required, proceed as follows:
1. Disconnect electrical power.
WARNING
To prevent death or personal injury due to
electric shock, disconnect electrical power.
Figure 33
Rollout Switch Relocation (Upflow)
2. See Figures 33 and 34. Remove the cover from the
burner box. Save the screws that held it in place. (Note:
There are several screw holes, but only four screws.
This is intentional, and not a manufacturing defect.)
3. As shipped, the rollout protection device is located near
the flame sensor end of the manifold assembly. Remove and save the mounting screws.
4. For most installations, it will not be necessary to remove
the wires from the rollout protection device.
5. For horizontal-left installations, a hole is provided near
the ignitor end of the manifold assembly. Insert the
rollout protection device into this hole and attach with
screws removed in step 3.
6. Secure rollout wires to manifold and insure no wires can
come in contact with burners or other hot surfaces.
7. Push the button to confirm the rollout control is in the
closed position.
8. Replace the cover on the burner box, placing the
screws from step 2 in their original locations.
WARNING
To prevent death, personal injury or property
damage due to fire or explosion, a qualified
servicer must determine the reason the
rollout protection device opened before the
device is reset.
Figure 34
Rollout Switch Relocation
(Counterflow)
22
Page 23
BURNER BOX
This furnace must use indoor air for combustion. It is not a
direct vent furnace, and it cannot be installed as a direct
vent furnace. The burner box (on some models) is present
only to reduce the burner sound transmission.
AUXILIARY LIMIT CONTROL (FIGURE 35)
A manual reset limit is located on the blower side of the
blower deck, near the center. To access this auxiliary limit,
disconnect the electrical power and remove the blower
door. If the limit control opens, the air circulation blower will
run continuously. The diagnostic light will flash four times.
These symptoms are identical to a trip of the primary limit
control. See Section X,
Ignition Control
The auxiliary limit control is designed to prevent furnace
operation in case of main blower failure on horizontal and
counterflow installations. It may also open if the power
supply is interrupted while the furnace is firing.
The auxiliary limit control is suitable for both horizontal right
and horizontal left installations. Regardless of airflow direction, it does not need to be relocated.
for diagnosis.
Abnormal Operation - Integrated
WARNING
To prevent death, personal injury or property
damage due to fire, follow these directions
for the auxiliary limit control. If the auxiliary
limit control opens, it may be reset one time
only.
(SERVICER’S NOTE: If it becomes necessary to slide the
blower assembly out of the furnace, the auxiliary limit
control should be removed first. After the blower assembly
is reinstalled, the auxiliary limit must be reinstalled.)
Figure 35
Auxiliary Limit Control
ABNORMAL OPERATION - INTEGRATED IGNITION
CONTROL
The following presents the probable causes of questionable furnace operation and how to fix them. Look through
the observation window in the blower access door and
make a note of the number of flashes in sequence between
pauses. Next, refer to the
interpretation of the signals and to this section for a description.
1. Internal Control Failure with Integrated Ignition
Control
An internal control failure occurs when the integrated
ignition control senses an internal problem and stops
the unit.
To solve this problem, replace the ignition control.
2. System Lockout
A system lockout occurs when the integrated ignition
control determines that a measurable combustion cannot be established or maintained after three consecutive tries (four, if flame is established then lost) to turn
on the furnace.
If a flame is not sensed during the first six seconds after
a gas valve has been energized, the ignition control will
internally turn off the gas. After 60 seconds, during
which time the induced draft blower purges the heat
exchanger, the ignitor will re-energize and preheat for
27 seconds. The gas valve is then re-energized. If a
flame is not sensed again in six seconds, the gas valve
will de-energize and another purge is performed. The
ignition control will cycle the gas valve
before it determines it cannot establish measurable
combustion and enter a lockout state. If a flame is
sensed but lost after 10 seconds, the control will cycle
four more times
ignition attempts and causes the air blower to run
continuously. The diagnostic light will indicate either
condition with one short flash followed by a longer off.
The control can be reset and brought out of lockout
mode by turning the thermostat off and then back on. It
can also reset by turning off the electrical disconnect
switch to the furnace for 30 seconds. The control will
reset after one hour.
IMPORTANT: If you have to frequently reset your furnace,
it means that a problem exists that should be corrected.
Contact a qualified servicer for further information.
3. Pressure Switch Stuck Closed
A sticking pressure switch can be caused by either a
faulty pressure switch, faulty wiring, a disconnected
hose, or a restricted intake or flue piping. In the case
of a pressure switch sticking closed, the probable
cause is a faulty pressure switch or wiring.
