This manual is to be used by qualified, professionally trained HVAC technicians only.
Goodman does not assume any responsibility for property damage or personal injury
due to improper service procedures or services performed by an unqualified person.
is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX. All rights reserved.
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however,
that during its lifetime a product may require service. Products should be serviced only by a qualified service technician
who is familiar with the safety procedures required in the repair and who is equipped with the proper tools, parts, testing
instruments and the appropriate service manual. REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE
SERVICE MANUAL BEFORE BEGINNING REPAIRS.
IMPORTANT NOTICES FOR CONSUMERS AND SERVICERS
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
WARNING
WARNING
INSTALLATION AND REPAIR OF THIS UNIT SHOULD BE PERFORMED ONLY BY INDIVIDUALS MEETING (AT
A MINIMUM) THE REQUIREMENTS OF AN “ENTRY LEVEL TECHNICIAN” AS SPECIFIED BY THE AIRCONDITIONING, HEATING AND REFRIGERATION INSTITUTE (AHRI). ATTEMPTING TO INSTALL OR REPAIR
THIS UNIT WITHOUT SUCH BACKGROUND MAY RESULT IN PRODUCT DAMAGE, PERSONAL INJURY
OR DEATH.
2
WARNING
THIS AIR CONDITIONER IS NOT MEANT TO PROVIDE
UNATTENDED COOLING OR LIFE SUPPORT FOR
PERSONS OR ANIMALS WHO ARE UNABLE TO
REACT TO THE FAILURE OF THIS PRODUCT.
THE FAILURE OF AN UNATTENDED AIR CONDITIONER MAY RESULT IN EXTREME HEAT IN THE CONDITIONED SPACE CAUSING OVERHEATING OR
DEATH OF PERSONS OR ANIMALS.
PRECAUTIONS MUST BE TAKEN TO WARN OF OR
GUARD AGAINST SUCH AN OCCURENCE.
WARNING
WARNING
GOODMAN WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM
IMPROPER SERVICE OR SERVICE PROCEDURES. IF YOU INSTALL OR PERFORM SERVICE ON THIS UNIT,
YOU ASSUME RESPONSIBILITY FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE WHICH MAY
RESULT. MANY JURISDICTIONS REQUIRE A LICENSE TO INSTALL OR SERVICE HEATING AND AIR
CONDITIONING EQUIPMENT.
To locate an authorized servicer, please consult your telephone book or the dealer
from whom you purchased this product. For further assistance, please contact:
CONSUMER INFORMATION LINE -
AMANA® BRAND PRODUCTS TOLL FREE
1-877-254-4729 (U.S. only)
email us at: customerservice@goodmanmfg.com
fax us at: (713) 856-1821
(Not a technical assistance line for dealers.)
Outside the U.S., call 1-713-861-2500.
(Not a technical assistance line for dealers.)
Your telephone company will bill you for the call.
is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company, L.P., Houston, TX. All rights reserved.
3
PRODUCT IDENTIFICATION
(
)
R
R
F Ant
PTC 07 3 E 35 A X X X
BASIC MODEL TYPEMAJOR/MINO R DESIGN REV.
PTC = Standard Cooler PTAC
PTH = Standard Heat Pump PTHP
DRY = Dehumid Cooler PTAC
* Actual vent CFM performance will vary du e to appl ication and installa tion condit ions.
Notes:
¹ All 265-vo l t models must use an Amana® brand sub- bas e (PT SB4** E) or an Amana® brand hard-wir e kit ( PT PWHWK4 ).
² Minimum C i rcuit Ampac ity (M C A) ratings confo r m to the Nation al Electri c Co de; however, l ocal codes s hould apply.
Minimum voltage on 230 /208-volt models is 1 97 volts; maximum is 253 volts.
³ Minimum voltage on 26 5-vol t models i s 239 volts; maximum is 292 vo l ts.
4
Ove r curre nt prot ection fo r al l units without electr i c heaters i s 15 amps. Over cur rent protection on 265- v olt models must be cartridge-style time-delay fuses
(included and factory-i nstall ed on all Ama na® brand 265-volt ch assis). See heater perf ormance for total MCA.
5
Heating capacity and effi ciency ba sed on unit oper a ti o n w i t h ou t conden s a t e pump; unit automati c ally swi tc hes to el ectr i c heat at approx imately 24°F outd oor ambient.
6
Specify two-digit heater kW size to complete model numbe r.
7
R-410A refrigerant used in all systems.
8
Al l uni ts meet or exceed A SH RAE 90. 1 standard s.
9
Al l uni ts less t han 250 volts hav e a Leak C urrent Detector I nterrupter (LCDI) pow er cord and meet UL 484 st andards.
10
Refer to electric heat pe r formance data fo r total MCA and rec ommended overcurr ent protection. Amps and Watts notation refer s to compresso r only.
EER - Energy Efficiency Ratio per The Air -Conditioning,
Heating, and Refrigeration Institute (AHRI) T est
Procedures and Canadian Standards Association
(CSA) T est Procedures.
* Actual vent CFM performance will vary du e to appl ication and installa tion condit ions.
Notes:
¹ All 265-vo l t models must use an Amana® brand sub- bas e (PT SB4** E) or an Amana® brand hard-wir e kit ( PT PWHWK4 ).
² Minimum C i rcuit Ampac ity (M C A) ratings confo r m to the Nation al Electri c Co de; however, l ocal codes s hould apply.
Minimum voltage on 230 /208-volt models is 1 97 volts; maximum is 253 volts.
³ Minimum voltage on 26 5-vol t models i s 239 volts; maximum is 292 vo l ts.
4
Ove r curre nt prot ection fo r al l units without electr i c heaters i s 15 amps. Over cur rent protection on 265- v olt models must be cartridge-style time-delay fuses
(included and factory-i nstall ed on all Ama na® brand 265-volt ch assis). See heater perf ormance for total MCA.
5
Heating capacity and effi ciency ba sed on unit oper a ti o n w i t h ou t conden s a t e pump; unit automati c ally swi tc hes to el ectr i c heat at approx imately 24°F outd oor ambient.
6
Specify two-digit heater kW size to complete model numbe r.
7
R-410A refrigerant used in all systems.
8
Al l uni ts meet or exceed A SH RAE 90. 1 standard s.
9
Al l uni ts less t han 250 volts hav e a Leak C urrent Detector I nterrupter (LCDI) pow er cord and meet UL 484 st andards.
