Instructions d’installation et Guide d’utilisation et d’entretien
Table of Contents/Table des matières.............................................................................2
IMPORTANT: READ AND SAVE THESE INSTRUCTIONS.
FOR RESIDENTIAL USE ONLY.
IMPORTANT : LIRE ET CONSERVER CES INSTRUCTIONS.
POUR UTILISATION RÉSIDENTIELLE UNIQUEMENT.
LI3VQB/W10274302C
TABLE OF CONTENTS
TABLE DES MATIÈRES
RANGE HOOD SAFETY .................................................................2
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.”
These words mean:
You can be killed or seriously injured if you don't immediately
DANGER
WARNING
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can
happen if the instructions are not followed.
follow instructions.
can be killed or seriously injured if you don't
You
instructions.
follow
2
IMPORTANT SAFETY INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OBSERVE THE
FOLLOWING:
■ Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the
manufacturer.
■ Before servicing or cleaning the unit, switch power off at
service panel and lock the service disconnecting means to
prevent power from being switched on accidentally. When
the service disconnecting means cannot be locked,
securely fasten a prominent warning device, such as a tag,
to the service panel.
■ Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable codes
and standards, including fire-rated construction.
■ Do not operate any fan with a damaged cord or plug.
Discard fan or return to an authorized service facility for
examination and/or repair.
■ Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel
burning equipment to prevent backdrafting. Follow the
heating equipment manufacturer's guideline and safety
standards such as those published by the National Fire
Protection Association (NFPA), the American Society for
Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE), and the local code authorities.
■ When cutting or drilling into wall or ceiling; do not damage
electrical wiring and other utilities.
■ Ducted fans must always be vented outdoors.CAUTION: For general ventilating use only. Do not use
to exhaust hazardous or explosive materials and vapors.
CAUTION: To reduce risk of fire and to properly exhaust
air, be sure to duct air outside - do not vent exhaust air into
spaces within walls or ceilings, attics or into crawl spaces,
or garages.
WARNING: TO REDUCE THE RISK OF FIRE, USE ONLY
METAL DUCTWORK.
WARNING: TO REDUCE THE RISK OF A RANGE TOP
GREASE FIRE:
■ Never leave surface units unattended at high settings.
Boilovers cause smoking and greasy spillovers that may
ignite. Heat oils slowly on low or medium settings.
■ Always turn hood ON when cooking at high heat or when
■ Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or filter.
■ Use proper pan size. Always use cookware appropriate for
the size of the surface element.
WARNING: TO REDUCE THE RISK OF INJURY TO
PERSONS IN THE EVENT OF A RANGE TOP GREASE
FIRE, OBSERVE THE FOLLOWING:
■ SMOTHER FLAMES with a close fitting lid, cookie sheet, or
metal tray, then turn off the burner. BE CAREFUL TO
PREVENT BURNS. If the flames do not go out
immediately, EVACUATE AND CALL THE FIRE
DEPARTMENT.
■ NEVER PICK UP A FLAMING PAN - you may be burned.
■ DO NOT USE WATER, including wet dishcloths or towels -
a violent steam explosion will result.
■ Use an extinguisher ONLY if:
– You know you have a class ABC extinguisher, and you
already know how to operate it.
– The fire is small and contained in the area where it
started.
– The fire department is being called.
– You can fight the fire with your back to an exit.
a
Based on "Kitchen Fire Safety Tips" published by NFPA.
■ WARNING: To reduce the risk of fire or electrical shock,
do not use this fan with any solid-state speed control
device.
a
READ AND SAVE THESE INSTRUCTIONS
INSTALLATION REQUIREMENTS
Tools and Parts
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools listed
here.
Tool s ne ed ed
■ Drill
■ 1¹⁄₄" (3.0 cm) drill bit
■ ¹⁄₈" (3.0 mm) drill bit for pilot holes
■ Pencil
■ Wire stripper or utility knife
■ Tape measure or ruler
■ Caulking gun and weatherproof caulking compound
■ Flat-blade screwdriver
■ Phillips screwdriver
For vented installations, you also need:
■ Saber or keyhole saw
■ Vent clamps
■ Metal snips
■ Compass or 8" (20.3 cm) circle template
Parts supplied
Remove parts from package. Check that all parts are included.