If the ignition control senses that the pressure switch
is closed and the induced draft blower is off, it will shut
down the unit until the fault is corrected. The light code
for this problem is two short flashes followed by a
longer pause.
4. Pressure Switch Stuck Open
A sticking open pressure switch can be caused by a
faulty pressure switch, a disconnected hose to the
pressure switch, a restricted air intake or flue piping, or
a faulty wiring.
If the ignition control senses that the induced draft
blower is energized but the pressure switch is not
closed, the control will keep the blower on and wait for
the switch to close. The diagnostic light code for this
problem is three short flashes followed by a pause.
Diagnostic Signal Chart
for an
three times
before locking out. A lockout stops
23
Page 24
5. Open Limit Control (Primary or Auxiliary)
An open limit control can be caused by a low conditioned air flow due to dirty filter or resistance in duct
work, a faulty blower, a blower speed set too low, or a
faulty limit.
When the limit control opens, the induced draft and air
circulation blowers are turned on. The induced draft
blower will remain on for the first fifteen seconds of this
period. The air circulation blower will remain on until
the limit control is closed. The diagnostic light code for
this is four short flashes followed by a pause.
6. Open Rollout Control
An open rollout control is can be caused by insufficient
combustion air, a restricted flue passage, or a restricted heat exchanger.
The opening of the rollout control signals the air circulation blower and the induced draft blower to turn on.
The air circulation blower will remain on until the limit
is manually reset. The induced draft blower will remain
on for the first fifteen seconds of this period. The
diagnostic light code for this is five short flashes
followed by a pause.
7. Flame Sensed with No Call for Heat
If the control senses a flame when the gas valve is deenergized, it will run the air circulation blower and the
induced draft blower continuously. The diagnostic light
code for this is continuous light flashing. Probable
cause is miswiring.
8. Replace the door on the front of the furnace.
9. Open the manual gas valve external to the furnace.
10. Turn on the electrical power supply to the furnace.
11. Set the room thermostat to the desired temperature.
NOTE: There is an approximate 20 second delay between
thermostat energizing and burner firing.
Gas Valves
Figure 36
Honeywell Model VR-8205
OPERATING INSTRUCTIONS
1. Close the manual gas valve external to the furnace.
2. Turn off the electrical power supply to the furnace.
3. Set room thermostat to lowest possible setting.
4. Remove the door on the front of the furnace.
Note: This furnace is equipped with an ignition device to
automatically light the burners. Do not try to light burners
by hand.
5.
Honeywell Model VR8205, or White Rodgers Model
36E36, or Robertshaw Model 7222:
Turn the gas
control knob clockwise to the OFF position.
Note: The knob should turn easily. Do not use exces-
sive force.
White Rodgers Model 36E22:
Push the switch to the
OFF position.
6. Wait five minutes to clear out any gas. Then smell for
gas, including near the floor.
7. If gas can be smelled following the five minute waiting
period in Step 6, immediately follow the instructions on
Page 2 of this manual. If you do not smell gas after five
minutes:
Honeywell Model VR8205, or White Rodgers Model
36E36, or Robertshaw Model 7222:
Turn the gas
control knob counterclockwise to the ON position. The knob should turn easily. Do not use exces-
sive force.
White Rodgers Model 36E22:
Push the switch to the
ON position.
Figure 37
White Rodgers Model 36E36
Gas Control
Valve Lever
(In ON Position)
INLET
Inlet Press ur e Tap
Figure 38
Robertshaw Model 7222
Outlet Pressure Tap
(Side of Valve)
OUTLET
Pressure Regulator
Adjustment (Under
Cap Screw)
24
Page 25
Redundant
Solenoid
INLET
ON/Off
Switch
WR
1
M
3
P
O
F
F
2
C
ON
Main
Solenoid
OUTLET
Inlet Pressure Tap
(Side of Valve)
Main Regulator
Adjust
Outlet Pressure Tap
(Side of Valve)
Figure 39
White Rodgers Model 36E22
CHECK GAS INPUT AND PRESSURES
Gas supply pressure and manifold pressure with the burners operating must be as specified on the rating plate.
CHECKING GAS PRESSURE
Gas inlet pressure should be checked and adjusted in
accordance to the type of fuel being consumed.
With Power and Gas Off:
1.
Honeywell Model VR8205, or White Rodgers Models
36E36 or 36E22, or Robertshaw Model 7222:
Connect
a water manometer or adequate gauge to the “inlet
pressure tap” of the gas valve.
As an alternative method, inlet gas pressure can also
be measured by removing the cap from the drip leg and
installing a predrilled cap with a hose fitting (Figure 41).