10
Refer to electric heat pe r formance data fo r total MCA and rec ommended overcurr ent protection. Amps and Watts notation refer s to compresso r only.
* Actual vent CFM performance will vary du e to appl icati on and i ns tallatio n condi tions.
Notes:
¹ All 265-vo l t models must use an Amana® brand sub- bas e (PT SB4** E) or an Amana® brand hard-wir e kit ( PTPWHWK4).
² Minimum C i rcuit Ampac ity (M C A) ratings confo r m to the Nation al Electri c Co de; howe ver, l ocal codes s hould apply.
Minimum voltage on 230 /208-volt models i s 197 volts; m aximum is 253 vol ts.
³ Minimum voltage on 26 5-vol t models i s 239 volts; maximum is 292 vo l ts.
4
Ove r curre nt prot ection fo r al l units without el ectri c heaters is 15 am ps. Over c urrent pr otection o n 265-vol t models must be cartridge-style time-delay fuses
(included and factory-i nstall ed on all Ama na® brand 265-volt ch assis). See heater perf ormance for total MCA.
5
Heating capacity and effi ciency ba sed on unit ope ration wit hout cond ens ate pum p; uni t autom ati cally swi tc hes to el ectric he at at approximately 24°F outd oor ambient.
6
Specify two-digit heater kW size to complete model number.
7
R-410A refrigerant used in all systems.
8
Al l uni ts meet or exceed A SH R AE 90.1 standard s.
9
Al l uni ts less t han 250 volts hav e a Leak Curr ent Detector Interrupt er (LCDI) pow er cord and meet UL 484 st andards.
10
Refer to electric heat pe r formance data fo r total MCA and recom mended overcurr ent protection. Amps and Watts notation refer s to compresso r only.
5.1
65*
6*
2.8
103
118
EER - Energy Efficiency Ratio per The Air -Conditioning,
Heating, and Refrigeration Institute (AHRI) T est
Procedures and Canadian Standards Association
(CSA) T est Procedures.
* Actual vent CFM performance will vary du e to appl ication and installa tion condit ions.
Notes:
¹ All 265-vo l t models must use an Amana® brand sub- bas e (PT SB4** E) or an Amana® brand hard-wir e kit ( PT PWHWK4 ).
² Minimum C i rcuit Ampac ity (M C A) ratings confo r m to the Nation al Electri c Co de; however, l ocal codes s hould apply.
Minimum voltage on 230 /208-volt models is 1 97 volts; maximum is 253 volts.
³ Minimum voltage on 26 5-vol t models i s 239 volts; maximum is 292 vo l ts.
4
Ove r curre nt prot ection fo r al l units without electr i c heaters i s 15 amps. Over cur rent protection on 265- v olt models must be cartridge-style time-delay fuses
(included and factory-i nstall ed on all Ama na® brand 265-volt ch assis). See heater perf ormance for total MCA.
5
Heating capacity and effi ciency ba sed on unit oper a ti o n w i t h ou t conden s a t e pump; unit automati c ally swi tc hes to el ectr i c heat at approx imately 24°F outd oor ambient.
6
Specify two-digit heater kW size to complete model numbe r.
7
R-410A refrigerant used in all systems.
8
Al l uni ts meet or exceed A SH RAE 90. 1 standard s.
9
Al l uni ts less t han 250 volts hav e a Leak C urrent Detector I nterrupter (LCDI) pow er cord and meet UL 484 st andards.
10
Refer to electric heat pe r formance data fo r total MCA and rec ommended overcurr ent protection. Amps and Watts notation refer s to compresso r only.
EER - Energy Efficiency Ratio per The Air -Conditioning,
Heating, and Refrigeration Institute (AHRI) T est
Procedures and Canadian Standards Association
(CSA) T est Procedures.
COP - Coefficient of Performance per AHRI Test
Procedures
8
SPECIFICATIONS
ELECTRIC HEAT PERFORMANCE
PTC***(E,F,G) & PTH***(E,F) Models
DRY***(E, G) Models
Voltage
Electric
Heater Size
(kW)
No. of
Stages
Nominal Heating (BTU/h)
@ 230V @ 208V @ 265V
Tota l
Watts
6
Total
Amps
Min. Circuit
Ampacity²
MOD
(amps)
4
Pow er Cord
230/208V2.518,5006,800- -2,570 / 2,11511.2 / 10.114.0156-15 P
230/208V3.5112,0009,900- -3,570 / 2,93515.5 / 14.119.4206-20 P
230/208V5117,100 14,000- -5,070 / 4,16022.1 / 20.027.5306-30 P
265V2.51- -- -8,5002,5709.712.1157-20 P
265V3.71- -- -12,6003,77014.217.8207-20 P
265V51- -- -17,1005,07019.223.9257-30 P
Notes:
¹ All 265-vol t models must use an Amana® brand sub-base (PTSB4* *E) or an Amana ® br and hard-wire kit (PT PWHWK4 ) .
² Minimum branch c ircuit am pacity ratings conform to the National El ec tric Code; however, local codes sh ould apply.
³ Minimum v ol tag e on 230/208-v olt models is 197 volts; m aximum is 253 volts.
Minimum voltage on 265 - v ol t models is 239 v olts; maxi m um is 292 v ol ts.
4
Over current protect i on fo r al l units w i thou t el ectri c heaters is 15 amps. Over curr ent pro tection on 265-vol t mode l s m ust be car tridge-style time-delay
fus es (included and fact ory-inst al led on all Amana® brand 265-v olt chassis).
5
Heati ng capacity and efficiency based on u ni t oper ation without condensate pump; un i t a utomatic al l y swi tches to el ectri c heat at approximately 24°F outdoor ambient.
6
Total watts for 15,000 BTU/h model s; s ubtra ct 20 watt s for PT 07/09/12
7
Specify two-digit heater kW size to complete model number.
8
R-41 0A r efr i gerant used in all sy stems.
9
All units meet or e xceed ASH R AE 90.1 standards.
10
All units l es s than 250 volts hav e a Leak C urr ent De tector Interru pter (LCDI) po we r cord and m eet UL 484 standard s.
EER - Energy Efficiency Ratio per The Air -Conditioning,
Heating, and Refrigeration Institute (AHRI) T est
Procedures and Canadian Standards Association
(CSA) T est Procedures.