■ 2 - Metal filters
■ 6 - 4.5 x 13 mm mounting screws
■ 3 - 4 x 8 mm damper screws
■ 3¹⁄₄" x 10" (8.3 x 25.4 cm) damper/vent connector
3
■ 4 - 5 x 45 mm screws
■ 4 - 8 x 40 mm wall anchors
■ Recirculating kit
■ Charcoal filters for non-vented (recirculating) installations.
See the “Assistance or Service” section to order replacement
filters.
Parts needed
For vented installations:
■ 3¹⁄₄" x 10" (8.3 x 25.4 cm) or 6" (15.2 cm) or larger round metal
venting
■ 6" (15.2 cm) or larger round damper, if using 6" (15.2 cm) or
larger round vent system
■ 3¹⁄₄" x 10" (8.3 x 25.4 cm) to 6" (15.2 cm) or larger diameter
transition piece if using 6" (15.2 cm) or larger diameter round
vent system.
For cabinets with recessed bottoms:
■ Two 2" (5.1 cm) wide filler strips. Length and thickness
determined by recess dimensions.
■ Four flat head wood screws or machine screws with washers
and nuts (to attach filler strips).
Location Requirements
IMPORTANT: Observe all governing codes and ordinances.
■ It is the installer’s responsibility to comply with installation
clearances specified on the model/serial rating plate. The
model/serial rating plate is located inside the range hood on
the left wall.
■ Range hood location should be away from strong draft areas,
such as windows, doors and strong heating vents.
■ Cabinet opening dimensions that are shown must be used.
Given dimensions provide minimum clearance. Consult the
cooktop/range manufacturer installation instructions before
making any cutouts.
■ Grounded electrical outlet is required. See “Electrical
Requirements” section.
■ The hood is factory-set for vented installations. For non-
vented (recirculating) installations, the Recirculation Kit is
included. See the “Assistance or Service” section to order
Replacement Charcoal Filters Part Number W10272068.
■ All openings in ceiling and wall where range hood will be
installed must be sealed.
Product Dimensions
12"
(30.5 cm)
7¹⁄₄"
2"
(5.1 cm)
(22.9 cm)
(18.4 cm)
9"
29 ⁷⁄₈" (75.9 cm) - 30" (76.2 cm) model
35 ⁷⁄₈" (91.1 cm) - 36" (91.4 cm) model
⁵⁄₈"
(1.6 cm)
⁵⁄₈"
(1.6 cm)
Installation Clearances
B
A
1³⁄₁₆"
(3.0 cm)
C
3" (7.6 cm) 30" (76.2 cm) model
5 ³⁄₄" (14.6 cm) 36" (91.4 cm) model
19
(50.2 cm)
D
³⁄₄
"
For Mobile Home Installations
The installation of this range hood must conform to the
Manufactured Home Construction Safety Standards, Title 24
CFR, Part 328 (formerly the Federal Standard for Mobile Home
Construction and Safety, title 24, HUD, Part 280) or when such
standard is not applicable, the standard for Manufactured Home
Installation 1982 (Manufactured Home Sites, Communities and
Setups) ANSI A225.1/NFPA 501A*, or latest edition, or with local
codes.
4
E
A. 18" (45.7 cm) min. clearance - upper cabinet to countertop
B. 24" (61.0 cm) min. for electric cooking surfaces
27" (68.6 cm) min. for gas cooking surfaces
30" (76.2 cm) suggested max. - bottom of range hood to
cooking surface
C. 30" (76.2 cm) or 36" (91.4 cm) min. cabinet opening width
D. 13" (33.0 cm) cabinet depth
E. 36" (91.4 cm) base cabinet height
Venting Requirements
E
(Vented Models Only)
■ Vent system must terminate to the outdoors, except for non-
vented (recirculating) installations.
■ Do not terminate the vent system in an attic or other enclosed
area.
■ Do not use a 4" (10.2 cm) laundry-type wall cap.
■ Use a 6" (15.2 cm) or larger round metal vent or a 3¹⁄₄" x 10"
(8.3 x 25.4 cm) rectangular metal vent. Rigid metal vent is
recommended. Plastic or metal foil vent is not recommended.
■ The length of vent system and number of elbows should be
kept to a minimum to provide efficient performance.
For the most efficient and quiet operation:
■ Use no more than three 90° elbows.