With Power and Gas On:
2. Put furnace into heating cycle and turn on all other gas
consuming appliances.
Inlet Gas Pressure Must Not Exceed the Maximum Value Shown.
Figure 40
If operating pressures differ from above, make necessary
pressure regulator adjustments, check piping size, etc.,
and/or consult with local utility.
Figure 41
Measuring Inlet Gas Pressure
(Alternate Method)
CHECK MANIFOLD PRESSURE
A tapped opening is provided in the gas valve to facilitate
measurement of the manifold pressure. See the “Outlet
Pressure Tap” in Figures 36, 37, 38, & 39. A “U Tube”
manometer having a scale range from 0 to 12 inches of
water should be used for this measurement. The manifold
pressure must be measured with the burners operating .
To adjust the pressure regulator, remove the adjustment
screw or cover on the gas valve. Turn out (counterclockwise)
to decrease pressure, turn in (clockwise) to increase pressure. Only small variations in gas flow should be made by
means of the pressure regulator adjustment. For natural
gas, the manifold pressure must be between 3.2 and 3.8
inches water column (3.5 nominal). For propane gas, the
manifold pressure must be between 9.7 and 10.3 inches
water column (10.0 nominal). Any major changes in flow
should be made by changing the size of the burner orifice.
CHECK GAS INPUT (NATURAL GAS ONLY)
To measure the gas input using the gas meter proceed as
follows:
1. Turn off gas supply to all other appliances except the
furnace.
2. With the furnace operating, time the smallest dial on the
meter for one complete revolution. If this is a 2 cubic
foot dial, divide the seconds by 2; if it is a 1 cubic foot
dial, use the seconds as is. This gives the seconds per
cubic foot of gas being delivered to the furnace.
25
Page 26
3. INPUT = GAS HTG VALUE x 3600 SEC. PER CUBIC
FOOT (3600 is a conversion factor- 3600 seconds = 1
hour.)
Example: Natural gas with a heating value of 1000 BTU
per cubic foot and 34 seconds per cubic foot as determined by Step 2, then:
Input = 1000 x 3600 x 34
= 106,000 BTU per Hour
NOTE: BTU content of the gas can be obtained from the
gas supplier.
This measured input must not be greater than the input
indicated in Specification Sheet.
4. Relight all other appliances turned off in Step 1. Be sure
all pilot burners are operating.
CHECK BURNER FLAMES
Flames should be stable, soft and blue, (dust may cause
orange tips but they must not be yellow), extending directly
outward from the burners without curling, floating or lifting
off.
CHECK TEMPERATURE RISE
Check the temperature rise through the unit by placing
thermometers in supply and return air registers as close to
the furnace as possible. Be sure the thermometers do not
“see” the heat exchangers or false readings could be
obtained.
1. All registers must be open, all duct dampers must be in
their final (fully or partially open) position, and the unit
operated for 15 minutes before taking readings.
2. The temperature rise must be within the range specified
on the rating plate or Specification Sheet.
NOTE: Air temperature rise is the temperature difference
between supply and return air.
With a properly designed system, the proper amount of
temperature rise will normally be obtained when the unit is
operated at rated input with the “as shipped” blower speed.
If the correct amount of temperature rise is not obtained, it
may be necessary to change the blower speed. A faster
blower speed will lower the temperature rise. A slower
blower speed will increase the temperature rise.
NOTE: Blower speed must be set to give the correct air
temperature rise through the furnace as marked on the
rating plate.
Connect the correct motor leads to the COOL, HEAT, and
PARK terminals. If heating speed will equal cooling speed,
use the jumper wire provided. All unused motor leads that
are not connected to “PARK” terminals on the control must
be taped to prevent shorts.
Figure 42
High Limit Control
CHECK HIGH LIMIT CONTROL
WARNING
To prevent death, personal injury, property
damage or premature failure of heat
exchanger, do not adjust the limit control
(factory preset).
Check limit control operation after 15 minutes of operation
by blocking the return air grille(s).
1. After several minutes the burners must go OFF. Blower
will continue to run.
2. Remove air restrictions and burners will relight after a
cool down period of a few minutes.
Adjust the thermostat setting below room temperature
1. Burners must go off.
2. Circulating air blower will continue to run for 60, 90, 120
or 180 seconds as set.
IMPORTANT NOTE: This unit must not be used as a
construction heater during the finishing phases of construction of a new structure. This type of use may result in
premature failure due to extremely low return air temperatures and exposure to corrosive or very dirty atmospheres.
CHANGING BLOWER SPEEDS
WARNING
To avoid death or personal injury due to
electrical shock, turn off power to the furnace
before changing speed taps.