* Actual vent C FM p er formance will var y due to applicat ion and instal l ation conditions.
Notes:
¹ All 265-vo lt mo dels must use an Am a na® brand s ub-bas e (PT SB4**E) or a n Amana® brand hard-wir e kit (PTP W H WK4).
² Minimum Ci r cuit Ampacity (MC A) r atings conform to the N ational Electric Code; howeve r, local c odes should apply.
Minimum vo ltage on 230/208-vo l t models is 197 v olts ; maximum is 253 v olts .
³ Minimum voltage on 265-volt models is 239 volts; maximum is 292 volt s.
4
Overcur r ent protection fo r all units without electric heaters is 15 amps. Overcurrent protecti on on 265-vol t models m ust be cartridge-style time-delay fuses
incl uded and factory-installed on al l Ama na® bra nd 265-volt ch assis). S e e he ater p e rformance for total MCA.
5
Heatin g capa city and ef ficiency based on un i t operation without condens ate pum p; unit automaticall y swi tch es to el ectric heat at approximately 24°F outdoor am bient.
6
Specify two-digit heater kW size to complete model nu mber.
7
R-410A refrigerant used in all systems.
8
All units meet o r exc eed ASHRAE 90.1 standards.
9
All units less than 250 volts have a Leak Current Detec tor Interrupter (LCDI ) power cord and m ee t UL 484 standa r ds.
10
Refer to electr i c heat performance da ta fo r total MCA and r ecommend ed over current pr otection. Am ps and W att s notation ref ers to compressor only.
EER - Energy Efficiency Ratio per The Air -Conditioning,
Heating, and Refrigeration Institute (AHRI) T est
Procedures and Canadian Standards Association
(CSA) T est Procedures.
COP - Coefficient of Performance per AHRI Test
Procedures
10
SPECIFICATIONS
(
HEAT PUMP - PTH
Model ¹, 6, 8,
Voltage ¹, ³
Capacity (BTU/h)11,500 / 11,30011,600
Amps
Watts
Dehum idification (Pints/Hr.)
Net Weight (lbs.)
Ship Weight (lbs.)
9
10
10
10
High290290
Low264264
High310310
Low282282
(Compressor & Fan)*6*6*
PTH
123F**AXXX
230 / 208265
5.6 / 5.64.8
1,125 / 1,0951,125
7.06.0
65*65*
3.63.6
115115
132132
PTH
124F**AXXX
PTH F SERIES
* Actual vent C FM p er formance will var y due to applicat ion and instal l ation conditions.
Notes:
¹ All 265-vo lt mo dels must use an Am a na® brand s ub-bas e (PT SB4**E) or a n Amana® brand hard-wir e kit (PTP W H WK4).
² Minimum Ci r cuit Ampacity (MC A) r atings conform to the N ational Electric Code; howeve r, local c odes should apply.
Minimum vo ltage on 230/208-vo l t models is 197 v olts ; maximum is 253 v olts .
³ Minimum voltage on 265-volt models is 239 volts; maximum is 292 volt s.
4
Overcur r ent protection fo r all units without electric heaters is 15 amps. Overcurrent protecti on on 265-vol t models m ust be cartridge-style time-delay fuses
incl uded and factory-installed on al l Ama na® bra nd 265-volt ch assis). S e e he ater p e rformance for total MCA.
5
Heatin g capa city and ef ficiency based on un i t operation without condens ate pum p; unit automaticall y swi tch es to el ectric heat at approximately 24°F outdoor am bient.
6
Specify two-digit heater kW size to complete model nu mber.
7
R-410A refrigerant used in all systems.
8
All units meet o r exc eed ASHRAE 90.1 standards.
9
All units less than 250 volts have a Leak Current Detec tor Interrupter (LCDI ) power cord and m ee t UL 484 standa r ds.
10
Refer to electr i c heat performance da ta fo r total MCA and r ecommend ed over current pr otection. Am ps and W att s notation ref ers to compressor only.
EER - Energy Efficiency Ratio per The Air -Conditioning,
Heating, and Refrigeration Institute (AHRI) T est
Procedures and Canadian Standards Association
(CSA) T est Procedures.
* Actual vent C FM p er formance will var y due to applicat ion and installation condi tions.
Notes:
¹ All 265-vo lt mo dels must u se an Am ana® brand s ub-base (P TSB4**E) or an Amana® br and hard-wire kit (PTPWHWK4).
² Minimum Ci r cuit Ampacity (MC A) r atings conform to the N ational Electric Code; howeve r , loc al codes s hould apply.
Minimum vo ltage on 230 /208-vol t models is 197 v ol ts; maximum is 253 v ol ts.
³ Minimum voltage on 265-volt models is 239 volts; maximum is 292 volt s.
4
Overcur r ent protection fo r all units without electric heaters is 15 amps. Overcurrent protection on 265-volt models must be cartridge-style time-delay fuses
incl uded and factory-installed on al l Ama na® brand 265-vol t chassis). S e e he ater p e rformance for total MCA.
5
Heatin g capa city and ef ficiency based on unit operation witho ut condens ate pum p; unit automaticall y swi tches to el ectr ic heat at approxim ately 24°F outd o or ambi ent.
6
Specify two-digit heater kW size to complete model nu mber.
7
R-410A refrigerant used in all systems.
8
All units meet o r exc eed ASHRAE 90.1 standards.
9
All units less than 250 volts have a Leak Current Detec tor Interrupter (LCDI) p ow er cord and m ee t UL 484 standa r ds.
10
Refer to electr i c heat perfor m anc e data for to tal MCA and recommended overcurrent protection. Am ps and W att s notation ref ers to compressor only.
EER - Energy Efficiency Ratio per The Air -Conditioning,
Heating, and Refrigeration Institute (AHRI) T est
Procedures and Canadian Standards Association
(CSA) T est Procedures.
COP = Coefficiency of Performance; per AHRI Test Procedures, units are rated for capacities and efficiencies.
Not es:
¹ All 2 65-volt mo d els m ust use an A m ana® bra nd su b- base (P TSB4**E) or an Amana® brand hard-wire ki t (PTPWHWK4).
² Minimum C ircuit Ampacity (MCA) r atings conform to th e N ational Elec tric Code; however, local cod es should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
³ Minimum voltage on 265-v o l t models is 239 volts; ma xim um is 292 vol ts.