■ Make sure there is a minimum of 24" (61 cm) of straight vent
between the elbows if more than 1 elbow is used.
■ Do not install 2 elbows together.
■ Use clamps to seal all joints in the vent system.
■ The vent system must have a damper. If roof or wall cap has a
damper, do not use damper supplied with the range hood.
■ Use caulking to seal exterior wall or roof opening around the
cap.
Cold Weather Installations
An additional back draft damper should be installed to minimize
backward cold air flow and a thermal break should be installed to
minimize conduction of outside temperatures as part of the vent
system. The damper should be on the cold air side of the thermal
break.
The break should be as close as possible to where the vent
system enters the heated portion of the house.
Makeup Air
Local building codes may require the use of make up air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.
Venting Methods
Roof VentingWall Venting
A
B
E
A
B
C
C
D
D
A. 6" (15.2 cm) or larger round
vent or a 3¹⁄₄" x 10" (8.3 x
25.4 cm) rectangular vent
through roof
B. Round vent: use 6" (15.2 cm)
or larger round damper
(purchased separately)
C. Round vent: use 3¹⁄₄" x 10"
(8.3 x 25.4 cm) to 6" (15.2 cm)
or larger diameter transition
piece (purchased separately)
D. 24" (61.0 cm) - 30" (76.2 cm)
above electric cooking
surface
27" (68.6 cm) - 30" (76.2 cm)
above gas cooking surface
E. Roof cap
A. 6" (15.2 cm) or larger round
vent or a 3¹⁄₄" x 10" (8.3 x
25.4 cm) rectangular vent
through the wall
B. Round vent: use 3¹⁄₄" x 10" (8.3
x 25.4 cm) to 6" (15.2 cm) or
larger diameter transition piece
(purchased separately)
C. 3¹⁄₄" x 10" (8.3 x 25.4 cm)
through the wall
D. 24" (61.0 cm) - 30" (76.2 cm)
above electric cooking surface
27" (68.6 cm) - 30" (76.2 cm)
above gas cooking surface
E. Wall cap
Calculating Vent System Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
6" (15.2 cm) or Larger Round Vent System
Vent PieceRound
45° elbow2.5 ft
(0.8 m)
Vent system can terminate either through the roof or wall. Use
3¹⁄₄" x 10" (8.3 x 25.4 cm) with a maximum vent length of
35 ft (10.7 m) or 6" (15.2 cm) or larger round vent with a maximum
length of 50 ft (15.2 m) for vent system.
NOTE: Flexible vent is not recommended. Flexible vent creates
back pressure and air turbulence that gently reduces
performance.
90° elbow5.0 ft
(1.5 m)
6" (15.2 cm) or larger
wall cap
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
to 6" (15.2 cm) or larger
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
to 6" (15.2 cm) or larger
0.0 ft
(0.0 m)
4.5 ft
(1.4 m)
5.0 ft
(1.5 m)
90° elbow
5
Example vent system
90˚ elbow
6 ft (1.8 m)
Wall cap
Electrical Requirements
WARNING
2 ft (0.6 m)
Maximum Recommended Length= 50 ft (15.2 m)
1 - 90° elbow= 5.0 ft (1.5 m)
1 - wall cap= 0.0 ft (0.0 m)
8 ft (2.4 m) straight= 8.0 ft (2.4 m)
Length of 7" (17.8 cm) system= 13.0 ft (3.9 m)
3¹⁄₄" x 10" (8.3 cm x 25.4 cm) Vent System
Vent Piece
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
90° elbow
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
flat elbow
3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
wall cap
5.0 ft
(1.5 m)
12.0 ft
(3.7 m)
0.0 ft
(0.0 m)
Example vent system
3
¹⁄₄" x 10"
elbow
6 ft (1.8 m)
Wall cap
(8.3 x 25.4 cm)
2 ft
(0.6 m)
Electrical Shock Hazard
Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.
Do not use an extension cord.
Failure to follow these instructions can result in death,
fire, or electrical shock.
IMPORTANT: The range hood must be electrically grounded in
accordance with local codes and ordinances, or in the absence
of local codes, with the National Electrical Code, ANSI/NFPA 70
(latest edition) or Canadian Electrical Code, CSA C22.1
No. 0-M91 (latest edition).