All furnaces ship at high speed for cooling and the speed
listed in Specification Sheet for heating. These speeds
should be adjusted by the installer to match the job requirements. See Specification Sheet for details.
TO TURN OFF FURNACE
1. Set the thermostat to lowest setting.
2. Turn off the electrical power supply to the furnace.
3.
Honeywell Model VR-8205, or White Rodgers Model
36E36, or Robertshaw Model 7222:
control knob clockwise to the OFF position.
The knob should turn easily. Do not use excessive
force.
White Rodgers Model 36E22:
position.
4. Close manual gas shutoff valve external to the furnace.
5. Replace the door on the unit.
26
Push switch to the OFF
Turn the gas
Page 27
XI. Maintenance
WARNING
To prevent death or personal injury due to
electric shock, disconnect electrical power
before performing any maintenance.
IMPORTANT NOTE: Handle the ignitor with care. Touch-
ing the ignitor body with bare fingers, rough handling, or
vibration could result in early ignitor failure. Only a qualified
servicer should ever handle the ignitor.
Have the furnace checked at least once a year, before the
heating season begins, to be sure there is adequate combustion air and the vent system is working properly.
Have vent pipe checked to be sure it is not blocked by debris
which could permit fumes to enter the house. Replace any
rusted or leaking sections of vent pipe.
To prevent death, personal injury or property
damage due to fire, never operate furnace
without a filter installed. Dust and lint will
build up on internal parts resulting in loss
of efficiency, equipment damage and
possible fire.
A return air filter is not supplied with this furnace; however,
there must be a means of filtering all of the return air. The
installer will supply filter(s) at the time of installation.
Filters should be inspected, cleaned or changed every two
months or as required. It is the owner’s personal responsibility to keep air filters clean. Remember - dirty filters are the
most common cause of inadequate heating or cooling
performance.
WARNING
To prevent death, personal injury or property
damage due to electrical shock, disconnect
electrical power to furnace before removing
filter or performing any other maintenance.
Become familiar with filter location and procedures for
removal, cleaning and replacing them. If help is needed,
contact the installer of the furnace or a qualified servicer.
AIR FILTER - UPFLOW FURNACES
If the filter is in the furnace retaining rails, remove it as
follows: Pull off the non-louvered door. The blower motor
will automatically stop through the interlock switch.
Grasp the lower portion of the filter, lift up to disengage it
from the lower railing, move towards blower, drop filter
down. Pull filter outward (Figure 43).
Replace the filter with the same type and size filter when
needed.
Use a vacuum cleaner to clean out the blower area and the
adjacent area of the return air duct.
Clean, wash and dry a permanent filter. When using a metal
filter, both sides should be sprayed with a dust adhesive as
recommended on adhesive container. Spray adhesives for
use with permanent metal filters can be found at some
hardware stores. Reinstall filter by placing it into the furnace
along the side of the blower. Engage filter in top rail, move
toward side of furnace and drop it into the bottom rail. BE
SURE AIRFLOW DIRECTION ARROW POINTS TOWARDS THE BLOWER.
When the filter is located in the bottom of the furnace on a
bottom return system the filter is held in place by a sheet
metal retainer strap. To change and clean the filter slide one
end of the retainer towards the front and remove filter.
AIR FILTER - COUNTERFLOW FURNACES
A furnace mounted filter rack, shipped with the furnace, can
be used in counterflow installation.
27
Page 28
The furnace-mounted filter rack
on the top of the furnace. Two filters fit into the rack and rest
against the sides of the return air plenum, forming a “V”
above the furnace.
The filters should be inspected frequently and cleaned or
replaced when necessary. In some installations, the filters
can be inspected after disconnecting the electrical power
and removing the optional access door in the return air
plenum. If this access panel is not present, proceed as
follows:
1. Disconnect the electrical power.
2. Remove the non-louvered door from the furnace.
3. Remove the left filter by reaching to the left side of the
blower, pushing the filter up slightly to remove it from
the filter rack, and pulling it down to the left of the blower
and out the blower door. Repeat with the right filter.
4a.Dirty throwaway filters must be replaced with the same
filter type and size.
4b.Dirty, permanent metal filters must be cleaned as
follows:
Wash, rinse, and dry the permanent filters. Both sides
should then be sprayed with a filter adhesive as is
recommended on the adhesive container. Many hardware stores stock spray adhesives for use with permanent filters.
If badly torn or uncleanable, these filters must be
replaced by equal size permanent, high velocity filters.
Throwaway filters must not be used as replacement for
permanent filters. Under normal use, permanent filters
should last for several years.