4
Overcurren t protection for all unit s without ele ctric heaters is 15 a m ps. Overcurrent protection on 265-volt m o dels must be cartri dge-style time-delay fuses
included and factory-installed on all Am ana® brand 265-vol t chassi s). See heater performan ce for total MCA.
5
Heating capacity an d efficiency base d on uni t operation without co nden s a te pump; unit automati cally switches to e lect ric heat at approximately 24°F outdoor ambie n t.
6
Sp ecify two-digi t heater kW size to complete model numbe r.
7
R-410A refrigerant used in all sys tems.
8
All units m eet or exceed ASH RAE 90.1 standards.
9
All u nits less than 2 50 volts have a Leak Current Detector Interrupter (LCDI) power cord and m eet UL 484 standar ds.
10
Refer to electric h eat pe r formance data for total MCA and r ecommended overcurrent protection. Amps and Watts notation refer s to compresso r only.
PTH F SERIES
Heating Capacity¹
Voltage ¹, ³
5
BTU/h
10
Amps
10
Watts
5
COP
PTH
123F**AXXX
230 / 208265
10,900 / 10,50011,000
5.6 / 5.64.8
1040 /10201040
3.1 / 3.13.1
C FM (Dry)310310
C O P = Coeffi c iency of P er fo rmanc e ; pe r AH R I Test Pr ocedur e s , un i t s ar e rated for c a pa c i ti es a n d effic iencie s .
Not es:
¹ All 2 65-volt mo d els m ust use an A m ana® bra nd su b- base (P TSB4**E) or an Amana® brand hard-wire ki t (PTPWHWK4).
² Minimum C ircuit Ampacity (MCA) r atings conform to th e N ational Elec tric Code; however, local cod es should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
³ Minimum voltage on 265-v o l t models is 239 volts; ma xim um is 292 vol ts.
4
Overcurren t protection for all unit s without ele ctric heaters is 15 a m ps. Overcurrent protection on 265-volt m o dels must be cartri dge-style time-delay fuses
included and factory-installed on all Am ana® brand 265-vol t chassi s). See heater performan ce for total MCA.
5
Heating capacity an d efficiency base d on uni t operation without co nden s a te pump; unit automati cally switches to e lect ric heat at approximately 24°F outdoor ambie n t.
6
Sp ecify two-digi t heater kW size to complete model numbe r.
7
R-410A refrigerant used in all sys tems.
8
All units m eet or exceed ASH RAE 90.1 standards.
9
All u nits less than 2 50 volts have a Leak Current Detector Interrupter (LCDI) power cord and m eet UL 484 standar ds.
10
Refer to electric h eat pe r formance data for total MCA and r ecommended overcurrent protection. Amps and Watts notation refer s to compresso r only.
COP = Coefficiency of Per form a nce; per AHRI Test Pr oc e dures , u nit s a r e rate d f or capacities and efficienc ies.
Not es:
¹ All 265-volt models must use an Amana® brand sub-base (PTSB4**E) or an Amana® brand hard-wire kit (PTPWHWK4).
² Minimum C i rcuit A m p acity (MC A) ratings con form to the Nat i onal Elec tri c Code; however, local cod es should apply.
Minimum voltage on 230/208-volt models is 197 volts; maximum is 253 volts.
³ Minimum voltage on 265-vol t models is 239 volts; ma xi mum is 292 volts.
4
Overcurren t protection for a ll un its without electric heat er s is 15 amps. Ov er current protection on 265-volt mod els must be cartridge-style time-delay fuses
(incl uded and factory-installed on all Amana® brand 265-volt chassis). See heater performance for total MCA.
5
Heating capacity an d efficiency based on u nit operation without condensate pump; unit automatically switches to electric heat at approximately 24°F outdoor ambie nt.
6
Specify two-digit heater kW size to complete model number.
7
R-410A refrigerant used in all sys tems .
8
All units meet or exceed ASHRAE 90.1 standards.
9
All units l e ss than 250 volt s have a Leak Current Detector Int errupter (LCDI) power cord and m eet UL 484 st andards .
10
Refer t o electr ic heat perform ance data fo r tota l MCA and recommended ove rcurrent pro tection. Amps and Watts no tatio n r efers to compressor only.
EER - Energy Efficiency Ratio per The Air -Conditioning,
Heating, and Refrigeration Institute (AHRI) T est
Procedures and Canadian Standards Association
(CSA) T est Procedures.
COP - Coefficient of Performance per AHRI Test
Procedures
PTH G SERIES
ELECTRIC HEAT PERFORMANCE
Voltage
Electric
Heater Size
(kW)
No. of
Stages
Nominal Heating (BTU/h)
@ 230V @ 208V @ 265V
Total
Watts
6
Total
Amps
Min. Circuit
Ampacity²
230/208V2.518,5006,800- -2,570 / 2,11511.2 / 10.114.1156-15 P
230/208V3.5112,0009,900- -3,570 / 2,93515.5 / 14.119.5206-20 P
230/208V5117,10014,000- -5,070 / 4,16022.1 / 20.027.6306-30 P
265V2.51- -- -8,5002,5709.712.2157-20 P
265V3.71- -- -12,6003,77014.217.9207-20 P
265V51- -- -17,1005,07019.223.9257-30 P
Notes:
¹ All 265-vol t models must use an Amana® bran d s ub-bas e (P TSB4* *E) or an Amana® brand hard-wire k it (PTPWHWK4 ) .
² Minimum branch circuit ampacity ratings conform to the National Electric Code; however, local codes should apply.
³ Minimum v ol tag e on 230/208-v olt models is 197 volts; m ax i m um is 253 volts.
Minimum voltage on 265 - v ol t models is 239 volts ; maxi m um is 292 v ol ts.
4
Over current protect i on fo r al l units w i thou t electr i c heaters i s 15 amps. Overcurrent protec tion on 265-vol t mode l s m ust be car tridge-style time-delay
fus es (incl uded and factory-installed on al l Am ana® brand 265-vol t chas s is).
5
Heati ng capacity and efficiency based on u ni t oper ation wit hout condensate pump; un i t a utomatic al ly switch es to elec tric heat at approximately 24°F outdoor ambient.
6
Total watts for 15,000 BTU/h model s; s ubtra ct 20 watt s for PT 07/09/12
7
Specify two-digit heater kW size to complete model number.
8
R-41 0A r efr i gerant used in all sy stems.