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine that
the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park
Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
■ A 120 volt, 60 Hz, AC only, 15- or 20-amp, fused electrical
circuit is required. A time-delay fuse or circuit breaker is also
recommended. It is recommended that a separate circuit
serving only this range hood be provided.
■ This range hood is equipped with a power supply cord having
a 3 prong grounding plug.
■ To minimize possible shock hazard, the cord must be
plugged into a mating, 3 prong, grounding-type outlet,
grounded in accordance with local codes and ordinances. If a
mating outlet is not available, it is the personal responsibility
and obligation of the customer to have the properly grounded
outlet installed by a qualified electrician.
Maximum Recommended Length= 35 ft (10.7 m)
1 - 90° elbow= 5.0 ft (1.5 m)
8 ft (2.4 m) straight= 8.0 ft (2.4 m)
1 - wall cap= 0.0 ft (0.0 m)
Length of 3¹⁄₄" x 10" (8.3 cm x 25.4 cm)
= 13.0 ft (3.9 m)
system
6
■ The grounded 3 prong outlet is to be located inside the
cabinet above the range hood at a maximum distance of
33⁷⁄₁₆" (85.0 cm) from where the power cord exits the hood.
See illustration.
33⁷⁄₁₆" (85 cm)
GROUNDING INSTRUCTIONS
■
For a grounded, cord-connected range hood:
This range hood must be grounded. In the event of an
electrical short circuit, grounding reduces the risk of electric
shock by providing an escape wire for the electric current.
This range hood is equipped with a cord having a grounding
wire with a grounding plug. The plug must be plugged into
an outlet that is properly installed and grounded.
INSTALLATION INSTRUCTIONS
Prepare Location
NOTE: For vented installations, it is recommended that the vent
system be installed before hood is installed.
Before making cutouts, make sure there is proper clearance
within the ceiling or wall for exhaust vent.
1. For vented installations, determine which venting method to
use: roof or wall.
2. Select a flat surface for assembling the range hood. Place
covering over that surface.
WARNING:
electric shock.
Consult a qualified electrician if the grounding instructions
are not completely understood, or if doubt exists as to
whether the range hood is properly grounded.
Do not use an extension cord. If the power supply cord is too
short, have a qualified electrician install an outlet near the
range hood.
Improper grounding can result in a risk of
SAVE THESE INSTRUCTIONS
Determine Wiring Hole Location
Cut only one 1¹⁄₄" (3.2 cm) diameter wiring access hole. See
Step 2 for wiring hole location instructions.
1. Determine and clearly mark a vertical centerline on the wall
and cabinet in the area the vent opening will be made.
WARNING
Excessive Weight Hazard
Use two or more people to move and install
range hood.
Failure to do so can result in back or other injury.
3. Using 2 or more people, lift the range hood and set it upside
down onto covered surface.
4. If cabinet has recessed bottom, add wood filler strips on each
side. Install screws to attach filler strips in locations shown.
Wood filler strips
(recessed cabinet
3" (7.6 cm)
3" (7.6 cm)
bottoms only)
Cabinet
bottom
Wall
A
A. Centerline
2. To wire through top:
Mark a line distance “A” from the left of the centerline on the
underside of the cabinet. Mark the point on this line that is
2" (5.0 cm) from back wall. Drill a 1¼" (3.0 cm) diameter hole
through the cabinet at this point.
2" (5.1 cm)
A
Centerline
A. 12" (30.5 cm) for 30" (76.2 cm) models
12¼" (31.1 cm) for 36" (91.4 cm) models
from wall,
not cabinet
frame
7
Style 1 - Cut Openings for 3¼" x 10" (8.3 cm x 25.4 cm)
Rectangular Vent System
Roof Venting
To make a 4¼" x 10½" (10.8 cm x 26.7 cm) rectangular cutout
on the underside of cabinet top and bottom:
1. Mark lines ½" (1.2 cm) and 4¾" (12.1 cm) from the back wall
on the centerline of the underside of cabinet.
2. Mark lines 5¼" (13.3 cm) to the right and left of the centerline
on the underside of cabinet.
3. Use saber or keyhole saw to cut a rectangular opening for
vent.