5. To reinstall the filters, first MAKE CERTAIN THE
AIRFLOW DIRECTION ARROW POINTS TOWARDS
THE FURNACE. Then insert the filters from the left side
of the blower. Starting with the right filter, push the filter
into the plenum so that the bottom of the filter rests in
the filter rack and the upper edge rests against the side
of the plenum. Repeat with the left filter (Figure 44).
6. Replace the blower door, then reconnect the electrical
power.
includes a rack mounted
BLOWER MOTOR
The air circulating blower motor bearings are permanently
lubricated. No further lubrication is required.
INDUCED DRAFT BLOWER MOTOR
The induced draft blower motor is permanently lubricated.
No further lubrication is required.
The fuel or combustion air supply can create a nearly
invisible coating on the flame sensor. This coating acts as
an insulator, causing a drop in the flame sensing signal. To
remove this coating, a qualified servicer should carefully
clean the flame sensor with emery cloth or steel wool. After
cleaning, the microamp signal should be in the range listed
in Specification Sheet.
IGNITOR (QUALIFIED SERVICER ONLY)
If the ignitor and the surrounding air are at about 70°F and
the ignitor wires are not connected to any other electrical
components, the resistance of the ignitor should not exceed 200 ohms. If it does, the ignitor should be replaced.
FLUE PASSAGES (QUALIFIED SERVICER ONLY)
At the start of each heating season, inspect and if necessary, clean the furnace flue passages.
CLEANING FLUE PASSAGES (QUALIFIED SERVICER
ONLY)
1. Shut off electric power and gas supply to the furnace.
2. Remove burner assembly by disconnecting the gas line
and removing the manifold brackets from the partition
panel.
3. Remove the flue from the induced draft blower and the
collector box from the partition panel.
4. The primary heat exchanger tubes can be cleaned
using a round wire brush attached to a length of high
grade stainless steel cable, such as drain cleanout
cable. Attach a variable speed reversible drill to the
other end of the spring cable. Slowly rotate the cable
with the drill and insert it into one of the primary heat
exchanger tubes. While reversing the drill, work the
cable in and out several times to obtain sufficient
cleaning. Use a large cable for the large tube, and then
repeat the operation with a small cable for the smaller
tube. Repeat for each tube.
5. When all heat exchanger tubes have been cleaned,
replace the parts in the reverse order in which they
were removed.
6. To reduce the chances of repeated fouling of the heat
exchanger, perform the steps listed in Section X,
up, Adjustments, and Checks
.
Start-
Figure 44
Furnace mounted Filter Rack
(Counterflow)
28
Page 29
BURNERS
WARNING
To prevent personal injury or death, do not
remove any internal compartment covers
or attempt any adjustment. Electrical
components are contained in both
compartments. Contact a qualified service
agent at once if an abnormal flame
appearance should develop.
Periodically during the heating season make a visual check
of the burner flames. Turn the furnace on at the thermostat.
Wait a few minutes, since any dislodged dust will alter the
normal flame appearance. Flames should be stable, quiet,
soft and blue with slightly orange tips. They should not be
yellow. They should extend directly outward from the burner
ports without curling downward, floating or lifting off the
ports.
CLEANING OF BURNERS (QUALIFIED SERVICER
ONLY)
1. Shut off electric power and gas supply to the furnace.
2. Remove the burner box front cover.
3. Remove the burner retention bracket.
4. Remove the burners.
5. Use bottle brush to clean burner insert and inside of
burner.
6. Replace burners and burner retention bracket, inspect
the burner assembly for proper seating of burners in
retention slots.
7. Reinstall the burner box front cover.
GENERAL INFORMATION
1. When ordering any of the listed functional parts, be sure
to provide the furnace model, manufacturing, and serial numbers with the order.
2. Although only functional parts are shown in the parts
list, all sheet metal parts, doors, etc. may be ordered by
description.
3. Parts are available from your Amana distributor
Gas ValveBlower/Box Gasket
Gas Orifice, NaturalFlame Roll-out Switch
Gas Orifice, PropaneAuxiliary Limit
BurnerHeat Exchanger
IgnitorDoor Switch
Flame SensorTransfo rmer
Gas ManifoldBlower Wheel
Ignition ControlBlower Housing
Limit SwitchBlower Cutoff
Pressure SwitchBlower Motor
Pressure Switch HoseMotor Mount Bracket
Induced Draft BlowerCapacitor
Collector Box
Check the burner flames for:
1. Good adjustment
2. Stable, soft and blue
3. Not curling, floating, or lifting off.
Figure 45
Burner Flame
29
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.