9
All units meet or e xceed ASHRAE 90.1 standards.
10
All units l ess than 250 volts hav e a Leak Cur r ent Detector Interrupter (LCDI) power c or d and meet UL 484 s tandar ds.
EER - Energy Efficiency Ratio per The Air -
Conditioning, Heating, and Refrigeration
Institute (AHRI) T est Procedures and
Canadian Standards Association (CSA)
T est Procedures.
COP - Coefficient of Performance per AHRI
T est Procedures
MOD
(amps)
4
Power Cord
14
PROPER INSTALLATION
OPERATING VOLTAGES
WARNING
USE EXTREME CAUTION WHEN CHECKING HIGH VOLTAGE.
Use a voltmeter, check the voltage at the outlet.
The reading must be within the minimums and maximums shown below for the operating voltage.
Operating Voltages
Operating VoltageMinimum VoltageMaximum Voltage
230/208197253
265238291
NOTE:
1. All 265 volt models must use subbase or hard wire kit.
2. Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply
if in conflict.
3. Minimum voltage on 230/208 volt models is 197 volts; maximum is 253 volts. Minimum on 265 volts is 238 volts;
maximum is 291 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models
must be cartridge-style time delay fuses (included and factory installed on chassis).
5. Heating capacity and efficiency is based on unit operation without condensate pump. Unit automatically switches to
electric heat at 25° F outdoor coil temperature.
6. Total watts for 15,000 BTUH models; subtract 30 watts for PT*12*E**** and 70 watts for PT*07/09*E****.
7. Please specify 2-digit heater kW size to compete model number.
8. Total amps for 12,000 and 15,000 BTUH models; subtract 0.2 amps for PT*07/09*E****.
• LCDI or AFCI Power Cords - Underwrites Laboratories and the National Electric Code (NEC) now require power cords
that sense current leakage and can open the electrical circuit to the unit on units rated at 250 volts or less. In the
event that unit does not operate, check the reset button located on or near the head of the power cord as part of
the normal troubleshooting procedure.
LCDI Power Cord
15
PROPER INSTALLATION
A
WALL SLEEVE INSTALLATION
The wall sleeve must be installed before the air conditioner
or heat pump chassis can be set in place. Read the instructions thoroughly before proceeding.
Pre-installation Considerations
Before proceeding with the sleeve installation, ensure the
following guidelines for locating the wall opening and sleeve
are met:
• The wall opening must be the correct size. See the figures below for wall sleeve Dimensions and minimum
wall opening size.
1
1
6
6
1
/
"
4
m
0
1
m
"
4
/
3
3
1
m
m
0
5
Wall Receptacle Within 58" From
Bottom R ight Side Corner on
208/230 VAC Units Only
3
• If installed in a concrete or masonry wall, a lintel must
be provided in the wall opening for support. Do not usethe wall sleeve as a lintel. See Framing with Lintel
Figure for a typical lintel construction.
Framing with Lintel
• When installed in the opening, the wall sleeve must be
horizontally level from side to side and pitched (one
quarter bubble in the sight glass) to the outside. DO
NOT INSTALL LEVEL (FRONT TO BACK) OR SLOPE THE
WALL SLEEVE TOWARD THE ROOM.
• The installer must determine and supply the mounting
bolts and/or screws to attach the wall sleeve to the
sides of the wall opening. Make sure the wall opening is
adequate for strong support.
• The installer must provide adequate sealing and insulation around the sleeve after it is installed (air and water tight). See Block and Brick Veneer Installation Figure for one of many types of constructions.
13 1/2" (340 mm)
Maximum
(No Ac ce s so ries)
Wall Sleeve Dimensions
Outside
Wall
Caulk Top,
Bottom, and
Both Sides
Internal
Adjacent
Wall
Allow Front Clearance (See Table 1)
Internal
djacent
Wall
Steel
Lintel
Minimum Unit Clearances
• The wall sleeve will need to be installed with minimum
clearances to the floor and adjacent walls. Minimum
projections of the sleeve into and out of the room will
also have to be met. See Minimum Unit Clearances and
Minimum Interior and Exterior Projections Figures as
well as Minimum Clearances and Projections table for
details.
16
Block and Brick Veneer Installation
PROPER INSTALLATION
Minimum Interior and Exterior Projections
MINIMUM CLEARANCES AND PROJECTIONS
Minimum
Option
in.mmin.mmin.mm
Wall Sleeve Only3750000
Subbase Kit3753 1/4852 3/470
Leveling Legs Kit375375250
Duct Kit375001 3/835
Drain Kit375
Hard Wire Kit3751 1/43000
Hydronic Heat Kit
"A" Series
Hydronic Heat Kit
"J" Series
1
If inside mounted then B = 1 1/2 inches (40 mm).
2
To achieve a flush fit between the hydronic front and the finished
9230
6150002 1/265
Clearances
ABC
1
0
0 to 3 1/4
3
1
0
0 to 85
wall, Dimension “C” must be between 3” and 3 1/8”. If this dimension is more than 3 1/8” there will be a gap between the front and
the wall. This gap could permit occupant access to hydronic lines or
other dangerous parts.
3
This dimension can be from 0” to 3-1/4”, but cannot exceed 3-1/4”.
If this dimension exceeds 3-1/4”, the skirt around the front will not
reach the floor.
• For installations in walls deeper than 13-1/2 inches,
special care is necessary to prevent problems with rain
water, condensate drainage and intake/discharge air.
Under these circumstances, careful job site analysis and
precautions are required. You must consult with your
Sales Representative and receive approval before attempting such installations.
• If used, a 230/208 volt wall receptacle must be located
within 58 inches of the lower right sleeve corner. Extension cords must not be used with the unit. See the
note on Wall Sleeve Dimensions Figure.
Minimum
Projection
00
3
32752
4
2
1
1
0
/
4
7
"
M
5
i
m
n
i
m
m
u
m
m
"
m
u
4
/
m
1
m
i
5
6
n
1
i
1
4
M
Dimension "B"
in Table 1
Minimum Wall Opening Dimensions
When 230/208 volt units are to be installed, the power supply may be either cord connected or permanent wiring. Permanent wiring may be done through the accessory hard wire
junction box, or the accessory subbase.
When 265 volt units are to be installed, the power supply
must be permanent wiring. Permanent wiring may be done
through the accessory hard wire junction box, or the accessory subbase. An exposed cord connection on 265 volt
units is not permitted.