4. Repeat steps 1-3 for the underside of the top of the cabinet.
Cabinet cutouts
*¹⁄₂" (1.2 cm)
*4³⁄₄"
(12.1 cm)
(13.3 cm)
*From wall, not cabinet frame
5¹/₄"
5¹/₄"
(13.3 cm)
3. Use saber or keyhole saw to cut a rectangular opening for
vent.
*¹⁄₂" (1.2 cm)
*4³⁄₄"
(12.1 cm)
(13.3 cm)
*From wall, not cabinet frame
5¹/₄"
5¹/₄"
(13.3 cm)
To make a circular vent opening on the underside of the
cabinet top:
1. Mark a centerline on the underside of the top of cabinet.
2. Mark a line 5" (12.7 cm) from the back wall on the underside
of the top of cabinet.
3. Use a compass or a circle template to draw a circle with a
diameter that is ¼" (0.64 cm) larger than the vent.
4. Use saber or keyhole saw to cut the circular vent opening.
Circular vent opening
Wall Venting
To make a 3½" x 10½" (8.9 cm x 26.7 cm) rectangle in the
wall:
1. Make 2 lines by measuring ³⁄₈" (9.5 mm) and 3⁷⁄₈" (9.8 cm)
down from underside of cabinet and mark on the centerline
on the back wall.
2. Mark lines 5¼" (13.3 cm) to the right and left of the centerline
on the wall.
3. Use saber or keyhole saw to cut a rectangular opening in the
wall for the vent.
Centerline
5
¹⁄₄"
(13.3 cm)
3 ⁷⁄₈"
(9.8 cm)
³⁄₈"
(0.9 cm)
Cabinet
front
Style 2 - Cut Openings for 3¼" x 10" (8.3 x 25.4 cm)
Rectangular Vent to Round Vent Transition
Roof Venting
To make a 4¼" x 10½" (10.8 cm x 26.7 cm) rectangular cutout
on the underside of cabinet bottom:
1. Mark lines ½" (1.2 cm) and 4¾" (12.1 cm) from the back wall
on the centerline of the underside of cabinet.
2. Mark lines 5¼" (13.3 cm) to the right and left of the centerline
on the underside of cabinet.
*5"
(12.7 cm)
Cabinet
cutouts
*From wall, not
cabinet frame
Install Vent System
1. Install vent through the vent opening in upper cabinet or wall.
Complete venting system according to the selected venting
method. See “Venting Requirements” section.
2. Use caulking to seal exterior wall or roof opening around the
cap.
8
Install Range Hood
B
1. Remove the grease filters. See the “Range Hood Care”
section.
■ If using rectangular vent, attach rectangular damper/vent
connectors to the range hood using sheet metal screws.
A
B
C
D
E
2. Remove mounting screws and lateral supports.
A
A. Lateral supports
B. Mounting screws
3. For vented installations:
■ Depending on your installation, remove either top or rear
rectangular vent knockout. If using round vent, remove
top rectangular knockout.
NOTE: Do not remove rectangular knockouts if
installation of range hood is to be non-venting
(recirculating).
■ Make sure damper pivot is nearest to top/back edge of
range hood.
■ Remove tape from damper flap.
NOTE: The exhaust adaptor/damper can be installed up
to 1" (2.5 cm) on either side of the hood center to
accommodate off-center ductwork.
B
A. Vertical vent
B. Sheet metal screws
C. Hinge pin
D. Vent knockouts
E. Horizontal vent
A
■ If using round vent, attach vent transition piece
C
(purchased separately) to range hood top using sheet
metal screws.
NOTE: If the wall cap is directly behind the vent
connector, the dampers in the connector and wall cap
must not interfere with each other. Remove the vent
connector damper if they interfere.
4. Lift the range hood up under cabinet and determine final
location by centering beneath cabinet. Mark on the underside
of cabinet the location of the 4 keyhole mounting slots on the
range hood. Set range hood aside on a covered surface.
A
A. Keyhole slot
5. Use ¹⁄₈" (3 mm) drill bit and drill 4 pilot holes as shown.
A
A. Drill pilot hole
6. Install the 4 - #10 x ⁵⁄₈" mounting screws in pilot holes. Leave
about ¹⁄₄" (6.4 cm) space between screw heads and cabinet
to slide range hood into place.
¹⁄₄"
(6.4 mm)
9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.