The subbase accessory includes leveling legs. If added wall
sleeve support is required and the subbase is not to be used
as an accessory, leveling leg kit may be installed.
Drain Kit
An indoor/outdoor drain kit is available as an accessory
item. When a drain kit is to be installed, do so before installing the wall sleeve in the wall. See the drain kit for
actual installation instructions.
Subbase, Leveling Legs, Main Duct, and Hydronic Heat
Kits
Installation of these kits requires drilling of mounting holes
on both sides of the wall sleeve. The minimum required
clearance distance between the wall sleeve and wall is shown
in Minimum Clearances and Projections Table. If the distance between wall sleeve and wall will be at or near the
minimum clearance distance, mount these kits on the sleeve
before installing the sleeve in the wall. The kit installation
instructions are included with the accessory kits.
17
PROPER INSTALLATION
Wall Receptacle Within 58" From
Bottom R ight Side Corner on
208/230 VAC Units Only
Wall Sleeve Dimensions
Outside Enclosure Panel Removal
The sleeve stiffener must be taken out before the enclosure panel can be removed from the sleeve.
The enclosure panel can be removed by folding the four
flaps up and downward and manipulating the front ends of
the top plus bottom towards the center. The entire panel
can be pulled out diagonally from one side.
Install the wall sleeve condenser air grille by using the screws
and holes provided.
Installation (WS900B or WS900D)
After the wall opening is checked and approved for location, size, and clearances, complete the following to install
the wall sleeve.
NOTE: Check with Amana® Brand Technical Service when a
chassis is installed in any wall sleeve not supplied by
Goodman.
1. Remove the outside enclosure panel from the wall sleeve.
2. Slide the wall sleeve into the wall opening. Do not distort the cabinet shape to fit the wall opening. The unit
chassis must fit snugly and uniformly into the wall
sleeve.
3. Locate the sleeve within the range of minimum projections, as shown in Minimum Wall Opening Dimensions
and Minimum Interior and Exterior Projections Figures,
so both sides are at least the minimum projection from
the wall.
4. Check the level of the wall sleeve. For proper drainage,
the sleeve should be level from side to side and onequarter bubble in the sight glass sloping to the outside.
5. Two holes will need to be drilled in both sides of the
wall sleeve for mounting into the wall. Drill holes of
proper size and in the proper location so the screws will
engage into strong supporting members of the wall. DONOT DRILL THROUGH BOTTOM OF SLEEVE. The following figure shows possible fastening methods.
Expansi on
Anchor Bolt
Plastic
Anchor
Attaching Wall Sleeve to Opening
6. Check the level of the wall sleeve and adjust if necessary.
7. Caulk or seal around the outside of the entire sleeve.
8. If the unit chassis will not be installed immediately,
replace the enclosure panel on the outside opening of
the sleeve. This will prevent weather damage to the
building interior.
9. Recycle or dispose of packaging materials per local
codes.
OUTDOOR GRILLE
An outside grille must be installed to direct air flow for proper
unit operation and also protect the outdoor coil. The grille
must be installed before installing the chassis. Refer to the
Installation Instructions supplied with the outdoor grille kit
for a complete description of the installation procedure.
This model requires either a Stamped Grille Kit (Model SGK-
-B) or an Architectural Grille Kit (Model AGK--B). When replacing an old chassis with an existing grille, please check
with your sales representative to determine if the new chassis should be used with the old outdoor grille. An improper
outdoor grille can decrease cooling or heating capacity, increase energy usage and shorten compressor life.
FRONT REMOVAL
1. Grasp the cabinet front as shown.
18
2. Pull the bottom of the cabinet front away from the chassis until the retaining clips disengage.
PROPER INSTALLATION
3. Lift the cabinet front off the chassis. Reverse this procedure to reinstall the cabinet front.
CHASSIS INSTALLATION
1. Remove the cabinet front from the chassis as described
in Front Removal.
2. Insert the chassis into the wall sleeve.
Wall Sleeve
Chassis
4. Secure the chassis to the wall sleeve using three screws
on each side of the chassis to ensure a proper seal between the chassis and the wall sleeve. The screws are
supplied in a plastic bag which is attached to the power
cord.
IMPORTANT NOTES:
1. The unit is equipped with a rubber grommet mounted
compressor. These grommets are factory set and require no adjustment.
2. If a standard subbase is used, be sure the right hand
subbase cover is removed before the chassis is installed
in the sleeve.
3. Check the indoor and outdoor grilles for obstructions to
air flow. The unit must be located where curtains, furniture, trees, shrubs or other objects do not block the
air flow to and from the unit. If air is obstructed and/or
deflected back into the unit, the air conditioner’s compressor may cycle on and off rapidly. This could damage the compressor and void the warranty.
Front Mounting Holes - Two mounting holes are provided to
give the owner the option of securing the front to the chassis. The mounting holes are located behind the intake grille.
The owner must supply two 1/2 inch long #8 sheet metal
screws per unit. The two screws must be removed before
the front can be removed.
Slide Chassis In
Outside
Wall
3. Slide the chassis into the wall sleeve until the chassis
flanges contact the front edge of the wall sleeve.
Wall Sleeve
Chassis
Outside
Wall
Front Mounting Screw
accessed
through louv er s.
Front Mounting Screws
19
PROPER INSTALLATION
SPECIFICATIONS
WIRING
CAUTION
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY
OR DEATH DUE TO ELECTRICAL SHOCK:
• DO NOT USE AN EXTENSION CORD WITH THIS UNIT.
• USE ONLY COPPER CONDUCTORS.
• WIRING TO THE UNIT MUST BE PROPERLY POLAR-
IZED AND GROUNDED.
OPERATING CONTROLS
Users Controls
Two rotary knobs controlling temperature and operational
SW2
M1
ON / OFF
MASTER SWIT CH
P10
COM A
DS1 DS2 MS1 MS2 EH IN LS FD1 FD2 TF- TF + C R G L W2 Y/W1 B GH
P12
REMOTE THERMOSTATAUXILIARY
P13
IAT
BLACK
M2
Cord connection to a wall socket is not permitted for 265volt units. All 265-volt units must be hard wired using the
hard wire kit or make use of the plug-in receptacle in the
standard subbase.
Heaterless Units
If a heaterless unit is ordered, field provisions must be made
for supplemental heat if desired. Refer to the Installation
Instructions supplied with the heater kit for a complete description of the installation procedures. All 208/230 volt
heaterless units are shipped with a 15 Amp power cord and
all heaterless 265 volt units are shipped with a 20 Amp power
cord.
When adding a heater kit to a unit, the power cord supplied
with the heater kit must be used in place of the power cord
supplied with the unit. The following table specifies power
cord rating requirements for the various heater kits.
POWER CORD REQUIREMENTS
Heater Size
(kW)
1.51520
2.51520
3.520Not Applicable
3.7Not Applicable20
530 30
230/208 Volt Units265 Volt Units
Power Cord Rating
(amp)
Power Cord Rating
(amp)
NOTE: Heaterless units are shipped with an auxiliary data
label on the front side of the mid-partition panel. If an
electric heater kit is field installed, the installer must mark
the appropriate box on the label to indicate the electric
heater capacity. If no heater is installed, the box labeled
“None” must be marked. Refer to the unit nameplate for
over current protection data.
Mode
Switches
Master Switch
The master switch disconnects power to all of the system
components. When this switch is in the off position, the
compressor, fan motor, reversing valve, and electric resistance heater will all be de-energized.
REMOTE/STANDARD
The remote/standard configuration is used to change the
control of the unit from the standard on board controls in
the standard mode, to a remote wall mounted thermostat
in the remote mode. For remote control configuration settings, refer to Configuration Settings.
Fan Cycle Configuration
The fan cycle configuration sets the operational mode of
the fan. In the ON position, the fan will run continuously
whenever the unit is in the heat or cool mode. In the AU
position, the fan will cycle on and off with the compressor
or electric heater when the unit is in the cool or heat mode.
Remote Control Inputs
The C, R, G, (GL for low fan speed or GH for high speed fan
on W2, Y/W1 and B terminals provide control inputs for a
remote wall mounted thermostat. See following illustra-
tion.
CAUTION
DO NOT INSTALL A 5kW HEATER KIT IN ANY 7,000
OR 9,000 BTU CHASSIS.
20
PROPER INSTALLATION
18 Pin Connector
IMPORTANT NOTE: Disconnect power to the unit and/or
turn the Master Switch on the control board to OFF when
connecting or altering wiring to any terminal. Failure to do
so may result in shorting the fuse or damaging the control
board.
Front Desk Control
The FD1 and FD2 provide control inputs for a front desk
switch. Shorting across these two terminals will disable
unit operation. The only control function which will remain
active when these terminals are shorted is freeze protection. Any switch which will produce a short circuit across
these two terminals can be used as a front desk switch.
The contact resistance of the switch, when closed, must be
less than 200 ohms for the front desk feature to operate
properly.
The following table shows the maximum wire length and
corresponding gage size for installation of a front desk
switch.
The figures below shows a wiring schematic for connecting
the front desk switch to the unit.
111+1
Front Desk Switch Wiring Schematic
IMPORTANT NOTE: Do not apply 24VAC across these ter-
minals. Applying 24VAC to these terminals will result in failure of the control board. Shorting these terminals to any
other terminals may also result in control board failure.
Remote Temperature Sensing
1. Remove indoor ambient thermistor from plastic holder
on indoor coil.
MAXIMUM WIRE LENGTH
FOR FRONT DESK SWITCH
Wire Size
(AWG)
#24400
#22600
#20900
#181500
#162000
Maximum
Length Allowed
(ft)
Indoor Ambient
Thermistor
Plastic
Holder
Indoor Coil
2. Cut off end of thermistor, separate leads 1” back from
cut and strip 1/2” of insulation from each lead.
21
PROPER INSTALLATION
3. Wire nut the stripped leads to the two sensor wires
running from terminals 2 and 3 on the remote temperature sensor base .
User Controls
Thermostat Setting
Pressing the COOL thermostat control and the up or down
arrows will provide a cooler room temperature, respectively. Pressing the HEAT thermostat control and the up or
down arrow keys will provide a warmer room temperature.
Fan Speed
4.Place the mode switch in the “OFF” position. Reestablish power to the unit. The remote temperature will
automatically activate.
NOTE: Ensure the mode switch is in the OFF position before
electrical power is applied to the unit. If the mode switch is
not in the OFF position when electrical power is applied to
the unit, the random restart feature will activate causing a
two to four minute start-up delay.
NOTE: Freeze protection temperatures will be sensed by
the remote temperature sensing device and not at the PTAC
unit (sensed at the PTAC unit when a remote thermostat is
used).
Temperature Limiter
The temperature limiting feature can reduce energy costs
by controlling the maximum temperature available in heating and the minimum temperature available in cooling. While
approximate temperature settings are shown below, actual
room temperature will vary slightly.
Users Controls "Digital Touch Pad"
A seven button touch key pad located behind the control
door controls both temperature and operation mode. The
key pads can be used alone or in combination.
The fan speed touch key will deliver high, low or auto fan
speed to circulate room air. NOTE: The AUTO selection will
not be available if a fan speed is selected without COOL or
Heat selection.
Fan Operation HIGH or LOW with HEAT or COOL mode selected - The selected fan speed shall run in the selected
speed.
Fan Operation AUTO with HEAT or COOL mode selected The fan will run in low and high speed. The changes in fan
speed are automatic. See "Configuration Settings" section
for further details.
Diagnostic Light
The green diagnostic light located in the lower left hand
corner of the touchpad and indicates operation warnings.
This light usually indicates that either the filter or coils need
cleaning. Please refer to the Maintenance and Cleaning
section for the proper cleaning procedure. If this light is
still on after cleaning, please refer to the Diagnostic & Sta-tus Report section for assistance.
Additional Control Inputs
The control inputs provide additional unit control and features. To access these control inputs, the cabinet front
must be removed (see Front Removal).
Master Switch
The master switch disconnects power to all of the system
components. When this switch is in the off position, the
compressor, fan motor, reversing valve, and electric resistance heater will all be de-energized.
22
PROPER INSTALLATION
WARNING
Rotate the vent control lever to either open or close the
damper.
Remote Control Inputs
The C, R, GL, W2, Y/W1, B/O, and GH terminals provide
control inputs for a “manufacturer-approved” remote wall
mounted thermostat. The “B” terminal can be configured
to become “O” if needed see Configuration Settings For
remote control thermostat operation, refer to the RemoteThermostat Operation section.
Vent Control
NOTE: Vent control is only used on units with the power
vent or power vent door kit not installed.
The vent control allows fresh air to be drawn into the conditioned area. This fresh air can provide ventilation when the
blower is operating, but it will increase the heating or cooling load and operating costs.
To obtain access to the vent control, remove the cabinet
front (see Front Removal). Remove the shipping screw (if
installed) from the vent door. Then remove the label (if
present) from over the vent control lever on the left side of
the chassis.
Vent
Open
Vent
Closed
HYDRONIC HEAT INSTALLATIONS
To avoid the risk of freezing the steam or water coil during
prolonged shut down periods, the vent door must be left
closed when the outdoor temperature might fall below freezing or a power door kit must be installed.
AIR DISCHARGE GRILLE
The discharge grille can be adjusted to expel air at either a
16° or 56° angle.
16°
Discharge
Air
56°
Discharge
Air
Vent Door
Shipping Screw
Vent
Control
Lever
Vent
Control
Discharge Grille Orientation Options
Use the following procedure to change the angle of the discharge air flow:
1. Remove the front cabinet (see Front Removal).
2. Position the front so that the backside is accessible.
Discharge Air Flow
3. Remove the four (4) screws which secure the discharge
air grille to the cabinet front.
23
PROPER INSTALLATION
Location of 4 Screws
4. Rotate the grille 180° end-for-end.
5. Reinstall the nuts securing the discharge air grille to
the cabinet front. Reinstall the cabinet front on the unit.
CONFIGURATION SETTINGS FOR R410A
E SERIES MODEL BOARDS
7 BUTTON TOUCH PAD WITH DISPLAY
The control can be configured to operate a wide range of
options. The options listed below with the * are the factory
default settings. If these are acceptable, then the unit does
not require any additional configuration and is fully operable. To configure the unit, first select the configuration
feature code setting and then an option code to change
from the factory default setting.
To enter configuration feature mode:
Once you have scrolled to the correct feature, then to
select the option code for your desired configuration,
press either the up or down key
the options of the selected feature code.
To exit configuration mode:
1. Press the OFF
mode will also exit if no keys are pressed for a period of two (2) minutes.
Refer to the Configuration Chart.
key. Configuration feature
to scroll through
Wireless Communications
PTAC models PT****B***M, N or P have the option to use a
wireless thermostat and door sensor. These features will
only work on the models listed above. The thermostat and /
or door sensor will require an antenna for communication
with the digital control board.
ANTENNA INSTALLATION FOR DT01* KIT
A DT01* antenna must be installed on the digital PTAC to
allow operation of either the DS01* remote RF thermostat
or a DD01* combination PIR motion sensor and door switch.
1. Press and hold the up and down arrow keys at the
same time and press the OFF key twice within
a two (2) second time frame. The display will indi-
cate - -., and then release the key and press the
key one time. The display will then alternate be-
tween C1 and 0.
To select a different configuration feature code,
press the HEAT key until the desired configu-
ration comes up. To scroll to a previously viewed configuration codes press the COOL key .
24
PREPARATION
1. Disconnect power to the unit by unplugging the power
cord at the wall outlet or subbase, or disconnect power
at the fuse box or circuit breaker.
2. If the cabinet front is screwed to the chassis, remove
the 1/4” screw (or screws). See following figure.
PROPER INSTALLATION
Front Mounting Screw
accessed
through louvers.
3. Remove cabinet front from chassis by tilting the bottom of the front forward, lifting slightly up and forward.
4. Mount the antenna as high up on the control panel as
possible and as far to the right as possible in a location
that will not interfere with the reinstallation of the PT AC
polymer room front. Mark holes for screw location. Remove antenna housing and drill two 1/8” holes where
marked. Some units may have the holes already predrilled in the correct location.
Wire
DT01* Mounting
5. Remove antenna cable and route cable through opening
in bottom of antenna housing.
6. Mount antenna housing with two screws as shown in
figure. (NOTE: The Amana® brand logo should be in the
lower right hand corner).
7. Plug wire harness from antenna into connector on the
control board to the right of the master switch, being
careful not to bend and/or break the wires when you
connect the cable to the PT AC. Gently push the connector into place by pushing on the edge of the connector
with your thumb nails. Avoid pushing directly on the
wires.
8. Restore power to the PT AC unit.
9. Reinstall the polymer room cover .
NOTE: The LED must be oriented at the top of the antenna
housing (the Amana® brand logo will be on the lower right)
for proper unit operation.
THERMOSTAT INSTALLATION FOR DS01E KIT
NOTE: A DT01* must be installed on the digital PTAC unit for
the DS01* to be operable.
Skip these steps if not installing.
1. Select thermostat mounting location about five feet
above the floor, on an inside wall, out of direct sunlight, away from sources of radiant heat (lamps, fireplaces, heating and air conditioning equipment, etc.),
away from windows or door to the outside, and avoid
areas with poor air circulation. If the PIR in the thermostat is to be used with a DD01* device as a 2nd motion sensor , point the thermostat towards the area where
you are requiring additional motion sensing.
Ensure location is out of the path of foot traffic where
a person might accidentally bump into the thermostats
and damage the device.
2. R emove thermostat from mounting plate by pulling apart
at the bottom of the thermostat about 1”, and slide
thermostat up to release from the top of the mounting
plate.
3. Place thermostat mounting plate against the wall at desired location and mark placement of mounting holes.
Make sure the UP arrow is pointing up on the mounting
plate.
4. If mounting in drywall, tap plastic anchors into wall. For
other surfaces, drill a 3/16” hole.
5. Screw mounting plate to the wall. DO NOT SNAP THERMOSTAT INTO PLACE UNTIL AFTER BINDING PROCESS.
See Binding Instructions.
6. Install four (4) AA batteries (included) into the back of
the thermostat. Terminals are marked “+” and “-” for
polarity.
NOTE: Do not install thermostat on wall plate until all configuration settings and binding processes have been completed.
WIRED POWER OPTION
1. If the option for wired power is used, the two thermostat wires (20 gauge minimum field supplied) can be
connected to the thermostat.
2. Route wires through the opening in the mounting plate.
3. Loosen set screws on wired terminal and insert wires
into the opening. Tighten set screws.
4. Connect wires at PTAC unit to terminal pins C and R.
The wire harness kit PWHK01C is required for this connection.
25
Loading...
+ 57 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.